ioegc_genetic_algorithm-
ioegc_genetic_algorithm-
Peer Reviewed
ISSN: 2350-8914 (Online), 2350-8906 (Print)
Year: 2020 Month: June Volume: 8
Abstract
Power transfer capability of a transmission line falls with the length of the line. Loading in the short line and
long line is permitted by thermal limit and stability limit respectively. In a power system consisting of long lines
and short lines, FACTS devices can be used for partial increase of power transfer in the long line as well as
improve the voltage profile of the line. The main objective of this study is to minimize system line loss, sum of
line loading ratio by optimal placement of Static Var Compensator (SVC) at bus and optimal placement of
Thyristor Controlled Series Compensator (TCSC) in long lines. The system line loss and sum of line loading
ratio has been separately minimized with the various combination of both TCSC and SVC. The optimization
was done with help of Genetic Algorithm (GA). In this work three cases (only SVC, only TCSC, both TCSC
& SVC) are considered for optimal power flow. It is observed that SVC is better in improving voltage profile
and reducing line loss. Similarly, for this system TCSC is better for partial increase in power flow of long line
but less capable of voltage profile improvement. With combination of both TCSC and SVC there is further
reduction of power loss, improvement of voltage profile and decrease in the sum of line loading ratio. The
result thus obtained was verified with MATLAB 2013Ra.
Keywords
Transmission Loss Minimization, Voltage Profile Enhancement, Genetic Algorithm (GA), Thyristor Controlled
Series Compensator(TCSC), Static Var Compensator (SVC)
Pages: 15 – 23
Optimal Setting and Siting of TCSC and SVC to Enhance Power System Performance
Controller (UPFC), TCPST (Thyristor Controlled requirement we can incorporate the FACTS devices
Phase Shifting Transformer) etc [1]. There are many optimally so that the capacity of the line can be made
advantages associated with the FACTS devices. Their flexible. Some research has used GA for optimal
main function is to control the power by controlling choice and allocation of FACTS devices in multi
parameters such as impedance, terminal voltages and machine power system and they have simultaneously
phase angles. They can control the flow of active and optimized rating, location and type of FACTS devices
reactive power in the network. They can minimize the [2].
congestion in the network. They can reduce power
In this study, Genetic Algorithm (GA) is used as a
losses and improve the voltage profile. Also these
minimization tool for optimal placement of TCSC and
device can improve the both transient stability and
SVC so that Line loading management, real power loss
small signal stability of the power system.
reduction and voltage profile enhancement is achieved.
The test system under study is Modified IEEE-14 Bus
system with two long lines introduced in the system.
2. Problem Formulation
The objective function in this study has two terms, the
first term represents the active power loss and second
term represents the sum of line loading ratio. Only one
objective function is considered at a time during the
entire study.
16
Proceedings of 8th IOE Graduate Conference
where n=1. In equation (3) SL corresponds to the 3. Modelling of TCSC and SVC
actual active power flowing through the line and SLmax
corresponds to the thermal limit for the short line while 3.1 Thyristor Controlled Series Compensator
stability limit for the long lines as that of base case.
TCSC consists of a Thyristor Controlled Reactor
However, during the study a power factor of 0.9 is
(TCR) in parallel with a capacitor bank and connected
used for converting SLmax into corresponding active
in series in the transmission line to compensate the
power. The stability limit under consideration is taken
line reactance. TCSC can serve as the capacitive or
for power angle corresponding to 30◦ .
inductive compensation respectively by smoothly
varying the reactance of the transmission line. Figure
2.2 Constraints 2 shows the schematic of TCSC. The reactance
offered by TCSC is dependent upon the firing angle
Following inequality constraints includes the limits of
input to the TCSC.
the concerned variables.
a) Reactive Power Generation Limit
17
Optimal Setting and Siting of TCSC and SVC to Enhance Power System Performance
Step 7: Stop
Vk2
Qsvc = (9) 4.2 Genetic Algorithm
Xsvc
Genetic Algorithm is the process of applying biology
where Vk is the voltage of the kth bus under
in engineering. Genetic algorithm which was first
consideration.
proposed by John Holland is based upon evolution
The range of firing for SVC is set between 0◦ to 90◦ . theory and genetics. This algorithm is based upon
In this study for a fixed value of L and C of SVC, Darwin’s Theory. The fundamental concept which is
firing angle is controlled to provide the variable associated with the GA is that it attempts to extract
compensation. Similarly, the position for its optimum value by minimizing a set of objective
installation is allowed on all bus except the bus function. Usually, Genetic algorithm performs three
containing generators (bus 1 and bus 2). basic operations. These operations are also called
18
Proceedings of 8th IOE Graduate Conference
selection, crossover and mutation. These operations upto 2 SVC and 2 TCSC installed in this system. With
are also known as genetic operations which are increase in more devices has minimum change in the
performed until the minimization is reached. Genetic objective function under study. The coding were done
algorithm generally operates on chromosomes. Each in MATLAB R2013a.
of the chromosomes are given certain fitness value.
GA forms new chromosomes in each generation and 5.1 Test System Under Study
hence only those chromosomes will survive which
had best fitness values. It is robust technique and it is The test system under study is obtained by modifying
easy to understand but it has slow convergence. the IEEE-14 Bus test system shown in figure 5. All
However for this study GA optimization solver tool of the synchronous compensators are removed so that
Matlab 2013Ra is used. the system demands for shunt compensation. Further,
one long line between bus 1 and bus 5 and another
long line between bus 2 and bus 3 are introduced by
linear scaling of existing original system for study
purpose. Line between bus 1 and bus 5 is Line-2.
Line between bus 2 and bus 3 is Line-3. The line
lengths of the system shown in figure 5 can be found in
various research papers [3]. The thermal limit of long
lines under study are considered as 1.83 p.u. Some
research has proposed the line limits of the IEEE-14
bus system and hence we have considered the same
line rating for all the lines except line 2 and line 3 for
our study purpose [4]. Similarly, the other conditions
such as generation and loads of the system were not
changed. Hence this causes the base case loading of
standard IEEE-14 bus and the system under study to
be different.
19
Optimal Setting and Siting of TCSC and SVC to Enhance Power System Performance
voltages are out of limit and voltage constraint is enough margin of operation. Hence it requires the
violated. Table 1 shows the line loss scenario with the redistribution of loadings of the lines so that long line
increase in loading from 70% to 100% of total load of transfers extra power within its margin thereby
system. It shows power loss increases with loading. creating relief in the short lines.
Figure 6: Voltage profile at bus before placement of Figure 8: Line loading ratio before placement of
TCSC and SVC TCSC and SVC
Figure 7 shows the phase angle condition of the system 5.3 Minimization Study with SVC only
at base case. It can be observed that the phase angles
This section shows the simulation result at base case
are within the limit at steady state conditions without
with the inclusion of SVC for power loss
addition of TCSC and SVC.
minimization. Figure 9 shows the variation of power
Table 1: Line loss with increased loading loss with increase in number of SVC. It can be
observed that with addition of 2 SVC drastically
SN Load%(P and Q) Overall Line loss
reduces the power loss and this value remains almost
1 70% 0.0968 p.u.
steady because the voltage are boosted within the
2 80% 0.132719 p.u.
limit with more increment of SVC. Hence we will
3 90% 0.236115 p.u.
consider study with 2 number of SVC in our base case.
4 100% 0.354075 p.u.
From table 2 it can be observed that the power loss
reduces by 40.63% with the inclusion of 2 number of
SVC. Table 3 gives the optimal location and optimal
rating for SVC. Optimal location is at Bus No-5 and
Bus No-7, and the optimal rating of SVC for these bus
are 0.369 p.u. and 0.4638p.u. respectively. From table
4 it can be observed that sum of line loading ratio also
decreased from 10.3443 to 10.1062.
20
Proceedings of 8th IOE Graduate Conference
Table 2: Losses before and after SVC Table 6: Optimal ratings and locations of TCSC
Loading Loss before SVC Loss after 2 SVC Loading Optimal ratings(p.u.) locations
Base case 0.354075 0.2102115 Base Case 0.0146,0.3159 Line-2,Line-3
Table 3: Optimal ratings locations of SVC Table 7: Losses before and after TCSC
Loading Optimal ratings(p.u.) locations Loading Before TCSC After 2 TCSC
Base case 0.369,0.4638 Bus-5,Bus-7 Base case 0.354075 p.u. 0.312705 p.u.
Table 4: Sum of line loading ratio before and after Figure 11 shows the voltage profile with the inclusion
SVC of TCSC. However, with the TCSC placed on line 2
and 3 the voltage limit is still violated for the system
Loading Before SVC After 2 SVC under study. Hence this necessitate SVC to be used
Base case 10.3443 10.1062 along with TCSC. Table 6 shows the location and
optimal rating of TCSC without considering voltage
5.4 Minimization Study with TCSC only constraint. Location for this case is line no 2 and line
no 3, and the corresponding rating can be found in
This section shows the simulation result at base case Table 6. Similarly, from table 7 it can be observed that
with the inclusion of TCSC for sum of line loading inclusion of TCSC has significantly less effect on the
ratio minimization. Figure 10 shows the variation of overall power loss.
Sum of line loading ratio with number of TCSC. It
can be observed from the table 5 that the sum of line
loading ratio decreased from 10.3443 to 9.3426 with
two number of TCSC. Since our aim in this study is to
locate TCSC in the long lines only and the long lines
under study are limited to two. Hence we will consider
two TCSC for our study purpose. The decrease in sum
of line loading ratio is quite more as that compared to
SVC case.
21
Optimal Setting and Siting of TCSC and SVC to Enhance Power System Performance
22
Proceedings of 8th IOE Graduate Conference
References
[1] S. Gerbex, R. Cherkaoui, and A. J. Germond. Optimal
location of multi-type facts devices in a power system
by means of genetic algorithms. IEEE Transactions on
Power Systems, 16(3):537–544, 2001.
23