window air conditioning
window air conditioning
BACHELOR OF TECHNOLOGY
IN
MECHANICAL ENGINEERING
Submitted by
CERTIFICATE
External Examiner
ACKNOWLEDGEMENT
We are highly thankful to Sri B.SAI RAM KRISHNA, Assistant. Prof, Department
of Mechanical for his precious guidance, for providing background knowledge, valuable
encouragement and timely suggestions throughout the project.
We have the immense and great pleasure expressing my thanks and deep sense of
gratitude to Sri B.PRANEETH, Head of Department, Mechanical Engineering for
extending necessary facilities for the completion of the project.
We are expressing our heart full thanks and sincere gratitude to Dr.M.SASIDHAR,
Principal, AMRITA SAI INSTITUTE OF SCIENCE AND TECHNOLOGY for giving
me the opportunity for the successfully completion of my degree. I would also like thank all
the teaching and non-teaching staff members of mechanical department who have extended
their full co-operation during course of my project
We are also thankful to Dr. K. SAI MANOJ, Honoarable C.E.O, and we express our
sincere gratitude and deep sense of respect for making us available with all the required
assistance and for his support and inspiration to carry out this project in the institute.
Finally we thank one and all who directly and indirectly helped us to complete our
project successfully.
Project Associates
I hereby declare that the work presented in this dissertation report titled “EXPERIMENTAL
INVESTIGATION OF WINDOW AIR CONDITIONING COP WITH AND WITHOUT
DIFFUSER AT COMPRESSOR INLET” is Submitted Towards completion of thesis work in
B.Tech (Mechanical Engineering) Amrita Sai Institute of Science and Technology Paritala. It is an
authentic record of my original work pursued under the supervision of, Mr. B.SAI RAM KRISHNA.
I have not submitted the matter embodied in this dissertation for the award of any other degree.
Project Associates
ABSTRACT i
LIST OF FIGURES ii
LIST OF GRAPHS iii
LIST OF TABLES iii
NOMENCLATURE iv
ABBREVIATIONS AND SUBSCRIPTS v
I. INTRODUCTION: 1-20
1.1 Introduction to window air conditioning 1-2
1.2 Indoor side components 2-6
1.3 Outdoor side components 6-9
1.4 Window air conditioning system working principle 10
1.5 Air circuit of window air conditioning system 10-12
1.6 Refrigerant 12
1.7 Classification of refrigerants 13-14
1.8 Selection of good refrigerants 14
1.9 Requirements of refrigerants 15
1.10 Properties of refrigerants 15-16
1.11 Commonly used refrigerants 16-18
1.12 Designation of refrigerant 19
1.13 Introduction to diffuser 19-20
II. LITERATURE REVIEW: 21-23
2.1 Literature survey 21-23
2.2 Scope of present work 23
III. ORGANISATION OF THESIS: 24
3.1 Flow chat for thesis organization 24
IV. DESIGN PROCEDURE & FABRICATION 25-31
4.1 Design procedure of window air conditioning test rig 25
4.2 Design of diffuser 26-27
4.3 Experimental setup with diffuser at compressor inlet 28-30
V. EXPERIMENTAL PROCEDURES 32-33
5.1 Experimental procedure of window air conditioning test rig without diffuser 32
5.2 Experimental procedure of window air conditioning test rig with 120 diffuser 33
5.3 Experimental procedure of window air conditioning test rig with 140 diffuser 33
VI. OBSERVATIONS AND CALCULATIONS 34- 43
6.1 Specifications of window air conditioning test rig 34
6.2 Standard values 34
6.3 Calculations of test rig without diffuser at compressor inlet 39-40
6.4 Calculations of test rig with 120 diffuser at compressor inlet 40-41
6.5 Calculations of test rig with 140 diffuser at compressor inlet 42-43
VII. RESULT AND DISCUSSION 44- 48
VIII. CONCLUSION 49
IX. FUTURE SCOPE 50
X. REFERENCES 51
ABSTRACT
One of the diffuser gives maximum cop, which will fixed at compressor inlet.
Diffusers at compressor inlet 12° divergence angle of diffuser, 14° divergence angle of
diffuser given the better coefficient of performance. But 14° divergence angle of
diffuser is given the higher coefficient of performance than the 14° divergence angle of
diffuser. The 14° divergence angle of diffuser is fixed at compressor inlet. At
compressor inlet 14° divergence angle of diffuser given the maximum cop (2.13).
i
LIST OF FIGURES
ii
LIST OF GRAPHS
Graph No. Graph Name Page No.
LIST OF TABLES
6.4 Refrigeration effect and cop for without and without diffuser 43
condition at compressor inlet
iii
NOMENCLATURE
T Temperature [0c]
T1 inlet temperature at compressor inlet [0c]
P pressure [bar]
V voltage [volts]
A current [amps]
iv
ABBREVIATIONS AND SUBSCRIPTS
HFC Hydrofluorocarbon
R134a 1,1,1,2-tetrafluoroethane
CFC Chlorofluorocarbon
HCFC Hydrochlorofluorocarbon
v
CHAPTER-I
INTRODUCTION
This refrigeration unit has a double shaft fan motor with fans mounted on both sides of the motor.
One at the evaporator side and the other at the condenser side.
The evaporator side is located facing the room for cooling of the space and the condenser side
outdoor for heat rejection. There is an insulated partition separating these two sides within the same
casing.
1
Front Panel
The front panel is the one that is seen by the user from inside the room where it is installed
and has a user interfaced control be it electronically or mechanically. Older unit usually are of
mechanical control type with rotary knobs to control the temperature and fan speed of the air
conditioner.
The newer units come with electronic control system where the functions are controlled using remote
control and touch panel with digital display.
The front panel has adjustable horizontal and vertical louvers where the direction of air flow is
adjustable to suit the comfort of the users.
The fresh intake of air called VENT (ventilation) is provided at the panel in the event that user would
like to have a certain amount of fresh air from the outside.
The indoor parts of a window air conditioner include Cooling Coil, Fan Blower, Capillary, Filter
EVAPORATOR:
Evaporator is nothing but the part which can produce a refrigerant effect. Here heat will
be taken from the load area almost at constant pressure. Large amount of heat is taken by the
refrigerant due to latent heat addition. The evaporator which was used in experimental setup as
shown below in Fig 1.2
Classification of Evaporators:
2
(c) According to operating conditions:
1. Frosting evaporator. 2. De Frosting evaporator. 3. non-frosting evaporator.
▪ Cooling Coil is a finned tube evaporator with a air filter mounted on it. The cooling coil is where
the heat exchange happens between the refrigerant in the system and the air in the room.
4. Length(mm) 15X15
Packing Type Box
5 Outer Material Stainless Steel
6 Voltage 220-380 V
7 Frequency 50Hz
3
▪ Fan Blower is a centrifugal evaporator blower to discharge the cool air to the room.
EXPANSION VALVE:
After the condenser, refrigerant will be sent to the expansion valve (capillary tube). In
this process heat and pressure both reduce by isenthalpic process. Here capillary tube inner and outer
diameters are 0.5mm, 1.5mm. The capillary tube used in this experimental setup as shown below in
Fig 1.4
2. Variable Restrictive Type Expansion Devices: In this, the extent of opening area of flow keeps
on changing depending on the type of control.
C. Float Valves
i) High side Float valve in this it maintains the liquid at a constant level in the condenser.
ii) Low side Float valve in this maintains the liquid at constant level in the Evaporator.
4
▪ Capillary Tube is used as an expansion device. It can be noisy during operation if installed too
▪ Operation Panel is used to control the temperature and speed of the blower fan. A thermostat is
used to sense the return air temperature and another one to monitor the temperature of the coil. Type
of control can be mechanical or electronic type.
▪ Filter Drier is used to remove the moisture from the refrigerant. A filter-drier in a refrigeration or
air conditioning system has two essential functions: one, to adsorb system contaminants, such as
water, which can create acids, and two, to provide physical filtration.
5
▪ Drain Pan is used to contain the water that condensate from the cooling coil and is discharged
Compressor is used to compress the refrigerant. Compressor used in the refrigeration system is a
hermetically sealed compressor which can produce 250 PSI pressure and rotates at 1400 RPM.
And this compressor capacity is 1.5 TOR capacity Pressure can be increased isentropically here by
compressing the refrigerant. The hermetically sealed compressor as shown below in Fig1.8
Types of Compressors:
6
4 According to the method of drive employed
(a) Belt drive compressors. (b) Direct drive compressors.
The specifications of the Hermetically sealed compressor which is used in the window air
conditioning test rig system is noted in the below Table 1.1.
7
Types of Condensers:
Condensers are classified based on the cooling medium used for condensation of refrigerant as
follows:
3. Evaporative condensers
▪ Air Cooled Condenser Coil is used to reject heat from the refrigeration to the outside air. In this
system air type condensers are used. Then the refrigerant will be sent to the condenser by the copper
tubes. Here high-pressure refrigerants can reject heat to the surroundings isobarically. A fan is placed
behind the condenser for the forced heat convection process to cool the refrigerant. The air-cooled
type of condenser as shown below in Fig1.9
8
▪ Propeller Fan is used in air-cooled condenser to help move the air molecules over the surface of
▪ Fan Motor is located here. It has a double shaft where the indoor blower and outdoor propeller
fan are connected together.
9
1.4 Window air conditioning system working principle:
High pressure, high temperature vapour refrigerant coming out of compressor is condensed in
condenser using outside (atmospheric) air as cooling medium. The liquid refrigerant is further passed
through capillary tube to reduce its own pressure and then passed over evaporator, where it absorbs
heat from air to cool it. Due to absorption of heat, the liquid refrigerant gets converted into vapour
refrigerant and these vapours are drawn into the compressor and cycle is repeated again and again.
The function of window air conditioner is to provide comfort to the occupants in the room by,
10
The air circuit of a window air conditioner consists of 3 major air circulation systems.
Room air
The air from the room is drawn over the evaporator fan (also called as indoor fan) through a filter,
which removes dirt, dust, impurities etc. The fan used may be propeller type or centrifugal type. The
air is cooled while passing over the evaporator tubes by giving its heat to the refrigerant circulating
inside the evaporator. thermostat (in control panel) is provided at the evaporator to measure the
temperature of air coming from the room. If the temperature is above the set or desired value, it
makes the compressor to switch “ON”. If the temperature is below the set value or desired value,
it makes the compressor to switch “OFF”.
Outside air
The outside (atmospheric) is drawn over the condenser fan. The vapour refrigerant circulating inside
the condenser coil gives up its heat to the air and gets condensed and cooled. The fan used here is of
propeller type.
Fresh air from outside
To maintain the purity of air inside the room, fresh outdoor air is made to enter into the room through
air damper. The fresh air is cooled by evaporator coils, while coming from damper. This cooled fresh
air is then mixed with the room air.
11
Fig.1.14 p-h Diagram of Simple VCR
The pressure-enthalpy (p-h) diagram is a thermodynamic property diagram commonly used in the
refrigeration field.
1.6 Refrigerant:
Refrigerant is defined as "the working fluid used to remove the heat from the space or products to
be cooled in a refrigerating system".
Refrigerant produces a cooling effect by absorbing heat from the products or space to be cooled in
the refrigerating system.
Refrigerant absorbs heat at a lower temperature and pressure in the evaporator and changes its state
from liquid to vapour during evaporation. Refrigerant rejects heat at high temperature and pressure
in the condenser and changes its state from vapour to liquid during condensation.
Examples of Refrigerants: Ice, Dry ice, Ice-Salt mixture, Sulphur dioxide, Ammonia, Carl dioxide,
Water, brines and freons.
12
1.7 CLASSIFICATION OF REFRIGERANTS:
Based on the heat absorbing capacity refrigerants are classified into two categories:
1. Primary refrigerants.
2. Secondary refrigerants.
Primary Refrigerants: The refrigerants which are capable of absorbing latent heat from the
refrigerating system are called "Primary Refrigerants".
The primary refrigerant cools the products directly in the refrigerating system. They change from
liquid state to vapour state during evaporation in the evaporator and again from vapour state to liquid
state during condensation in the condenser. These refrigerants are mostly used in Vapour
Compression Refrigeration systems.
Examples: Ammonia (NH3), Carbon dioxide (CO₂), Sulphur dioxide (SO₂), Methyl chloride, Aqua
Ammonia and Freons.
1. Halo Carbon Compounds: These contain halogens (chlorine, fluorine and bromine) as one of
the main elements. They are available in the market under trade names denoted as Freons or CFCs
(Chloro-Fluoro-Carbons). These are used in domestic refrigerators, commercial and industrial
purposes.
Example:
Freon-11 or F-11: Trichloromonofluoromethane - CCl3F.
Freon-12 or F-12: Dichlorodifluoromethane - CCl2F2.
Freon-22 or F-22: Monochlorodifluoro methane - CHClF2.
2. Azeotropes: These are stable mixtures of various refrigerants. They evaporate and condense as
a single substance and do not separate into individual constituents.
Example: Refrigerant-500 is a mixture of 73.8% of F-12 and 26.2% of F-152.
13
3. Hydrocarbons: Refrigerants containing organic compounds come under this group The
refrigerants possess good thermodynamic properties but are highly flammable. They are used in
industrial and commercial applications like petroleum and petrochemical industries
Example: Methane -CH4, Ethane- C2H6, Propane - C2H8
4. Inorganic Compounds: They process excellent thermodynamic and physical properties and are
widely used in domestic, commercial and industrial applications.
Example: Ammonia-NH3: Water- H2O, Air, Carbon Dioxide -CO2, Sulphur dioxide - SO2
Secondary Refrigerants:
The refrigerants which are capable of absorbing sensible heat from the refrigerating system are called
"Secondary Refrigerants". The secondary refrigerants carry heat from the products and are cooled
by the primary refrigerant circulated in the evaporator. They indirectly cool the products in the
refrigerating system. They do not undergo any phase changes during the cycle. The secondary
refrigerant circuits are very much useful in all major commercial and industrial refrigeration plants.
Examples: Air, Water, Brine solution of Sodium Chloride, Calcium Chloride and Propylene
glycol.
14
1.9 REQUIREMENTS OF REFRIGERANTS:
The refrigerants used for refrigeration purpose must meet the following requirements
1. The refrigerant should have a low boiling point.
2. The refrigerant should have a low freezing point.
3. The refrigerant must have low specific heat
4. The refrigerant must possess high latent heat of evaporation
5. The refrigerant must give high COP
6. The refrigerant must have a high critical temperature and pressure.
7. The refrigerant should have low specific volume.
8. The refrigerant must have high thermal conductivity.
9. The refrigerant should not be toxic, corrosive, flammable and explosive.
10. The refrigerant must be cheap and readily available.
Thermodynamic Properties:
1. Boiling Point: The refrigerant should have a low boiling point. It increases the capacity of the
refrigerating system.
2. Freezing Point: The refrigerant should have a low freezing point. It prevents choking of refrigerant
in the pipes and valves.
3. Evaporator and condenser pressure: The evaporator pressure and condenser pressure should be
above the atmospheric pressure to avoid air leakages into the system from the surroundings.
4. Latent heat of vaporization: The Latent heat of vaporization should be high to minimize the
quantity of refrigerant used and also to get maximum refrigeration effect.
5. Critical temperature and pressure: The critical temperature of the refrigerant should be high for
easy condensation of the vapour refrigerant.
15
Physical Properties:
1. Specific volume: The specific volume should be low to reduce the size of the compressor.
2. Specific heat: The specific heat should be low for liquid refrigerant to increase the refrigerating
effect per kg of refrigerant circulated in the system.
3. Thermal conductivity: The refrigerant must have high thermal conductivity as it reduces the mass
flow rate of refrigerant and area of heat transfer in the condenser and evaporator
4. Viscosity: The viscosity must be low for better heat transfer and low pumping power.
5. Dielectric Strength: High Dielectric strength is desirable to provide effective insulation against
electricity leakages
16
Carbon dioxide (R-744)
Properties: Non-toxic, non-flammable, odorless, chemically stable, non-corrosive and non-
explosive, highly safe in operation, requires robust condenser and evaporator, High power
consumption, Low Cop.
Boiling point is 78.6°C., Freezing point is 56.6°C.
Applications: Air conditioning of hostels, theaters, hospitals and manufacturing of dry ice.
Freon-11 (F-11)
Chemically known as Trichloromonofluoromethane-CCl3F.
Properties: Non-toxic, Non-flammable, Non-corrosive. Low Operating pressures; Suitable for
centrifugal compressors.
Boiling point is 23.3°C, Freezing point is -111°C.
Applications: Air conditioning of hotels, theaters, departmental stores
Freon-12 (F-12)
Chemically known as Dichlorodifluoromethane methane -CC/2F2.
Properties: Highly stable; non-toxic; non-flammable, non-corrosive, non-explosive; colourless and
odourless liquid, Good miscibility, Suitable for reciprocating, rotary and centrifugal compressors.
Boiling point is - 29.8°C, Freezing point is 157.8°C.
Applications: Most popular and widely used refrigerant - all refrigeration purposes, like domestic
refrigerators, water coolers, freezers, and air conditioning plants.
Freon-22 (F-22)
Chemically known as Monochlorodifluoro methane - CHC/F2. Properties: Non-toxic: non-
flammable, non-corrosive, non-explosive.
More refrigerating effect and less power consumption than F-12. Suitable for reciprocating
17
compressors with the temperature requirements up to 900C
Boiling point is-41.3°C: Freezing point is 160°C.
Applications: All condensing units, all refrigeration applications especially in fast frea units at low
temperatures.
Water
Water is used as a secondary refrigerant if the temperature to be maintained is above 0°C in the
refrigerated space. Water is first cooled by the primary refrigerant and then the chilled water is used
for cooling purposes.
Boiling point is - 100°C, Freezing point is 0°C.
Applications: Air conditioning plants and industrial cooling installations.
Brines
Brines are salt solutions used as secondary refrigerants These are used when the temperature to be
maintained in the refrigerated space is below freezing point of the water.
Example:
1. Sodium chloride brine (NaCl) is a solution of sodium chloride salt and water. It Freezes at -21°C
at a salt concentration of 23% by weight.
2. Calcium chloride brine (CaCl₂) is a solution of calcium chloride salt and water. It freezes at -55°C
at a salt concentration of 30% by weight. Applications: freezing of fish, meat, ice plants and chemical
plants.
18
1.12 Designation of Refrigerant:
Refrigerants are internationally designated as "R" followed by certain numbers such as R-11,R-12,
R-114 etc.
Refrigerants followed by a two-digit number indicates that a refrigerant is derived from methane
base.
Refrigerants followed by a three-digit number indicates that refrigerant is derived from ethane base.
Chemical Formula CmHn ClpFq
Chemical Formula is correct, when: n+p+q=2m+2
Complete Numerical Designation: R(m-1)(n+l)(q)
DESIGNATION OF R-22
19
Use of diffuser at compressor inlet
In the present cycle, initially testing the two diffusers at compressor inlet. Diffuser raises pressure
and temperature of refrigerant before enter the compressor. It reduces the compressor work. Due to
this reduction of the compressor work, system performance will increase. One of the diffuser gives
maximum cop, which will fixed at compressor inlet.
DIMENSIONS OF A DIFFUSER:
Length of diffuser (L) = 20 mm
Entrance outer diameter (d1) = 10 mm
Entrance inner diameter (d2) = 6 mm
Exit outer diameter (D1) = 14 mm
Exit inner diameter (D2) = 10mm
Divergence angles of four diffusers (θ) =12°, 14°
20
CHAPTER-II
LITERATURE REVIEW
A broad variety of research is already being performed to study the coefficient of performance of
the window air conditioning test rig system. The diffuser which is placed before the compressor inlet
is responsible for increasing the coefficient of performance in the window air conditioning test rig.
In this literature to make the project at the lowest cost and get more COP.
JOURNAL BY: Nurul Seraj et al. have studied in this paper the coefficient of performance of the
vapour compression refrigeration system is enhanced by using the diffuser at inlet of the condenser.
For enhancement of coefficient of performance of the system is required if you increase the
refrigeration effect or decrease the power consumption of the compressor input. Basically these two
are the parameters to enhance the COP of the refrigeration system. In this experiment the COP of
the refrigeration system increases by decreasing the compressor work by using a diffuser at the
condenser inlet. The diffuser was placed in between the compressor and condenser. The inlet
diameter of the diffuser is equal to the discharging tube diameter of the compressor and outer
diameter of the diffuser is equal to the inlet tube diameter of the condenser. The diffuser cross
sectional area profile increases. So the COP of the vapour compression refrigeration system is
enhanced.
JOURNAL BY: C. Lokesh et al. to study the experimental data to analyze the performance of the
refrigeration system with and without nozzle at condenser outlet. Due to the nozzle further reduction
of pressure of refrigerant before entering into the evaporator. This improves the refrigerating effect
and cop of the refrigeration system.
JOURNAL BY: B.SanhyaRani et al. In this experiment to design and analysis nozzle at outlet to
condenser in the vapour compression refrigeration cycle. In each component the refrigerant passed
through it and undergoes phase change. High pressure is generated at nozzle that high pressure helps
to achieve the high performance in vapour compression refrigeration system. Further the angle of
nozzle was increases from 10 to 14 degrees. The coefficient of performance increases and decreases
thereafter. But the nozzle of 14 degrees divergent angle gives the batter performance compared with
the other nozzles. The refrigeration increased by 7.16% and 2.6% of compression work was reduced.
21
JOURNAL BY: Dr. B. Sachuthananthan, T.Naresh Kumar, A.Muthu Manokar
In this paper, simulation studies of a one TR window air conditioner were carried out with three
different mixtures of R22 and R290 M1 (50-50) %, M2 (25-75) % and M3 (75-25) %. Performance
parameters like refrigerant mass flow rate, refrigerant capacity, compressor power, C.O.P, condenser
inlet temperature, condenser outlet temperature, capillary tube inlet temperature and compressor
shell inlet temperature were analyzed at varying conditions, evaporator temperature varied from 60C
to120C and condenser temperature varied from 400C to 550C and results were analyzed.
Performance parameters of R22 and R290 are compared using CYCLE _D software. Simulation
results show that R290 has a maximum mass flow rate. Only a marginal variation of capacity is
observed with all working fluids. The condenser inlet temperature is minimum for R290 and
maximum for R22. Condenser outlet temperature variation is marginal for all refrigerants. R290 has
a minimum power consumption and maximum C.O.P. The simulation results show that the use of
hydrocarbon refrigerant (R290) improves the performance of window air conditioner.
22
JOURNAL BY: Lal et al. give experimental investigation on the performance of a window air-
conditioner operated with R22 and M20 refrigerant mixture tested at different refrigerant charge
levels. It was concluded that among the mixtures considered M20 (R407C 80% & HC blend 20%)
had the optimal composition in respect of better COP and per day energy consumption.
23
CHAPTER-III
ORGANIZATION OF THESIS
CHAPTER-I
INTRODUCTION
CHAPTER-III
ORGANIZATION OF
THESIS Components and fabrication of window air
conditioning system.
Manfacturing of diffusers
CHAPTER-IV
DESIGN PROCEDURE
Incorporating the diffusers at compressor
inlet
CHAPTER-VI
OBSERVATIONS AND
CALCULATIONS
CHAPTER-VII
RESULTS AND
DISCUSSIONS
24
CHAPTER-IV
DESIGN PROCEDURE
4.1 DESIGN PROCEDURE OF WINDOW AIR CONDITIONING TEST RIG:
25
4.2 Design of diffuser:
Diffuser is a passive device; it will increase the pressure energy by converting the available kinetic energy at
the inlets. The velocity of refrigerant is subsonic in window air conditioning systems and the diffuser can be
manufactured with the following dimensions. The diagrams of diffusers as shown below in figures.
26
Fig.4.2 Making of diffuser on lathe machine
27
4.3 Experimental set up with diffuser at compressor inlet:
It mainly consists of the main system. The main loop is
consisting of a compressor, condenser, capillary tube valve (expansion valve) and evaporator. The
compressor used in this one is hermetically sealed reciprocating type compressor and capacity is 1.5
TOR. The condenser and evaporator both are the coppered single tube. In this single flow tube
condenser, inner side refrigerant flows and air is flows outside of the tube. The refrigerant then flows
into the evaporator through expansion valve. The capillary tube is used to control the flow rate of
the refrigerant into the evaporator coil and also to set the difference pressure. In the one flow tube
evaporator, To minimize the heat losses, the tube is insulated. The two diffusers were tested at
compressor inlet by changing one by one diffuser.
The readings were taken with changing the diffuser at compressor inlet. By using the two pressure
gauges, these gauges are incorporated in the system to note down the pressure at various points
(diffuser inlet, outlet, compressor outlet, condenser outlet and inlet of evaporator). By using the
temperature sensors, to measure the temperatures at various points in the system like as pressure
gauges. The voltage and the current in the system are measured by using the voltmeter and ammeter.
Five digital thermometer thermocouple sensors - 50~80°c are used to measure the temperature at
various positions in the system (Diffuser inlet and outlet, compressor outlet, condenser outlet and
evaporator inlet). Temperatures at different positions mentioned in Fig.4.4 are measured. Power
consumption of the system is constant that is 1020 watts.
28
Where
T1-Temperature at diffuser inlet
T2-Temperature at compressor inlet
T3-Temperature at condenser inlet
T4-Temperature at inlet of expansion valve
T5- Temperature at Evaporator Inlet
P1-Pressure at diffuser inlet
P2-Pressure at compressor inlet
D1-Diffuser with angle 12°
D2-Diffuser with angle 14°
In this experimental work a domestic window air conditioning system has been used. In any
compression refrigeration system, there are two different pressure conditions. One is called the low-
p r e s s u r e side (evaporator), a n d another one is high pressure side (condenser), heat is absorbed
in low pressure side and suction line which is entrance to the compressor suction valve is also on the
low-pressure side. The condenser is in high pressure side where the heat is released from the
refrigerant. The compressor outlet valve, liquid receiver by filter-drier and the refrigerant flows the
high-pressure side. Expansion device connects both pressure sides and it is designed such that no
liquid refrigerant will flow through it until and unless the pressure in the evaporator is reduced by
running of the compressor. Refrigerant is sprayed into the evaporator due to low pressure; it boils
rapidly and absorbs heat. The vaporized refrigerant moves back to compressor through the suction
line and it compressed to high pressure side as super-heated vapour. While through the air-cooled
condenser it is cooled, gives up heat that absorbed in the evaporator and returns to liquid then flows
into liquid receiver ready to repeat the cycle of system. The experimental setup of the Window air
conditioning system test rig as shown below in Fig4.6
29
Fig.4.6 Experimental test rig with and without diffuser at compressor inlet
30
The component used in the Window air conditioning test rig are shown in the below table 4.1
Table 4.1 Components used for window air conditioning test rig
1 Flare Nut
2 Gauge Adapter
3
Tee Fitting
4
Valve
5
Pressure Gauge
6
Temperature Gauge
Energy Meter
8
Voltmeter and Ammeter
31
CHAPTER-V
EXPERIMENTAL PROCEDURE
5.1 Experimental procedure of window air conditioning test rig without diffuser:
The experimental setup of the water cooler test rig system with and without diffuser at condenser
inlet is shown in the below in Fig.5.1
Fig 5.1 Experimental test rig with and without diffuser at compressor inlet
32
5.2 Experimental procedure of window air conditioning test rig with 12° diffuser
• Identify each component of window air conditioning test rig.
• Record The values of pressure and temperature after the pressure gauges get stabilized.
• Record the energy meter reading.
• Take the entire enthalpy from pressure gauge Stabilized of given refrigerators.
• Now evaluate the theoretical and actual relative COP.
12° Diffuser
5.3 Experimental procedure of window air conditioning test rig with 14 ° diffuser:
• Identify each component of window air conditioning test rig.
• Record The values of pressure and temperature after the pressure gauges get stabilized.
• Record the energy meter reading.
• Take the entire enthalpy from pressure gauge Stabilized of given refrigerators.
• Now evaluate the theoretical and actual relative COP.
14° Diffuser
33
CHAPTER-VI
OBSERVATIONS AND CALCULATIONS
34
CALCULATIONS
35
36
Fig6.1 Refrigeration table of R-22
37
CALCULATIONS
A. tonnage capacity = ma(h1 –h2) /3.517 TR
B. manometric head (hf) = L sinƟ
C. density of manometric fluid (ρf) =810 kg / m3
D. Air density (ρa) = pa /Ra Ta
E. Find manometric head (ha): ρaha = ρfhf
F. Find velocity of air (va) = √(2 x g x ha)
G. Discharge (Qa) = Aa x va
H. Mass flow rate of air (ma)
I. Refrigerating effect (React) = ma x (h1 – h2)
J. Tonnage capacity = R.E.act/3.517
K. ACTUAL COP Compressor work = (Final reading – Initial reading) / Time in hour
L. Actual cop = RE/Work
M. Theoretical COP = RE/
38
6.3 Calculations of test rig without diffuser at compressor inlet
1. Inlet condition: DBT = 33 0c & WBT = 280c
2. Outlet conditions: DBT = 280c & WBT = 250c
h1 = 82.5 kj/kg
h2 = 53 kj/kg
3. Manometric head (hf)
hf = L sin Ɵ
hf = 2 x sin (5.71)
= 0.1989 mm
4. density of manometric fluid ((ρf)
ρf = density of fluid = 812 kg/ m3
39
11. Tonnage capacity = R.E.act/3.517
=2.8917/3.517
=0.8232
12. ACTUAL COP Compressor work
= (Final reading – Initial reading) / Time in hour
= 52.30-49.25/30/60
= 3.1 kw
40
6. Find velocity of air (va) = √(2 x g x ha)
= √(2 x 9.83 x 0.1862)
=3.38 m/s
7. Discharge (Qa) = Aa x va
=0.0531 x 3.38
=0.126 m3/s
8. Mass flow rate of air (ma)
= Qa x ρa 0.126 x 2.088
=0.238
41
6.5 Calculations of test rig with 140 diffuser at compressor inlet
42
10. Tonnage capacity = R.E.act/3.517
=4.7/3.517
=2.82
11. ACTUAL COP Compressor work
= (Final reading – Initial reading) / Time in hour
= 52.30-51.25/30/60
= 3.3 kw
12. Actual cop = RE/Work
=4.7/3.3
=2.13
13. Theoretical COP = RE/W (or) h4-h3/h1-h4
= 480-250/460-418
=5
43
CHAPTER-VII
RESULTS AND DISCUSSIONS
Diffuser at compressor inlet Table 6.1 summarizes pressure and temperature readings of
refrigerant at various state points as shown in table 6.1 summarizes refrigerating effect, reduction
in compressor work and coefficient of performance without and with diffuser conditions.
Figure 7.1 shows the variation of cop with respect to divergence angles. It is observed that
maximum gain in COP at diffuser with divergence angle 14°at pressure of 2.5 bars. Applying first
law thermodynamics to diffuser. It was observed that increase in enthalpy proportional to kinetic
energy of the refrigerant. The rise in enthalpy is without consumption of power from system.
Hence, the compression work is reduced for some refrigerating effect, COP of the system is
increased. During a process through diffuser, pressure and temperature of refrigerant increases.
Due to this variation in pressure and temperature of refrigerant flows through compressor. Hence,
some compression work is reduced
44
Fig.7.2 Variation of temperature without and with diffuser
Figure 7.2 shows the variation of temperature with divergence angle. Initially temperature at 36°
without using the diffuser. When using diffusers, the temperature decreasing first at 12° divergence
angle and then increases up to certain temperature (37°). This is the maximum temperature at 14°
divergence angle of diffuser is (40°)
Chart Title
60
50
40
30
20
10
0
Pressure At Without Pressure At Diffuser Pressure At Diffuser
Diffuser Angle12° Angle14°
45
Figure 7.3 shows the effect of divergence angles on the diffuser pressure. It is find out that, initially
the pressure at 48 bar without any diffuser(zero degrees). When using the 12° divergence angle of
diffuser pressure is increases to 52 bar and then starts to increases 0.55 bar at 14° and 57 bar at 14°
divergence angle. Then pressure decreases up to 0.34 bar when using the 14° diffuser. At 14°
divergence angle the system given by maximum pressure.
46
CHAPTER VIII
CONCLUSION
• Experimental investigation has been carried out to place and test the effect of two diffusers
of divergence angle 12° 14° at compressor inlets on water cooler test rig systems.
• The 12°,14° divergence angled diffusers are fixed at the compressor inlet.
• Diffusers at the compressor inlet with 14° divergence angle gives higher coefficient of
performance than the 12° divergence angle diffuser and then normal procedure.
• Diffuser with divergence angle of 14° given the maximum cop (2.13) as compared to 12°
diffuser
• The pressure increases from 47 to 57 bars and the compressor work is reduced by 4%.
Percentage of increase in COP is approximately 4%
47
CHAPTER-IX
FUTURE SCOPE
The present work on the Window air conditioning test rig system which has been carried out by
our batch has provided an efficient novel refrigeration system. Many operation and design
parameters have been considered in this research. However, there are still many other areas that
can be investigated. Recommended future studies are as follows:
● For different application areas, the cycle may be analyzed for different types of refrigerants.
● Research can be done on finding the optimum size of the diffuser by varying the shape and size so
that it gives its best results.
● Research can be done on the finding coefficient of performance of combined diffusers placed at
compressor inlet.
● In the cycle the capillary is replaced with a Solenoidal valve to increase its performance.
● In this cycle the diffuser is replaced with heat exchangers to find the COP.
● In this cycle the diffuser is replaced with nozzles to increase the COP.
48
CHAPTER-X
REFERENCES
[1] M.Ashok Chakravarthy, M.L.S.Deva Kumar. “Experimental Investigation of an Alternate Refrigerant
for R22 in Window Air Conditioning System,” International Journal of Scientific and Research
Publications, Volume 2, ISSN 2250-3153.
[2] 1K. John Samuel, 2K. Govindarajulu and 1G. Edison. An “Experimental Investigation and
Performance Evaluation of 1.5 TR WindowAir-Conditioner by Using R22, R407C and R410A by
Varying the Capillary Pitch,” World Applied Sciences Journal 29 (11): 1468- 1472, 2014,ISSN 1818-
4952,© IDOSI Publications, 2014, DOI: 10.5829/idosi.wasj.2014.29.11.1706
[3] Prof. S.M.Shaikh1, Prof. A.M.Patil2, Prof. A. M. Vibhute3. “Performance Investigation of Window
Air Conditioner,” IOSR Journal of Civil and Mechanical Engineering (IOSR-JMCE) ISSN: 2278-1684,
PP: 32-37.
[4] Madhu Jhariya1*, P.K.Jhinge and R.C. Gupta2. “Experimental stedy on performance of condenser of
two different types used in Window Air Conditioner,” Int.J.Curr.Res.Aca.Rev.2013;1(4):35-41
[5] M Sidhartha Bhatt and R Sudhir Kumar. “Window Air Conditioners: Evaluation and Energy
Conservation,” Journal of Scintific & Industrial Research, Vol.60, August 2011, pp655-661
[6] Sheik Ismail THARVES MOHIDEENa and Nagachari NETHAJIb. “Experimental Studies on
Improvement of COP of Window Air Conditioning Unit,” aDepartment of Mechanical Engineering,
Institute of Road and Transport Technology, Erode, India. bDepartment of Mechanical Engineering,
DDCSM Polytechnic College, Palacode, India.
[8] J. Paul Guyer. “An Introduction to Air Conditioning System Design” by, P.E., R.A., Fellow ASCE,
Fellow AEI, 2009
[9] Dr. Robert Hammon, “HVAC DESIGN GUIDE,” California Energy Commission, Public Interest
Energy Research (PIER) Program, JULY 2005.
[10] “Refrigeration and Air Conditioning”, 3rd Edition, by C. P. Arora, The McGraw-Hill Companies
49