ET Lab Manual ECE
ET Lab Manual ECE
ENGINEERING COLLEGE
(An Autonomous Institution)
Puducherry-605107
Register No :
Name :
Subject :
Branch :
Year/Semester :
Certificate
Certified that this is the bonafide record of Practical Work done by the above
student in the ELECTRICAL TECHNOLOGY LABORATORY (U23EEPC01) during
the academic year .
1. Domestic Wiring Practice (Staircase Wiring, Doctor’s Room Wiring, Go down Wiring).
2. Load test on single phase transformer.
3. Load test on 3 phase transformers.
4. Measurement of three phase power using two watt meter method.
5. OCC and Load test on DC shunt Generator.
6. Load test on DC shunt motor.
7. Load test on DC series motor.
8. Speed control methods of DC motor.
9. Load test on single phase Induction Motor.
10. Load test on 3 phase induction motor.
Ex. Page
Date Title of the Experiment Marks Signature
No. No.
10
11
12
CIRCUIT DIAGRAM:
LAYOUT DIAGRAM:
EXP NO: DOMESTIC WIRING PRACTICE DATE:
AIM:
To study about the various types of wiring and to verify its truth table experimentally.
A) STAIR-CASE WIRING
OBJECTIVE:
COMPONENTS REQUIRED:
PROCEDURE:
1. Initially suitable junction boxes, PVC pipes and switch boxes are selected
2. As per the layout diagram (1b) junction boxes, PVC pipes and switch boxes are fixedrigidly
on the wooden board with the help of GI clamps.
3. As per the circuit diagram (1a) the connections are given
4. The Phase wire is connected to the common terminal of the two-way switch (SPDT-1)
through fuse.
5. From the other two throw points of SPDT-1, wires are connected to the two throwpoints
of SPDT-2. (i.e. top terminals of SPDT-1 and SPDT-2 are connected and bottom terminals
of SPDT-1 and SPDT-2 are connected).
6. From the common terminal of SPDT-2, wire is taken to any one terminal of the
incandescent lamp (bulb).
7. The other terminal is taken out as the neutral line.
8. Connections are checked using the wiring diagram (1c) and the truth table (1d) is
verified for different combinations.
9. Now the lamp can be controlled from two places irrespective of the position of the
switches.
WIRING DIAGRAM:
TRUTH TABLE:
S1 S2 Lamp
T T On
T B Off
B B On
B T Off
RESULT:
Thus the experiment of various wiring done and verified the truth table.
CIRCUIT DIAGRAM:
LAYOUT DIAGRAM:
B. DOCTOR’S ROOM WIRING
OBJECTIVE:
COMPONENTS REQUIRED:
PROCEDURE:
1. Initially suitable junction boxes, PVC pipes and switch boxes are selected. Required
connecting wires are taken.
2. As per the layout diagram (2b) junction boxes, PVC pipes and switch boxes are fixedrigidly
on the wooden board with the help of GI clamps.
4. The phase wire is connected to the top terminal of the bell push S1 through properfuse.
5. From the bottom terminal of the S1, wire is taken and connected to the common
terminal of S2 (SPDT).
6. From top terminal of the switch S2, two wires are taken, one wire is connected to one terminal
of batten holder (lamp-1) and other wire is connected to one terminal of the ceiling rose
(buzzer).
7. From the bottom terminal of S2, a wire is taken and connected to one terminal of the batten
holder (lamp-2).
8. Other terminals from the button holders (L1 – L2) and the ceiling rose (buzzer) are connected
together and taken out as neutral wire.
9. Connections are checked using the wiring diagram (2c) and the truth table (2d) is verified for
different combinations.
10. Now the lamps (Lamp in and Lamp out) and the buzzer can be controlled.
WIRING DIAGRAM:
TRUTH TABLE:
ON T RING ON OFF
ON B OFF OFF ON
OFF T/B OFF OFF OFF
RESULT:
Thus the experiment of Doctors room wiring has done and verified the truth table.
CIRCUIT DIAGRAM:
LAYOUT DIAGRAM:
C).GODOWN WIRING
OBJECTIVE:
COMPONENTS REQUIRED:
PROCEDURE:
1. Initially suitable junction boxes, PVC pipes and switch boxes are selected. Required
connecting wires are taken.
2. As per the layout diagram (3b) junction boxes, PVC pipes and switch boxes are fixedrigidly
on the wooden board with the help of GI clamps.
3. As per the circuit diagram (3a) the connections are given:
4. The phase wire is given to the top terminal of the switch S1 (SPST) through proper fuse.
5. The bottom terminal of S1 and the common terminal of switch S2 (SPDT) are connected.
6. The top terminal of S2 is connected to one end of the batten holder (for L1) and the bottom
terminal of S2 is connected to the common terminal of switch S3 (SPDT).
7. Again the top terminal of the switch S3 is connected to the one terminal of the batten holder
(for L2) and the bottom terminal of S3 is connected to any one terminal of the batten holder
(for L3).
8. The remaining unconnected terminals of the batten holders are connected togetherand
taken out as neutral wire.
9. Connections checked using the wiring diagram and the truth table is verified for
different combinations.
10. Now the three lamps can be controlled from three different places.
WIRING DIAGRAM:
TRUTH TABLE:
S1 S2 S3 L1 L2 L3
ON T T ON OFF OFF
ON B T OFF ON OFF
ON B B OFF OFF ON
ON B T OFF ON OFF
ON T T ON OFF OFF
Thus the experiment of Go down wiring has done and verified the truth table.
INFERENCE:
Through the experiment, students will infer the importance of electrical continuity in ensuring
that the lamp operates correctly when switches are toggled.
Considering practical applications in residential or commercial lighting installations where two-
way switching provides convenience and flexibility of usage.
It can develop skills in troubleshooting by identifying and rectifying common issues such as
loose connections or faulty switches that affect the operation of the circuit.
They will appreciate the role of different wires (live, neutral, and possibly earth) in providing
electrical power to the lamp and completing the circuit.
Viva Marks 10
Experiment
Conduction Mark 15
Total Marks 25
Signature of Lab In-
charge
Name Plate Details: Calculation of Fuse Rating:
AIM:
To conduct load test on single phase transformer and to obtain percentage regulation
and efficiency.
APPARATUS REQUIRRED:
1 Voltmeter
2 Ammeter
3 Wattmeter
4 Auto Transformer
5 Resistive load
6 Connecting Wires
THEORY:
When the secondary is loaded the secondary current I2 is setup. The magnitude and phase of
I2 with respect to V2 is determined by the characteristics of the load. The secondary current sets
up its own emf and hence its own flux ф 2which is in opposition to main primary flux ф which is
due to I0 the secondary ampere turns N2*I2are known as demagnetizing ampere turns .The
opposing secondary flux I2 weakens the primary flux ф momentary. Hence primary back Emf
E1 tends to be reduced. For a moment V1 gain the upper hand over E1 and hence causes more
current to flow in.
Let the additional primary current be I21 .It is known as load component of primary current.
This current is anti phase with I21 the additional primary emf N1*I2 setsup its own flux ф21 which
is in opposite to ф2 and is equal to its magnitude .Hence the two cancel each other out. So the
magnetic effects of secondary current I2are immediately neutralized by the additional primary
current I21.Hence whatever the load conditions be
,the net flux passing through core is approximately the same as no-load.
Calculation of Rated current on primary and secondary:
P1
Primary current (I1) =
V1 Cos (1)
2000
=
230*1
=8.69A
P2
Secondary current (I2) =
V2 Cos (2)
2000
=
115*1
=17.39A
Output power
% ���������� �=
Input power
E0 -V
% ����������=
V
Watt meter
Primary W1
Primary Secondary Input Output
current Multiplication Secondary
voltage V1 current I2( Voltage
power power( %Efficiency (ή) %
S. I1 factor=2
(Volts) A) (W) W) Regulation
No. (A) V2( Volts)
Obs Act
8
PRECAUTIONS:
PROCEDURE:
=7.5×112×1
Efficiency (ƞ) = Output power ×100
Input power
=440×100
480
=91.6%
R
Regulation R %
Efficiency %
Thus, the load test on single phase transformer was performed and the respectivegraphs
were plotted.
INFERENCE:
The Following Points are noted from the output characteristics of single phase transformer
Viva Marks 10
Experiment
15
Conduction Mark
Total Marks 25
Signature of Lab In-
charge
VIVAQUESTIONS:
AIM:
To calculate the percentage efficiency and percentage voltage regulation for the given
3φ transformer at various load.
APPARATUSREQUIRED:
S.No Apparatus Type Range Quantity
1 Voltmeter
2 Ammeter
3 Watt meter
4 Resistive load
5 Auto Transformer
6 Connecting Wires
THEORY:
The three cores are arranged at 120o from each other. Only primary wingdings are
show on the cores for simplicity. The primaries are connected to the three-phase
supply. The primaries carry the currents IR, IY and IB producing the fluxes ΦR, ΦY and
ΦB in the individual cores. The common leg of the cores
i.e .center leg formed carries sum of the all three fluxes.
But at any instant, in a three-phase system, ĪR + ĪY + ĪB = 0, hence the sum of the
three fluxes is also zero at any instant .Hence the center leg does not carry any flux.
So if center leg is removed, It hardly makes any difference in the other conditions of the
transformer. If it is removed, any two legs provide the return path for the current hence
the flux in the third leg. This is the general principle used in the design of three phase
core type transformers.
The three phase transformers can be core type or shell type. The three-core type single
phase transformers can be combined to get three phase core type transformers .Similarly
,three single phase shell type transformers can be combined together to form a three-
phase shell type transformer.
Calculation of Rated current on primary and secondary:
P1
Primary current (I1) =
3V2Cos(⌽2)
3000
=
3*440*1
=3.93A
P2
Secondary current (I2) =
3V2Cos(2)
3000
=
3*220*1
=7.87A
FORMULA USED:
Output power
%Efficiency η = X100
Input power
VNL–VFL
%Regulation = X100
VNL
PRECAUTIONS:
PROCEDURE:
1. Connections are given as per the circuit diagram.
2. Auto transformer is adjusted for voltmeter in the primary side to read the rated
voltage.
3. The output voltage corresponding to the rated primary voltage is noted. This is
noload secondary voltage.
4. The watt meter and ammeter readings corresponding to no load is also noted.
5. Load is gradually increased .All meter readings are noted at each stage.
6. The above procedure is repeated till the secondary current exceeds rated current.
Tabulation:
VFL
%Regulation = 0.05
MODEL GRAPH:
Regulation R %
R
Efficiency%
GRAPHS:
INFERENCE:
The Following Points are noted from the output characteristics of three phase transformer
i) The maximum Efficiency of the transformer is at the load current of
Viva Marks 10
Experiment
Conduction Mark 15
Total Marks 25
Signature of Lab In-
charge
VIVAQUESTIONS:
1. What is the function of transformer?
It transforms electric power from one circuit to another circuit without any change in
frequency
2. Why the efficiency of a transformer is higher than that of motors?
Motors has moving parts so there is always a loss, but transformer has no moving
parts so more efficiency.
3. Distinguish between core type and shell type
transformers?
Core type transformer
The coils are wound around the two limbs of a rectangular magnetic core.
The winding surrounds the core
Single magnetic path
Shell type transformer
The coils are wound on the central limb of a three limb core.
The core surrounds the winding
Two magnetic paths
4. What is the power formula for single phase and three phase?
Electric power is the rate of energy consumption in an electrical circuit.
For single phase(1Φ)– P=VIcosΦ
For three phase (3Φ)–P=current VLILcosΦ In terms of line voltage and line
APPARATUS REQUIRED:
THEORY:
The connection diagram for the measurement of power in a three-phase circuit using two
watt meter's, is given in Fig. This is irrespective of the circuit connection – star or delta. The
circuit may be taken as unbalanced one, balanced type being only a special case. Please note the
connection of the two watt meter. The current coils of the watt meters, 1 & 2, are in series with the
two phases, R&B, with the pressure or voltage coils being connected across Y R− Y and B−Y
respectively. Y is the third phase, in which no current coil is connected.
So, it can be concluded that the sum of the two watt meter readings is the total power
consumed in the three-phase circuit, assumed here as a star-connected one. This may also be easily
proved for delta connected circuit. As no other condition is imposed, the circuit can be taken as an
unbalanced one, the balanced type being only a special case, as stated earlier.
FORMULA USED:
3. P1 =3VL IL Cos ϕ.
4. P.F = Cos ϕ.
P1- P2
5. Percentage Error =------------------ x 100%
P1
PRECAUTIONS:
1. Auto Transformer should be in minimum position.
2. There should be no load at the time of starting.
PROCEDURE:
1. Connections are given as per the circuit diagram.
2. Adjust the Auto transformer till the rated voltage is reached.
3. If any Watt meter shows negative reading then interchange M and L connections andreadings are taken in negative.
4. At no load, the readings of voltmeter, ammeter and watt meter are noted.
5. Load is gradually increased. All meter readings are noted at each stage.
6. The above procedure is repeated till the rated current is reached.
TABULATION:
Wattmeter W1 Wattmeter W2
Load M.F = M.F = Φ = tan-1√3 Power P1 =
Load Power P2 = % Error = ((P1 –
S.No. Current ((W1–W2)/ Factor √3VLILcos
Voltage VL W1+W2 P2) / P1) × 100
IL Obs Act Obs Act (W1+W2)) cosΦ Φ
MODEL CALCULATION:
RESULT:
Calculated the three phase power using two watt meter method and calculated % error
and Plotted the curve
INFERENCE:
The Following Points are noted from the measurement of three phase power using two wattmeter
method
i) The maximum Three phase power is at the load current of
Viva Marks 10
Experiment
15
Conduction Mark
Total Marks 25
Signature of Lab In-
charge
Name plate details of DC Motor: Name plate details of DC Generator:
S.No
Apparatus Range Type Qty
.
1 Voltmeter
2 Ammeter
3 Rheostat
4 Tachometer
5 Resistive Load
Connecting
6
Wires
THEORY:
A DC generator requires an excitation circuit to generate an induce voltage depending
on whether excitation circuit consumes power for the armature of the machine or from
separately require power supply. Generators may be classified as self-excited or
separately excited generators respectively. The induced emf in DC generators is given by
the equation PфZN/60A volts. State P,Z,A are constants the above equation are written
as Eg=KфN. If the speed of the generator also maintained constant then Eg=Kф but the
flux is directly proportional to the current Hence Eg=K2 If. From the above equation it is
clear that the induced emf is directly propositional to the field current whenspeed
maintained constant,. The plot between the induced emf and the field current is known
as open circuit characteristics of the DC generator. The induced emf when the field
current is zero is known as residual voltage . This emf is due to the presence of a small
amount of flux detained. In the field poles of the generator called residual flux. Oncethe
OCC is obtained parameters such as critical field resistance, critical speed and the
maximum voltage to which the machine can build up can be determined .If required the
OCC at a different speeds can also be obtained.
Critical speed is minimum speed below which the generator shunt fails to excite.
Calculation of Fuse Rating for load test:
PRECAUTIONS:
1. Remove the fuse carriers before wiring and start wiring as per the circuit diagram.
2. Keep the motor field rheostat at minimum resistance position and generators field
rheostat at maximum resistive position.
3. The SPST switch is kept open at the time of starting the experiment.
4. As the no load test is conducting the required fuse ratings are 20% of motor rated
current.
5. Replace the fuse carriers with appropriate fuse wires after the circuit connections
are checked by the staff-in-charge.
PROCEDURE:
OPEN CIRCUIT CHARACTERISTICS
1. The connections are given as per the circuit diagram.
2. Supply is given to motor by enclosing DPSTS1
3. Motor is started using Three point Starter.
4. The field Rheostat of motor is varied to make the motor run at rated speed of the
generator.
5. Note residual voltage before closing the SPST switch.
6. The voltmeter and ammeter readings are noted.
7. The field rheostat of generator is varied gradually and the readings of ammeter
and voltmeter are noted in steps.
8. Bring the generator field rheostat and motor field rheostat to the original position
and open the DPSTS1.
TABULATION:
OCC CHARACTERISTICS:
LOAD CHARACTERISTICS:
5. Now the load side DPST2 is closed and load is applied gradually up to
rated current.
6. The speed is maintained constant at each load.
7. The readings of ammeter and voltmeter are noted at each load.
8. Remove the load completely.
9. Open the load side DPST2. Bring the field rheostat of generator and motor to its
original position and open the DPST1.
CIRCUIT DIAGRAM TO MEASURE Ra
Armature Armature
Resistance R
Sl. current Ia voltage
a(Ω)
No. (A) Va(V)
4
Average
CIRCUIT GRAPHS:
MODEL GRAPH:
Load characteristics:
RESULT:
Thus, the OCC and load characteristics of DC shunt generator when it is separately
excited are determined.
INFERENCE:
The Following Points are noted from the characteristics of DC shunt generator
i) For OCC Characteristics the Maximum Open circuit Voltage occurs at the field
current of
ii) For Load Characteristics the Maximum Open circuit Voltage occurs at the field
current of
Viva Marks 10
Experiment
15
Conduction Mark
Total Marks 25
Signature of Lab In-
charge
VIVA QUESTIONS:
1. What is self–excited generator?
Self-excited generators are those whose field magnets are energized by the current
produced by the generator themselves.
2. What are the types of self–excited generator?
Based on the type of armature connection the self-excited generators are classified into
3types
(i) Shunt wound
(ii) Series wound
(iii) Compound wound
3. How will you find residual voltage in DC series generator?
Thus by making SPST switch open, there will not be any current flow in field winding
and It does not produce flux .In that case, the voltage which is induced due to residual flux
(some flux stored inside the machine)is called residual voltage.
4. What is mean by excitation?
The process of generating a magnetic field by means of an electric current is called
excitation.
5. What is the purpose of motor field rheostat in the circuit?
To adjust the motor speed as required (rated speed).
By adjusting the field rheostat, we can change the field current and correspondingly
flux changes. As speed (N) inversely proportional to flux (∅),
We can vary speed as required. N = k 1∅
6. What is the purpose of generator field rheostat in the circuit?
To vary the field current of generator (Initial to maximum excitation current).To
perform OCC test in generator, we need to increase the field current and correspondingly
flux increases. Due to that generated emf will be increased. As Generated emf (E) directly
proportional speed (N) and flux (∅).
Name plate details of DC Motor: Calculation of Fuse Rating:
AIM:
APPARATUS REQUIRED:
S.No
Apparatus Range Type Qty
.
1 Voltmeter
2 Ammeter
3 Rheostat
4 Tachometer
Connecting
5
Wires
THEORY:
The shunt motor has a definite no load speed hence it does not run away when load
is suddenly thrown off provided the field circuit remains closed. The drop in speed
from no-load to full load is small hence this motor is usual referred to a constant speed
motor.
The efficiency curve is usually of the same shape for all electric motors and
generators. The shape of efficiency curve and the point of maximum efficiency can be
varied considerably by the designer, though it is advantageous to have an efficiency
curve which is fairly flat. So that there is little change inefficiency between load and
25% overload and to have the maximum efficiency as near to the full load as possible.
From the curves it is observed that is certain value of current is required even when
output is zero. The motor input under no-load conditions goes to meet the various
losses ,occurring within the machine.
MODELCALCULATION:
T
Radius R r In meter.
2
2NT
Output Power, W0 Watts
60
Output Power
Percentage Efficiency 100
Input Power
PRECAUTIONS:
PROCEDURE:
Spring balance
Load Load Reading
Speed Torque Input Output Efficiency
Sl.No voltage current
N(RPM) Nm power power %
VL(V) IL(A) S1 S2
Kg Kg
1.
2.
3.
4.
5.
6.
7.
8.
MODEL GRAPH
RESULT:
Thus, the performance and load characteristics of a DC shunt motor are drawn.
INFERENCE:
The Following Points are noted from the load characteristics of a DC shunt motor
i) For Load Characteristics the Maximum Speed occurs at the load current of
ii) For Load Characteristics the Maximum Efficiency occurs at the load current of
Viva Marks 10
Experiment
15
Conduction Mark
Total Marks 25
Signature of Lab In-
charge
VIVAQUESTIONS:
AIM:
APPARATUS REQUIRRED:
THEORY:
The drop in speed with increased load is much prominent in series motor than in a
shunt motor hence a series motor is not suitable for application requiring a substantially
constant speed.
For a given current input a starting torque developed by a series motor is greater than
that developed by a shunt motor. Hence series motors are used where huge starting
torques is necessary that means for cranes and traction purpose. In addition to huge
starting torque there is another unique characteristic of series motor which makes this
especially desirable for traction work that means when a load comes on a series motor it
response by decreasing its speed and supplies the increased torque with a small increase in
current.
On the other hand a shunt motor under the same condition would hold its speed nearly
constant and would supply the required increased torque with a large increase of input
current.
FORMULA USED:
T
Radius R r
2
Torque 9.81 R S1 S2 N - m
Input Power Wi Vi Ii Watts
2N
Output Power, W0 Watts
60
Output Power
Percentage Efficiency 100
Input Power
PRECAUTIONS:
1. Ensure that some load is applied to the brake drum initially (S1=S2=5kg).
2. Check the correct fuse ratings.
3. Ensure that there are no loose connections.
4. Under no circumstances, the motor should be unloaded fully during operation.
5. The motor should be cooled by circulating water in the brake drum
throughout theexperiment.
6. It is ensured that the MC (Moving Coil) meters are connected with proper polarities.
Tabulation:
Spring balance
Load Load Reading
Speed Torque Input Output Efficiency
Sl. No voltage current
N(RPM) Nm power power %
VL(V) IL(A)
S1 S2
Kg Kg
1.
2.
3.
4.
5.
6.
7.
8.
PROCEDURE:
2. Ensure that some load is applied to the brake drum initially (S1=S2=5Kg).
5. The readings of ammeter, voltmeter, tachometer and spring balance are noted.
6. The load is then gradually increased in steps and the readings are noted up to rated load.
Thus, the performance and load characteristics of a DC shunt motor are drawn.
INFERENCE:
The Following Points are noted from the load characteristics of a DC Series motor
i) For Load Characteristics the Maximum Speed occurs at the load current of
ii) For Load Characteristics the Maximum Efficiency occurs at the load current of
Viva Marks 10
Experiment
15
Conduction Mark
Total Marks 25
Signature of Lab In-
charge
EXP. NO.: DATE:
AIM:
APPARATUS REQUIRRED:
S.No
Apparatus Range Type Qty
.
1 Voltmeter
2 Ammeter
3 Rheostat
4 Tachometer
Connecting
5
Wires
THEORY:
The speed the DC motor is inversely propositional to the flux per pole , when the
armature voltage is kept constant. By decreasing the flux the speed can be increased and
vice–versa. Hence the main flux of field control method the flux of a DC motor can be
changed by changing field current with help of a shunt field rheostat. Since shunt field
current is respectively small shunt field rheostat has to carry only a small amount of
current which means I2R losses is small so that rheostat is small in size. This method
is very efficient.
ARMATURECONTROLMETHOD
This method is used when speed below the no load speed are required. As the supply
voltage is normally constant the voltage across the armature is varied by inserting a
variable rheostat in series with the armature circuit. As conductor resistance is increased
potential difference across the armature is decreased, her by decreasing the armature
speed. For a load of constant torque speed is approximately propositional to the potential
difference across the armature.
TABULATION:
3
PRECAUTIONS:
1. Check for the correct fuse ratings.
2. Ensure there are no loose connections.
3. Field rheostat should be kept in minimum resistive position initially.
4. Armature resistance rheostat is kept initially at maximum resistive position.
PROCEDURE:
1. The connections are made as per the circuit diagram.
2. Field rheostat is initially kept in the minimum resistive position and the armature
rheostat is in the maximum resistive position.
3. Supply is given to the motor by closing the DPST switch.
4. Motor is started using a three point starter.
5. Adjust the armature rheostat to get rated voltage.
6. In actual case adjust to about 200V, beyond this speed will be more than1500rpm.
7. The field rheostat is adjusted to make the motor run at the rated speed.
GRAPHS:
Capacity : 3.5 W
Voltage : 220 V
Current : 16 A
Speed : 1500 RPM
INFERENCE:
The Following Points are noted from the speed control characteristics of DC shunt motor
i) For Load Characteristics the Maximum Speed occurs at the Armature current of
ii) For Load Characteristics the Maximum Speed occurs at the Field current of
Viva Marks 10
Experiment
15
Conduction Mark
Total Marks 25
Signature of Lab In-
charge
VIVA QUESTIONS:
1. How does the speed of a DC shunt motor vary with armature voltage
and field current?
5. Why we are using low range ammeter (less than rated current) at
supply side?
Due to no load, current flow will be very low, for that 25 % of rated current is
enough to perform the test. So low range ammeters (25 % of rated current) are used.
6. What are the methods available for speed control other than these
two methods?
Voltage control
(i) Multiple voltage control
(ii) Ward Leonard method
(iii) Tapping’s
NAME PLATE DETAILS FUSE RATING CALCULATION
APPARATUS REQUIRRED:
S.No
Apparatus Range Type Qty
.
1 Voltmeter
2 Ammeter
3 Watt meter
4 Tachometer
5 Autotransformer
6 Connecting wires
THEORY:
In the single-phase induction motor, single phase A.C. supply is given to the stator
winding. The stator winding carries an alternating current which produces the flux which is
also alternating in nature. This flux is called main flux. This flux links with the rotor
conductors and due to transformer action E.M.F. gets induced in the rotor .The induced
E.M.F. drives current through the rotor as rotor circuit is closed circuit. This rotor current
produces another flux called rotor flux required for the motoring action. Thus second flux is
produced according to induction principle due to induced E.M.F. hence the motor is called
induction motor. As against this in D.C. motor a separate supply is required to armature to
produce armature flux. This is an important difference between D.C. motor and an induction
motor. The single-phase induction motors are not self-starting , to make a
single-phase induction motor self-starting , the following methods are used
(i) Split-phase motors
(ii) Capacitor-Start Motor
(iii) Capacitor- Start Capacitor-Run Motor
(iv) Shaded-pole motors
FORMULA USED
Where, f=frequency in Hz
P =no. of poles
NS N
6. %Slip = 100
NS
Where, Ns=synchronous speed in rpm
VLIL
PRECAUTION
1) Before switching on the supply the auto transformer is kept in minimum position.
2) There should be no load while starting the motor.
PROCEDURE
Observation Tabulation
Spring
Input
Balance
Line Line
Power Pi, M.F= Speed( Reading (S1~
S.N Voltage Current
Observe N) S2)
o. VL IL
d Actual S1 S2
V A W W Rpm Kg Kg Kg
1.
2.
3.
4.
5.
6.
7.
8.
CALCULATION TABULATION:
Sl. No.
Power
Factor=
Torque
%Slip
Input
Power
Output
N-m %
cos Pi(W) Power(W
)
1.
2.
3.
4.
5.
6.
7.
8.
MODEL CALCULATION:
1. Input power= W
= Watts
4. % = Output
100
Input
= ×100= %
NSNr
5. Slip= 100
NS
N 120f
s P
12050
N 1500
S 4
Slip=
Pin V
6. Power factor= cos
vI
L L
=
MODEL GRAPHS:
GRAPHS:
1. Output Power Vs speed
2. Output power Vs Efficiency
3. Output power Vs Load Current
4. Output power Vs Power factor
5. Torque Vs Slip
RESULT
Thus, the load test on single phase induction motor was per formed and the
respective graphs were drawn.
INFERENCE:
The Following Points are noted from the load test on single phase induction motor
i) For Load Characteristics the Maximum Slip occurs at the load current of
ii) For Load Characteristics the Maximum Efficiency occurs at the load current of
iii) For Load Characteristics the Maximum Power factor occurs at the load current of
iv) For Load Characteristics the Maximum torque occurs at the load current of
Viva Marks 10
Experiment
Conduction Mark 15
Total Marks 25
Signature of Lab In-
charge
VIVA QUESTIONS:
2. How will you change the direction of rotation of a single phase induction
motor?
The direction of rotation of a single phase induction motor can be changed by
changing the direction of current either in the starting winding or in the running
winding.
7. What are the classifications of single phase induction motor based on the
method of starting?
a) Split phase motor
b) Capacitor start motor
c) Capacitor start Capacitor run motor
d) Shaded pole motor
APPARATUS REQUIRRED:
S.No
Apparatus Range Type Qty
.
1 Voltmeter
2 Ammeter
3 Watt meter
4 Tachometer
5 Auto transformer
6 Connecting wires
THEORY:
Induction motor works on the principle of Faradays Law of Electromagnetic
induction. When a three phase supply is given to the three phase stator winding, a
rotating magnetic field of constant magnitude will be produced. The speed of this
rotation magnetic field is synchronous speed Ns r.p.m.
Ns=120f/P
Now at this instant rotor is stationery and stator flux R.M.F. is rotating. So it’s
obvious that there exists a relative motion between the R.M.F. and rotor conductors.
Whenever conductor cuts the flux, e.m.f. gets induced in it. So e.m.f. gets induced in
the rotor conductors called rotor induced e.m.f. As rotor forms closed circuit, induced
e.m.f. circulates current through rotor called rotor current.
Any current carrying conductor produces its own flux. So rotor produces its flux
called rotor flux. This direction can be easily determined using right hand thumb rule.
Now there are two fluxes, one R.M.F. and other rotor flux. Both the fluxes interact
with each. On left of rotor conductor, two fluxes cancel each other to produce low
flux area. As flux lines act as stretched rubber band, high flux density area exerts
a push on rotor conductor towards low flux density area. So rotor conductor
experiences a force.
As all the rotor conductors experience a force, the overall rotor experiences a
torque and starts rotating
FORMULA USED
4. %Efficiency = Output
100
Input
5. Synchronous speed, N 120f
S
P (Rpm)
Where, f =frequency in Hz
P =no. of poles
NSN
6. %Slip ,s= 100
NS
Where, Ns=synchronous speed in rpm
Nr=speed of the rotor in rpm
Where, R =Radius of brake drum of motor in
meterS1, S2=spring balance reading in
kg
7. Power factor= cos
PRECAUTION
PROCEDURE
Observation Tabulation:
Input
Line Line Power Spring
Sl. Speed (S1~S2)
Voltage Current Pi(Watts) Balance
No. (N)rpm Kg
VL(V) IL(A) W1 W2 Reading
Obs Act. Obs Act. S1K S2Kg
. . g
1.
2.
3.
4.
5.
6.
CALCULATION TABULATION:
Power
Sl.No. Factor=
Torque
%Slip
Input Output
cos
N-m Power Pi (W) Power(W)
1.
2.
3.
4.
5.
6.
MODEL CALCULATION:
= Watts
Output
4.%= 100
Input
=
NSN
5. Slip= 100
NS
=
MODEL GRAPHS:
GRAPHS:
1. Output Power Vs Efficiency
2. Output Power Vs Load Current
3. Output Power Vs Power factor
4. Output Power Vs %Speed
5. Torque Vs Slip
RESULT:
INFERENCE:
The Following Points are noted from the load test on three phase induction motor
i) For Load Characteristics the Maximum Slip occurs at the load current of
ii) For Load Characteristics the Maximum Efficiency occurs at the load current of
iii) For Load Characteristics the Maximum Power factor occurs at the load current of
iv) For Load Characteristics the Maximum torque occurs at the load current of
Viva Marks 10
Experiment
15
Conduction Mark
Total Marks 25
Signature of Lab In-
charge
VIVAQUESTIONS:
1. What are the fundamental characteristics of a rotating magnetic field?
The resultant of three alternating fluxes separated from each other by 120 degree
has constant amplitude of 1.5 Фm, where Фm is maximum amplitude of an individual
flux due to any phase.
The resultant always keeps on rotating with certain speed in space, and the speed
is given by Ns = 120f / P
4. What is the effect of slip on frequency, induced emf and power factor?
(a). fr=sf
(b). E2r=sE2
(c). CosФ2r=R2/Z2r .
5. The squirrel cage rotor is also known as short circuited rotor .Why?
In squirrel cage rotor, the copper bars are placed in the slots. These bars are short
circuited at each end with the help of conducting copper ring called end ring. The entire
rotor resistance is very small. Hence this rotor is also called as short circuited rotor.
CONTENT BEYOND THE SYLLABUS
Capacity = Capacity =
Voltage = Voltage =
Current = Current =
Speed = Speed =
For load test on alternator=125%*Rated Excitation voltage =
current of alternator Excitation current =
= (125/100)* For Motor =125%*
Rated current of DC motor
= A
= (125/100)*
= A
=
EXP. NO : DATE:
APPARATUS REQUIRRED:
S.No
Apparatus Range Type Qty
.
1 Voltmeter
2 Ammeter
3 Watt meter
4 Tachometer
5 Autotransformer
6 Connecting wires
THEORY:
The alternators works on the principle of electromagnetic induction.
When there is a relative motion between the conductors and the flux EMF get induced
in the conductors. Consider a relative motion of a single conductor under the
magnetic field produced by two stationary poles which is shown below.
Fig.Alternator
Let conductor starts rotating from position 1. At this instant, the entire velocity
component is parallel to the flux lines. Hence there is no cutting of flux lines by the
conductor. So dΦ/dt at this instant is zero and hence induced E.M.F. in the conductor is
also zero.
FORMULA USED:
1. DC Motor Input power= Vm× Im Watts
2. DC Motor Out put power= Motor Input power Watt
100
3.Assume efficiency of motor=80%
4.Output Power of Alternator= VL IL cos
Cos Ø =1 (for resistive load)
5.Input Power of alternator = Output Power of DC motor
Output
6.%Alternator efficiency = 100
Input
VNLVFL
7.%Regulation= 100
VNL
As the conductor moves from position 1 towards position 2, the part of the
velocity component becomes perpendicular to the flux lines and proportional to that, e.m.f. gets
induced in the conductor. The magnitude of such an induced e.m.f. increases as the conductor moves
from position 1 towards 2.
At position 2, the entire velocity component is perpendicular to the flux lines. Hence there
exists maximum cutting of the flux lines. At this instant, the induced E.M.F. in the conductor is
at its maximum. As the position of conductor changes from 2 towards 3, the velocity
component perpendicular to the flux starts decreasing and hence induced E.M.F. magnitude
also starts decreasing. At position 3, again the entire velocity component is parallel to the flux
lines and hence at this instant induced E.M.F. in the conductor is zero. As the conductor moves
from 3 towards 4, the velocity component perpendicular to the flux lines again starts
increasing. But the direction of velocity component now is opposite to the direction of velocity
component existing during the movement of the conductor from position 1 to 2. Hence an
induced E.M.F. in the conductor increases but in the opposite direction.
At position 4, it achieves maxima in the opposite direction, as the entire velocity component
becomes perpendicular to the flux lines.
1. Motor filed rheostat should be kept in minimum resistance position at the time
of starting.
2. The potential divider should be kept at maximum resistance position at the time
of starting
3. There should be no load at the time of starting
PROCEDURE
Observation Tabulation:
2.
3.
4.
5.
6.
7.
8.
CALCULATION TABULATION:
Motor Alternator
Motor Input Alternator
output
S.No. power
power
output % %Regulation
(W) power(W)
(W)
1.
2.
3.
4.
5.
6.
7.
8.
MODEL CALCULATION:
= Watts
3. Output Power of Alternator= VL IL cos
= × ×
= Watts
4.% = Output
100
Input
= ×100%= %
VNLVFL
5.%Regulation= 100
VNL
%Regulation =
MODEL GRAPHS:
GRAPHS:
Thus, the load test on three phase alternator was performed and the respective
graphs were drawn.
AIM:
To examine the construction of the universal motor; to determine its no-load and full-load characteristics.
THEORY:
The AC/DC universal motor is found in portable tools such as electric drills, saws, sanders, etc., and in
home appliances such as vacuum cleaners, electric mixers, blenders, etc., where high speed, power and small size
are an advantage. However, it is closer in concept to the DC motor than to the AC motor and, therefore, has
some inherent disadvantages, which could be avoided in purely AC induction motors; chiefly, the need for
commutation and brushes.
The universal motor is basically a series DC motor which is specially designed to operate on AC as well as
on DC. A standard DC series motor has very poor characteristics when operated on AC ,mainly due to two reasons:
a) The high reactance of both the armature and field windings limits AC current to a much lower value than
DC current (for the same line voltage).
b) If solid steel is used for the stator frame, AC flux will produce large eddy currents in the frame with
consequent heating
CONNECTION DIAGRAM:
RESULT:
Thus constructed the universal motor and know the application of this.