NOTES

1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF ALL SERVICES.


2. ALL DUCT AND GRILLE SIZES ARE IN MM.
3. ALL PIPE SIZES ARE IN MM.
4. ALL DUCT WORK TO BE INSULATED IN ACCORDANCE WITH THE SPECIFICATION.
5. ALL CONDENSATE DRAINS SHALL RUN WITH A FALL TO THE NEAREST DEDICATED CONDENSATE DRAIN
NETWORK OR FLOOR DRAIN.
6. ALL DUCT CONNECTIONS TO AHU & FCU SHALL BE OF THE FLEXIBLE TYPE.
7. PROPRIETARY, INSULATED ACCESS PANELS SHALL BE INSTALLED AT ALL FD'S VCD'S AND NRD'S.
8. FD'S SHALL BE PROVIDED WHERE DUCTS CROSS FIRE BARRIERS. ALL FD'S TO HAVE BLADES OUT OF
THE AIR STREAM.
9. SUITABLE, APPROVED SLEEVES AND SEALANTS SHALL BE PROVIDED WHERE BOTH INSULATED AND NON
INSULATED DUCTS PASS THROUGH WALLS/FLOORS ETC.
10. ALL CHILLED WATER VALVES ETC. IN PLANT ROOMS, RISER SHAFTS, ABOVE FALSE CEILINGS IN
CORRIDORS AND EXTERNAL SHALL BE INSTALLED IN APPROVED ACCESSIBLE VALVE BOXES WITH QUICK
FAF / 2B - 2 RELEASE FASTENINGS.
11. CHILLED WATER PIPE SUPPORTS SHALL NOT PENETRATE INSULATION VAPOUR SEALS.
(SUPPLY AIR FAN / FAN GUARD / GRAVITY LOUVER) 12. ALL DUCT WORK WITHIN 4.0 M OF UNITS OUTLETS SHALL BE ACOUSTICALLY LINED.
13. ALL DUCTWORK/PIPEWORK CROSSING EXPANSION JOINTS TO BE PROVIDED WITH EXPANSION
MASONRY SUPPLY AIR DUCT 2000 X 1100 mm COMPENSATION FITTINGS.
FROM GROUND FLOOR WITH AIR INTAKE LOUVER 14. CONTRACTOR SHALL PROVIDE BALANCING DAMPERS ON EACH DUCT BRANCH AND WHERE REQUIRED TO
Note: 150Ø mm Rain Water Drain Point. (Connected to nearest rain water pipe) ACHIEVE AIR BALANCE.
15. CONTRACTOR SHALL PROVIDE BALANCING AND REGULATING VALVES IN CHILLED WATER PIPE WORK AS
REQUIRED TO ACHIEVE WATER BALANCE EVEN NOT INDICATED ON DRAWINGS.
16. CONTRACTOR SHALL PROVIDE SOUND ATTENUATORS WITHIN DUCTWORK AND OTHER SOUND ATTENUATION
CAR PARKING SMOKE MANAGEMENT (EXHAUST AIR FAN) CAR PARKING SMOKE MANAGEMENT (SUPPLY AIR FAN)
TOTAL NUMBER OF EXHAUST AIR FAN = 2 No's TOTAL NUMBER OF SUPPLY AIR FAN = 2 No's 1 2 3 4 5 6 7 MEANS TO ENSURE FOLLOWING NOISE LEVELS ARE NOT EXCEEDED.
BED ROOMS - NC 35

IT
LIM
(TWO SPEED FAN) (TWO SPEED FAN) 9200 8650 8650 8650 8650 9200 GUEST ROOMS - NC 35

OT
LOUNGES/LOBBIES/PREFUNCTION - NC 35
X

PL
DURING SMOKE MODE : ( HIGH SPEED) DURING SMOKE MODE : ( HIGH SPEED) SERVICE AREAS - NC 45
AIR FLOW PER FAN - 16.66 CMS AIR FLOW PER FAN - 14.16 CMS E 229768.989 17. PROVIDE STEEL PLATFORMS/RAISED WALKWAYS TO CROSS OVER SERVICES ON ROOF & PLANT ROOMS, TO
- N 405395.854 ACHIEVE ADEQUATE MAINTANANCE ACCESS TO THE APPROVAL OF THE ENGINEER.
DURING NORMAL MODE : ( LOW SPEED) DURING NORMAL MODE : ( LOW SPEED) ECQ-B-06 -
AIR FLOW PER FAN - 10.00 CMS AIR FLOW PER FAN - 8.50 CMS 72167 - - NEIGHBOR 18. THE CONTRACTOR SHALL VERIFY SIZES OF PIPES & CIRCULATION PUMPS AND EXPANSION VESSELS OF
PAVEMENT HEAT RECOVERY SYSTEMS AS PER THE MANUFACTURER'S RECOMMENDATIONS. THE CALCULATION SHALL
-8.400 FF

600
IMPULSE JET FAN DETAILS -8.675 SS -8.400 FF BE SUBMITTED TO THE ENGINEER FOR APPROVAL.
PL 5000 -8.675 SS 19. CONTRACTOR SHALL CALCULATE EXACT HEAD OF ALL PUMPS/FANS AND CALCULATIONS SHALL BE
TOTAL NUMBER OF IMPULSE JET FAN = 8 No's E 229696.843 OT
L SUBMITTED TO THE APPROVAL OF ENGINEER.
IM
(TWO SPEED FAN) N 405397.595 IT 20. FINAL LOCATION OF THERMOSTATS FOR COMMON AREAS LIKE BED ROOMS, GUEST ROOMS, CORRIDORS,
STORE-2 VESTIBULES, OFFICES, GATHERING SPACE, etc. TO BE AGREED WITH ENGINEER DURING CONTRACT
DURING SMOKE MODE=HIGH SPEED EXECUTION.

IT
STORE-1

LI M
AIR FLOW PER FAN -2.42 CMS. A FROM 1ST BASEMENT 21. THERMOSTAT MOUNTING HEIGHT SHALL BE 1.5m FROM FINISHED FLOOR LEVEL.

CK
DRAIN CHANNEL
X' 22. PROVIDE LIGHTWEIGHT PARTITION WITHIN CEILING VOIDS AS REQUIRED TO PREVENT MIXING OF

SETBACK LIMIT

A
DURING NORMAL MODE=LOW SPEED

TB
PARKING RETURN AIR- WHEN TWO OR MORE UNITS ARE CONNECTED TO A COMMON CEILING VOID FOR RETURN

7500

SE
AIR FLOW PER FAN-1.21 CMS. E 229768.634

6832
AIR.
N 405388.399
A SE
23. THE CONTRACTOR SHALL PROVIDE A THERMOSTAT FOR EACH FCU/AHU/VAV BOX AND THE EXACT
LOCATION TO BE CO-ORDINATED WITH FURNITURE LAYOUT TO THE APPROVAL OF THE ENGINEER.
E 229696.513
N 405390.802 B
T BA
CK
LIM
-8.575 FF
-8.675 SS
TO 1ST BASEMENT
PARKING V E 229768.486 24. ANY DISCREPANCIES FOUND ON THE DRAWINGS SHALL BE REPORTED TO THE ENGINEER IMMEDIATELY.

JET FAN
N 405385.868
IT
FAF / 2B - 1 -8.400 FF
-8.675 SS PAVEMENT ALL MECHANICAL DRAWINGS SHALL BE READ IN CONJUNCTION WITH
(SUPPLY AIR FAN / FAN GUARD / GRAVITY LOUVER)
8650
ARCHITECTURAL, STRUCTURAL & ELECTRICAL DRAWINGS.

10000
2 HOURS FIRE RATED
MASONRY SUPPLY AIR DUCT 2500 X 1500 mm 15000
SETBACK LIMIT
JET FAN FRESH AIR
FROM GROUND FLOOR WITH AIR INTAKE LOUVER -8.400 FF SHAFT ABOVE ALL WORK SHALL BE CARRIED OUT IN ACCORDANCE WITH GSAS/GORD, QCDD
-8.675 SS E 229767.9432
Note: 150Ø mm Rain Water Drain Point. (Connected to nearest rain water pipe) PARKING N 405377.4806 (QATAR CIVIL DEFENCE), CURRENT BUILDING CODES AND TO THE ENGINEER’S

10000
FHC FHC COMPLETE SATISFACTION.

- - - SECONDARY ROAD (28.8m WIDE) - - -


B 7500
SETBACK LIMIT
E 229767.828
E 229695.874
N 405380.822 C 2 HOURS FIRE RATED
SPEED HUMP AS PER SPEC.
SUB-STATION
U N 405375.890

FRESH AIR
TRENCH ABOVE
8650

SHAFT ABOVE
DRIVEWAY STORE-3 0 17-08-2023 ISSUED FOR CONSTRUCTION
-8.575 FF
-8.400 FF -8.675 SS -8.400 FF

9999
-8.675 SS -8.675 SS
JET FAN

C
10000

SUB-STATION
TRENCH ABOVE
E 229695.054 PARKING
N 405370.856
JET FAN

D T E 229767.015
N 405365.923
8650

WHEEL STOPPER
RAD-150X150 @ 25 L/s
DUCT-150X150

DUCT- 150X150 @ 25 L/S (T/A)


LIFT STAIR-2
STORE-4 10 UP
JET FAN ELE.RM 9 11
DUCT- 150X150 @ 15 L/S (T/A)

10001
UP 8
7
12
13 E 229766.3738
20 -8.400 FFL 6 14
19 1
-8.675 SSL 5 15 N 405359.1442
D
18 2
17 3 LIFT 4 16
17
LIFT LOBBY 3

JET FAN
16 4 2 18
15 5
14 6 FD FD/VD
BMS ROOM 1 19
20
10000

PARKING 13 7 VD FD UP

CUPBOARD FOR
12 8
PARKING 11 9 LIFT JANI. WHEEL STOPPER

ELECTRICAL
UP
10 H.TOI. -8.575 FF
RM. RETURN AIR GRILLE -8.675 SS
STAIR-1 SIZE-150X150 @ 15 L/S
-8.575 FF PAVEMENT DOOR GRILL
-8.675 SS DG - 300 x 200
8650

-8.400 FFL
-8.400 FF
E 229694.053
N 405360.906 E
DRIVEWAY -8.675 SS
2ND BAS PAVEMENT -8.400 FF
-8.675 SS
DRIVEWAY
S E 229766.048
N 405355.969 -
R644803
DOMESTIC WATER TANK-1
PARKING
50 m³
DOMESTIC
STORE-5 4/M A --
-8.575 FFL PUMP ROOM
-8.675 SSL
E DOMESTIC WATER TANK-2
50 m³ PARKING
-8.575 FFL -8.400 FFL
-8.675 SSL -8.400 FFL
10000

-8.675 SSL

15211
-8.675 SSL
8650

E 229693.1541
N 405353.2256 SUMP PIT - 1
1.2m x 1.2m x 1.2m
E 229692.870
N 405350.976 F PARKING
WHEEL STOPPER
E 229764.282
N 405340.860

F FHC FHC IMPORTANT NOTE:


R FADEL FOUANI --
(A) PROVIDE FIREPLOT
DAMPERS
LIMIT / MOTORIZED COMBINATION FIRE
3226 --
SMOKE DAMPERS AS PER REQUIREMENTS OF NFPA / LOCAL QATAR

1991
CIVIL DEFENSE DEPARTMENT WHETHER SHOWN ON DESIGN
8050

STAIR-3 DRIVEWAY -8.575 FF


9999

UP

-8.675 SS DRAWING OR NOT. CONTRACTOR SHALL SUBMIT ARCHITECTURAL


11
12
13
14
15
16
17
18
19
20

IT

FIRE ZONES DRAWING INDICATING ALL DUCT PENETRATING. THE


Q
IM

3500
KL
UP

-8.575 FF FIRE WALLS AND ALSO INDICATE ALL FIRE / MOTORIZED DAMPERS
10
9
8
7
6
5
4
3
2
1

AC

-8.675 SS
E 229763.974APPROVAL. THE DAMPERS ITS
TB

JET FAN & OBTAIN LOCAL CIVIL DEFENSE


SE

RAIN N 405338.884
-8.400 FF
ACTUATORS AND ALL OTHER ACCESSORIES SHALL BE ACCESSIBLE
WATER TANK
FOR INSPECTION TESTINGE 229762.807
AND SERVICE. ALL FIRE ACCESSORIES
G E 229691.507
G 206 m³
-8.675 SS

9
349
N 405341.070 -8.575 FFL SHALL BE (FM/UL) LISTED. N 405335.584
ED
AT EXTRACT AIR
IRRIGATION ER
PARKING
PAVEMENT FIR SHAFT ABOVE
(B) CONTRACTOR SHALL PROVIDE AIR BALANCING DAMPERS
PUMP ROOM S
-8.400 FFL
SUMP PIT-1X1X1.7 OUR (VCD) ON EACH SUPPLY / RETURN DUCT, BRANCH DUCT AND Commercial License: 13160 Exp: 12/12/2023 l MME / EEOACC: 4/M Exp: 13/01/2025

00
2H
O
-8.675 SSL

35
-8.575 FFL OILFIRE
2 HOURS & SAND INTERCEPTOR
RATED WHERE REQUIREDE 229761.017
TO ACHIEVE AIR BALANCE. THE HAND
28.2 m³
1.2 X 0.8 X 1.6 LOCK SHALL
BE ACCESSIBLE
N 405332.577 FOR INSPECTION TESTING AND
(2B+G+M+3 TYP FLRS) OFFICE BUILDING
-8.575 FFL
0 SERVICE / AIR BALANCING.
350
10000

E 229758.671
IRRIGATION EXTRACT AIR
0
N
(C) MEANS OFN 405329.979
ACTUATION
TO FIRE MODE FOR THE (ECQ-B04, PIN:69040300)
E 229689.964
WATER TANK SHAFT ABOVE 350 BASEMENT CAR PARK VENTILATION SYSTEM SHALL BE THRU
N 405331.190 THE ACTIVATION OF SPRINKLER FLOW SWITCH SERVING THE
3500
M FIRE AREA ". ENERGY CITY - QATAR
H 1999
2405

L (D) CFD ANALYSIS REPORT SHALL CONFORM THE LATEST


QATAR ENDOWMENT AUTHORITY
IM
IT
55214 I J K EPARAMETERS
229755.861
N 405327.892
OF THE QCD FIRE SAFETY GUIDELINES (2015) " .

PLOT LIMIT
L
EF / 2B - 1 OT EF / 2B - 2
PL - - - MINOR ROAD (18.0m WIDE) - - - E 229752.697
(EXHAUST AIR FAN / FAN GUARD / GRAVITY LOUVER) N 405326.396 (EXHAUST AIR FAN / FAN GUARD / GRAVITY LOUVER) AUG.2023 18-505
E 229744.909
MASONRY EXHAUST AIR DUCT 2500 X 1500 mm N 405325.517
E 229746.903 E 229749.301 MASONRY EXHAUST AIR DUCT 2000 X 1400 mm
FROM GROUND FLOOR WITH AIR EXHAUST LOUVER N 405325.364 N 405325.550 FROM GROUND FLOOR WITH AIR EXHAUST LOUVER
Note: 150Ø mm Rain Water Drain Point. (Connected to nearest rain water pipe) Note: 150Ø mm Rain Water Drain Point. (Connected to nearest rain water pipe) SECOND BASEMENT FLOOR PLAN
MECHANICAL VENTILATION LAYOUT
M-MV-191 1:200
IFC

KR IRF IRFAN AHMAD


- 2ND BASEMENT PLAN 3529 3529
- Scale: 1:200