Date 1/20/2024

Officials Rest House Lighting

Created with DIALux


Officials Rest House Lighting

Table of Contents

Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 .............................

Product data sheets


Philips - (1x 9150058074 MESON 6500K 23.5W) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13.............................
Philips - (1x TLED 36W 6500K 160D 9290013463) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14............................

Officials Rest House Site


Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
.............................

Officials Rest House Site - Officials Rest House Building

Ground Floor
Room list / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 .............................

Officials Rest House Site - Officials Rest House Building - Ground Floor

Bath
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35 .............................
Working plane (Bath) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . .37 .............................

Officials Rest House Site - Officials Rest House Building - Ground Floor

Bath
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43 .............................
Working plane (Bath) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . .45 .............................
Officials Rest House Lighting

Table of Contents

Officials Rest House Site - Officials Rest House Building - Ground Floor

Bath
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
48
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51.............................
Working plane (Bath) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . 53. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.

Officials Rest House Site - Officials Rest House Building - Ground Floor

Bath
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
56
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59.............................
Working plane (Bath) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . 61. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.

Officials Rest House Site - Officials Rest House Building - Ground Floor

Bath
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
64
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67.............................
Working plane (Bath) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . 69. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.

Officials Rest House Site - Officials Rest House Building - Ground Floor

Bath
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
72
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75.............................
Working plane (Bath) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . . 77. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.

Officials Rest House Site - Officials Rest House Building - Ground Floor

Bath
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
80.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
81.............................
Officials Rest House Lighting

Table of Contents

Working plane (Bath) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . .83


.............................

Officials Rest House Site - Officials Rest House Building - Ground Floor

Bed Room
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .84 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
87.............................
Working plane (Bed Room) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . .89. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.

Officials Rest House Site - Officials Rest House Building - Ground Floor

Bed Room
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
94.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
95 .............................
Working plane (Bed Room) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . .
97. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.

Officials Rest House Site - Officials Rest House Building - Ground Floor

Bed Room
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
100 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
102. .............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
103. .............................
Working plane (Bed Room) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . .
105. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. .

Officials Rest House Site - Officials Rest House Building - Ground Floor

Bed Room
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .106 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
108
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
110
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
111..............................
Working plane (Bed Room) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . .
113 .............................

Officials Rest House Site - Officials Rest House Building - Ground Floor

Bed Room
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .114 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
116
Officials Rest House Lighting

Table of Contents

Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .118


..............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
119
Working plane (Bed Room) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . .
121 .............................

Officials Rest House Site - Officials Rest House Building - Ground Floor

Corridor
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .122 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
124
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
126..............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
127..............................
Working plane (Corridor) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . .
129..............................

Officials Rest House Site - Officials Rest House Building - Ground Floor

Dinning
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
132
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
135..............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
136..............................
Working plane (Dinning ) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . .
138..............................

Officials Rest House Site - Officials Rest House Building - Ground Floor

Entrance
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .139 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
141
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
143..............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
144..............................
Working plane (Entrance) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . .
146 .............................

Officials Rest House Site - Officials Rest House Building - Ground Floor

Kitchen
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .147 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
149
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
151..............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
152..............................
Working plane (Kitchen) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . .
154.............................
Officials Rest House Lighting

Table of Contents

Officials Rest House Site - Officials Rest House Building - Ground Floor

Pantry
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .155 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
157
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
159..............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
160..............................
Working plane (Pantry) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . .
162.............................

Officials Rest House Site - Officials Rest House Building - Ground Floor

Stair Landing
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .163 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
165
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
168
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
169..............................
Working plane (Stair Landing) / Light scene 1 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . .
171 .............................
(adaptive)

Officials Rest House Site - Officials Rest House Building

First Floor
Room list / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172 ..............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
180
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
181

Officials Rest House Site - Officials Rest House Building - First Floor

Bath
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .184 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
186
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
188..............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
189..............................
Working plane (Bath) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . .
191 .............................

Officials Rest House Site - Officials Rest House Building - First Floor

Bath
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .192 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
194
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
196
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
197..............................
Officials Rest House Lighting

Table of Contents

Working plane (Bath) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . .199


..............................

Officials Rest House Site - Officials Rest House Building - First Floor

Bath
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .200 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202 ..............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
204..............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
205..............................
Working plane (Bath) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . .
207 .............................

Officials Rest House Site - Officials Rest House Building - First Floor

Bath
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .208 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
210
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
212..............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
213..............................
Working plane (Bath) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . .
215 .............................

Officials Rest House Site - Officials Rest House Building - First Floor

Bath
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .216 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
218
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
220..............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
221..............................
Working plane (Bath) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . .
223 .............................

Officials Rest House Site - Officials Rest House Building - First Floor

Bath
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .224 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
226
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
228..............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
229..............................
Working plane (Bath) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . .
231 .............................

Officials Rest House Site - Officials Rest House Building - First Floor

Bath
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .232
..............................
Officials Rest House Lighting

Table of Contents

Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .234 ..............................


Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
236..............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
237..............................
Working plane (Bath) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . . .
239 .............................

Officials Rest House Site - Officials Rest House Building - First Floor

Bed Room
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .240 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
242
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
245
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
246..............................
Working plane (Bed Room) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . .
248 .............................

Officials Rest House Site - Officials Rest House Building - First Floor

Bed Room
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .249 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
251
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
254
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
255..............................
Working plane (Bed Room) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . .
257 .............................

Officials Rest House Site - Officials Rest House Building - First Floor

Bed Room
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .258 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
260
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
262
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
263..............................
Working plane (Bed Room) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . .
265 .............................

Officials Rest House Site - Officials Rest House Building - First Floor

Bed Room
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .266 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
268
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
270
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
271..............................
Working plane (Bed Room) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . .
273 .............................
Officials Rest House Lighting

Table of Contents

Officials Rest House Site - Officials Rest House Building - First Floor

Bed Room
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .274 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
276
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
278
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
279..............................
Working plane (Bed Room) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . .
281 .............................

Officials Rest House Site - Officials Rest House Building - First Floor

Bed Room
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .282 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
284
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
286
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
287..............................
Working plane (Bed Room) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . .
289 .............................

Officials Rest House Site - Officials Rest House Building - First Floor

Bed Room
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .290 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
292
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
294
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
295..............................
Working plane (Bed Room) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . .
297 .............................

Officials Rest House Site - Officials Rest House Building - First Floor

Corridor
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .298 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
300
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
302..............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
303..............................
Working plane (Corridor) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . .
305..............................

Officials Rest House Site - Officials Rest House Building - First Floor

Entrance
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .306 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
308
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
310
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
311..............................
Officials Rest House Lighting

Table of Contents

Working plane (Entrance) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . .313


..............................

Officials Rest House Site - Officials Rest House Building - First Floor

Kitchen
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .314 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .316 ..............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
318..............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
319..............................
Working plane (Kitchen) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . .
321.............................

Officials Rest House Site - Officials Rest House Building - First Floor

Pantry
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .322 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
324
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
326..............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
327..............................
Working plane (Pantry) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . .
329.............................

Officials Rest House Site - Officials Rest House Building - First Floor

Stair Landing
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .330 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
332
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
335
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
336..............................
Working plane (Stair Landing) / Light scene 1 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . .
338 .............................
(adaptive)

Officials Rest House Site - Officials Rest House Building

Mumpty Floor
Room list / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339 ..............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .341
..............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 342 ...............................

Officials Rest House Site - Officials Rest House Building - Mumpty Floor

Stair Landing
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .344 ..............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .346
..............................
Officials Rest House Lighting

Table of Contents

Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .349


..............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
350
Working plane (Stair Landing) / Light scene 1 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . .
352 .............................
(adaptive)
Officials Rest House Lighting

Luminaire list

Φtotal Ptotal Luminous efficacy


659326 lm 4524.0 W 145.7 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

110 Philips 36.0 W 5597 lm 155.5 lm/W

24 Philips 23.5 W 1819 lm 77.4 lm/W

12
Officials Rest House Lighting

Product data sheet

Philips -

P 23.5 W

ΦLamp 1820 lm

ΦLuminaire 1819 lm

η 99.96 %

Luminous efficacy 77.4 lm/W

CCT 3000 K Polar LDC

CRI 100

UGR diagram (SHR: 0.25)

13
Officials Rest House Lighting

Product data sheet

Philips -

P 36.0 W

ΦLamp 5600 lm

ΦLuminaire 5597 lm

η 99.94 %

Luminous efficacy 155.5 lm/W

CCT 3000 K Polar LDC

CRI 100

UGR diagram (SHR: 0.25)

14
Officials Rest House Lighting

Officials Rest House Site


Luminaire layout plan

15
Officials Rest House Lighting

Officials Rest House Site


Luminaire layout plan

Manufacturer Philips P 23.5 W

Fitting 1x 9150058074 ΦLuminaire 1819 lm


MESON 6500K 23.5W

Individual luminaires

X Y Mounting Luminaire
height

10.186 m 26.914 m 7.100 m 1

9.825 m 26.914 m 3.450 m 2

17.325 m 26.914 m 7.100 m 3

16.948 m 26.914 m 3.450 m 4

11.300 m 26.865 m 10.750 m 5

27.675 m 26.840 m 7.100 m 6

27.822 m 26.831 m 3.450 m 7

-0.800 m 26.765 m 3.450 m 8

-0.600 m 26.765 m 7.100 m 9

16.100 m 26.665 m 10.750 m 10

-0.899 m 21.115 m 3.450 m 11

28.049 m 21.115 m 3.450 m 12

27.850 m 21.090 m 7.100 m 13

16
Officials Rest House Lighting

Officials Rest House Site


Luminaire layout plan

X Y Mounting Luminaire
height

-0.899 m 21.025 m 7.100 m 14

16.000 m 19.667 m 10.750 m 15

11.328 m 19.643 m 10.750 m 16

-0.725 m 15.540 m 7.100 m 17

28.024 m 15.498 m 3.450 m 18

-0.725 m 15.440 m 3.450 m 19

9.825 m 15.365 m 7.100 m 20

17.053 m 15.315 m 7.100 m 21

17.640 m 15.315 m 3.450 m 22

9.825 m 15.315 m 3.450 m 23

27.847 m 15.290 m 7.100 m 24

17
Officials Rest House Lighting

Officials Rest House Site


Luminaire list

Φtotal Ptotal Luminous efficacy


43656 lm 564.0 W 77.4 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

24 Philips 23.5 W 1819 lm 77.4 lm/W

18
Officials Rest House Lighting

Officials Rest House Building · Ground Floor (Light scene 1)


Room list

19
Officials Rest House Lighting

Officials Rest House Building · Ground Floor (Light scene 1)


Room list

Bath

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


72.0 W 4.26 m² 16.90 W/m² = 5.17 W/m²/100 lx (Room) 327 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

2 Philips 36.0 W 5597 lm

Bath

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


72.0 W 4.26 m² 16.90 W/m² = 5.11 W/m²/100 lx (Room) 331 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

2 Philips 36.0 W 5597 lm

Bath

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


72.0 W 4.24 m² 17.00 W/m² = 5.23 W/m²/100 lx (Room) 325 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

2 Philips 36.0 W 5597 lm

20
Officials Rest House Lighting

Officials Rest House Building · Ground Floor (Light scene 1)


Room list

Bath

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


72.0 W 4.26 m² 16.90 W/m² = 5.20 W/m²/100 lx (Room) 325 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

2 Philips 36.0 W 5597 lm

Bath

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


72.0 W 4.26 m² 16.90 W/m² = 5.16 W/m²/100 lx (Room) 328 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

2 Philips 36.0 W 5597 lm

Bath

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


72.0 W 4.26 m² 16.90 W/m² = 5.20 W/m²/100 lx (Room) 325 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

2 Philips 36.0 W 5597 lm

21
Officials Rest House Lighting

Officials Rest House Building · Ground Floor (Light scene 1)


Room list

Bath

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


72.0 W 4.26 m² 16.90 W/m² = 5.16 W/m²/100 lx (Room) 327 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

2 Philips 36.0 W 5597 lm

Bed Room

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


108.0 W 20.49 m² 5.27 W/m² = 2.10 W/m²/100 lx (Room) 251 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

3 Philips 36.0 W 5597 lm

Bed Room

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


108.0 W 20.53 m² 5.26 W/m² = 2.07 W/m²/100 lx (Room) 254 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

3 Philips 36.0 W 5597 lm

22
Officials Rest House Lighting

Officials Rest House Building · Ground Floor (Light scene 1)


Room list

Bed Room

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


108.0 W 20.18 m² 5.35 W/m² = 2.09 W/m²/100 lx (Room) 256 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

3 Philips 36.0 W 5597 lm

Bed Room

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


108.0 W 20.49 m² 5.27 W/m² = 2.06 W/m²/100 lx (Room) 256 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

3 Philips 36.0 W 5597 lm

Bed Room

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


108.0 W 20.48 m² 5.27 W/m² = 2.09 W/m²/100 lx (Room) 253 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

3 Philips 36.0 W 5597 lm

23
Officials Rest House Lighting

Officials Rest House Building · Ground Floor (Light scene 1)


Room list

Corridor

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


432.0 W 36.12 m² 11.96 W/m² = 2.99 W/m²/100 lx (Room) 400 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

12 Philips 36.0 W 5597 lm

Dinning

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


216.0 W 48.65 m² 4.44 W/m² = 1.72 W/m²/100 lx (Room) 258 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

6 Philips 36.0 W 5597 lm

Entrance

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


72.0 W 13.31 m² 5.41 W/m² = 2.33 W/m²/100 lx (Room) 232 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

2 Philips 36.0 W 5597 lm

24
Officials Rest House Lighting

Officials Rest House Building · Ground Floor (Light scene 1)


Room list

Kitchen

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


108.0 W 20.58 m² 5.25 W/m² = 2.03 W/m²/100 lx (Room) 258 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

3 Philips 36.0 W 5597 lm

Pantry

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


72.0 W 4.26 m² 16.90 W/m² = 5.16 W/m²/100 lx (Room) 328 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

2 Philips 36.0 W 5597 lm

Stair Landing

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


108.0 W 16.52 m² 6.54 W/m² = 2.14 W/m²/100 lx (Room) 305 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

3 Philips 36.0 W 5597 lm

25
Officials Rest House Lighting

Officials Rest House Building · Ground Floor


Luminaire list

Φtotal Ptotal Luminous efficacy


319029 lm 2052.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

57 Philips 36.0 W 5597 lm 155.5 lm/W

26
Officials Rest House Lighting

Officials Rest House Building · Ground Floor (Light scene 1)


Calculation objects

27
Officials Rest House Lighting

Officials Rest House Building · Ground Floor (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Dinning ) 258 lx 148 lx 326 lx 0.57 0.45 WP1


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bath) 327 lx 305 lx 344 lx 0.93 0.89 WP2


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Pantry) 328 lx 303 lx 347 lx 0.92 0.87 WP3


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bath) 325 lx 298 lx 347 lx 0.92 0.86 WP4


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Kitchen) 258 lx 172 lx 320 lx 0.67 0.54 WP5


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bed Room) 251 lx 164 lx 328 lx 0.65 0.50 WP6
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Entrance) 232 lx 184 lx 275 lx 0.79 0.67 WP7


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Stair Landing) 305 lx 199 lx 384 lx 0.65 0.52 WP8
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Corridor) 400 lx 259 lx 441 lx 0.65 0.59 WP9


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bed Room) 254 lx 167 lx 326 lx 0.66 0.51 WP10
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bath) 325 lx 278 lx 343 lx 0.86 0.81 WP11


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

28
Officials Rest House Lighting

Officials Rest House Building · Ground Floor (Light scene 1)


Calculation objects

Working plane (Bath) 328 lx 309 lx 344 lx 0.94 0.90 WP12


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bath) 325 lx 297 lx 344 lx 0.91 0.86 WP13


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bed Room) 253 lx 153 lx 331 lx 0.60 0.46 WP14
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bath) 327 lx 306 lx 346 lx 0.94 0.88 WP15


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bed Room) 256 lx 173 lx 328 lx 0.68 0.53 WP16
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bed Room) 256 lx 170 lx 335 lx 0.66 0.51 WP17
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bath) 331 lx 307 lx 351 lx 0.93 0.87 WP38


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

29
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Summary

Ground area 4.26 m² Clearance height 3.450 m

Reflection factors Ceiling: 70.0 %, Mounting height 3.450 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

30
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 327 lx ≥ 200 lx WP2

Uo (g1 ) 0.93 ≥ 0.50 WP2

Glare valuation(1) RUG, max 25 ≤ 25

Energy estimation(2) Consumption 11.9 kWh/a max. 200 kWh/a

Room Lighting power density 16.90 W/m² –

5.17 W/m²/100 lx –

(1) Based on a rectangular space of 1.775 m x 2.400 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Philips 24 36.0 W 5597 lm 155.5 lm/W

31
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire layout plan

32
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

Individual luminaires

X Y Mounting Luminaire
height

0.300 m 1.200 m 3.450 m 1

1.450 m 1.200 m 3.450 m 2

33
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire list

Φtotal Ptotal Luminous efficacy


11194 lm 72.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 Philips 36.0 W 5597 lm 155.5 lm/W

34
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Calculation objects

35
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 327 lx 305 lx 344 lx 0.93 0.89 WP2


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

36
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Working plane (Bath)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 327 lx 305 lx 344 lx 0.93 0.89 WP2


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

37
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Summary

Ground area 4.26 m² Clearance height 3.450 m

Reflection factors Ceiling: 70.0 %, Mounting height 3.450 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

38
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 331 lx ≥ 200 lx WP38

Uo (g1 ) 0.93 ≥ 0.50 WP38

Glare valuation(1) RUG, max 25 ≤ 25

Energy estimation(2) Consumption 11.9 kWh/a max. 200 kWh/a

Room Lighting power density 16.90 W/m² –

5.11 W/m²/100 lx –

(1) Based on a rectangular space of 2.400 m x 1.775 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Philips 24 36.0 W 5597 lm 155.5 lm/W

39
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire layout plan

40
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

Individual luminaires

X Y Mounting Luminaire
height

0.271 m 1.185 m 3.450 m 1

1.421 m 1.185 m 3.450 m 2

41
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire list

Φtotal Ptotal Luminous efficacy


11194 lm 72.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 Philips 36.0 W 5597 lm 155.5 lm/W

42
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Calculation objects

43
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 331 lx 307 lx 351 lx 0.93 0.87 WP38


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

44
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Working plane (Bath)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 331 lx 307 lx 351 lx 0.93 0.87 WP38


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

45
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Summary

Ground area 4.24 m² Clearance height 3.450 m

Reflection factors Ceiling: 70.0 %, Mounting height 3.450 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

46
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 325 lx ≥ 200 lx WP4

Uo (g1 ) 0.92 ≥ 0.50 WP4

Glare valuation(1) RUG, max 25 ≤ 25

Energy estimation(2) Consumption 11.9 kWh/a max. 150 kWh/a

Room Lighting power density 17.00 W/m² –

5.23 W/m²/100 lx –

(1) Based on a rectangular space of 1.775 m x 2.387 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Philips 24 36.0 W 5597 lm 155.5 lm/W

47
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire layout plan

48
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

Individual luminaires

X Y Mounting Luminaire
height

0.295 m 1.185 m 3.450 m 1

1.445 m 1.185 m 3.450 m 2

49
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire list

Φtotal Ptotal Luminous efficacy


11194 lm 72.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 Philips 36.0 W 5597 lm 155.5 lm/W

50
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Calculation objects

51
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 325 lx 298 lx 347 lx 0.92 0.86 WP4


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

52
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Working plane (Bath)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 325 lx 298 lx 347 lx 0.92 0.86 WP4


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

53
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Summary

Ground area 4.26 m² Clearance height 3.450 m

Reflection factors Ceiling: 70.0 %, Mounting height 3.450 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

54
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 325 lx ≥ 200 lx WP11

Uo (g1 ) 0.86 ≥ 0.50 WP11

Glare valuation(1) RUG, max 25 ≤ 25

Energy estimation(2) Consumption 11.9 kWh/a max. 200 kWh/a

Room Lighting power density 16.90 W/m² –

5.20 W/m²/100 lx –

(1) Based on a rectangular space of 2.400 m x 1.775 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Philips 24 36.0 W 5597 lm 155.5 lm/W

55
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire layout plan

56
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

Individual luminaires

X Y Mounting Luminaire
height

0.329 m 1.123 m 3.450 m 1

1.479 m 1.123 m 3.450 m 2

57
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire list

Φtotal Ptotal Luminous efficacy


11194 lm 72.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 Philips 36.0 W 5597 lm 155.5 lm/W

58
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Calculation objects

59
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 325 lx 278 lx 343 lx 0.86 0.81 WP11


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

60
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Working plane (Bath)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 325 lx 278 lx 343 lx 0.86 0.81 WP11


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

61
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Summary

Ground area 4.26 m² Clearance height 3.450 m

Reflection factors Ceiling: 70.0 %, Mounting height 3.450 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

62
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 328 lx ≥ 200 lx WP12

Uo (g1 ) 0.94 ≥ 0.50 WP12

Glare valuation(1) RUG, max 25 ≤ 25

Energy estimation(2) Consumption 11.9 kWh/a max. 200 kWh/a

Room Lighting power density 16.90 W/m² –

5.16 W/m²/100 lx –

(1) Based on a rectangular space of 2.400 m x 1.775 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Philips 24 36.0 W 5597 lm 155.5 lm/W

63
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire layout plan

64
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

Individual luminaires

X Y Mounting Luminaire
height

0.354 m 1.123 m 3.450 m 1

1.504 m 1.123 m 3.450 m 2

65
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire list

Φtotal Ptotal Luminous efficacy


11194 lm 72.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 Philips 36.0 W 5597 lm 155.5 lm/W

66
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Calculation objects

67
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 328 lx 309 lx 344 lx 0.94 0.90 WP12


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

68
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Working plane (Bath)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 328 lx 309 lx 344 lx 0.94 0.90 WP12


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

69
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Summary

Ground area 4.26 m² Clearance height 3.450 m

Reflection factors Ceiling: 70.0 %, Mounting height 3.450 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

70
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 325 lx ≥ 200 lx WP13

Uo (g1 ) 0.91 ≥ 0.50 WP13

Glare valuation(1) RUG, max 25 ≤ 25

Energy estimation(2) Consumption 11.9 kWh/a max. 200 kWh/a

Room Lighting power density 16.90 W/m² –

5.20 W/m²/100 lx –

(1) Based on a rectangular space of 2.400 m x 1.775 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Philips 24 36.0 W 5597 lm 155.5 lm/W

71
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire layout plan

72
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

Individual luminaires

X Y Mounting Luminaire
height

0.329 m 1.093 m 3.450 m 1

1.479 m 1.093 m 3.450 m 2

73
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire list

Φtotal Ptotal Luminous efficacy


11194 lm 72.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 Philips 36.0 W 5597 lm 155.5 lm/W

74
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Calculation objects

75
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 325 lx 297 lx 344 lx 0.91 0.86 WP13


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

76
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Working plane (Bath)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 325 lx 297 lx 344 lx 0.91 0.86 WP13


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

77
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire layout plan

78
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

Individual luminaires

X Y Mounting Luminaire
height

0.354 m 1.093 m 3.450 m 1

1.504 m 1.093 m 3.450 m 2

79
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath


Luminaire list

Φtotal Ptotal Luminous efficacy


11194 lm 72.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 Philips 36.0 W 5597 lm 155.5 lm/W

80
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Calculation objects

81
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 327 lx 306 lx 346 lx 0.94 0.88 WP15


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

82
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bath (Light scene 1)


Working plane (Bath)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 327 lx 306 lx 346 lx 0.94 0.88 WP15


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

83
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room


Luminaire layout plan

84
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

2 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 2.017 m / 1.396 m /
3.450 m 2.017 m 2.671 m 3.450 m 2

X-direction 1 pcs., Centre - 2.017 m 1.396 m 3.450 m 3


centre, Distances not
equal

Y-direction 2 pcs., Centre -


centre, Distances not
equal

Arrangement A1

Individual luminaires

X Y Mounting Luminaire
height

-1.215 m 2.777 m 3.450 m 1

85
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room


Luminaire list

Φtotal Ptotal Luminous efficacy


16791 lm 108.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

3 Philips 36.0 W 5597 lm 155.5 lm/W

86
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Calculation objects

87
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 251 lx 164 lx 328 lx 0.65 0.50 WP6
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

88
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Working plane (Bed Room)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 251 lx 164 lx 328 lx 0.65 0.50 WP6
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

89
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Summary

Ground area 20.53 m² Clearance height 3.450 m

Reflection factors Ceiling: 70.0 %, Mounting height 3.450 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

90
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 254 lx ≥ 200 lx WP10

Uo (g1 ) 0.66 ≥ 0.50 WP10

Glare valuation(1) RUG, max 27 ≤ 25

Energy estimation(2) Consumption 17.8 kWh/a max. 750 kWh/a

Room Lighting power density 5.26 W/m² –

2.07 W/m²/100 lx –

(1) Based on a rectangular space of 4.050 m x 5.875 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Philips 26 36.0 W 5597 lm 155.5 lm/W

91
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room


Luminaire layout plan

92
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

2 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.950 m / 1.420 m /
3.450 m 1.950 m 2.695 m 3.450 m 2

X-direction 1 pcs., Centre - 1.950 m 1.420 m 3.450 m 3


centre, Distances not
equal

Y-direction 2 pcs., Centre -


centre, Distances not
equal

Arrangement A1

Individual luminaires

X Y Mounting Luminaire
height

5.050 m 1.150 m 3.450 m 1

93
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room


Luminaire list

Φtotal Ptotal Luminous efficacy


16791 lm 108.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

3 Philips 36.0 W 5597 lm 155.5 lm/W

94
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Calculation objects

95
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 254 lx 167 lx 326 lx 0.66 0.51 WP10
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

96
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Working plane (Bed Room)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 254 lx 167 lx 326 lx 0.66 0.51 WP10
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

97
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Summary

Ground area 20.18 m² Clearance height 3.450 m

Reflection factors Ceiling: 70.0 %, Mounting height 3.450 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

98
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 256 lx ≥ 200 lx WP16

Uo (g1 ) 0.68 ≥ 0.50 WP16

Glare valuation(1) RUG, max 27 ≤ 25

Energy estimation(2) Consumption 17.8 kWh/a max. 750 kWh/a

Room Lighting power density 5.35 W/m² –

2.09 W/m²/100 lx –

(1) Based on a rectangular space of 4.050 m x 5.775 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Philips 26 36.0 W 5597 lm 155.5 lm/W

99
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room


Luminaire layout plan

100
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

2 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 4.027 m / 1.336 m /
3.450 m 4.027 m 2.611 m 3.450 m 2

X-direction 1 pcs., Centre - 4.027 m 1.336 m 3.450 m 3


centre, Distances not
equal

Y-direction 2 pcs., Centre -


centre, Distances not
equal

Arrangement A1

Individual luminaires

X Y Mounting Luminaire
height

0.875 m 1.150 m 3.450 m 1

101
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room


Luminaire list

Φtotal Ptotal Luminous efficacy


16791 lm 108.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

3 Philips 36.0 W 5597 lm 155.5 lm/W

102
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Calculation objects

103
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 256 lx 173 lx 328 lx 0.68 0.53 WP16
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

104
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Working plane (Bed Room)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 256 lx 173 lx 328 lx 0.68 0.53 WP16
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

105
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Summary

Ground area 20.49 m² Clearance height 3.450 m

Reflection factors Ceiling: 70.0 %, Mounting height 3.450 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

106
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 256 lx ≥ 200 lx WP17

Uo (g1 ) 0.66 ≥ 0.50 WP17

Glare valuation(1) RUG, max 27 ≤ 25

Energy estimation(2) Consumption 17.8 kWh/a max. 750 kWh/a

Room Lighting power density 5.27 W/m² –

2.06 W/m²/100 lx –

(1) Based on a rectangular space of 5.875 m x 4.050 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Philips 26 36.0 W 5597 lm 155.5 lm/W

107
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room


Luminaire layout plan

108
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

2 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.950 m / 1.420 m /
3.450 m 1.950 m 2.695 m 3.450 m 2

X-direction 1 pcs., Centre - 1.950 m 1.420 m 3.450 m 3


centre, Distances not
equal

Y-direction 2 pcs., Centre -


centre, Distances not
equal

Arrangement A1

Individual luminaires

X Y Mounting Luminaire
height

4.867 m 2.777 m 3.450 m 1

109
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room


Luminaire list

Φtotal Ptotal Luminous efficacy


16791 lm 108.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

3 Philips 36.0 W 5597 lm 155.5 lm/W

110
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Calculation objects

111
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 256 lx 170 lx 335 lx 0.66 0.51 WP17
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

112
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Working plane (Bed Room)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 256 lx 170 lx 335 lx 0.66 0.51 WP17
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

113
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Summary

Ground area 20.48 m² Clearance height 3.450 m

Reflection factors Ceiling: 70.0 %, Mounting height 3.450 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

114
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 253 lx ≥ 200 lx WP14

Uo (g1 ) 0.60 ≥ 0.50 WP14

Glare valuation(1) RUG, max 27 ≤ 25

Energy estimation(2) Consumption 17.8 kWh/a max. 750 kWh/a

Room Lighting power density 5.27 W/m² –

2.09 W/m²/100 lx –

(1) Based on a rectangular space of 5.875 m x 4.050 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Philips 26 36.0 W 5597 lm 155.5 lm/W

115
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room


Luminaire layout plan

116
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

2 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 4.275 m / 1.438 m /
3.450 m 4.275 m 2.713 m 3.450 m 2

X-direction 1 pcs., Centre - 4.275 m 1.438 m 3.450 m 3


centre, Distances not
equal

Y-direction 2 pcs., Centre -


centre, Distances not
equal

Arrangement A1

Individual luminaires

X Y Mounting Luminaire
height

0.985 m 2.777 m 3.450 m 1

117
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room


Luminaire list

Φtotal Ptotal Luminous efficacy


16791 lm 108.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

3 Philips 36.0 W 5597 lm 155.5 lm/W

118
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Calculation objects

119
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 253 lx 153 lx 331 lx 0.60 0.46 WP14
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

120
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Bed Room (Light scene 1)
Working plane (Bed Room)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 253 lx 153 lx 331 lx 0.60 0.46 WP14
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

121
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Corridor (Light scene 1)


Summary

Ground area 36.12 m² Clearance height 3.450 m

Reflection factors Ceiling: 70.0 %, Mounting height 3.450 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

122
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Corridor (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 400 lx ≥ 200 lx WP9

Uo (g1 ) 0.65 ≥ 0.50 WP9

Glare valuation(1) RUG, max 29 ≤ 25

Energy estimation(2) Consumption 71.3 kWh/a max. 1300 kWh/a

Room Lighting power density 11.96 W/m² –

2.99 W/m²/100 lx –

(1) Based on a rectangular space of 23.300 m x 1.550 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

12 Philips 28 36.0 W 5597 lm 155.5 lm/W

123
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Corridor


Luminaire layout plan

124
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Corridor


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

12 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.023 m / 0.786 m /
3.450 m 1.023 m 0.786 m 3.450 m 1

X-direction 12 pcs., Centre - 2.958 m 0.785 m 3.450 m 2


centre, 1.936 m
4.894 m 0.784 m 3.450 m 3
Arrangement A1
6.830 m 0.782 m 3.450 m 4

8.766 m 0.781 m 3.450 m 5

10.702 m 0.779 m 3.450 m 6

12.637 m 0.778 m 3.450 m 7

14.573 m 0.776 m 3.450 m 8

16.509 m 0.775 m 3.450 m 9

18.445 m 0.773 m 3.450 m 10

20.380 m 0.772 m 3.450 m 11

22.316 m 0.770 m 3.450 m 12

125
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Corridor


Luminaire list

Φtotal Ptotal Luminous efficacy


67164 lm 432.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

12 Philips 36.0 W 5597 lm 155.5 lm/W

126
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Corridor (Light scene 1)


Calculation objects

127
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Corridor (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Corridor) 400 lx 259 lx 441 lx 0.65 0.59 WP9


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

128
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Corridor (Light scene 1)


Working plane (Corridor)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Corridor) 400 lx 259 lx 441 lx 0.65 0.59 WP9


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

129
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Dinning (Light scene 1)


Summary

Ground area 48.65 m² Clearance height 3.450 m

Reflection factors Ceiling: 70.0 %, Mounting height 3.450 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

130
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Dinning (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 258 lx ≥ 200 lx WP1

Uo (g1 ) 0.57 ≥ 0.50 WP1

Glare valuation(1) RUG, max 27 ≤ 25

Energy estimation(2) Consumption 35.6 kWh/a max. 1750 kWh/a

Room Lighting power density 4.44 W/m² –

1.72 W/m²/100 lx –

(1) Based on a rectangular space of 10.050 m x 5.876 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

6 Philips 27 36.0 W 5597 lm 155.5 lm/W

131
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Dinning


Luminaire layout plan

132
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Dinning


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

1 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 4.901 m / 7.201 m /
3.450 m 4.901 m 7.201 m 3.450 m 2

X-direction 1 pcs., Centre -


centre, Distances not
equal

Y-direction 2 pcs., Centre -


centre, Distances not
equal

Arrangement A1

4 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.637 m / 1.094 m /
3.450 m 1.637 m 8.858 m 3.450 m 3

X-direction 1 pcs., Centre - 1.637 m 6.270 m 3.450 m 4


centre, 3.800 m
1.637 m 3.682 m 3.450 m 5
Y-direction 4 pcs., Centre -
centre, 2.588 m 1.637 m 1.094 m 3.450 m 6

133
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Dinning


Luminaire layout plan

Arrangement A2

Individual luminaires

X Y Mounting Luminaire
height

5.036 m 2.777 m 3.450 m 1

134
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Dinning


Luminaire list

Φtotal Ptotal Luminous efficacy


33582 lm 216.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

6 Philips 36.0 W 5597 lm 155.5 lm/W

135
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Dinning (Light scene 1)


Calculation objects

136
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Dinning (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Dinning ) 258 lx 148 lx 326 lx 0.57 0.45 WP1


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

137
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Dinning (Light scene 1)


Working plane (Dinning )

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Dinning ) 258 lx 148 lx 326 lx 0.57 0.45 WP1


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

138
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Entrance (Light scene 1)


Summary

Ground area 13.31 m² Clearance height 3.450 m

Reflection factors Ceiling: 70.0 %, Mounting height 3.450 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

139
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Entrance (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 232 lx ≥ 200 lx WP7

Uo (g1 ) 0.79 ≥ 0.50 WP7

Glare valuation(1) RUG, max 25 ≤ 25

Energy estimation(2) Consumption 11.9 kWh/a max. 500 kWh/a

Room Lighting power density 5.41 W/m² –

2.33 W/m²/100 lx –

(1) Based on a rectangular space of 3.200 m x 4.158 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Philips 24 36.0 W 5597 lm 155.5 lm/W

140
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Entrance


Luminaire layout plan

141
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Entrance


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

2 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.600 m / 1.101 m /
3.450 m 1.600 m 2.988 m 3.450 m 1

X-direction 1 pcs., Centre - 1.600 m 1.101 m 3.450 m 2


centre, 2.762 m

Y-direction 2 pcs., Centre -


centre, 1.887 m

Arrangement A1

142
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Entrance


Luminaire list

Φtotal Ptotal Luminous efficacy


11194 lm 72.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 Philips 36.0 W 5597 lm 155.5 lm/W

143
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Entrance (Light scene 1)


Calculation objects

144
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Entrance (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Entrance) 232 lx 184 lx 275 lx 0.79 0.67 WP7


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

145
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Entrance (Light scene 1)


Working plane (Entrance)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Entrance) 232 lx 184 lx 275 lx 0.79 0.67 WP7


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

146
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Kitchen (Light scene 1)


Summary

Ground area 20.58 m² Clearance height 3.450 m

Reflection factors Ceiling: 70.0 %, Mounting height 3.450 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

147
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Kitchen (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 258 lx ≥ 200 lx WP5

Uo (g1 ) 0.67 ≥ 0.50 WP5

Glare valuation(1) RUG, max 27 ≤ 25

Energy estimation(2) Consumption 17.8 kWh/a max. 750 kWh/a

Room Lighting power density 5.25 W/m² –

2.03 W/m²/100 lx –

(1) Based on a rectangular space of 5.875 m x 4.050 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Philips 26 36.0 W 5597 lm 155.5 lm/W

148
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Kitchen


Luminaire layout plan

149
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Kitchen


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

2 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 3.938 m / 1.138 m /
3.450 m 3.938 m 2.913 m 3.450 m 2

X-direction 1 pcs., Centre - 3.938 m 1.138 m 3.450 m 3


centre, 3.200 m

Y-direction 2 pcs., Centre -


centre, 1.775 m

Arrangement A1

Individual luminaires

X Y Mounting Luminaire
height

1.019 m 1.250 m 3.450 m 1

150
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Kitchen


Luminaire list

Φtotal Ptotal Luminous efficacy


16791 lm 108.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

3 Philips 36.0 W 5597 lm 155.5 lm/W

151
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Kitchen (Light scene 1)


Calculation objects

152
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Kitchen (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Kitchen) 258 lx 172 lx 320 lx 0.67 0.54 WP5


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

153
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Kitchen (Light scene 1)


Working plane (Kitchen)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Kitchen) 258 lx 172 lx 320 lx 0.67 0.54 WP5


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

154
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Pantry (Light scene 1)


Summary

Ground area 4.26 m² Clearance height 3.450 m

Reflection factors Ceiling: 70.0 %, Mounting height 3.450 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

155
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Pantry (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 328 lx ≥ 200 lx WP3

Uo (g1 ) 0.92 ≥ 0.50 WP3

Glare valuation(1) RUG, max 25 ≤ 25

Energy estimation(2) Consumption 11.9 kWh/a max. 200 kWh/a

Room Lighting power density 16.90 W/m² –

5.16 W/m²/100 lx –

(1) Based on a rectangular space of 1.775 m x 2.400 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Philips 24 36.0 W 5597 lm 155.5 lm/W

156
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Pantry


Luminaire layout plan

157
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Pantry


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

Individual luminaires

X Y Mounting Luminaire
height

0.325 m 1.200 m 3.450 m 1

1.475 m 1.200 m 3.450 m 2

158
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Pantry


Luminaire list

Φtotal Ptotal Luminous efficacy


11194 lm 72.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 Philips 36.0 W 5597 lm 155.5 lm/W

159
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Pantry (Light scene 1)


Calculation objects

160
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Pantry (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Pantry) 328 lx 303 lx 347 lx 0.92 0.87 WP3


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

161
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Pantry (Light scene 1)


Working plane (Pantry)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Pantry) 328 lx 303 lx 347 lx 0.92 0.87 WP3


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

162
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Stair Landing (Light scene 1)
Summary

Ground area 16.52 m² Clearance height 3.450 m

Reflection factors Ceiling: 70.0 %, Mounting height 3.450 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

163
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Stair Landing (Light scene 1)
Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 305 lx ≥ 200 lx WP8

Uo (g1 ) 0.65 ≥ 0.50 WP8

Glare valuation(1) RUG, max 25 ≤ 25

Energy estimation(2) Consumption 17.8 kWh/a max. 600 kWh/a

Room Lighting power density 6.54 W/m² –

2.14 W/m²/100 lx –

(1) Based on a rectangular space of 3.200 m x 5.163 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Philips 24 36.0 W 5597 lm 155.5 lm/W

164
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Stair Landing


Luminaire layout plan

165
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Stair Landing


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

1 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 2.452 m / 2.400 m /
3.450 m 2.452 m 2.400 m 3.450 m 2

X-direction 1 pcs., Centre -


centre, 3.200 m

Y-direction 1 pcs., Centre -


centre, 5.163 m

Arrangement A1

1 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.702 m / 2.400 m /
3.450 m 0.702 m 2.400 m 3.450 m 3

X-direction 1 pcs., Centre -


centre, 3.200 m

Y-direction 1 pcs., Centre -


centre, 5.163 m

Arrangement A2

166
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Stair Landing


Luminaire layout plan

1 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.600 m / 4.350 m /
3.450 m 1.600 m 4.350 m 3.450 m 1

X-direction 1 pcs., Centre -


centre, 3.200 m

Y-direction 1 pcs., Centre -


centre, 5.163 m

Arrangement A3

167
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Stair Landing


Luminaire list

Φtotal Ptotal Luminous efficacy


16791 lm 108.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

3 Philips 36.0 W 5597 lm 155.5 lm/W

168
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Stair Landing (Light scene 1)
Calculation objects

169
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Stair Landing (Light scene 1)
Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Stair Landing) 305 lx 199 lx 384 lx 0.65 0.52 WP8
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

170
Officials Rest House Lighting

Officials Rest House Building · Ground Floor · Stair Landing (Light scene 1)
Working plane (Stair Landing)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Stair Landing) 305 lx 199 lx 384 lx 0.65 0.52 WP8
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

171
Officials Rest House Lighting

Officials Rest House Building · First Floor (Light scene 1)


Room list

172
Officials Rest House Lighting

Officials Rest House Building · First Floor (Light scene 1)


Room list

Bath

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


36.0 W 4.26 m² 8.45 W/m² = 3.50 W/m²/100 lx (Room) 241 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

1 Philips 36.0 W 5597 lm

Bath

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


36.0 W 4.26 m² 8.45 W/m² = 3.49 W/m²/100 lx (Room) 242 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

1 Philips 36.0 W 5597 lm

Bath

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


36.0 W 4.26 m² 8.45 W/m² = 3.46 W/m²/100 lx (Room) 244 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

1 Philips 36.0 W 5597 lm

173
Officials Rest House Lighting

Officials Rest House Building · First Floor (Light scene 1)


Room list

Bath

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


36.0 W 4.26 m² 8.45 W/m² = 3.50 W/m²/100 lx (Room) 242 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

1 Philips 36.0 W 5597 lm

Bath

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


36.0 W 4.26 m² 8.45 W/m² = 3.51 W/m²/100 lx (Room) 241 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

1 Philips 36.0 W 5597 lm

Bath

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


36.0 W 4.26 m² 8.45 W/m² = 3.45 W/m²/100 lx (Room) 245 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

1 Philips 36.0 W 5597 lm

174
Officials Rest House Lighting

Officials Rest House Building · First Floor (Light scene 1)


Room list

Bath

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


36.0 W 4.26 m² 8.45 W/m² = 3.48 W/m²/100 lx (Room) 243 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

1 Philips 36.0 W 5597 lm

Bed Room

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


108.0 W 20.53 m² 5.26 W/m² = 1.71 W/m²/100 lx (Room) 307 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

3 Philips 36.0 W 5597 lm

Bed Room

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


108.0 W 20.53 m² 5.26 W/m² = 1.71 W/m²/100 lx (Room) 308 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

3 Philips 36.0 W 5597 lm

175
Officials Rest House Lighting

Officials Rest House Building · First Floor (Light scene 1)


Room list

Bed Room

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


108.0 W 20.49 m² 5.27 W/m² = 1.71 W/m²/100 lx (Room) 309 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

3 Philips 36.0 W 5597 lm

Bed Room

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


108.0 W 20.53 m² 5.26 W/m² = 1.69 W/m²/100 lx (Room) 312 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

3 Philips 36.0 W 5597 lm

Bed Room

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


108.0 W 20.18 m² 5.35 W/m² = 1.71 W/m²/100 lx (Room) 314 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

3 Philips 36.0 W 5597 lm

176
Officials Rest House Lighting

Officials Rest House Building · First Floor (Light scene 1)


Room list

Bed Room

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


108.0 W 20.49 m² 5.27 W/m² = 1.69 W/m²/100 lx (Room) 313 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

3 Philips 36.0 W 5597 lm

Bed Room

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


108.0 W 20.48 m² 5.27 W/m² = 1.71 W/m²/100 lx (Room) 308 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

3 Philips 36.0 W 5597 lm

Corridor

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


432.0 W 42.47 m² 10.17 W/m² = 2.38 W/m²/100 lx (Room) 428 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

12 Philips 36.0 W 5597 lm

177
Officials Rest House Lighting

Officials Rest House Building · First Floor (Light scene 1)


Room list

Entrance

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


72.0 W 13.31 m² 5.41 W/m² = 1.84 W/m²/100 lx (Room) 294 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

2 Philips 36.0 W 5597 lm

Kitchen

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


108.0 W 20.58 m² 5.25 W/m² = 1.68 W/m²/100 lx (Room) 313 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

3 Philips 36.0 W 5597 lm

Pantry

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


36.0 W 4.26 m² 8.45 W/m² = 3.46 W/m²/100 lx (Room) 245 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

1 Philips 36.0 W 5597 lm

178
Officials Rest House Lighting

Officials Rest House Building · First Floor (Light scene 1)


Room list

Stair Landing

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


108.0 W 16.52 m² 6.54 W/m² = 1.75 W/m²/100 lx (Room) 374 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

3 Philips 36.0 W 5597 lm

179
Officials Rest House Lighting

Officials Rest House Building · First Floor


Luminaire list

Φtotal Ptotal Luminous efficacy


274253 lm 1764.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

49 Philips 36.0 W 5597 lm 155.5 lm/W

180
Officials Rest House Lighting

Officials Rest House Building · First Floor (Light scene 1)


Calculation objects

181
Officials Rest House Lighting

Officials Rest House Building · First Floor (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 245 lx 217 lx 268 lx 0.89 0.81 WP18


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bed Room) 308 lx 179 lx 422 lx 0.58 0.42 WP19
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bath) 241 lx 210 lx 265 lx 0.87 0.79 WP20


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bed Room) 313 lx 199 lx 427 lx 0.64 0.47 WP21
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bed Room) 314 lx 194 lx 423 lx 0.62 0.46 WP22
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bed Room) 312 lx 201 lx 424 lx 0.64 0.47 WP23
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Corridor) 428 lx 283 lx 465 lx 0.66 0.61 WP24


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Stair Landing) 374 lx 208 lx 493 lx 0.56 0.42 WP25
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Entrance) 294 lx 222 lx 368 lx 0.76 0.60 WP26


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bed Room) 309 lx 191 lx 423 lx 0.62 0.45 WP27
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Kitchen) 313 lx 197 lx 402 lx 0.63 0.49 WP28


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

182
Officials Rest House Lighting

Officials Rest House Building · First Floor (Light scene 1)


Calculation objects

Working plane (Bath) 242 lx 211 lx 264 lx 0.87 0.80 WP29


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bed Room) 307 lx 180 lx 419 lx 0.59 0.43 WP31
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Pantry) 245 lx 217 lx 268 lx 0.89 0.81 WP32


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bath) 244 lx 218 lx 267 lx 0.89 0.82 WP33


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bath) 242 lx 215 lx 264 lx 0.89 0.81 WP34


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bed Room) 308 lx 170 lx 419 lx 0.55 0.41 WP35
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bath) 241 lx 208 lx 265 lx 0.86 0.78 WP36


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Working plane (Bath) 243 lx 214 lx 266 lx 0.88 0.80 WP37


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

183
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Summary

Ground area 4.26 m² Clearance height 2.750 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.750 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

184
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 241 lx ≥ 200 lx WP36

Uo (g1 ) 0.86 ≥ 0.50 WP36

Glare valuation(1) RUG, max 25 ≤ 25

Energy estimation(2) Consumption 5.94 kWh/a max. 200 kWh/a

Room Lighting power density 8.45 W/m² –

3.50 W/m²/100 lx –

(1) Based on a rectangular space of 1.775 m x 2.400 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Philips 24 36.0 W 5597 lm 155.5 lm/W

185
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire layout plan

186
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

2 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.800 m / 1.303 m /
2.750 m 0.800 m 1.303 m 2.750 m 1

X-direction 1 pcs., Centre -


centre, 1.775 m

Y-direction 2 pcs., Centre -


centre, 2.752 m

Arrangement A1

187
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire list

Φtotal Ptotal Luminous efficacy


5597 lm 36.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 Philips 36.0 W 5597 lm 155.5 lm/W

188
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Calculation objects

189
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 241 lx 208 lx 265 lx 0.86 0.78 WP36


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

190
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Working plane (Bath)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 241 lx 208 lx 265 lx 0.86 0.78 WP36


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

191
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Summary

Ground area 4.26 m² Clearance height 2.750 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.750 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

192
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 242 lx ≥ 200 lx WP29

Uo (g1 ) 0.87 ≥ 0.50 WP29

Glare valuation(1) RUG, max 25 ≤ 25

Energy estimation(2) Consumption 5.94 kWh/a max. 200 kWh/a

Room Lighting power density 8.45 W/m² –

3.49 W/m²/100 lx –

(1) Based on a rectangular space of 1.775 m x 2.400 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Philips 24 36.0 W 5597 lm 155.5 lm/W

193
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire layout plan

194
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

1 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.888 m / 1.263 m /
2.750 m 0.888 m 1.263 m 2.750 m 1

X-direction 1 pcs., Centre -


centre, Distances not
equal

Y-direction 2 pcs., Centre -


centre, Distances not
equal

Arrangement A1

195
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire list

Φtotal Ptotal Luminous efficacy


5597 lm 36.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 Philips 36.0 W 5597 lm 155.5 lm/W

196
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Calculation objects

197
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 242 lx 211 lx 264 lx 0.87 0.80 WP29


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

198
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Working plane (Bath)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 242 lx 211 lx 264 lx 0.87 0.80 WP29


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

199
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Summary

Ground area 4.26 m² Clearance height 2.750 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.750 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

200
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 244 lx ≥ 200 lx WP33

Uo (g1 ) 0.89 ≥ 0.50 WP33

Glare valuation(1) RUG, max 25 ≤ 25

Energy estimation(2) Consumption 5.94 kWh/a max. 200 kWh/a

Room Lighting power density 8.45 W/m² –

3.46 W/m²/100 lx –

(1) Based on a rectangular space of 2.400 m x 1.775 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Philips 24 36.0 W 5597 lm 155.5 lm/W

201
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire layout plan

202
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

1 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.868 m / 1.203 m /
2.750 m 0.868 m 1.203 m 2.750 m 1

X-direction 1 pcs., Centre -


centre, 1.775 m

Y-direction 1 pcs., Centre -


centre, 2.400 m

Arrangement A1

203
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire list

Φtotal Ptotal Luminous efficacy


5597 lm 36.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 Philips 36.0 W 5597 lm 155.5 lm/W

204
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Calculation objects

205
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 244 lx 218 lx 267 lx 0.89 0.82 WP33


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

206
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Working plane (Bath)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 244 lx 218 lx 267 lx 0.89 0.82 WP33


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

207
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Summary

Ground area 4.26 m² Clearance height 2.750 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.750 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

208
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 242 lx ≥ 200 lx WP34

Uo (g1 ) 0.89 ≥ 0.50 WP34

Glare valuation(1) RUG, max 25 ≤ 25

Energy estimation(2) Consumption 5.94 kWh/a max. 200 kWh/a

Room Lighting power density 8.45 W/m² –

3.50 W/m²/100 lx –

(1) Based on a rectangular space of 2.400 m x 1.775 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Philips 24 36.0 W 5597 lm 155.5 lm/W

209
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire layout plan

210
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

1 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.845 m / 1.203 m /
2.750 m 0.845 m 1.203 m 2.750 m 1

X-direction 1 pcs., Centre -


centre, 1.775 m

Y-direction 1 pcs., Centre -


centre, 2.400 m

Arrangement A1

211
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire list

Φtotal Ptotal Luminous efficacy


5597 lm 36.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 Philips 36.0 W 5597 lm 155.5 lm/W

212
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Calculation objects

213
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 242 lx 215 lx 264 lx 0.89 0.81 WP34


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

214
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Working plane (Bath)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 242 lx 215 lx 264 lx 0.89 0.81 WP34


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

215
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Summary

Ground area 4.26 m² Clearance height 2.750 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.750 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

216
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 241 lx ≥ 200 lx WP20

Uo (g1 ) 0.87 ≥ 0.50 WP20

Glare valuation(1) RUG, max 25 ≤ 25

Energy estimation(2) Consumption 5.94 kWh/a max. 200 kWh/a

Room Lighting power density 8.45 W/m² –

3.51 W/m²/100 lx –

(1) Based on a rectangular space of 2.400 m x 1.775 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Philips 24 36.0 W 5597 lm 155.5 lm/W

217
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire layout plan

218
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

1 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.913 m / 1.171 m /
2.750 m 0.913 m 1.171 m 2.750 m 1

X-direction 1 pcs., Centre -


centre, 1.775 m

Y-direction 1 pcs., Centre -


centre, 2.400 m

Arrangement A1

219
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire list

Φtotal Ptotal Luminous efficacy


5597 lm 36.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 Philips 36.0 W 5597 lm 155.5 lm/W

220
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Calculation objects

221
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 241 lx 210 lx 265 lx 0.87 0.79 WP20


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

222
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Working plane (Bath)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 241 lx 210 lx 265 lx 0.87 0.79 WP20


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

223
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Summary

Ground area 4.26 m² Clearance height 2.750 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.750 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

224
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 245 lx ≥ 200 lx WP18

Uo (g1 ) 0.89 ≥ 0.50 WP18

Glare valuation(1) RUG, max 25 ≤ 25

Energy estimation(2) Consumption 5.94 kWh/a max. 200 kWh/a

Room Lighting power density 8.45 W/m² –

3.45 W/m²/100 lx –

(1) Based on a rectangular space of 2.400 m x 1.775 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Philips 24 36.0 W 5597 lm 155.5 lm/W

225
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire layout plan

226
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

1 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.853 m / 1.216 m /
2.750 m 0.853 m 1.216 m 2.750 m 1

X-direction 1 pcs., Centre -


centre, 1.775 m

Y-direction 1 pcs., Centre -


centre, 2.400 m

Arrangement A1

227
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire list

Φtotal Ptotal Luminous efficacy


5597 lm 36.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 Philips 36.0 W 5597 lm 155.5 lm/W

228
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Calculation objects

229
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 245 lx 217 lx 268 lx 0.89 0.81 WP18


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

230
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Working plane (Bath)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 245 lx 217 lx 268 lx 0.89 0.81 WP18


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

231
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Summary

Ground area 4.26 m² Clearance height 2.750 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.750 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

232
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 243 lx ≥ 200 lx WP37

Uo (g1 ) 0.88 ≥ 0.50 WP37

Glare valuation(1) RUG, max 25 ≤ 25

Energy estimation(2) Consumption 5.94 kWh/a max. 200 kWh/a

Room Lighting power density 8.45 W/m² –

3.48 W/m²/100 lx –

(1) Based on a rectangular space of 2.400 m x 1.775 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Philips 24 36.0 W 5597 lm 155.5 lm/W

233
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire layout plan

234
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

2 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.950 m / 1.173 m /
2.750 m 0.950 m 1.173 m 2.750 m 1

X-direction 1 pcs., Centre -


centre, 1.775 m

Y-direction 2 pcs., Centre -


centre, 2.525 m

Arrangement A1

235
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath


Luminaire list

Φtotal Ptotal Luminous efficacy


5597 lm 36.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 Philips 36.0 W 5597 lm 155.5 lm/W

236
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Calculation objects

237
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 243 lx 214 lx 266 lx 0.88 0.80 WP37


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

238
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bath (Light scene 1)


Working plane (Bath)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bath) 243 lx 214 lx 266 lx 0.88 0.80 WP37


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

239
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Summary

Ground area 20.53 m² Clearance height 2.750 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.750 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

240
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 307 lx ≥ 200 lx WP31

Uo (g1 ) 0.59 ≥ 0.50 WP31

Glare valuation(1) RUG, max 27 ≤ 25

Energy estimation(2) Consumption 17.8 kWh/a max. 750 kWh/a

Room Lighting power density 5.26 W/m² –

1.71 W/m²/100 lx –

(1) Based on a rectangular space of 4.050 m x 5.875 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Philips 27 36.0 W 5597 lm 155.5 lm/W

241
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire layout plan

242
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

2 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 5.050 m / 2.698 m /
2.750 m 5.050 m 2.698 m 2.750 m 3

X-direction 1 pcs., Centre -


centre, 1.775 m

Y-direction 2 pcs., Centre -


centre, 2.525 m

Arrangement A1

2 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.636 m / 1.414 m /
2.750 m 1.636 m 2.689 m 2.750 m 1

X-direction 1 pcs., Centre - 1.636 m 1.414 m 2.750 m 2


centre, Distances not
equal

Y-direction 2 pcs., Centre -


centre, Distances not
equal

243
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire layout plan

Arrangement A2

244
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire list

Φtotal Ptotal Luminous efficacy


16791 lm 108.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

3 Philips 36.0 W 5597 lm 155.5 lm/W

245
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Calculation objects

246
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 307 lx 180 lx 419 lx 0.59 0.43 WP31
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

247
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Working plane (Bed Room)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 307 lx 180 lx 419 lx 0.59 0.43 WP31
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

248
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Summary

Ground area 20.53 m² Clearance height 2.750 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.750 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

249
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 308 lx ≥ 200 lx WP35

Uo (g1 ) 0.55 ≥ 0.50 WP35

Glare valuation(1) RUG, max 27 ≤ 25

Energy estimation(2) Consumption 17.8 kWh/a max. 750 kWh/a

Room Lighting power density 5.26 W/m² –

1.71 W/m²/100 lx –

(1) Based on a rectangular space of 5.875 m x 4.050 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Philips 27 36.0 W 5597 lm 155.5 lm/W

250
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire layout plan

251
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

2 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 4.900 m / 1.201 m /
2.750 m 4.900 m 1.201 m 2.750 m 1

X-direction 1 pcs., Centre -


centre, 1.775 m

Y-direction 2 pcs., Centre -


centre, 2.752 m

Arrangement A1

2 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.636 m / 1.414 m /
2.750 m 1.636 m 2.689 m 2.750 m 2

X-direction 1 pcs., Centre - 1.636 m 1.414 m 2.750 m 3


centre, Distances not
equal

Y-direction 2 pcs., Centre -


centre, Distances not
equal

252
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire layout plan

Arrangement A2

253
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire list

Φtotal Ptotal Luminous efficacy


16791 lm 108.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

3 Philips 36.0 W 5597 lm 155.5 lm/W

254
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Calculation objects

255
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 308 lx 170 lx 419 lx 0.55 0.41 WP35
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

256
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Working plane (Bed Room)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 308 lx 170 lx 419 lx 0.55 0.41 WP35
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

257
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Summary

Ground area 20.49 m² Clearance height 2.750 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.750 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

258
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 309 lx ≥ 200 lx WP27

Uo (g1 ) 0.62 ≥ 0.50 WP27

Glare valuation(1) RUG, max 27 ≤ 25

Energy estimation(2) Consumption 17.8 kWh/a max. 750 kWh/a

Room Lighting power density 5.27 W/m² –

1.71 W/m²/100 lx –

(1) Based on a rectangular space of 5.875 m x 4.050 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Philips 27 36.0 W 5597 lm 155.5 lm/W

259
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire layout plan

260
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

2 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 2.017 m / 1.396 m /
2.750 m 2.017 m 2.671 m 2.750 m 2

X-direction 1 pcs., Centre - 2.017 m 1.396 m 2.750 m 3


centre, Distances not
equal

Y-direction 2 pcs., Centre -


centre, Distances not
equal

Arrangement A1

Individual luminaires

X Y Mounting Luminaire
height

-1.215 m 2.777 m 2.750 m 1

261
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire list

Φtotal Ptotal Luminous efficacy


16791 lm 108.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

3 Philips 36.0 W 5597 lm 155.5 lm/W

262
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Calculation objects

263
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 309 lx 191 lx 423 lx 0.62 0.45 WP27
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

264
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Working plane (Bed Room)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 309 lx 191 lx 423 lx 0.62 0.45 WP27
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

265
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Summary

Ground area 20.53 m² Clearance height 2.750 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.750 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

266
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 312 lx ≥ 200 lx WP23

Uo (g1 ) 0.64 ≥ 0.50 WP23

Glare valuation(1) RUG, max 27 ≤ 25

Energy estimation(2) Consumption 17.8 kWh/a max. 750 kWh/a

Room Lighting power density 5.26 W/m² –

1.69 W/m²/100 lx –

(1) Based on a rectangular space of 4.050 m x 5.875 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Philips 27 36.0 W 5597 lm 155.5 lm/W

267
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire layout plan

268
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

2 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.950 m / 1.420 m /
2.750 m 1.950 m 2.695 m 2.750 m 2

X-direction 1 pcs., Centre - 1.950 m 1.420 m 2.750 m 3


centre, Distances not
equal

Y-direction 2 pcs., Centre -


centre, Distances not
equal

Arrangement A1

Individual luminaires

X Y Mounting Luminaire
height

5.050 m 1.150 m 2.750 m 1

269
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire list

Φtotal Ptotal Luminous efficacy


16791 lm 108.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

3 Philips 36.0 W 5597 lm 155.5 lm/W

270
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Calculation objects

271
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 312 lx 201 lx 424 lx 0.64 0.47 WP23
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

272
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Working plane (Bed Room)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 312 lx 201 lx 424 lx 0.64 0.47 WP23
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

273
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Summary

Ground area 20.18 m² Clearance height 2.750 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.750 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

274
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 314 lx ≥ 200 lx WP22

Uo (g1 ) 0.62 ≥ 0.50 WP22

Glare valuation(1) RUG, max 27 ≤ 25

Energy estimation(2) Consumption 17.8 kWh/a max. 750 kWh/a

Room Lighting power density 5.35 W/m² –

1.71 W/m²/100 lx –

(1) Based on a rectangular space of 4.050 m x 5.775 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Philips 27 36.0 W 5597 lm 155.5 lm/W

275
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire layout plan

276
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

2 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 4.027 m / 1.336 m /
2.750 m 4.027 m 2.611 m 2.750 m 2

X-direction 1 pcs., Centre - 4.027 m 1.336 m 2.750 m 3


centre, Distances not
equal

Y-direction 2 pcs., Centre -


centre, Distances not
equal

Arrangement A1

Individual luminaires

X Y Mounting Luminaire
height

0.875 m 1.150 m 2.750 m 1

277
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire list

Φtotal Ptotal Luminous efficacy


16791 lm 108.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

3 Philips 36.0 W 5597 lm 155.5 lm/W

278
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Calculation objects

279
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 314 lx 194 lx 423 lx 0.62 0.46 WP22
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

280
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Working plane (Bed Room)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 314 lx 194 lx 423 lx 0.62 0.46 WP22
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

281
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Summary

Ground area 20.49 m² Clearance height 2.750 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.750 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

282
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 313 lx ≥ 200 lx WP21

Uo (g1 ) 0.64 ≥ 0.50 WP21

Glare valuation(1) RUG, max 27 ≤ 25

Energy estimation(2) Consumption 17.8 kWh/a max. 750 kWh/a

Room Lighting power density 5.27 W/m² –

1.69 W/m²/100 lx –

(1) Based on a rectangular space of 5.875 m x 4.050 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Philips 27 36.0 W 5597 lm 155.5 lm/W

283
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire layout plan

284
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

2 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.950 m / 1.420 m /
2.750 m 1.950 m 2.695 m 2.750 m 2

X-direction 1 pcs., Centre - 1.950 m 1.420 m 2.750 m 3


centre, Distances not
equal

Y-direction 2 pcs., Centre -


centre, Distances not
equal

Arrangement A1

Individual luminaires

X Y Mounting Luminaire
height

4.867 m 2.777 m 2.750 m 1

285
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire list

Φtotal Ptotal Luminous efficacy


16791 lm 108.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

3 Philips 36.0 W 5597 lm 155.5 lm/W

286
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Calculation objects

287
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 313 lx 199 lx 427 lx 0.64 0.47 WP21
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

288
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Working plane (Bed Room)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 313 lx 199 lx 427 lx 0.64 0.47 WP21
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

289
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Summary

Ground area 20.48 m² Clearance height 2.750 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.750 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

290
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 308 lx ≥ 200 lx WP19

Uo (g1 ) 0.58 ≥ 0.50 WP19

Glare valuation(1) RUG, max 27 ≤ 25

Energy estimation(2) Consumption 17.8 kWh/a max. 750 kWh/a

Room Lighting power density 5.27 W/m² –

1.71 W/m²/100 lx –

(1) Based on a rectangular space of 5.875 m x 4.050 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Philips 27 36.0 W 5597 lm 155.5 lm/W

291
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire layout plan

292
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

2 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 4.275 m / 1.438 m /
2.750 m 4.275 m 2.713 m 2.750 m 2

X-direction 1 pcs., Centre - 4.275 m 1.438 m 2.750 m 3


centre, Distances not
equal

Y-direction 2 pcs., Centre -


centre, Distances not
equal

Arrangement A1

Individual luminaires

X Y Mounting Luminaire
height

0.985 m 2.777 m 2.750 m 1

293
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room


Luminaire list

Φtotal Ptotal Luminous efficacy


16791 lm 108.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

3 Philips 36.0 W 5597 lm 155.5 lm/W

294
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Calculation objects

295
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 308 lx 179 lx 422 lx 0.58 0.42 WP19
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

296
Officials Rest House Lighting

Officials Rest House Building · First Floor · Bed Room (Light scene 1)
Working plane (Bed Room)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Bed Room) 308 lx 179 lx 422 lx 0.58 0.42 WP19
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

297
Officials Rest House Lighting

Officials Rest House Building · First Floor · Corridor (Light scene 1)


Summary

Ground area 42.47 m² Clearance height 2.750 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.750 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

298
Officials Rest House Lighting

Officials Rest House Building · First Floor · Corridor (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 428 lx ≥ 200 lx WP24

Uo (g1 ) 0.66 ≥ 0.50 WP24

Glare valuation(1) RUG, max 29 ≤ 25

Energy estimation(2) Consumption 71.3 kWh/a max. 1500 kWh/a

Room Lighting power density 10.17 W/m² –

2.38 W/m²/100 lx –

(1) Based on a rectangular space of 1.550 m x 27.402 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

12 Philips 28 36.0 W 5597 lm 155.5 lm/W

299
Officials Rest House Lighting

Officials Rest House Building · First Floor · Corridor


Luminaire layout plan

300
Officials Rest House Lighting

Officials Rest House Building · First Floor · Corridor


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

12 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Line arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 17.587 m / 0.769 m /
2.750 m -2.920 m 0.766 m 2.750 m 1

X-direction 12 pcs., Centre - -0.641 m 0.766 m 2.750 m 2


centre, 2.279 m
1.637 m 0.766 m 2.750 m 3
Arrangement A1
3.916 m 0.767 m 2.750 m 4

6.194 m 0.767 m 2.750 m 5

8.473 m 0.767 m 2.750 m 6

10.752 m 0.768 m 2.750 m 7

13.030 m 0.768 m 2.750 m 8

15.309 m 0.768 m 2.750 m 9

17.587 m 0.769 m 2.750 m 10

19.866 m 0.769 m 2.750 m 11

22.145 m 0.769 m 2.750 m 12

301
Officials Rest House Lighting

Officials Rest House Building · First Floor · Corridor


Luminaire list

Φtotal Ptotal Luminous efficacy


67164 lm 432.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

12 Philips 36.0 W 5597 lm 155.5 lm/W

302
Officials Rest House Lighting

Officials Rest House Building · First Floor · Corridor (Light scene 1)


Calculation objects

303
Officials Rest House Lighting

Officials Rest House Building · First Floor · Corridor (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Corridor) 428 lx 283 lx 465 lx 0.66 0.61 WP24


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

304
Officials Rest House Lighting

Officials Rest House Building · First Floor · Corridor (Light scene 1)


Working plane (Corridor)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Corridor) 428 lx 283 lx 465 lx 0.66 0.61 WP24


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

305
Officials Rest House Lighting

Officials Rest House Building · First Floor · Entrance (Light scene 1)


Summary

Ground area 13.31 m² Clearance height 2.750 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.750 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

306
Officials Rest House Lighting

Officials Rest House Building · First Floor · Entrance (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 294 lx ≥ 200 lx WP26

Uo (g1 ) 0.76 ≥ 0.50 WP26

Glare valuation(1) RUG, max 27 ≤ 25

Energy estimation(2) Consumption 11.9 kWh/a max. 500 kWh/a

Room Lighting power density 5.41 W/m² –

1.84 W/m²/100 lx –

(1) Based on a rectangular space of 3.200 m x 4.158 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 Philips 26 36.0 W 5597 lm 155.5 lm/W

307
Officials Rest House Lighting

Officials Rest House Building · First Floor · Entrance


Luminaire layout plan

308
Officials Rest House Lighting

Officials Rest House Building · First Floor · Entrance


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

2 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.600 m / 2.988 m /
2.750 m 1.600 m 2.988 m 2.750 m 1

X-direction 1 pcs., Centre - 1.600 m 1.101 m 2.750 m 2


centre, 2.762 m

Y-direction 2 pcs., Centre -


centre, 1.887 m

Arrangement A1

309
Officials Rest House Lighting

Officials Rest House Building · First Floor · Entrance


Luminaire list

Φtotal Ptotal Luminous efficacy


11194 lm 72.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 Philips 36.0 W 5597 lm 155.5 lm/W

310
Officials Rest House Lighting

Officials Rest House Building · First Floor · Entrance (Light scene 1)


Calculation objects

311
Officials Rest House Lighting

Officials Rest House Building · First Floor · Entrance (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Entrance) 294 lx 222 lx 368 lx 0.76 0.60 WP26


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

312
Officials Rest House Lighting

Officials Rest House Building · First Floor · Entrance (Light scene 1)


Working plane (Entrance)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Entrance) 294 lx 222 lx 368 lx 0.76 0.60 WP26


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

313
Officials Rest House Lighting

Officials Rest House Building · First Floor · Kitchen (Light scene 1)


Summary

Ground area 20.58 m² Clearance height 2.750 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.750 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

314
Officials Rest House Lighting

Officials Rest House Building · First Floor · Kitchen (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 313 lx ≥ 200 lx WP28

Uo (g1 ) 0.63 ≥ 0.50 WP28

Glare valuation(1) RUG, max 27 ≤ 25

Energy estimation(2) Consumption 17.8 kWh/a max. 750 kWh/a

Room Lighting power density 5.25 W/m² –

1.68 W/m²/100 lx –

(1) Based on a rectangular space of 5.875 m x 4.050 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Philips 27 36.0 W 5597 lm 155.5 lm/W

315
Officials Rest House Lighting

Officials Rest House Building · First Floor · Kitchen


Luminaire layout plan

316
Officials Rest House Lighting

Officials Rest House Building · First Floor · Kitchen


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

2 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 3.938 m / 1.138 m /
2.750 m 3.938 m 2.913 m 2.750 m 2

X-direction 1 pcs., Centre - 3.938 m 1.138 m 2.750 m 3


centre, 3.200 m

Y-direction 2 pcs., Centre -


centre, 1.775 m

Arrangement A1

Individual luminaires

X Y Mounting Luminaire
height

1.019 m 1.250 m 2.750 m 1

317
Officials Rest House Lighting

Officials Rest House Building · First Floor · Kitchen


Luminaire list

Φtotal Ptotal Luminous efficacy


16791 lm 108.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

3 Philips 36.0 W 5597 lm 155.5 lm/W

318
Officials Rest House Lighting

Officials Rest House Building · First Floor · Kitchen (Light scene 1)


Calculation objects

319
Officials Rest House Lighting

Officials Rest House Building · First Floor · Kitchen (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Kitchen) 313 lx 197 lx 402 lx 0.63 0.49 WP28


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

320
Officials Rest House Lighting

Officials Rest House Building · First Floor · Kitchen (Light scene 1)


Working plane (Kitchen)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Kitchen) 313 lx 197 lx 402 lx 0.63 0.49 WP28


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

321
Officials Rest House Lighting

Officials Rest House Building · First Floor · Pantry (Light scene 1)


Summary

Ground area 4.26 m² Clearance height 2.750 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.750 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

322
Officials Rest House Lighting

Officials Rest House Building · First Floor · Pantry (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 245 lx ≥ 200 lx WP32

Uo (g1 ) 0.89 ≥ 0.50 WP32

Glare valuation(1) RUG, max 25 ≤ 25

Energy estimation(2) Consumption 5.94 kWh/a max. 200 kWh/a

Room Lighting power density 8.45 W/m² –

3.46 W/m²/100 lx –

(1) Based on a rectangular space of 1.775 m x 2.400 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

1 Philips 24 36.0 W 5597 lm 155.5 lm/W

323
Officials Rest House Lighting

Officials Rest House Building · First Floor · Pantry


Luminaire layout plan

324
Officials Rest House Lighting

Officials Rest House Building · First Floor · Pantry


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

1 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.938 m / 1.200 m /
2.750 m 0.938 m 1.200 m 2.750 m 1

X-direction 1 pcs., Centre -


centre, 1.775 m

Y-direction 1 pcs., Centre -


centre, 2.400 m

Arrangement A1

325
Officials Rest House Lighting

Officials Rest House Building · First Floor · Pantry


Luminaire list

Φtotal Ptotal Luminous efficacy


5597 lm 36.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

1 Philips 36.0 W 5597 lm 155.5 lm/W

326
Officials Rest House Lighting

Officials Rest House Building · First Floor · Pantry (Light scene 1)


Calculation objects

327
Officials Rest House Lighting

Officials Rest House Building · First Floor · Pantry (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Pantry) 245 lx 217 lx 268 lx 0.89 0.81 WP32


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

328
Officials Rest House Lighting

Officials Rest House Building · First Floor · Pantry (Light scene 1)


Working plane (Pantry)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Pantry) 245 lx 217 lx 268 lx 0.89 0.81 WP32


Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

329
Officials Rest House Lighting

Officials Rest House Building · First Floor · Stair Landing (Light scene 1)
Summary

Ground area 16.52 m² Clearance height 2.750 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.750 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

330
Officials Rest House Lighting

Officials Rest House Building · First Floor · Stair Landing (Light scene 1)
Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 374 lx ≥ 200 lx WP25

Uo (g1 ) 0.56 ≥ 0.50 WP25

Glare valuation(1) RUG, max 27 ≤ 25

Energy estimation(2) Consumption 17.8 kWh/a max. 600 kWh/a

Room Lighting power density 6.54 W/m² –

1.75 W/m²/100 lx –

(1) Based on a rectangular space of 3.200 m x 5.163 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

3 Philips 26 36.0 W 5597 lm 155.5 lm/W

331
Officials Rest House Lighting

Officials Rest House Building · First Floor · Stair Landing


Luminaire layout plan

332
Officials Rest House Lighting

Officials Rest House Building · First Floor · Stair Landing


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

1 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 2.452 m / 2.400 m /
2.750 m 2.452 m 2.400 m 2.750 m 2

X-direction 1 pcs., Centre -


centre, 3.200 m

Y-direction 1 pcs., Centre -


centre, 5.163 m

Arrangement A1

1 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.702 m / 2.400 m /
2.750 m 0.702 m 2.400 m 2.750 m 3

X-direction 1 pcs., Centre -


centre, 3.200 m

Y-direction 1 pcs., Centre -


centre, 5.163 m

Arrangement A2

333
Officials Rest House Lighting

Officials Rest House Building · First Floor · Stair Landing


Luminaire layout plan

1 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.600 m / 4.350 m /
2.750 m 1.600 m 4.350 m 2.750 m 1

X-direction 1 pcs., Centre -


centre, 3.200 m

Y-direction 1 pcs., Centre -


centre, 5.163 m

Arrangement A3

334
Officials Rest House Lighting

Officials Rest House Building · First Floor · Stair Landing


Luminaire list

Φtotal Ptotal Luminous efficacy


16791 lm 108.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

3 Philips 36.0 W 5597 lm 155.5 lm/W

335
Officials Rest House Lighting

Officials Rest House Building · First Floor · Stair Landing (Light scene 1)
Calculation objects

336
Officials Rest House Lighting

Officials Rest House Building · First Floor · Stair Landing (Light scene 1)
Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Stair Landing) 374 lx 208 lx 493 lx 0.56 0.42 WP25
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

337
Officials Rest House Lighting

Officials Rest House Building · First Floor · Stair Landing (Light scene 1)
Working plane (Stair Landing)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Stair Landing) 374 lx 208 lx 493 lx 0.56 0.42 WP25
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

338
Officials Rest House Lighting

Officials Rest House Building · Mumpty Floor (Light scene 1)


Room list

339
Officials Rest House Lighting

Officials Rest House Building · Mumpty Floor (Light scene 1)


Room list

Stair Landing

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


144.0 W 21.76 m² 6.62 W/m² = 1.67 W/m²/100 lx (Room) 396 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

4 Philips 36.0 W 5597 lm

340
Officials Rest House Lighting

Officials Rest House Building · Mumpty Floor


Luminaire list

Φtotal Ptotal Luminous efficacy


22388 lm 144.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

4 Philips 36.0 W 5597 lm 155.5 lm/W

341
Officials Rest House Lighting

Officials Rest House Building · Mumpty Floor (Light scene 1)


Calculation objects

342
Officials Rest House Lighting

Officials Rest House Building · Mumpty Floor (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Stair Landing) 396 lx 241 lx 530 lx 0.61 0.45 WP30
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

343
Officials Rest House Lighting

Officials Rest House Building · Mumpty Floor · Stair Landing (Light scene 1)
Summary

Ground area 21.76 m² Clearance height 2.750 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.750 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.000 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

344
Officials Rest House Lighting

Officials Rest House Building · Mumpty Floor · Stair Landing (Light scene 1)
Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 396 lx ≥ 200 lx WP30

Uo (g1 ) 0.61 ≥ 0.50 WP30

Glare valuation(1) RUG, max 27 ≤ 25

Energy estimation(2) Consumption 23.8 kWh/a max. 800 kWh/a

Room Lighting power density 6.62 W/m² –

1.67 W/m²/100 lx –

(1) Based on a rectangular space of 6.800 m x 3.200 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

4 Philips 27 36.0 W 5597 lm 155.5 lm/W

345
Officials Rest House Lighting

Officials Rest House Building · Mumpty Floor · Stair Landing


Luminaire layout plan

346
Officials Rest House Lighting

Officials Rest House Building · Mumpty Floor · Stair Landing


Luminaire layout plan

Manufacturer Philips P 36.0 W

Fitting 1x TLED 36W 6500K ΦLuminaire 5597 lm


160D 9290013463

1 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.702 m / 2.400 m /
2.750 m 0.702 m 2.400 m 2.750 m 2

X-direction 1 pcs., Centre -


centre, 3.200 m

Y-direction 1 pcs., Centre -


centre, 5.163 m

Arrangement A1

1 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 2.452 m / 2.400 m /
2.750 m 2.452 m 2.400 m 2.750 m 3

X-direction 1 pcs., Centre -


centre, 3.200 m

Y-direction 1 pcs., Centre -


centre, 5.163 m

Arrangement A2

347
Officials Rest House Lighting

Officials Rest House Building · Mumpty Floor · Stair Landing


Luminaire layout plan

1 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.600 m / -0.550 m /
2.750 m 1.600 m -0.550 m 2.750 m 4

X-direction 1 pcs., Centre -


centre, 3.200 m

Y-direction 1 pcs., Centre -


centre, 5.163 m

Arrangement A3

1 x Philips ledtube_1500mm_36w_g5_865_5600lm-ies (1).ies

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.600 m / 4.350 m /
2.750 m 1.600 m 4.350 m 2.750 m 1

X-direction 1 pcs., Centre -


centre, 3.200 m

Y-direction 1 pcs., Centre -


centre, 5.163 m

Arrangement A4

348
Officials Rest House Lighting

Officials Rest House Building · Mumpty Floor · Stair Landing


Luminaire list

Φtotal Ptotal Luminous efficacy


22388 lm 144.0 W 155.5 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

4 Philips 36.0 W 5597 lm 155.5 lm/W

349
Officials Rest House Lighting

Officials Rest House Building · Mumpty Floor · Stair Landing (Light scene 1)
Calculation objects

350
Officials Rest House Lighting

Officials Rest House Building · Mumpty Floor · Stair Landing (Light scene 1)
Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Stair Landing) 396 lx 241 lx 530 lx 0.61 0.45 WP30
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

351
Officials Rest House Lighting

Officials Rest House Building · Mumpty Floor · Stair Landing (Light scene 1)
Working plane (Stair Landing)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Stair Landing) 396 lx 241 lx 530 lx 0.61 0.45 WP30
Perpendicular illuminance (adaptive) (≥ 200 lx) (≥ 0.50)
Height: 0.000 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)