Vacon 100 FLOW Application Manual DPD01083B En
Vacon 100 FLOW Application Manual DPD01083B En
ac drives
application manual
vacon • 0
TABLE OF CONTENTS
Document: DPD01083B
Version release date: 4.3.13
Corresponds to software package FW0159V002.vcx
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
vacon • 2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
vacon • 4
NOTE! This manual includes a large amount of parameter tables. Below you can find the
column names and their explanations:
Location indication
on the keypad; Name of the Short description
Minimum value Maximum value ID number of
Shows the operator parameter of parameter values
of the parameter of the parameter the parameter
the parameter number and/or its function
Index
Figure 1.
Features
• Extensive wizards for start-up, Standard, HVAC, PID-control, Multipump (Single drive
and Multidrive) and Fire Mode used to facilitate commissioning
• FUNCT button for easy change between Local (keypad) and Remote control place. The
remote control place is selectable by parameter (I/O or Fieldbus)
• 8 preset frequencies
• Motor potentiometer functions
• Flushing function
• 2 programmable ramp times, 2 supervisions and 3 ranges of prohibited frequencies
• Quick stop
• Control page for easy operation and monitoring of the most essential values.
• Fieldbus data mapping
• Automatic reset
• Different pre-heat modes used to avoid condensation problems
• Maximum output frequency 320Hz
• Real-time clock and timer functions available (optional battery required). Possible to
programmme 3 time channels to achieve different functions on the drive (e.g. Start/
Stop and Preset frequencies)
• External PID-controller available. Can be used to control e.g. a valve using the AC
drive's I/O
• Sleep mode function which automatically enables and disables drive running with user
defined levels to save energy.
• 2-zone PID-controller (2 different feedback signals; minimum and maximum control)
• Two setpoint sources for the PID-control. Selectable with digital input
• PID setpoint boost function
• Feedforward function to improve the response to the process changes
• Process value supervision
• Multipump control for Single drive and Multidrive systems
• Multimaster and Multifollower modes in Multidrive system
• Real-time clock based multipump alternation
• Maintenance counter
• Pump control functions: Autochange, Priming Pump Control, Jockey Pump Control,
Pump Impeller Auto-Cleaning, Anti-blocking, Pump Input Pressure Supervision and
Frost Protection function
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon®100 FLOW - Quick startup guide vacon • 6
9086.emf
Figure 2.
1.1.2 Display
The keypad display indicates the status of the motor and the drive and any irregularities in the
motor or drive functions. On the display, the user sees information about the drive and the
present location in the menu structure and the item displayed.
Graphical display:
Status field Status field
STOP/RUN READY/NOT READY/FAULT
ALARM Control place:
Direction
PC/IO/KEYPAD/FIELDBUS
STOP READY I/O
Location field
Main Menu (Parameter ID number and
ID: M1 current menu location
Quick Setup Activated group/item:
( 17 ) Press OK to enter
Monitor
( 5 )
Number of items
Parameters
in the group
( 12 )
9159.emf
Figure 3.
If the text on the text line is too long to fit in the display, the text will scroll from left to right to
show the whole text string:
Text display:
Indicators: Indicators:
Status Alarm, Fault
Group or parameter
name
Menu location
9167.emf
Indicators: Indicators:
Direction Control place
Figure 4.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1
Vacon®100 FLOW - Quick startup guide vacon • 8
Yes
6 Run Startup Wizard?
No
Select ‘Yes’ and push OK. If you select ‘No’ the drive will exit the wizard.
NOTE! If you select ‘No’ and push OK, you will have to set all parameter values manually.
Standard
HVAC
Select preset application configu-
7 ration (P1.2 Application (ID 212))
PID Control
Multipump (Single drive)
Multipump (Multidrive)
NOTE! If you change the value of P1.2 Application (ID 212) later on the graphical keypad, the
wizard will guide you from step 8 to step 17 and jump then to the selected application wizard.
If ‘Induction Motor’ has been selected in step 8, steps 9 - 13 appear. If ‘PM Motor’ has been
selected, steps 9 - 12 appear and the wizard will jump to step 14 after them.
If you select ‘Yes’ and push the OK button you will be taken to the application wizard according
to the selection you made in step 7.
If you select ‘No’ and push OK, the wizard will stop and you will have to set all parameter values
manually.
Now the Startup Wizard is completed.
The Startup Wizard can be re-initiated by activating the parameteter P6.5.1 Restore factory
defaults OR by choosing Activate for parameter B1.1.2 Startup Wizard.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1
Vacon®100 FLOW - Quick startup guide vacon • 10
Test Mode can be used to test the Fire Mode function without voiding the warranty. Read
important information about the password and warranty issues in chapter 8.13, before you
proceed.
Fire Mode Wizard is intended for easy commissioning of the Fire Mode function. The Fire Mode
Wizard can be initiated by choosing Activate for parameter 1.1.2 in the Quick setup menu.
After this the wizard moves to application-specific steps, which are presented in the following
chapters:
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1
Vacon®100 FLOW - Quick startup guide vacon • 12
However, if you have selected Standard Application or HVAC Application in the Startup Wizard
step 7 (see chapter 1.2), only this step will appear:
However, if you have selected PID Control Application in step 7 of the Startup Wizard, the
following steps will appear next after the Startup Wizard step 18 (see chapter 1.2):
If % is selected as process unit, the wizard will directly jump to step 6. If any other unit than %
is selected, the following steps appear:
If one of the analogue input signals is selected in step 6, step 7 appears. Otherwise the wizard
will jump directly to step 8.
If one of the analogue input signals is selected in step 9, step 10 appears and step 12 after
that. If any other selection than AI1 - AI6 is made, the wizard will jump to step 11.
If either of the options ‘Keypad Setpoint 1’ or ‘Keypad Setpoint 2’ is chosen in step 9, the wizard
will jump directly to step 12.
If option ‘Yes´is selected, the following steps appear. Otherwise, the wizard will jump directly
to the end.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1
Vacon®100 FLOW - Quick startup guide vacon • 14
However, if you have selected Multipump (Single drive) Application in step 7 of the Startup
Wizard, the following steps will appear next after the Startup Wizard step 18 (see chapter 1.2):
If % is selected as process unit, the wizard will directly jump to step 6. If any other unit than %
is selected, the following steps appear:
If one of the analogue input signals is selected in step 6, step 7 appears. Otherwise the wizard
will jump directly to step 8.
If one of the analogue input signals is selected in step 9, step 10 appears and step 12 after
that. If any other selection thant AI1 - AI6 is made, the wizard will jump to step 11.
If either of the options ‘Keypad Setpoint 1’ or ‘Keypad Setpoint 2’ is chosen in step 9, the wizard
will jump directly to step 12. .
Sleep Function? 0 = No
12 1 = Yes
If option ‘Yes´is selected, steps 13 - 15 appear. Otherwise, the wizard will jump directly to the
step 16.
If Autochange function is enabled, steps 19-24 will appear. If Autochange is disabled, the
wizard will jump directly to step 25.
0 = Auxiliary pumps
19 Autochanged pumps (P3.15.7)
1 = All pumps
Step 20 appears only if option 'Enabled (Interval)' was selected in step 18.
Steps 21-22 appear only if option 'Enabled (Real Time)' was selected in step 18.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1
Vacon®100 FLOW - Quick startup guide vacon • 16
However, if you have selected Multipump (Multidrive) Application in step 7 of Startup Wizard,
the following steps will appear next after Startup Wizard step 18 (see chapter 1.2):
If % is selected as the process unit, the wizard will directly jump to step 6. If any other unit than
% is selected, the following steps appear:
If one of the analogue input signals is selected in step 6, step 7 appears. Otherwise the wizard
will jump directly to step 8.
If one of the analogue input signals is selected in step 9, step 10 appears and step 12 after that.
If any other selection thant AI1 - AI6 is made, the wizard will jump to step 11.
If either of the options ‘Keypad Setpoint 1’ or ‘Keypad Setpoint 2’ is chosen in step 9, the wizard
will jump directly to step 12.
If option ‘Yes´is selected, steps 13 - 15 appear. Otherwise, the wizard will jump directly to step
16.
If Autochange function is enabled (interval), step 23 will appear and after that the wizard will
jump to step 26. If Autochange function is enabled (Weekdays), the wizard will jump to step 24.
If Autochange is disabled, the wizard will jump directly to step 26.
0 = Auxiliary pumps
22 Autochanged pumps (P3.15.7)
1 = All pumps
Step 23 appears only if option 'Enabled (Interval)' was selected in step 18.
Steps 24-25 appear only if option 'Enabled (Weekdays)' was selected in step 18.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1
Vacon®100 FLOW - Quick startup guide vacon • 18
24V auxiliary
30 +24Vin input voltage
A RS485 Serial bus, negative
Modbus RTU
B RS485 Serial bus, positive
21 RO1/1 NC Relay output 1
RUN
22 RO1/2 CM RUN
23 RO1/3 NO
24 RO2/1 NC Relay output 2
FAULT 25 RO2/2 CM FAULT
26 RO2/3 NO
32 RO3/2 CM Relay output 3
READY
33 RO3/3 NO
9301.emf
Figure 5.
*) Digital inputs can be isolated from the ground with a DIP switch, see the figure below:
Digital inputs
Floating
Connected to GND (Default!)
9109.emf
Figure 6.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1
Vacon®100 FLOW - Quick startup guide vacon • 20
M1.1 Wizards
M1 Quick Setup:
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1
Vacon®100 FLOW - Quick startup guide vacon • 22
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1
Vacon®100 FLOW - Quick startup guide vacon • 24
2-wire transmitter
4 AI2+ Analogue input 2 +
Actual value PID feedback
+ (actual value)
(default: 4...20mA)
5 AI2- Analogue input 2 -
I = (0)4...20mA -
6 24Vout 24V auxiliary voltage
7 GND I/O ground
Place A: Start forward
8 DI1 Digital input 1 (PID controller)
24V auxiliary
30 +24Vin input voltage
A RS485 Serial bus, negative
Modbus RTU
B RS485 Serial bus, positive
21 RO1/1 NC Relay output 1
RUN
22 RO1/2 CM RUN
23 RO1/3 NO
24 RO2/1 NC Relay output 2
FAULT 25 RO2/2 CM FAULT
26 RO2/3 NO
32 RO3/2 CM Relay output 3
READY
33 RO3/3 NO
9303.emf
Figure 7.
*) Digital inputs can be isolated from the ground with a DIP switch, see figure below
Digital inputs
Floating
Connected to GND (Default!)
9109.emf
Figure 8.
M1 Quick Setup:
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1
Vacon®100 FLOW - Quick startup guide vacon • 26
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1
Vacon®100 FLOW - Quick startup guide vacon • 28
3~
Start / Stop
RO2
RO3
M1 M2 M3
M1
M2 PT
M3
3068.emf
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1
Vacon®100 FLOW - Quick startup guide vacon • 30
Autochange -function can be used for equalising the wear of all motors in the system.
Autochange function monitors the running hours of each motor and arranges the starting
order of the motors according to them. Motor with the lowest running hours is started first and
motor with the greatest running hours is started last. Autochange (change of starting order)
can be configured to take place based on autochange interval time or based on drives internal
real time clock (if RTC-battery is installed into the drive).
Autochange can be configured to cover all the pumps in the system or only the auxiliary pumps.
NOTE! Different connections, depending on selected autochange mode (See Figure 10 and
Figure 11).
3~
K2 K3
M1 M2 M3
3069.emf
Figure 10. Principal control diagram, when only auxiliary motors are autochanged.
M1 M2 M3
3070.emf
Figure 11. Principal control diagram, when all pumps are autochanged
Two individual control places can be used. Selection between control places A and B is done
with DI6. When control place A is active, start/stop commands are given with DI1 and frequency
reference is taken from PID controller. When control place B is active, start/stop commands
are given with DI4 and frequency reference is taken directly from AI1.
All drive outputs are freely configurable. One analogue output (Output Frequency) and three
relay outputs (Run, Fault, Ready) are available on the basic I/O board.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1
Vacon®100 FLOW - Quick startup guide vacon • 32
2-wire transmitter
4 AI2+ Analogue input 2 +
Actual value PID feedback
+ (actual value)
(default: 4...20mA)
5 AI2- Analogue input 2 -
I = (0)4...20mA -
6 24Vout 24V auxiliary voltage
7 GND I/O ground
Place A: Start forward
8 DI1 Digital input 1 (PID controller)
Place B: Start forward
9 DI2 Digital input 2 (Freq. reference P3.3.1.6)
24V auxiliary
30 +24Vin input voltage
A RS485 Serial bus, negative
Modbus RTU
B RS485 Serial bus, positive
21 RO1/1 NC Relay output 1
Motor 1 control
22 RO1/2 CM (Multi-pump K1 contactor)
A1 A2
23 RO1/3 NO
24 RO2/1 NC Relay output 2
Motor 2 control
25 RO2/2 CM (Multi-pump K2 contactor)
A1 A2
26 RO2/3 NO
32 RO3/2 CM Relay output 3 Motor 3 control
A1 A2 (Multi-pump K3 contactor)
33 RO3/3 NO
3074.emf
Figure 12.
*) Digital inputs can be isolated from the ground with a DIP switch, see figure below
Digital inputs
Floating
Connected to GND (Default!)
9109.emf
Figure 13.
M1 Quick Setup:
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1
Vacon®100 FLOW - Quick startup guide vacon • 34
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1
Vacon®100 FLOW - Quick startup guide vacon • 36
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1
Vacon®100 FLOW - Quick startup guide vacon • 38
Each motor is controlled by its own drive. Drives of the system are communicating with each
other by Modbus RTU communication.
3~
Start / Stop
FB
M1 M2 M3
M1
M2 PT
M3 3071.emf
The process variable (e.g. pressure) is controlled by controlling the speed of the motors and
the number of running motors. The internal PID controller of the leading drive controls the
speed of the motors and requests the other motors to start/stop when needed.
The operation of the system depends on the selected operation mode. In Multifollower mode,
auxiliary motors follow the speed of the regulating drive.
RPM
fmax
A
fmin
3072.emf
P1 P2 P3
Figure 15. Regulation in Multifollower mode. Pump 1 is regulating and pumps 2 and 3 are
following the speed of pump 1, as shown with curves A.
The figure below shows an example of Multimaster mode, where the speed of the regulating
motor is locked to constant production speed (B), when next motor is started. (A = regulating
curves of the pumps)
RPM
B
fmax
A
fmin
t
3073.emf
P1 P2 P3
Figure 16. Regulation in Multimaster mode.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1
Vacon®100 FLOW - Quick startup guide vacon • 40
Autochange function can be used for equalising the wear of all motors in the system.
Autochange function monitors the running hours of each motor and arranges the starting
order of the motors according to them. Motor with the lowest running hours is started first and
motor with the greatest running hours is started last. Autochange (change of starting order)
can be configured to take place based on autochange interval time or based on drives internal
real time clock (if RTC-battery is installed into the drive).
Figure 17.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1
Vacon®100 FLOW - Quick startup guide vacon • 42
Digital inputs
Floating
Connected to GND (Default!)
9335.emf
Figure 18.
STOP / RUN
L1 L2 L3 L1 L2 L3 L1 L2 L3
vacon • 43
13
-SF1
14
GND1 DI1 RS485- RS485+ GND1 DI1 RS485- RS485+ GND1 DI1 RS485- RS485+
-TA1 L1 L2 L3 -TA1 L1 L2 L3 -TA1 L1 L2 L3
7 8 A B 7 8 A B 7 8 A B
EARTHING DIGITAL FLOAT OFF SERIAL SERIAL EARTHING DIGITAL FLOAT OFF SERIAL SERIAL EARTHING DIGITAL FLOAT OFF SERIAL SERIAL
3~ FOR DI INPUT GND ON BUS BUS 3~ FOR DI INPUT GND ON BUS BUS 3~ FOR DI INPUT GND ON BUS BUS
DIO's RS-485 DIO's RS-485 DIO's RS-485
Termination Termination Termination
EARTHING DIGITAL ANALOG FLOATING SUPPLY ANALOG EARTHING DIGITAL ANALOG FLOATING SUPPLY ANALOG EARTHING DIGITAL ANALOG FLOATING SUPPLY ANALOG
3~ FOR DI INPUT INPUT FOR DI FOR DI INPUT 3~ FOR DI INPUT INPUT FOR DI FOR DI INPUT 3~ FOR DI INPUT INPUT FOR DI FOR DI INPUT
13 15 4 11 6 5 13 15 4 11 6 5 13 15 4 11 6 5
U V W PE U V W PE U V W PE
GND2 DI5 AI2+ CMA 24V1 AI2- GND2 DI5 AI2+ CMA 24V1 AI2- GND2 DI5 AI2+ CMA 24V1 AI2-
x1 x1
1 1 1
-TB5 -TB5
-PE x2 -PE x2 -PE
Figure 19.
1 1 -WGB 1
-PE -PE -PE
1 3 5 13 1 3 5 13 1 3 5 13
-QB2 -QB2 -QB2
2 4 6 14 2 4 6 14 2 4 6 14
-WGB
- +
U1 V1 W1 U1 V1 W1 U1 V1 W1
M I M M
-MA1 -TF5 -MA1 -MA1
3~ PRESSURE 3~ 3~
PE SENSOR PE PE
1 1 1
-PE -PE -PE
3099.emf
Vacon®100 FLOW - Quick startup guide
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
Vacon®100 FLOW - Quick startup guide vacon • 44
M1 Quick Setup:
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1
Vacon®100 FLOW - Quick startup guide vacon • 46
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
1
Vacon®100 FLOW - Quick startup guide vacon • 48
The data on the control keypad are arranged in menus and submenus. Use the Up and Down
arrows to move between the menus. Enter the group/item by pressing the OK button and return
to the former level by pressing the Back/Reset button.
The Location field indicates your current location. The Status field gives information about the
present status of the drive. See Figure 21.
The basic menu structure is depicted in Figure 20.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
2
Main menu Submenus Main menu Submenus Main menu Submenus
M1 Quick setup M1.1 Wizards M3 Parameters M3.1 Motor Settings M4 Diagnostics M4.4 Total Counters
M5.9 Ethernet
M2.9 Ext PID Controller M3.10 Automatic Reset
2
vacon • 51 User interfaces on Vacon®100 FLOW
Monitor
( 5 )
Number of items
Parameters
in the group
( 12 )
9159.emf
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
2
User interfaces on Vacon®100 FLOW vacon • 52
Start/Stop Setup Rem Control Place Rem Control Place
ID:172 M3.2.1 ID: M3.2.1 M3.2.1
Start/Stop Setup Rem Control Place
ID:172 M3.2.1 M3.2.1
9160.emf
Start Function
Ramping
9257.emf
...
9256.emf
Control places
The control place is the source of control, where the drive can be started and stopped. Every
control place has its own parameter for selecting the frequency reference source. The Local
control place is always the keypad. The Remote control place is determined by parameter
P3.2.1 (I/O or Fieldbus). The selected control place can be seen on the status bar of the keypad.
Remote control place
I/O A, I/O B and Fieldbus can be used as remote control places. I/O A and Fieldbus have the
lowest priority and can be chosen with parameter P3.2.1 (Rem Control Place). I/O B, again,
can bypass the remote control place selected with parameter P3.2.1 using a digital input. The
digital input is selected with parameter P3.5.1.7 (I/O B Ctrl Force).
Local control
Keypad is always used as the control place while in local control. Local control has higher
priority than remote control. Therefore, if, for example, bypassed by parameter P3.5.1.7
through digital input while in Remote, the control place will still switch to Keypad if Local is
selected. Switching between Local and Remote Control is made by pressing the FUNCT button
on the keypad or by using the "Local/Remote" (ID211) parameter.
Changing control places
Change of control place from Remote to Local (keypad).
1. Anywhere in the menu structure, push the FUNCT button.
2. Push the Arrow up or the Arrow down button to select Local/Remote and confirm with the
OK button.
3. On the next display, select Local or Remote and again confirm with the OK button.
4. The display will return to the same location as it was when the FUNCT button was pushed.
However, if the Remote control place was changed to Local (Keypad), you will be instructed
to keypad reference.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
2
User interfaces on Vacon®100 FLOW vacon • 54
?
Main Menu Choose action Local/Remote
ID: M1 ID:
ID:1805 ID:
ID:211
Monitor
( 12 ) FUNCT Change direction
Local
Control page
Parameters
( 21 ) Local/Remote Remote
Diagnostics
( 6 )
Monitor
( 12 )
Parameters
( 21 )
9161.emf
Diagnostics
( 6 )
Monitor
( 12 ) FUNCT
Change direction
Control page
0.00 Hz
Output Frequency Motor Torque
Parameters
( 21 ) Local/Remote
0.00Hz 0.00%
Motor Current Motor Power
Diagnostics
( 6 ) ( 6 )
0.00A 0.00%
0.00 Hz
Output Frequency Motor Torque
0.00Hz 0.00%
Motor Current Motor Power
( 6 )
0.00A 0.00%
9162.emf
Changing direction
Rotation direction of the motor can quickly be changed by applying the FUNCT button.
NOTE! Changing direction command is not visible in the menu unless the selected control
place is Local.
1. Anywhere in the menu structure, push the FUNCT button.
2. Push the Arrow up or the Arrow down button to select Change direction and confirm with
the OK button.
3. Then choose the direction you wish to run the motor to. The actual rotation direction is
blinking. Confirm with the OK button.
4. The rotation direction changes immediately and the arrow indication in the status field
changes.
Monitor
( 7 ) FUNCT
Parameters Change direction Reverse
( 15 ) Control page Forward
Diagnostics
( 6 )
Local/Remote
Monitor
( 7 )
Parameters
( 15 )
9163.ai
Diagnostics
( 6 )
Figure 27.
Quick edit
Through the Quick edit functionality you can quickly access the desired parameter by entering
the parameter’s ID number.
1. Anywhere in the menu structure, push the FUNCT button.
2. Push the Arrow up or the Arrow down buttons to select Quick Edit and confirm with the OK
button.
3. Then enter the ID number of parameter or monitoring value you wish to access. Press OK
button to confirm.
4. Requested Parameter/Monitoring value appears on the display (in editing/monitoring
mode.)
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
2
User interfaces on Vacon®100 FLOW vacon • 56
ID:
Main Menu
M6 ID:
User settings
M6.5 ID:
Parameter backup
M6.5
M6.5.1
User settings
( 4 ) Parameter backup
( 7 )
Save to keypad
9164.emf
Favourites
( 0 )
Drive name
Drive
Restore from keypad
NOTE! If the keypad is changed between drives of different sizes, the copied values of these
parameters will not be used:
Motor nominal current (P3.1.1.4)
Motor nominal voltage (P3.1.1.1)
Motor nominal speed (P3.1.1.3)
Motor nominal power (P3.1.1.6)
Motor nominal frequency (P3.1.1.2)
Motor cos phii (P3.1.1.5)
Switching frequency (P3.1.2.3)
Motor current limit (P3.1.3.1)
Stall current limit (P3.9.3.2)
Maximum frequency (P3.3.1.2)
Field weakening point frequency (P3.1.4.2)
U/f midpoint frequency (P3.1.4.4)
Zero frequency voltage (P3.1.4.6)
Start magnetising current (P3.4.3.1)
DC brake current (P3.4.4.1)
Flux braking current (P3.4.5.2)
Motor thermal time constant (P3.9.2.4)
9305.emf
Current parameter value
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
2
User interfaces on Vacon®100 FLOW vacon • 58
Digital Inputs Ctrl signal 1 A Ctrl signal 1 A
ID:403 M3.5.1.1 ID:403 M3.5.1.1 ID:403 M3.5.1.1
9165.emf
Ctrl Signal 1 B
Add to favorites
( 6 ) ( 6 )
Indicators: Indicators:
Status Alarm, Fault
Group or parameter
name
Menu location
9167.emf
Indicators: Indicators:
Direction Control place
Figure 31.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
2
User interfaces on Vacon®100 FLOW vacon • 60
BACK
RESET
9168.emf
FUNCT
9169.emf
FUNCT
9170.emf
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
2
User interfaces on Vacon®100 FLOW vacon • 62
Changing direction
Rotation direction of the motor can quickly be changed by applying the FUNCT button.
NOTE! Changing direction command is not visible in the menu unless the selected control
place is Local.
1. Anywhere in the menu structure, push the FUNCT button.
2. Push the Arrow up or the Arrow down button to select Change direction and confirm with
the OK button.
3. Then choose the direction you wish to run the motor to. The actual rotation direction is
blinking. Confirm with the OK button.
4. The rotation direction changes immediately and the arrow indication in the status field
changes.
Quick edit
Through the Quick edit functionality you can quickly access the desired parameter by entering
the parameter’s ID number.
1. Anywhere in the menu structure, push the FUNCT button.
2. Push the Arrow up or the Arrow down buttons to select Quick Edit and confirm with the OK
button.
3. Then enter the ID number of parameter or monitoring value you wish to access. Press OK
button to confirm.
4. Requested Parameter/Monitoring value appears on the display (in editing/monitoring
mode).
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
2
User interfaces on Vacon®100 FLOW vacon • 64
2.4.2 Monitor
Multi-monitor
NOTE! This menu is not available in text keypad.
On the multi-monitor page, you can collect four to nine values that you wish to monitor The
number of the monitored items can be selected with parameter 3.11.4.
Main Menu Monitor
ID: M1 ID: M2.1
Quick Setup Multimonitor
( 4 )
Monitor Basic
( 12 ) (7)
Parameters Timer functions
( 21 ) (13)
Multimonitor FreqReference
ID25 FreqReference ID:1 M2.1.1.1
Output frequency 0.00 Hz
0.00 Hz
FreqReferenc Output Freq Motor Speed
9171.emf
Change the monitored value by activating the value cell (with arrow buttons left/right) and
clicking OK. Then choose a new item on the Monitoring values list and click OK again.
Trend curve
The Trend Curve feature is a graphical presentation of two monitor values at a time.
Basic
The basic monitoring values are the actual values of selected parameters and signals as well
as statuses and measurements.
I/O
Statuses and levels of various input and output signal values can be monitored here. See
chapter 3.1.4.
Temperature inputs
see chapter 3.1.5
Extras/Advanced
Monitoring of different advanced values, e.g. fieldbus values. See chapter 3.1.6.
Timer functions
Monitoring of timer functions and the Real Time Clock. See chapter 3.1.7.
PID Controller
Monitoring of PID controller values. See chapter 3.1.8.
External PID controller
Monitoring of external PID controller values. See chapter 3.1.9.
Multipump
Monitoring of values related to the use of several drives. See chapter 3.1.10.
Maintenance counters
Monitoring of values related to Maintenance counters. See chapter 3.1.11.
Fieldbus data
Fieldbus data shown as monitor values for debugging purposes at e.g. fieldbus commissioning.
See chapter 3.1.12.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
2
User interfaces on Vacon®100 FLOW vacon • 66
NOTE! Find more information on using Vacon Live in the program help
3. MONITORING MENU
3.1 Monitor group
The AC drive provides you with a possibility to monitor the actual values of parameters and
signals as well as statuses and measurements. Some of the values to be monitored are
customisable.
3.1.1 Multimonitor
On the multi-monitor page you can collect four to nine values that you wish to monitor. The
number of the monitored items can be selected with parameter P3.11.4. See Table 50 for more
information.
3100.emf
Figure 37.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
3
Monitoring menu vacon • 68
9250.emf
Figure 38.
The Trend Curve feature also allows you to halt the progression of the curve and read the exact
invidual values.
1. In Trend curve view, select the display with the arrow button up (the frame of the display
turns bold) and press OK at the desired point of the progressing curve. A vertical hairline
appears on the display.
2. The display freezes and the values at the bottom of the display correspond to the location of
the hairline.
3. Use the arrow buttons left and right to move the hairline to see the exact values of some
other location.
9251.emf
Figure 39.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
3
Monitoring menu vacon • 70
3.1.3 Basic
The basic monitoring values are presented in Table 3. below.
NOTE! Only standard I/O board statuses are available in the Monitor menu. Statuses for all I/O
board signals can be found as raw data in the I/O and Hardware system menu.
NOTE! Check expander I/O board statuses when required in the I/O and Hardware system
menu.
3.1.4 I/O
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
3
Monitoring menu vacon • 72
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
3
Monitoring menu vacon • 74
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
3
Monitoring menu vacon • 76
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
3
Monitoring menu vacon • 78
Monitoring
Index Unit Scale ID Description
value
Fieldbus control word used by application in
bypass mode/format. Depending on the fieldbus
V2.12.1 FB Control Word 1 874
type or profile the data can be modified before
sent to application.
Speed reference scaled between minimum and
maximum frequency at the moment it was
FB speed received by the application. Minimum and
V2.12.2 Varies 875
reference maximum frequencies can be changed after the
reference was received without affecting the
reference.
V2.12.3 FB data in 1 1 876 Raw value of process data in 32-bit signed format
V2.12.4 FB data in 2 1 877 Raw value of process data in 32-bit signed format
V2.12.5 FB data in 3 1 878 Raw value of process data in 32-bit signed format
V2.12.6 FB data in 4 1 879 Raw value of process data in 32-bit signed format
V2.12.7 FB data in 5 1 880 Raw value of process data in 32-bit signed format
V2.12.8 FB data in 6 1 881 Raw value of process data in 32-bit signed format
V2.12.9 FB data in 7 1 882 Raw value of process data in 32-bit signed format
V2.12.10 FB data in 8 1 883 Raw value of process data in 32-bit signed format
Fieldbus status word sent by application in bypass
V2.12.11 FB Status Word 1 864 mode/format. Depending on the FB type or profile
the data can be modified before sent to the FB.
Actual speed in %. 0 and 100% correspond to
minimum and maximum frequencies respectively.
V2.12.12 FB speed actual 0.01 865 This is continuously updated depending on the
momentary min and max frequencies and the
output frequency.
V2.12.13 FB data out 1 1 866 Raw value of process data in 32-bit signed format
V2.12.14 FB data out 2 1 867 Raw value of process data in 32-bit signed format
V2.12.15 FB data out 3 1 868 Raw value of process data in 32-bit signed format
V2.12.16 FB data out 4 1 869 Raw value of process data in 32-bit signed format
V2.12.17 FB data out 5 1 870 Raw value of process data in 32-bit signed format
V2.12.18 FB data out 6 1 871 Raw value of process data in 32-bit signed format
V2.12.19 FB data out 7 1 872 Raw value of process data in 32-bit signed format
V2.12.20 FB data out 8 1 873 Raw value of process data in 32-bit signed format
4. PARAMETERS MENU
4.1 Group 3.1: motor settings
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 80
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 82
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 84
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 86
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 88
Flushing parameters
Table 22. Flushing parameters
* Default value when using Standard Application. See the values for the other applications in
Appendix 1.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 90
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 92
Analogue input 2
Table 30. Analogue input 2 settings
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 94
Analogue input 3
Table 31. Analogue input 3 settings
Analogue input 4
Table 32. Analogue input 4 settings
Analogue input 5
Table 33. Analogue input 5 settings
Analogue input 6
Table 34. Analogue input 6 settings
* Default value when using Standard Application. See the values for the other applications in Appendix 1
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 96
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 98
Example: Value ‘2500’ for Output Frequency corresponds to ‘25.00 Hz’ (scaling value is 0.01).
All monitoring values listed in Chapter 3.1.12 Fieldbus data monitoring are given the scaling
value.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 100
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 102
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 104
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 106
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 108
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 110
Interval 2
Table 52. Timer functions, Interval 2
Interval 3
Table 53. Timer functions, Interval 3
Interval 4
Table 54. Timer functions, Interval 4
Interval 5
Table 55. Timer functions, Interval 5
Timer 1
Table 56. Timer functions, Timer 1
Timer 2
Table 57. Timer functions, Timer 2
Timer 3
Table 58. Timer functions, Timer 3
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 112
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 114
4.13.2 Setpoints
Table 60. Setpoints settings
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 116
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 118
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 120
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 122
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 124
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 126
4.14.3 Feedbacks
For more detailed information, see chapter 4.13.
Table 71. External PID-controller, feedbacks
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 128
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 130
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 132
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 134
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 136
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
4
Parameters menu vacon • 138
5. DIAGNOSTICS MENU
5.1 Active faults
Table 85.
Menu Function Description
Active faults When a fault/faults appear(s), the The fault remains active until it is
display with the name of the fault cleared with the Reset button (push
starts to blink. Press OK to return for 2 s) or with a reset signal from the
to the Diagnostics menu. The I/O terminal or fieldbus or by
Active faults submenu shows the choosing Reset faults (see below).
number of faults. Select the fault The memory of active faults can
and push OK to see the fault-time store the maximum of 10 faults in
data. the order of appearance.
Table 86.
Menu Function Description
Reset faults In this menu you can reset faults.
For closer instructions, see
chapter 9.1 Fault appears.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
5
Diagnostics menu vacon • 140
See further information on the counters in chapter 8.11.6 Pump running time counters.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
5
Diagnostics menu vacon • 142
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
6
I/O and hardware menu vacon • 144
Sine filter
Sine filter support restricts overmodulation depth and prevents thermal management func-
tions from decreasing switching frequency.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
6
I/O and hardware menu vacon • 146
6.5 Keypad
Table 96. I/O and Hardware menu, Keypad parameters
6.6 Fieldbus
Parameters related to different fieldbus boards can also be found in the I/O and Hardware
menu. These parameters are explained in more detail in the respective fieldbus manual.
Table 97.
Submenu level 1 Submenu level 2 Submenu level 3 Submenu level 4
RS-485 Common settings Protocol NA
Ethernet Common settings IP address mode NA
IP address NA
Subnet mask NA
Default gateway NA
MAC address NA
Modbus/TCP Common settings Connection limit
Slave address
Communication timeout
BacNet IP Settings Instance number
Communication timeout
Protocol in use
BBMD IP
BBMD port
Time to live
Monitoring FB protocol status
Communication status
Actual instance
Control Word
Status Word
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
6
User settings, favourites and user level menus vacon • 148
7.2 Favourites
NOTE! This menu is not available in the text keypad.
Favourites are typically used to collect a set of parameters or monitoring signals from any of
the keypad menus.
You might need to refer to certain parameter values or other items often. Instead of locating
them one by one in the menu structure, you may want to add them to a folder called Favourites
where they can easily be reached.
To add items or parameters to the Favourites folder, do the flollowing:
STOP READY I/O STOP READY I/O STOP READY I/O
Basic Settings Motor Nom Freq Motor Nom Freq
9166.emf
Motor Nom Speed
Add to favorites
1430 rpm
Favorites Motor Nom Freq
Help 9172.emf
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
7
User settings, favourites and user level menus vacon • 150
User levels Access code
ID:2362 P8.2 ID:2362 P8.2
User level
Normal 00000
Access code
00000
Min:0
Max:9
9173.emf
Figure 42.
8. PARAMETER DESCRIPTIONS
Due to its user-friendliness and simplicity of use, most parameters of the drive only require a
basic description, which is given in parameter tables in chapter 4 Parameters menu.
In this chapter, you will find additional information on certain most advanced parameters of the
drive. If you do not find the information you need, contact your distributor.
NOTE! The application wizards are presented in chapter 1.4 Application wizards.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 152
Table 101.
Selection
Selection name Description
number
0 Induction motor (IM) Select if an induction motor is used.
1 Permanent Magnet Motor (PM) Select if a permanent magnet motor is used.
When this parameter is changed, parameters P3.1.4.2 and P3.1.4.3 will be automatically
initialised according to the selected motor type.
See Table 102 for the initialisation values:
Table 102.
Selection
Selection name Description
number
0 No action No identification requested.
1 Identification at The drive is run without speed to identify the motor parameters.
standstill The motor is supplied with current and voltage but with zero
frequency. U/f ratio is identified.
2 Identification with The drive is run with speed to identify the motor parameters. U/f
motor rotating ratio and magnetisation current are identified.
NOTE! This identification run must be performed with no load on
the motor shaft for accurate results.
The automatic identification is activated by setting this parameter to the desired value and
giving a start command in the requested direction. The start command to the drive has to be
given within 20 s. If no start command is given within this time, the identification run is
cancelled, the parameter will be reset to its default setting and an Identification alarm will be
launched.
The identification run can be stopped at any time with normal stop command and the
parameter is reset to its default setting. An Identification alarm will be launched if the
identification run has failed.
NOTE! New start command (Rising edge) is required to start the drive after identification.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 154
3~
1
0
MS
M
3076.emf
E.g. if load drooping is set to 10% for a motor with a nominal frequency of 50 Hz and the motor
is loaded with nominal load (100 % of torque), the output frequency is allowed to decrease 5 Hz
from the frequency reference.
(ID656)
fout
3081.emf
Figure 44. Dynamic load drooping, ID 656 = P3.1.2.8 Load drooping time
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 156
U [V]
F
-EM
Stator Voltage Adjust ck
ba
Field Weakening (50..200 %)
Point Voltage
%
0
20
%
0
10
Motor Nominal
Voltage
%
50
Zero Frequency
Voltage
f [Hz]
Table 104.
Selection
Selection name Description
number
0 Linear The voltage of the motor changes linearly as a function of output
frequency from zero frequency voltage (P3.1.4.6) to the field
weakening point (FWP) voltage (P3.1.4.3) at FWP frequency
(P3.1.4.2). This default setting should be used, if there is no special
need for another setting.
1 Squared The voltage of the motor changes from zero Frequency voltage
(P3.1.4.6) following a squared curve form from zero to the Field
weakening point frequency (P3.1.4.2). See Figure 46. The motor
runs undermagnetised below the field weakening point and
produces less torque. Squared U/f ratio can be used in
applications, where torque demand is proportional to the square of
the speed, e.g. in centrifugal fans and pumps.
2 Programmable The U/f curve can be programmed with three different points (see
Figure 47.): Zero frequency voltage (P1), Midpoint voltage/
frequency (P2) and Fieldweakening point (P3). Programmable U/f
curve can be used if more torque is needed at low frequencies. The
optimal settings can automatically be achieved with Motor
identification run (P3.1.2.4).
U[V]
Un
ID603 Default: Nominal Field
voltage of the motor weakening
point
Linear
Default:
Squared Nominal frequency
of the motor f[Hz]
ID602 9094.emf
Figure 46. Linear and squared change of motor voltage, ID 602 = P3.1.4.2 Field weakening
point, ID 603 = P3.1.4.3 Voltage at field weakening point
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 158
U[V]
P3
Un
ID603 Default: Nominal Field weakening point
voltage of the motor
ID605
P2
ID606 P1 Default: Nominal
frequency of the motor
f[Hz]
ID604 ID602
9119.emf
Figure 47. Programmable U/f curve, D 602 = P3.1.4.2 Field weakening point, ID 603 =
P3.1.4.3 Voltage at field weakening point, ID 604 = P3.1.4.4 U/f midpoint frequency, ID
605 = P3.1.4.5 U/f midpoint voltage, ID 606 = P3.1.4.6 Zero frequency voltage
NOTE! This parameter is forced to value ‘1’ Linear when parameter Motor type is set to value
‘1’ Permanent Magnet Motor (PM).
NOTE! When this parameter is changed, parameters P3.1.4.2 Field weakening point frequency,
P3.1.4.3 Voltage at field weakening point, P3.1.4.4 U/f midpoint frequency, P3.1.4.5 U/f
midpoint voltage and P3.1.4.6 Zero frequency voltage will be automatically set to their default
values, if parameter P3.1.2.2 Motor type is set to ‘0’ Induction Motor (IM).
P3.1.4.7
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 160
fout
P3.1.4.12.3
MC
P3.1.4.12.2
t [s]
3082.emf
Figure 48. I/f start (MC = Motor Current), P3.1.4.12.2 = I/f start frequency, P3.1.4.12.3 =
I/f start current
Selection
Selection name Description
number
0 Coasting The motor is allowed to stop on its own inertia. The control by the
drive is discontinued and the drive current drops to zero as soon as
the stop command is given.
1 Ramp After the Stop command, the speed of the motor is decelerated
according to the set deceleration parameters to zero speed.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 162
EQ
V Control Place IN 1
1 CTRL PLACE I/O A IN 2
AND
IN 1
V Start Allowed IN 2 IO_StartFunction
KeypadStopButton:
NO = FALSE SEL
YES = TRUE P KeypadStopButton G
0 FALSE IN 0 V Trig Panel Info Info Message
KP StopButton IN 1
Drive has been forced to stop state
from keypad
9144.emf
Table 106.
Selection
Selection name Note
number
0 CS1: Forward The functions take place when the contacts are closed.
CS2: Backward
FWD Output
frequency
Set frequency
t
0 Hz
Set frequency
REV
Run enable
Ctrl signal 1
Ctrl signal 2
Keypad start
button
Keypad stop
button
1 2 3 4 5 6 7 8 9 10 11 12 13
9135.emf
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 164
Table 108.
Selection
Selection name Description
number
1 CS1: Forward (edge) For 3-wire control (pulse control)
CS2: Inverted stop
CS3: Backward (edge)
FWD Output
frequency
Set frequency
t
0 Hz
Set frequency
REV
Run enable
Ctrl signal 1
Ctrl signal 2
Ctrl signal 3
Keypad stop
button
1 2 3 4 5 6 7 8 9 10
9120.emf
Table 110.
Selection
Selection name Note
number
2 CS1: Forward (edge) Shall be used to exclude the possibility of an unintentional start.
CS2: Backward (edge) The Start/Stop contact must be opened before the motor can be
restarted.
FWD Output
frequency
Set frequency
t
0 Hz
Set frequency
REV
Run enable
Ctrl signal 1
Ctrl signal 2
1 2 3 4 5 6 7 8 9 10 11 12
9121.emf
Explanations:
Table 111.
Control signal (CS) 1 activates causing the
CS1 activates and the motor accelerates (FWD)
1 output frequency to rise. The motor runs 7
towards the set frequency
forward.
CS2 activates which, however, has no effect on Run enable signal is set to FALSE, which drops
2 the output frequency because the first selected 8 the frequency to 0. The run enable signal is
direction has the highest priority. configured with parameter P3.5.1.15.
Run enable signal is set to TRUE, which, unlike if
CS1 is inactivated which causes the direction to
value 0 is selected for this parameter, has no
3 start changing (FWD to REV) because CS2 is still 9
effect because rising edge is required to start
active.
even if CS1 is active.
Keypad stop button is pressed and the frequency
CS2 inactivates and the frequency fed to the
4 10 fed to the motor drops to 0. (This signal only
motor drops to 0.
works if P3.2.3 Keypad stop button = Yes)
CS2 activates again causing the motor to CS1 is opened and closed again which causes
5 11
accelerate (REV) towards the set frequency. the motor to start.
CS2 inactivates and the frequency fed to the CS1 inactivates and the frequency fed to the
6 12
motor drops to 0. motor drops to 0.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 166
Table 112.
Selection
Selection name Note
number
3 CS1: Start
CS2: Reverse
FWD Output
frequency
Set frequency
t
0 Hz
Set frequency
REV
Run enable
Ctrl signal 1
Ctrl signal 2
1 2 3 4 6 7 8 9 10 11 12
5 9142.emf
Table 113.
Control signal (CS) 1 activates causing the Run enable signal is set to FALSE, which drops
1 output frequency to rise. The motor runs 7 the frequency to 0. The run enable signal is
forward. configured with parameter P3.5.1.15.
Run enable signal is set to TRUE, which causes
CS2 activates which causes the direction to start
2 8 the frequency to rise towards the set frequency
changing (FWD to REV).
because CS1 is still active.
CS2 is inactivated which causes the direction to Keypad stop button is pressed and the frequency
3 start changing (REV to FWD) because CS1 is still 9 fed to the motor drops to 0. (This signal only
active. works if P3.2.3 Keypad stop button = Yes)
Also CS1 inactivates and the frequency drops to The drive starts through pushing the Start
4 10
0. button on the keypad.
Despite the activation of CS2, the motor does not The drive is stopped again with the stop button
5 11
start because CS1 is inactive. on the keypad.
CS1 activates causing the output frequency to The attempt to start the drive through pushing
6 rise again. The motor runs forward because CS2 12 the Start button is not successful because CS1 is
is inactive. inactive.
Table 114.
Selection
Selection name Note
number
4 CS1: Start (edge) Shall be used to exclude the possibility of an unintentional start.
CS2: Reverse The Start/Stop contact must be opened before the motor can be
restarted.
FWD Output
frequency
Set frequency
t
0 Hz
Set frequency
REV
Run enable
Ctrl signal 1
Ctrl signal 2
1 2 3 4 6 7 8 9 10 11
5
9143.emf
Table 115.
Control signal (CS) 1 activates causing the Run enable signal is set to FALSE, which drops
1 output frequency to rise. The motor runs 7 the frequency to 0. The run enable signal is
forward because CS2 is inactive. configured with parameter P3.5.1.15.
CS2 activates which causes the direction to start Before a successful start can take place, CS1
2 8
changing (FWD to REV). must be opened and closed again.
CS2 is inactivated which causes the direction to Keypad stop button is pressed and the frequency
3 start changing (REV to FWD) because CS1 is still 9 fed to the motor drops to 0. (This signal only
active. works if P3.2.3 Keypad stop button = Yes)
Also CS1 inactivates and the frequency drops to Before a successful start can take place, CS1
4 10
0. must be opened and closed again.
Despite the activation of CS2, the motor does not
5 11 CS1 inactivates and the frequency drops to 0.
start because CS1 is inactive.
CS1 activates causing the output frequency to
6 rise again. The motor runs forward because CS2
is inactive.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 168
8.3 References
REMOTE CONTROL PLACE (FIELDBUS): THE FREQUENCY REFERENCE COMES FROM FIELDBUS IF THE DEFAULT VALUE FOR PARAMETER
P3.3.1.10 IS KEPT.
Table 116.
Selection
Selection name Description
number
0 Binary coded Combine activated inputs according to Table 118 to choose the
Preset frequency needed.
1 Number (of inputs According to how many of the inputs assigned for Preset fre-
used) quency selections are active you can apply the Preset fre-
quencies 1 to 3.
Preset frequency 0 can be chosen as reference by selecting Value 0 (Preset Frequency 0) for
parameter P3.3.1.5 I/O A reference selection, P3.3.1.6 I/O B reference Selection, P3.3.1.7
Keypad Ctrl reference selection and P3.3.1.10 Fieldbus control reference selection.
Other preset frequencies 1 to 7 are selected as reference by dedicating digital inputs for
parameters P3.3.3.10, P3.3.3.11 and/or P3.3.3.12. Combinations of active digital inputs
determine the used preset frequency according to Table 118 below.
The values of the preset frequencies are automatically limited between the minimum and
maximum frequencies (P3.3.1.1 and P3.3.1.2). See table below:
Table 117.
Required action Activated frequency
Choose value 1 for parameters Preset frequency 0
P3.3.1.5, P3.3.1.6, P3.3.1.7 and
P3.3.1.10.
Preset frequencies 1 to 7:
Table 118. Selection of preset frequencies; = input activated
Connect a digital input to these functions (see chapter 8.5.1 Programming of digital and
analogue inputs) to be able to apply Preset frequencies 1 to 7 (see Table 118 above).
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 170
Selection
Selection name Note
number
0 No reset The previous motor potentiometer frequency reference is kept
past the stop state and stored to memory in case of powerdown.
1 Stop state Motor potentiometer frequency reference is set to zero when the
drive is in stop state or the drive is powered down.
2 Powered down Motor potentiometer frequency reference is set to zero only in a
powerdown situation.
Frequency
Reference
Max
Frequency
Motor potentiometer
ramp time
Min
Frequency
Time [s]
Motor potentiometer
UP
Motor potentiometer
DOWN
9122.emf
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 172
The start and end of acceleration and deceleration ramps can be smoothed with these
parameters. Setting the value to 0.0% gives a linear ramp shape, which causes acceleration
and deceleration to act immediately to the changes in the reference signal.
Setting the value to 1.0…100.0% for this parameter produces an S-shaped acceleration/
deceleration. This function is typically used to reduce mechanical erosion and current spikes
when the reference is changed.
fout
0%
10 %
t [s]
3077.emf
Figure 56.
fout
[Hz]
P3.4.2.2 P3.4.2.3
P3.4.5.2
P3.4.1.2
P3.4.1.3
t [s]
3079.emf
Figure 57. Ramp 2 activation when output frequency exceeds the threshold level.
(P.3.4.5.2 = Ramp threshold freg., P3.4.1.2 = Acc. time 1, P3.4.2.2 = Acc. time 2, P3.4.1.3
=Dec. time 1, P3.4.2.3 = Dec. time 2)
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 174
Figure 59.
Given the standard I/O board compilation on the Vacon® 100 AC drive, there are 6 digital inputs
available (Slot A terminals 8, 9, 10, 14, 15 and 16). In the programming view, these inputs are
referred to as follows:
Table 120.
In the example 61, the function External fault close located in menu M3.5.1 as parameter
P3.5.1.11, is by default given the value DigIN SlotA.3 (graphical keypad) or dI A.3 (text keypad).
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 176
This means that the function External fault close is now controlled with a digital signal to
digital input DI3 (terminal 10).
This is what is shown in Table 28. Digital input settings in chapter 4:
Code Parameter Default ID Description
FALSE = OK
P3.5.1.11 External fault close DigIN SlotA.3 405
TRUE = External fault
Assume you need to change the selected input. Instead of DI3 you wish to use DI6 (terminal 16)
on the standard I/O. Do as instructed here:
BACK
BACK RESET
RESET
9260.emf
PROGRAMMING INSTRUCTIONS
Graphical keypad Text keypad
1. Select the parameter and push the Arrow 1. Select the parameter and push the OK but-
right button. ton.
2. You are now in the Edit mode as the slot 2. You are now in the Edit mode as the letter d
value DigIN SlotA. is blinking and is blinking. (Should you have more digital
underlined. (Should you have more digital inputs available in your I/O, for example,
inputs available in your I/O, for example, through inserted option boards in slots C, D
through inserted option boards in slots C, or E, they can also be selected here.). See
D or E, they can also be selected here.). Figure 62.
See Figure 62.
3. Push the Arrow right button again to acti- 3. Push the Arrow right button to activate the
vate the terminal value 3. terminal value 3. The letter d stops blinking.
4. Push the Arrow up button three times to 4. Push the Arrow up button three times to
change the terminal value to 6. Confirm change the terminal value to 6. Confirm with
with OK button. OK button.
5. NOTE! If the digital input DI6 was already 5. NOTE! If the digital input DI6 was already
used for some other function a message is used for some other function a message will
displayed. You might then want to change scroll through the display. You might then
either of these selections. want to change either of these selections.
Now, the function External fault close is controlled with a digital signal to digital input DI6
(terminal 16).
NOTE! The function is not assigned to any terminal, or, the the input is set to be always FALSE,
if its value is DigIN Slot0.1 (graphical keypad) or dI 0.1 (text keypad). This is the default value of
the majority of parameters in the group M3.5.1.
On the other hand, some inputs have been by default set to be always TRUE. Their value shows
DigIN Slot0.2 (graphical keypad) or dI 0.2 (text keypad).
NOTE! Also Time Channels can be assigned to digital inputs. See more information in Table 63.
Sleep function settings in chapter 4.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 178
Parameter name
Parameter value (= selected analogue input)
GRAPHICAL KEYPAD
Parameter name
Figure 62.
Given the standard I/O board compilation on the Vacon® 100 AC drive, there are two analogue
inputs available (Slot A terminals 2/3 and 4/5). In the programming view, these inputs are
referred to as follows:
Table 122. Programming analogue inputs
In the example 64, the parameter AI1 signal selection located in menu M3.5.2.1 with
parameter code P3.5.2.1.1, is by default given the value AnIN SlotA.1 (graphical keypad) or AI
A.1 (text keypad). This means that the target input for the analogue frequency reference signal
AI1 is now the analogue input in terminals 2/3. Whether the signal is voltage or current, must
be determined with the dip switches. See the Installation manual for more information.
This is what is shown in the parameter list in Table 29. General protections settings in chapter
4:
Code Parameter Min Max Unit Default ID Description
Connect the AI1 signal to the
AnIN analogue input of your choice
P3.5.2.1.1 AI1 signal selection 377
SlotA.1 with this parameter.
Programmable. See ch. 8.5.1
Assume you need to change the selected input. Instead of AI1 you wish to use the analogue
input on your option board in slot C. Do as instructed here:
9264 emf
Figure 63. Programming analogue inputs with graphical keypad
PROGRAMMING INSTRUCTIONS
Graphical keypad Text keypad
1. Select the parameter and push the Arrow 1. Select the parameter and push the OK
right button. button.
2. You are now in the Edit mode as the slot 2. You are now in the Edit mode as the letter A
value AnIN SlotA. is blinking and is blinking.
underlined.
3. Push the Arrow up button once to change 3. Push the Arrow up button once to change
the slot value to AnIN SlotC. Confirm with the slot value to C. Confirm with OK button.
OK button.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 180
Source Function
Digital inputs:
A digital signal can be forced to a constant OPEN or CLOSED
state using this functionality.
For example, some signals have been set to be always in
CLOSED state by manufacturer, e.g parameter P3.5.1.15
(Run enable). Unless changed, Run enable signal is always
on.
Slot0.# # = 1: Always OPEN
# = 2-10: Always CLOSED
Analogue inputs (used for testing purposes):
# = 1: Analogue input = 0% signal strength
# = 2: Analogue input = 20% signal strength
# = 3: Analogue input = 30% signal strength
etc.
# = 10: Analogue input = 100% signal strength
SlotA.# Number (#) corresponds to digital input in slot A.
Unfiltered signal
100%
Filtered signal
63%
t [s]
ID378
9095.emf
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 182
Selection
Selection name Description
number
0 0…10 V/0…20 mA Analogue input signal range 0…10 V or 0…20
mA (depending on dip switch settings on the
control board). Input signal used 0…100%.
Frequency
reference
[Hz]
Max freq
reference
Selection
Selection name Description
number
1 2…10 V/4…20 mA Analogue input signal range 2…10 V or 4…20
mA (depending on dip switch settings on the
control board). Input signal used 20…100%.
Frequency
reference
[Hz]
Max freq
reference
9245.emf
Min freq Analog input
reference 0% 20 % 50 % 100 % signal [%]
0 mA 4 mA 10 mA 20 mA
These parameters allow you to freely adjust the analogue input signal range between -160…160%.
Example: If the analogue input signal is used as frequency reference and these parameters
are set to 40…80%, the frequency reference is changed between the Minimum frequency
reference and the Maximum frequency reference when the analogue input signal is changed
between 8…16 mA.
Frequency
reference
[Hz]
Max freq
reference
9246.emf
Min freq Analog input
reference 0% 40% 80% 100 % signal [%]
0 mA 8 mA 16 mA 20 mA
AI custom AI custom
min max
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 184
In the following examples, the analogue input signal is used as frequency reference. The
figures show how the scaling of the analogue input signal is changed depending on the setting
of this parameter.
Selection
Selection name Description
number
0 Normal No inversion. The analogue input signal value
0% corresponds to the Minimum frequency
reference and the analogue input signal value
100% to the Maximum frequency reference.
Frequency
Reference
[Hz]
Max Freq
Reference
9247.emf
Frequency
reference
[Hz ]
Max freq
reference
9248.emf
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 186
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 188
These parameters can be used to freely adjust the analogue output signal scaling. The scale is
defined in process units and it depends on the selection of parameter P3.5.4.1.1.
Example: The drive’s output frequency is selected for the content of the analogue output
signal and parameters P3.5.4.1.4 and P3.5.4.1.5 are set to 10…40 Hz.
When the drive’s output frequency changes between 10 and 40 Hz the analogue output signal
changes between 0…20 mA.
Analog
output signal
[%]
100%
20 mA
50%
10 mA
9249.emf Output
0%
0 mA frequency
0 Hz 10 Hz 40 Hz Max freq
reference
[Hz]
AO min AO max
scale scale
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 190
Actual Reference
High Lim
Low Lim
9118.emf
Output Frequency
[Hz]
High Lim
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 192
8.7 Supervisions
CAUTION! The calculated model does not protect the motor, if the airflow
to the motor is reduced by a blocked air-intake grill. The model starts from
13006.emf
zero, if the control board is powered off.
P
cooling
Overload area
100% IT
Par.
ID706=40%
0 Corner freq fn f
9129.emf
Figure 74. Motor thermal current IT curve, ID 706 = P3.9.2.3 Zero speed cooling factor
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 194
I/IT
Current
t
T
100%
63%
9077.emf
t
T = Motor thermal time constant
I/IT
Current
t
Fault/
Alarm
T
Trip area
105%
9078.emf
t
Loadability 80%
Loadability 100%
Loadability 130%
I 9130.emf
Stall area
Par. ID710
Par. ID712
Figure 77. Stall characteristics settings, ID 710 = P3.9.3.2 Stall current, ID 712 = P3.9.3.4
Stall frequency limit
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 196
Par.
ID714
Par.
ID715 Underload area
f
5 Hz Fieldweakening
point 9131.emf
Figure 78. Setting of minimum load, ID 714 = P3.9.4.2 Underload protection: Field
weakening area load, ID 715 = P3.9.4.3 Underload protection: Zero frequency load
Trip area
Par. ID716
Trip/warning
par. ID713
Time
Underload•
No underl.
9132.emf
Figure 79. Underload time counter function, ID 713 = P3.9.4.1 Underload fault, ID 716 =
P3.9.4.4 Underload protection:Time limit
The Quick stop function is a way to stop the drive in an exceptional manner from I/O or Fieldbus
in an exceptional situation. The drive can be made to decelerate and stop according to a
separately defined method when the Quick stop is activated. An alarm or fault response can
also be set to leave a mark that a quick stop has been requested in the fault history, if a reset
is required for restart.
NOTE! Quick stop is not an emergency stop or safety function! It is advised that an emergency
stop physically cuts the power supply to the motor.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 198
FB Control Word.B12
OR
Quick Stop
IN 1
Activated
IN 2
Yes
Start stop
sequence
according to
”Quick Stop Mode”
and ”Quick Stop
Deceleration
Time”
Drive stopped?
NO
Yes
Drive forced to
”Not Ready” mode
and alarm/fault
trigged according
to ”Quick Stop
Fault Response”
Quick Stop
Activated
9124.emf
Selection
Selection name Description
number
1 Protection disabled
2 Protection enabled in The protection is enabled only when the
Run state drive is in run state
3 Protection enabled in Protection is enabled in both, run and stop
Run and Stop states
Selection
Selection name Description
number
1 Alarm
2 Alarm P3.9.1.13 is set to frequency reference
3 Alarm The last valid frequency is kept as
frequency reference
4 Fault Stop according to Stop mode P3.2.5
5 Fault Stop by coasting
NOTE! AI Low Fault response 3 (Alarm + Previous Freq) can be used only, if analogue input 1
or analogue input 2 is used as frequency reference.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 200
NOTE! Automatic reset is allowed for certain faults only. By giving the parameters P3.10.6 to
P3.10.13 the value 0 or 1 you can either allow or deny the automatic reset after the respective
faults.
Alarm
Reset 1 Reset 2
Autoreset
Fault active
9096.emf
Figure 81. Automatic reset function, ID = 717 P3.10.3 Wait time, P3.10.4 Trial time,
ID 759 = P3.10.5 Number of trials
P AssignToChannel
Interval 1
TimeChannel 1
Interval 2
Interval 3
Interval 4
TimeChannel 2
Interval 5
Timer 1
Timer 2
TimeChannel 3
Timer 3
9146.emf
Figure 82. The intervals and timers can be assigned to time channels in a flexible way.
Every interval and timer has its own parameter for assigning to a time channel.
Intervals
Every interval is given an "ON Time" and "OFF Time" with parameters. This is the daily time
that the interval will be active during the days set with "From Day" and “To Day” parameters.
E.g. the parameter setting below means that the interval is active from 7 am to 9 am every
weekday (Monday to Friday). The Time Channel to which this Interval is assigned will be seen
as a closed "virtual digital input" during that period.
ON Time: 07:00:00
OFF Time: 09:00:00
From Day: Monday
To Day: Friday
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 202
Timers
Timers can be used to set the active Time Channel during a certain time by a command from a
digital input (or a Time Channel).
The below parameters will set the Timer active when Digital Input 1 on Slot A is closed and
keep it active for 30 s after it is opened.
Duration: 30 s
Timer: DigIn SlotA.1
Tip! A duration of 0 seconds can be used for simply overriding a Time channel activated from
a digital input without any off delay after the falling edge.
EXAMPLE
Problem:
We have an AC drive for air conditioning in a warehouse. It needs to run between 7am - 5pm
on weekdays and 9am - 1pm on weekends. Additionally, we need to be able to manually force
the drive to run outside working hours, if there are people in the building and to leave it running
for 30 min afterwards.
Solution:
We need to set up two intervals, one for weekdays and one for weekends. A Timer is also
needed for activation outside the office hours. An example of configuration below.
Interval 1:
P3.12.1.1: ON Time: 07:00:00
P3.12.1.2: OFF Time: 17:00:00
P3.12.1.3: Days: Monday, Tuesday, Wednesday, Thursday, Friday
P3.12.1.4: Assign to channel: Time channel 1
Interval 1 Days Days
ID:1466 M3.12.1.3 ID: M3.12.1.3 ID: M3.12.1.3.1
ON Time Sunday
Edit
07:00:00 Monday
Days Thursday
Add to favorites
0 Friday
9158.emf
Figure 83.
Interval 2:
P3.12.2.1: ON Time: 09:00:00
P3.12.2.2: OFF Time: 13:00:00
P3.12.2.3: Days: Saturday, Sunday
P3.12.2.4: AssignToChannel: Time channel 1
Timer 1
The manual bypassing can be handled by a digital input 1 on slot A (by a different switch or
connection to lighting).
P3.12.6.1: Duration: 1800 s (30 min)
P3.12.6.3: Assign to channel: Time channel 1
Figure 84. Final configuration, where Time channel 1 is used as control signal for start
command instead of a digital input.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 204
Actual value
Dead band delay (ID1057)
Output locked
9097.emf
8.10.1 Feedforward
Level ref
+ +
PID FFW
LT FT Outflow
control
Level control
9099.emf
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 206
Actual value
Wake-up level
(ID1018)
Sleep delay
Frequency
(ID1017)
Sleep limit
9098.emf
(ID1016)
If the actual value does not reach the incremented setpoint, the boost value is anyway cleared
after the time set with P3.13.5.5. In this case the drive returns to normal regulation with normal
setpoint.
ID736)
Reference
Lower limit
(ID758)
Delay (ID737)
9100.emf
Regulating mode Alarm or fault
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 208
Pressure
No flow
With flow
Pipe length
PT PT
Position 1 Position 2
9101.emf
When pressurising a long pipe with many outlets, the best place for the sensor would probably
be halfway down the pipe (Position 2). However, sensors might, for example, be placed directly
after the pump. This will give the right pressure directly after the pump, but farther down in
the pipe the pressure will drop depending on the flow.
Setpoint
Setpoint
Pipe length
PT PT
Position 1 Position 2
9102.emf
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 210
0 = Disabled
Soft Fill function is disabled and not used.
1 = Enabled (Level)
Soft Fill function is enabled. When the drive is started, the drive runs at a constant frequency
(P3.13.8.2 Soft Fill Frequency) until the PID feedback signal reaches the soft fill level (P3.13.8.3
Soft Fill Level). When soft fill level is reached, PID controller starts to regulate.
In addition, if the soft fill level is not reached within the soft fill timeout (P3.13.8.4 Soft Fill
Timeout), a soft fill fault is generated (if P3.13.8.4 Soft Fill Timeout is set to greater than zero).
The soft fill mode is typically used in vertical installations.
2 = Enabled (Timeout)
Soft Fill function is enabled. When the drive is started, the drive runs at a constant frequency
(P3.13.8.2 Soft Fill Frequency) until the soft fill time (P3.13.8.4 Soft Fill Timeout) has elapsed.
After the soft filling time, PID controller starts to regulate.
In this mode, soft fill fault is not available.
This soft fill mode is typically used in horizontal installations.
Reference
Actual value
Soft fill level
Frequency
9105.emf
Soft fill mode Regulating mode
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 212
A temporary bias value is added to Actual value. If Output frequency falls below Sleep
frequency threshold for the required amount of time while Error remains within the band, the
drive enters sleep mode and Actual value bias is removed.
If any of the following conditions occur:
- The error exceeds the hysteresis band
- Output frequency variation exceeds SNDD frequency hysteresis,
the bias on Actual is removed and normal operation is resumed.
The bias increment on Actual will be positive with direct PID regulation (P3.13.1.8 = Normal),
and negative with reverse PID regulation (P3.13.1.8 =Inverted).
The function is enabled by parameter SNDD Enable. The function is inactive, if any of the
related parameters = 0.
fout
A
D E t
G H I
t
3094.emf
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 214
3~
PT
I O 3080.emf
Input Pressure
PID Setpoint
PID Setpoint
Reduction
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 216
Now, the basic settings of Multipump system are configured. Same check list can be used
when configuring the next drives in the system.
Single Drive mode is designed to control a system of one variable speed pump and up to 7
auxiliary pumps. The internal PID controller of the drive controls the speed of one pump and
gives control signals (via relay outputs) to start/stop the auxiliary pumps. External contactors
are needed to switch the auxiliary pumps to supply mains.
3~
Start / Stop
RO2
RO3
RO8
M1 M2 M3 M8
M1
PT
M2
M3
M8
3088.emf
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 218
Multidrive configuration
Multidrive modes (Multimaster and Multifollower) are designed to control a system of up to 8
variable speed pumps. Each pump is controlled by its own drive. The internal PID controller of
the drive regulates all pumps. Drives communicate via communication bus (Modbus RTU).
The figure below presents the Multidrive configuration principle. See also the general electric
diagramme of a multipump system in chapter 1.5.4.2 Multipump (Multidrive) system electric
wiring diagramme.
3~
Start / Stop
M1 M2 M3 M8
M1
PT
M2
M3
3089.emf
M8
0 = Single drive
Single drive mode is designed to control a system of one variable speed pump and up to 7
auxiliary pumps. The internal PID controller of the drive controls the speed of one pump and
gives control signals (via relay outputs) to start/stop the auxiliary pumps. External contactors
are needed to switch the auxiliary pumps to supply mains.
One of the pumps is connected to the drive. This pump operates as a regulating pump. When
the regulating pump notices a demand for more capacity (running at maximum frequency),
but cannot produce this by itself, it requests the next auxiliary pump to start via relay output
signal. When the auxiliary pump is started, the regulating pump continues regulating, starting
from minimum frequency.
When the regulating pump notices that there is too much capacity (running at minimum
frequency), it requests the recently started auxiliary pump to stop. If there are no auxiliary
pumps running when the regulating pump notices overcapacity, it will go into Sleep mode (if
Sleep function is enabled).
RPM
B
fmax
fmin
3095.emf
P1 P2 P3
Figure 97. Pump regulation in Single drive mode
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 220
When the regulating pump notices that there is too much capacity (running at minimum
frequency), it requests the recently started pump to stop. If there are no auxiliary pumps
running when the regulating pump notices overcapacity, it will go into Sleep mode (if Sleep
function is enabled).
RPM
fmax
A
fmin
3072.emf
P1 P2 P3
Figure 98. Regulation in Multifollower mode. Pump 1 is regulating, and pumps 2 and 3 are
following the speed of pump 1, as shown with curves A.
1 = Multimaster
Multimaster mode is designed to control a system of up to 8 variable speed pumps. Each
pump is controlled by its own drive. The internal PID controller of the drive regulates the
pumps.
One of the pumps operates always as a regulating pump. When the regulating pump notices a
demand for more capacity (running at maximum frequency), but cannot produce this by itself,
it locks itself at a constant producing speed and requests the next pump to start and start to
regulate.
When the regulating pump notices that there is too much capacity (running at minimum
frequency), it stops itself and the pump running at a constant producing speed starts to
regulate.
If there are several pumps running at a constant producing speed, the recently started pump
starts to regulate. If there are no pumps running at constant producing speed when the
regulating pump notices overcapacity, it will go into Sleep mode (if Sleep function is enabled).
B
RPM
fmax
A
fmin
t
3073.emf
P1 P2 P3
Figure 99. Regulation in Multimaster mode. Curves A show the regulating of the pumps.
B = The pumps are locked to constant production frequency
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 222
8.11.3 Interlocks
Interlock function can be used to tell Multipump system by digital input signals, which pumps
are available in the system, and which are not. Multipump system controls only the pumps with
active interlock data.
This function can be used to tell the Multipump system e.g. if one of the pumps is removed from
the system for maintenance. Interlock signals typically come from motor switches.
3096.emf
A common sensor can also be used. The sensor (transducer) can be supplied either by using
the external 24V power supply or from the drive control board.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 224
3097.emf
Figure 101.Principle wiring of common sensor (supplied from the drive I/O board)
- External 24V
+ Supply
3098.emf
Figure 102. Principle wiring of common sensor (supplied from the external 24V)
In Multidrive configuration, the digital inputs are isolated from the ground, meaning that digital
input is active when connected to GND. Isolation DIP switch needs to be set to 'Float' position.
See Figure 103. below.
Digital inputs
Floating
Connected to GND (Default!)
9109.emf
Table 129.
EXAMPLE:
In the autochange sequence after the autochange has taken place, the motor with the highest
priority is placed last and the others are moved up by one place:
Starting order/priority of motors: 1->2->3->4->5
--> Autochange -->
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 226
Table 130.
WIRING
There are two different ways to make the connections depending on whether selection 0 or 1
is set as parameter value.
0 = Auxiliary pumps:
The AC drive or the regulating motor is not included in the autochange or interlocks logic. The
drive is directly connected to motor 1 as in Figure 104. below. The other motors are auxiliary
ones, connected to the mains by contactors and controlled by relays in the drive.
3~
K2 K3
M1 M2 M3
M1 RO M2 RO M3 RO
X K2 K3
3086.emf
1 = All pumps:
If the regulating motor needs to be included in the autochange or interlock logic, make the
connection according to Figure 105. below.
Every motor is controlled with one relay and the contactor logic makes sure that the first
connected motor is always connected to the drive and next to the mains.
3~
M1 M2 M3
M1 RO M2 RO M3 RO
K3 K2 K3 K3 K1 K3 K1 K2 K1
K2 K1 K2
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 228
Figure 106. Criteria for starting and stopping the auxiliary pumps. (P3.15.13 = Bandwidth,
P3.15.14 = Bandwidth delay)
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 230
These parameters define the digital inputs of the drive, where the interlocking (feedback)
signals of pumps 2…8 are read.
NOTE! These parameters are used in Single Drive mode only.
If Pump Interlocking function (P3.15.5) is enabled, the drive will read the status of Pump
Interlock (feedback) digital inputs. If the input is closed (TRUE), the motor is available for the
Multipump system, otherwise it will not be included to Multipump system.
If Pump Interlocking -function (P3.15.5) is not used, the statuses of Pump Interlock (feedback)
digital inputs are not read and the Multipump system assumes that all pumps in the system
are available.
Pr essur e
PID Feedback
Superv. (ID21)
Alarm Level
ID1699
PID Setpoint
ID167
Motor 2 ON
OFF
Motor 3 ON
OFF
9133.emf
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 232
NOTE! In Multimaster and Multifollower modes, it is possible to reset (or set to desired value)
only the "Pump (1) Running Time" counter. (In Multimaster and Multifollower modes, "Pump
(1) Running Time" monitoring value indicates the hours of the pump, which is connected to this
drive, regardless of the pump ID number).
Example:
In Multipump (Single drive) system, pump number 4 has been replaced with a totally new pump
and the "Pump 4 Running Time" counter value needs to be reset.
1. Select 'Pump' 4 by parameter P3.15.19.3.
2. Set parameter P3.15.19.2 value to '0 h'.
3. Press button-type parameter P3.15.19.
4. "Pump 4 Running Time" has been reset.
NOTE!
• In Multipump (Single drive) mode, alarm and fault limits are common for all pumps. An
alarm or fault will be triggrered, if any of the individual runtime counters (Pump
1…Pump 8) exceeds the limit value.
• In Multimaster and Multifollower modes, each drive monitors only its own pump
running time ('Pump (1) Running Time'). This means that alarm and fault limits have to
be activated and configured individually for each drive.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 234
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 236
Normal
Start
Run
Enable
Run
Interlock 1
Run
Interlock 2
Fire Mode
Activation
(Close contact)
Motor Speed
Fire Mode
Speed
Normal
Speed
Stopped
9138.emf
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 238
8.15.1 Auto-cleaning
Auto-cleaning function is used to remove any dirt or other material that may have attached to
the pump impeller. Auto-cleaning is used e.g. in wastewater systems to keep up the
performance of the pump. Auto Cleaning function can also be used to clear the blocked pipe or
valve.
The function is based on rapidly accelerating and decelerating the pump. See Figure 109. and
the parameter descriptions below:
fout
ID1721 ID1722
ID1718
ID1717
ID1719
ID1720
ID1715
3090.emf
Figure 109. Auto-cleaning function. (0 = zero frequency, ID1716 = cleaning cycles 1 and
2), ID 1715 = P3.5.1.41 Auto-cleaning activation, ID 1717 = P3.21.1.8 Clean forward
frequency, ID 1718 = P3.21.1.9 Clean forward time, ID 1719 = P3.21.1.10 Clean reverse
frequency, ID 1720 = P3.21.1.11 Clean reverse time, ID 1721 = P3.21.1.12 Cleaning
acceleration time, ID 1722 = P3.21.1.13 Cleaning deceleration time
NOTE! The cleaning sequence can always be stopped by deactivating the drive start command.
If Auto Cleaning function is enabled by parameter P3.21.1.1, Auto Cleaning sequence will be
started by activating the digital input signal selected by parameter P3.21.1.2.
The cleaning function is based on rapidly accelerating and decelerating the pump. With these
parameters the user can define the forward/reverse cycle times.
The user can also define separated acceleration and deceleration ramps for Auto-cleaning
function with these parameters.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 240
Table 132.
Selection
Selection name Description
number
0 Not used
1 PID sleep Jockey pump will start when the PID Sleep on the main pump is
active and stopped when the main pump wakes from sleep.
2 PID sleep (level) Jockey pump will start when PID Sleep is active and the PID
feedback signal goes below the level defined by parameter
P3.21.2.2. Jockey Pump will be stopped when the feedback
exceeds the level defined by parameter P3.21.2.3 or the main
pump wakes from sleep.
Start
Command
(Main Pump)
Priming Pump
Control
(Digital Output Signal)
Priming Time
Output Freq
(Main Pump) 9141.emf
Figure 111.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 242
8.15.6 Counters
Vacon® 100 drive has different counters based on the drive operating time and energy
consumption. Some of the counters are measuring total values and some counters can be
reset by the user.
Energy counters are used to measure the energy taken from the supply network and the other
counters are used to measure e.g. drive operation time or motor running time.
All counter values can be monitored either from PC, Keypad or Fieldbus. In case of Keypad or
PC monitoring, counter values can be monitored from M4 Diagnostics menu. In case of
Fieldbus, counter values can be read by means of ID numbers.
The purpose of this chapter is to describe counter values and ID numbers, which are needed
when reading the counter values via Fieldbus.
This chapter is valid for software packages FW0065V017.vcx and FW0072V003.vcx or newer.
Example:
Operating Time Counter value ‘1a 143d 02:21’ is read from Fieldbus:
ID1754: 1 (years)
ID1755: 143 (days)
ID1756: 2 (hours)
ID1757: 21 (minutes)
ID1758: 0 (seconds)
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 244
Example:
Operating Time Trip Counter value ‘1a 143d 02:21’ is read from Fieldbus:
ID1754: 1 (years)
ID1755: 143 (days)
ID1756: 2 (hours)
ID1757: 21 (minutes)
ID1758: 0 (seconds)
Example:
Run Time Counter value ‘1a 143d 02:21’ is read from Fieldbus:
ID1754: 1 (years)
ID1755: 143 (days)
ID1756: 2 (hours)
ID1757: 21 (minutes)
ID1758: 0 (seconds)
Example: Power On Time Counter value ‘1a 240d 02:18’ is read from Fieldbus:
ID1754: 1 (years)
ID1755: 240 (days)
ID1756: 2 (hours)
ID1757: 18 (minutes)
ID1758: 0 (seconds)
Energy counter
Total amount of energy taken from supply network. The counter cannot be reset. The counter value can
be read from the drive by reading the values of the following ID numbers via Fieldbus.
Energy Counter value consists of the following 16-bit (UINT) values.
Example:
0.001 kWh
0.010 kWh
0.100 kWh
1.000 kWh
10.00 kWh
100.0 kWh
1.000 MWh
10.00 MWh
100.0 MWh
1.000 GWh
…etc.
Example:
If value 4500 is read from ID2291, and value 42 from ID2303 and value 0 from ID2305:
This means 45.00 kWh.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Parameter descriptions vacon • 246
Example:
0.001 kWh (Format = 43)
100.0 kWh (Format = 41)
10.00 MWh (Format = 42)
0 = kWh
1 = MWh
2 = GWh
3 = TWh
4 = PWh
Energy Counter format and unit can be monitored by ID2307 Energy Trip Counter Format and
ID2309 Energy trip Counter unit.
Example:
0.001 kWh
0.010 kWh
0.100 kWh
1.000 kWh
10.00 kWh
100.0 kWh
1.000 MWh
10.00 MWh
100.0 MWh
1.000 GWh
…etc.
Example:
0.001 kWh (Format = 43)
100.0 kWh (Format = 41)
10.00 MWh (Format = 42)
In case of Fieldbus, Energy Trip Counter can be reset by writing rising edge (0 => 1) to ID2312 Energy
Trip Counter Reset.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
8
Fault tracing vacon • 248
9. FAULT TRACING
When an unusual operating condition is detected by the AC drive control diagnostics, the drive
initiates a notification visible, for example, on the keypad. The keypad will show the code, the
name and a short description of the fault or alarm.
The notifications vary in consequence and required action. Faults make the drive stop and
require reset of the drive. Alarms inform of unusual operating conditions and require
resetting, but the drive will continue running. Infos require resetting but do not affect the functioning
of the drive.
For some faults you can programme different responses in the application. See parameter
group Protections.
The fault can be reset with the Reset button on the control keypad or through the I/O terminal,
fieldbus or PC tool. The faults are stored in the Fault history menu which can be browsed. The
different fault codes you will find in the table below.
NOTE! When contacting distributor or factory because of a fault condition, always write down
all texts on the display, the fault code, the fault ID, the source info, the Active Fault list and the
Fault History.
Source info tells the user the origin of the fault, what caused it, where it happened, and other
detailed information
Main Menu Diagnostics Reset faults
ID: M4 ID: M4.1 ID: M4.2
Monitor Active faults
( 5 ) ( 0 ) Reset faults
Parameters
( 12 ) Reset faults Help
9152.emf
Diagnostics
( 6 )
Fault history
( 39 )
Figure 112.
12. For text keypad only: By selecting value Yes for the parameter and clicking OK.
9153.emf
Figure 113.
Diagnostics Fault history Device removed
ID: M4.1 ID: M4.3.3 ! ID: M4.3.3.2
Active faults External Fault 51 Code 39
( 0 ) ! Fault old 891384s ID 380
External Fault 51 State Info old
Reset faults ! Fault old 871061s Date 7.12.2009
9154.emf
Fault history Device removed 39 Time 04:46:33
( 39 ) ! Info old 862537s Operating time 862537s
Source1
Source2
Source3
Figure 114.
The displays on the Text keypad:
9155.emf
Figure 115.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
9
Fault tracing vacon • 250
Fault Fault
Fault name Possible cause Remedy
code ID
Overcurrent AC drive has detected too high a cur-
1 Check loading.
(hardware fault) rent (>4*IH) in the motor cable:
Check motor.
• sudden heavy load increase Check cables and connections.
1 • short circuit in motor cables
Overcurrent Make identification run.
2 • unsuitable motor Set acceleration time longer
(software fault)
• parameter settings are not properly (P3.4.1.2/ P3.4.2.2).
made
Overvoltage The DC-link voltage has exceeded the Set deceleration time longer
10
(hardware fault) limits defined. (P3.4.1.3/P3.4.2.3).
2
Overvoltage (soft- • too short a deceleration time Activate overvoltage controller.
11 • high overvoltage spikes in supply Check input voltage.
ware fault)
Earth fault (hard- Current measurement has detected
20
ware fault) that the sum of motor phase current is
Check motor cables and motor.
3 not zero.
Earth fault (soft- • insulation failure in cables or motor Check filters.
21
ware fault) • filter (du/dt, sinus) failure
Reset the fault and restart.
Check the feedback signal and
Charging switch is closed and the feed- the cable connection between
back information still is ‘OPEN’. the control board and the power
5 40 Charging switch
• faulty operation board.
• component failure Should the fault re-occur,
contact the distributor near to
you.
Various causes:
Cannot be reset from keypad.
• IGBT does not execute its operation
Switch off power.
(is defective)
7 60 Saturation DO NOT RESTART or
• de-saturation short-circuit in IGBT
RE-CONNECT POWER!
• brake resistor short-circuit or over-
Contact factory.
load
Fault Fault
Fault name Possible cause Remedy
code ID
600 Communication between control board
601 and power unit has failed.
Component failure.
602
Faulty operation.
Component failure.
Faulty operation.
603
Voltage of auxiliary power in power unit
is too low.
Component failure. Reset the fault and restart.
Faulty operation. Download and update with the
604 Output phase voltage does not follow latest software available on
the reference. Vacon website.
Feedback fault. Should the fault re-occur,
contact the distributor near to
Component failure.
605 you.
Faulty operation.
Control and power unit software are
606
incompatible
Software version cannot be read. There
is no software in power unit.
607 Component failure.
Faulty operation (power board or mea-
8 System fault surement board problem).
608 CPU overload.
RESET the fault and power the
drive down twice.
Component failure.
609 Download and update with the
Faulty operation.
latest software available on
Vacon website.
Component failure.
610
Faulty operation.
Configuration error
Software error Reset the fault and restart.
614 Download and update with the
Component failure (control board)
Faulty operation latest software available on
Vacon website.
Component failure. Should the fault re-occur, con-
647
Faulty operation. tact the distributor near to you.
Faulty operation.
648 System software and application are
not compatible.
Load factory default settings.
Resource overload.
Download and update with the
649 Parameter loading, restoring or saving
latest software available on
failure.
Vacon website.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
9
Fault tracing vacon • 252
Fault Fault
Fault name Possible cause Remedy
code ID
In case of temporary supply
DC-link voltage is under the voltage voltage break reset the fault
limits defined. and restart the AC drive. Check
• too low a supply voltage the supply voltage. If it is
Undervoltage • component failure adequate, an internal failure
9 80
(fault) • defect input fuse has occurred.
• external charge switch not closed Check the electrical network
NOTE! This fault is activated only if the for failures.
drive is in Run state. Contact the distributor near to
you.
• problem in supply voltage
Check supply voltage, fuses and
• fuse failure or failure in the supply
supply cable, rectifying bridge
10 91 Input phase cables
and gate control of the thyristor
The load must be 10-20% minimum in
(MR6->).
order to the supervision to work.
Current measurement has detected
Output phase missing current in one motor phase. Check motor cable and motor.
11 100
supervision • problem in motor or motor cables. Check the du/dt or sinus filter.
• filter (du/dt, sinus) failure
Brake chopper Check brake resistor and
110 supervision No brake resistor installed. cabling.
12 (hardware fault) Brake resistor is broken. If these are ok, the resistor or
Brake chopper Brake chopper failure. the chopper is faulty. Contact
111 the distributor near to you.
saturation alarm
AC drive Too low temperature measured in The ambient temperature is too
13 120 undertemperatur power unit’s heatsink or on power low for the AC drive. Move the
e (fault) board. AC drive in a warmer place.
AC drive
130 overtemperature
Check the actual amount and
(fault, heatsink)
flow of cooling air.
AC drive Check the heatsink for dust.
131 overtemperature Too high temperature measured in Check the ambient
(alarm, heatsink) power unit’s heatsink or on the power temperature.
14 board.
AC drive Make sure that the switching
NOTE! Heatsink temperature limits are
132 overtemperature frame-specific. frequency is not too high in
(fault, board) relation to ambient
temperature and motor load.
AC drive
Check cooling fan.
133 overtemperature
(alarm, board)
15 140 Motor stall Motor is stalled. Check motor and load.
Decrease motor load.
If no motor overload exists,
Motor
16 150 Motor is overloaded. check the temperature model
overtemperature
parameters (parameter Group
3.9: Protections).
Check load.
17 160 Motor underload Motor is underloaded. Check parameters.
Check du/dt and sinus filters.
Fault Fault
Fault name Possible cause Remedy
code ID
Power overload
180 (short-time
supervision) Decrease load.
19 AC drive power is too high. Check dimensioning of drive. Is
Power overload it too small for the load?
181 (long-time
supervision)
Appears only in customer specific
Reset the fault and restart the
application, if the feature is in use.
AC drive. Increase identification
240 Motor control Start angle identification has failed.
25 current level.
241 fault • Rotor moves during identification
See fault history source for
• New identified angle does not match
more info.
with existing value
Start-up of the drive has been
prevented. Run request is ON when a Reset the fault and stop the AC
Start-up new software (firmware or application), drive.
26 250
prevented parameter setting or any other file, Load the software and start the
which has affects the operation of the AC drive.
drive, has been loaded to drive.
Atex thermistor has detected the Reset the fault. Check
29 280 Atex thermistor
overtemperature thermistor and its connections.
Safe Off signal A does not allow AC Reset the fault and restart the
290 Safe Off
drive to be set to READY state AC drive.
Check the signals from the
Safe Off signal B does not allow AC control board to the power unit
291 Safe Off
drive to be set to READY state and the D connector.
Remove the Safety
Safety Appears when the Safety Configuration
500 Configuration Switch from the
configuration Switch has been installed
control board.
Too many STO option boards have been
Safety Remove the extra STO option
501 detected in the drive. Only one is
configuration boards. See Safety manual.
supported.
Safety STO option board has been installed in Place the STO option board into
502
configuration incorrect slot. correct slot. See Safety manual.
Install the Safety Configuration
Safety Safety Configuration Switch is missing
503 Switch on the control board.
30 configuration from the control board.
See Safety manual.
Install the Safety Configuration
Safety Configuration Switch has been
Safety Switch in correct place on the
504 installed incorrectly on the control
configuration control board. See Safety
board.
manual.
Check the Safety configuration
Safety Configuration Switch on the STO
Safety switch installation on the STO
505 option board has been installed
configuration option board. See Safety
incorrectly.
manual.
Check the installation of STO
Safety Communication with STO option board
506 option board. See Safety
configuration has been lost.
manual.
Reset the drive and restart. If
Safety Hardware does not support STO option
507 the fault reoccurs contact your
configuration board
nearest distributor.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
9
Fault tracing vacon • 254
Fault Fault
Fault name Possible cause Remedy
code ID
Safety
520 Component failure on STO option board Reset the drive and restart.
diagnostics
If the fault reoccurs change the
Safety ATEX thermistor diagnostic fault. ATEX option board.
521
diagnostics thermistor input connection has failed.
Check ATEX thermistor input
connection.
30 Safety Short-circuit in ATEX thermistor input Check external ATEX
522
diagnostics connection. connection.
Check external ATEX
thermistor.
Emergency stop button has been When the STO function is
530 Safe torque off connected or some other STO activated, the drive is in safe
operation has been activated. state.
Fan speed does not follow the speed
reference accurately. However, the AC Reset the fault and restart.
311 Fan cooling
drive operates properly. This fault Clean or change the fan.
32 appears in MR7 and bigger drives only.
Change fan and reset fan life
312 Fan cooling Fan life time (50,000h) is up.
time counter.
Fire mode of the drive is enabled. The
Check the parameter settings
Fire mode drive's protections are not in use.
33 320 and signals. Some of the driver
enabled NOTE! This alarm is automatically reset
protections are disabled.
when fire mode is disabled.
Power unit has been changed for
Device changed another of corresponding size. Reset the fault.
361
(same type) The device is ready to use. Parameters NOTE! Drive reboots after reset.
are already available in the drive.
Option board in slot B changed for one
Device changed Reset the fault. Old parameter
362 previously inserted in the same slot.
(same type) settings will be used.
37 The device is ready to use.
Device changed
363 Same as ID362 but refers to Slot C. See above.
(same type)
Device changed
364 Same as ID362 but refers to Slot D. See above.
(same type)
Device changed
365 Same as ID362 but refers to Slot E. See above.
(same type)
Option board added into slot B. The
Device is ready for use. Old
Device added option board was previously inserted in
372 parameter settings will be
(same type) the same slot. The device is ready to
used.
use.
Device added
38 373 Same as ID372 but refers to Slot C. See above.
(same type)
Device added
374 Same as ID372 but refers to Slot D. See above.
(same type)
Device added
375 Same as ID372 but refers to Slot E. See above.
(same type)
Fault Fault
Fault name Possible cause Remedy
code ID
382 Device removed Option board removed from slot A or B.
383 Device removed Same as ID380 but refers to Slot C Device no longer available.
39
384 Device removed Same as ID380 but refers to Slot D Reset the fault.
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
9
Fault tracing vacon • 256
Fault Fault
Fault name Possible cause Remedy
code ID
At least one of the available analogue Change the failed parts.
input signals has gone below 50% of Check the analogue input
50 1050 AI low fault the defined minimum signal range. circuit.
Control cable is broken or loose. Check that parameter AI1
Signal source has failed. signal range is set correctly.
Digital input signal defined by
User-defined fault.
Device external parameter P3.5.1.11 or P3.5.1.12 has
51 1051 Check digital inputs/
fault been activated to indicate the fault
schematics.
situation in external device.
Keypad
1052 The connection between the control Check keypad connection and
52 communication
1352 keypad and AC drive is broken possible keypad cable
fault
Fieldbus The data connection between the
Check installation and fieldbus
53 1053 communication fieldbus master and fieldbus board is
master.
fault broken
1354 Slot A fault
1454 Slot B fault
Check board and slot.
54 1554 Slot C fault Defective option board or slot Contact your nearest
distributor.
1654 Slot D fault
1754 Slot E fault
Check that motor is connected
to the drive.
Make sure that there is no load
on the motor shaft.
57 1057 Identification Identification run has failed.
Make sure that the start
command will not be removed
before completion of
identification run.
1063 Quick Stop fault Quick stop activated Check reason for quick stop
activation. Once found and
corrective actions taken, reset
63
1363 Quick Stop alarm Quick stop activated the fault and restart the drive.
See parameter P3.5.1.26 and
parameter group 3.4.22.5.
PC Check the installation, cable
The data connection between the PC
65 1065 communication and terminals between the PC
and AC drive is broken
fault and the AC drive.
Thermistor input Check motor cooling and load.
1366
1 fault Check thermistor connection
Thermistor input The thermistor input has detected an If thermistor input is not in use
66 1466
2 fault increase of motor temperature it has to be short circuited.
Thermistor input Contact your nearest
1566 distributor.
3 fault
Fault Fault
Fault name Possible cause Remedy
code ID
Maintenance Maintenance counter has reached the
1301
counter 1 alarm alarm limit.
Maintenance Maintenance counter has reached the Carry out the needed
1302
counter 1 fault fault limit. maintenance and reset counter.
68
Maintenance Maintenance counter has reached the See parameters B3.16.4 or
1303 P3.5.1.40.
counter 2 alarm alarm limit.
Maintenance Maintenance counter has reached the
1304
counter 2 fault alarm limit.
Non-existing ID number is used for Check parameters in Fieldbus
1310 mapping values to Fieldbus Process Data Mapping menu (chapter
Data Out. 4.6).
The value being mapped may
Fieldbus be of undefined type. Check
Not possible to convert one or more
69 1311 communication parameters in Fieldbus
values for Fieldbus Process Data Out.
fault DataMapping menu (chapter
4.6).
Overflow when mapping and converting Check parameters in Fieldbus
1312 values for Fieldbus Process Data Out Data Mapping menu (chapter
(16-bit). 4.6).
Start command is active and was Reset drive to restore the
blocked in order to prevent normal operation. The need of
76 1076 Start prevented
unintentional rotation of the motor restart depends on the
during the first power-up. parameter settings.
Maximum number of 5 simultaneous
Remove excessive active
77 1077 >5 connections active fieldbus or PC tool connections
connections.
supported by the application exceeded.
The Soft fill function in the PID Reason might be a pipe burst.
controller has timed out. The desired Check the process.
100 1100 Soft fill timeout
process value was not achieved within Check the parameters in the
this time. Soft fill menu M3.13.8.
PID controller: Feedback value has
Feedback Check the process.
gone beyond supervision limits
101 1101 supervision fault Check parameter settings,
(P3.13.6.2, P3.13.6.3) and the delay
(PID1) supervision limits and delay.
(P3.13.6.4) if set.
External PID controller: Feedback
Feedback Check the process.
value has gone outside supervision
105 1105 supervision fault Check parameter settings,
limits (P3.14.4.2, P3.14.4.3) and the
(ExtPID) supervision limits and delay.
delay (P3.14.4.4) if set.
Input pressure supervision signal
1109 (P3.13.9.2) has gone below the alarm Check the process.
limit (P3.13.9.7). Check the parameters in menu
Input pressure
109 M3.13.9.
supervision Input pressure supervision signal Check the input pressure
1409 (P3.13.9.2) has gone below the fault sensor and connections.
limit (P3.13.9.8).
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
9
Fault tracing vacon • 258
Fault Fault
Fault name Possible cause Remedy
code ID
At least one of the selected tempera-
1315 ture input signals (P3.9.6.1) has
Temperature reached the alarm limit (P3.9.6.2). Find the cause of temperature
111 raise.
fault 1 At least one of the selected tempera-
1316 ture input signals (P3.9.6.1) has Check the temperature sensor
reached the fault limit (P3.9.6.3). and connections.
Check that the temperature
At least one of the selected tempera- input is hardwired if no sensor
1317 ture input signals (P3.9.6.5) has is connected.
Temperature reached the fault limit (P3.9.6.6). See option board manual for
112
fault 2 At least one of the selected tempera- further information.
1318 ture input signals (P3.9.6.5) has
reached the fault limit (P3.9.6.7).
Carry out the needed mainte-
In Multipump system, at least one of
Pump running nance actions, reset the run-
1113 the pump runtime counters has
time time counter and reset the
exceeded a user-defined alarm limit
alarm. (See ch. 4.15.4)
113
Carry out the needed mainte-
In Multipump system, at least one of
Pump running nance actions, reset the run-
1313 the pump runtime counters has
time time counter and reset the
exceeded a user-defined fault limit
fault. (See ch. 4.15.4)
700 Unsupported application used. Change the application
300 Unsupported
701 Unsupported option board or slot used. Remove the option board
10. APPENDIX 1
10.1 Default parameter values according to the selected
application
The default values of the following parameters vary according to the selected application
wizard.
Table 134. Default parameter values according to application
Default
(Single drive)
(Multidrive)
PID Control
Multipump
Multipump
Standard
Index Parameter Unit ID Description
6 = AI1 + AI2
P3.3.1.5 I/O A Reference Selection 6 6 7 7 7 117
7 = PID
P3.3.1.6 I/O B Reference Selection 4 4 4 4 4 131 4 = AI1
Run time
P3.3.1.7 2 2 2 2 2 121 2 = Keypad Reference
(text keypad)
Run time
P3.3.1.10 3 3 3 3 3 122 3 = Fieldbus Reference
(text keypad)
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
10
Appendix 1 vacon • 260
P3.5.2.1.1 AI1 Signal Selection 100 100 100 100 100 377
P3.5.2.1.2 AI1 Filter Time 0.1 0.1 0.1 0.1 0.1 s 378
P3.5.2.1.3 AI1 Signal Range 0 0 0 0 0 379 0 = 0…10V / 0…20 mA
P3.5.2.1.4 AI1 Custom Min 0.0 0.0 0.0 0.0 0.0 380
P3.5.2.1.5 AI1 Custom Max 100.0 100.0 100.0 100.0 100.0 381
P3.5.2.1.6 AI1 Signal Inversion 0 0 0 0 0 387
P3.5.2.2.1 AI2 Signal Selection 101 101 101 101 101 388
P3.5.2.2.2 AI2 Filter Time 0.1 0.1 0.1 0.1 0.1 s 389
P3.5.2.2.3 AI2 Signal Range 1 1 1 1 1 390 1 = 2…10V / 4…20 mA
P3.5.2.2.4 AI2 Custom Min 0.0 0.0 0.0 0.0 0.0 391
P3.5.2.2.5 AI2 Custom Max 100.0 100.0 100.0 100.0 100.0 392
P3.5.2.2.6 AI2 Signal Inversion 0 0 0 0 0 398
www.vacon.com
Manual authoring:
[email protected]
Document ID:
Vacon Plc.
Runsorintie 7
65380 Vaasa
Finland