SBC_vs_NFPA_Code_Comparative_Analysis__1735091840
SBC_vs_NFPA_Code_Comparative_Analysis__1735091840
ANALYSIS
6
Intent of SBC 801
NFPA REFERENCED
STANDARDS
7
NFPA 101 Life Safety Code
Scope
NFPA 101 Life Safety Code -
Intent
Why Did we Select NFPA 101 for
comparison ?
• It is the only document that covers life safety
for new and existing structures.
• NFPA 101 lays out (mostly with references to
other applicable codes), protective features
and systems, building services, operating
characteristics, maintenance activities and
other provisions for additional safeguards to
effectively and competently meet requirements
for the protection of building occupants from
death by fire.
Why Did we Select NFPA 101 for
comparison ?
• While the SBC is a far-reaching code
encompassing structural, sanitation, lighting,
ventilation, and several other areas, life safety
considerations for MISSION CRITICAL
facilities/System & environments is not an
important area of focus for SBC
• On the other hand, NFPA 101 has a more
detailed perspective for mission critical facilities
than SBC and is limited to life safety and
What Defines Mission Critical
Facilities ?
Mission critical facilities are broadly defined as
containing any operation that, if interrupted, will
cause a negative impact on business activities,
ranging from losing revenue to jeopardizing legal
conformity to, in extreme cases, loss of life.
SBC- 801/201 Code or
Standard: What’s the
Difference?
For model codes to be enforceable as law,
they must be adopted through the legislative
process by the state, county, city, or other
jurisdiction.
13
SBC- 801/201 Code or
Standard: What’s the
Difference?
A code is a legal document that governs
certain activities—it tells the user what must be
done.
14
SBC- 801/201 Code or
Standard: What’s the
Difference?
For Example :
15
SBC- 801/201 Code or
Standard: What’s the
Difference?
So, at this point of time can we understand that
standard referenced in SBC 801 is also
enforceable ???
Absolutely Yes…….
16
SBC- 801/201 Code or
Standard: What’s the
Difference?
17
SBC- 801/201 Code or Standard:
What’s the Difference?
WHEN TO DO IT
HOW TO DO IT
WHAT TO DO
REFERENCE
PRODUCT
STANDARDS AND
TEST PROTOCOL
18
SBC- 801/201 Code or Standard:
What’s the Difference?
General
Fire and Building Codes reference the Installation and ITM Standards
19
Detailed
SBC 801/201 VS NFPA
STANDARDS
What If There is
CONFLICT Between SBC
801 & Referenced
Standards(NFPA Design
Standards) ..?
20
SBC 801/201 VS NFPA
STANDARDS
21
DEVELOPMENT OF NFPA
DOCUMENTS
Almost 300 Codes, Standards, Recommended
Practices & Guides.
All Are Voluntary Documents ( They do not have
the power of law unless AHJ adopts them)
They are developed through consensus process
More than 200 Technical committees.
Governed by 13 member standard council also
composed of volunteers.
Its Technical Committee who are responsible for
document content not NFPA Staff.
22
TECHNICAL COMMITTEES
More than 6000 volunteers serve on NFPA technical Committees,
with selection of these volunteers based on their back ground and
expertise.
NFPA uses the following membership categories to fill and
balance committee.
Manufacturer
User
Installer/Maintainer
Labor representative
Enforcing authority
Insurance representative
Special Expert
Consumer
Applied Research/Testing Lab.
TECHNICAL COMMITTEES
Consensus occurs when a majority of
committee accepts a proposed change to the
document it overseas.
Acceptance by committee and its subsequent
recommendations for change requires at least
two third majority vote by written ballot.
SEQUENCE OF EVENTS FOR
ISSUANCE OF NFPA
DOCUMENT
STEP -1
CALL FOR PROPOSAL
STEP -2
REPORT ON PROPOSAL
(ROP)
SEQUENCE OF EVENTS FOR
ISSUANCE OF NFPA
DOCUMENT
STEP -3
REPORT ON COMMENTS
(ROC)
STEP -4
TECHNICAL COMMITTEE REPORT
SESSION
STEP -5
STANDARD COUNCIL ISSUANCE
CORRECTION TO
DOCUMENTS
Between revisions of the documents, errata
and temporary interim amendment (TIA) may
be issued.
FORMAL INTERPRETATION
(FI)
It’s a mechanism for providing an explanation of
the meaning or intent of any specific provision that
is included in an issued NFPA code or standard.
FIs are processed through the technical committee
that is responsible for the document and must be
clearly worded to solicit a “yes” or “No” answer
from committee.
Confirmation from the technical committee for an
FI is achieved through a letter ballot. If a 3/4th
Majority is not achieved, the FI fails and the item is
placed on the committee next meeting agenda.
When to Use Which Code?
It Depends on ;
Assembling the design criteria for a structures
SBC Definition
2. Occupancy Classifications
Occupancy SBC (Saudi Building Code) NFPA
Classification Life Safety Code and NFPA 5000
ASSEMBLY A-1 Assembly, Theaters (Fixed Seats) A - Assembly (variations noted by occupant
A-2 Assembly, Food and/or Drink Consumption load)
A-3 Assembly, Worship, Recreation, Amusement
A-4 Assembly, Indoor Sporting Events
A-5 Assembly, Outdoor Activities
BUSINESS B- Business B –Business
AHC- Ambulatory Health Care
EDUCATIONAL E- Educational (includes some day care) E- Educational
Definition
Means of
General Occupant
Egress
Requirement Load
Component
Accessible
means of
Egress
8. Means of Egress
The SBC 801 discusses the Means of Egress in
one chapter (chapter 10) for all occupancies.
The NFPA 101 addresses Means of Egress in
general terms in one chapter (chapter 7) and
then provides additional Means of Egress
requirements in each chapter of the individual
occupancies.
8. Means of Egress
Both allow projections into the minimum ceiling height to 6’-8” above
finished floor, but the IBC allows 50% of the ceiling to be less than 7’-6”.
The NFPA 101 requires a stricter 2/3 of the ceiling area to be at least 7’-6”.
NFPA 101
SBC 801
8. Means of Egress
Occupant Load : The SBC- 801 load table is Table 1004.1.2 The NFPA 101
load table is Table 7.3.1.2.
NFPA 101
8. Means of Egress
Occupant Load : The SBC- 801 load table is Table 1004.1.2 The NFPA 101
load table is Table 7.3.1.2.
SBC 801
8. Means of Egress
The outstanding difference between the two occupant loads is in how each
code directs the application of the loading factors.
The SBC code states the loading be applied to each portion of the building
based on occupancy of each portion. The most restrictive requirements are
to be applied to only the portion of the egress system that is used by more
than one occupancy.
8. Means of Egress
The outstanding difference between the two occupant loads is in how each
code directs the application of the loading factors.
The NFPA 101 also requires the loading be based on each type of
occupancy, but requires the restrictive condition of applying the Means of
Egress, type of construction and other safeguards of the most restrictive
occupancy to the entire building.
8. Means of Egress
The outstanding difference between the two occupant loads is in how each
code directs the application of the loading factors.
The NFPA 101 also requires the loading be based on each type of
occupancy, but requires the restrictive condition of applying the Means of
Egress, type of construction and other safeguards of the most restrictive
occupancy to the entire building.
8. Means of Egress
Egress Width :
Ramps
Dead End
Corridor
9. Integrated Fire & Safety
Approach
Use and
Fire Rated Means of
Occupancy
Construction Egress
classification
KEY POINTS COMPARISION
A SUMMARY
Title SBC NFPA 101 Preferred Code
(SBC/NFPA)
Classification of Specify high-hazard materials, NFPA 101 does not specifically define "high-hazard
Hazard of and classifies Group H materials" or provide construction requirements for high-
Contents occupancies based on the level hazard occupancies. NFPA 101 classifies High-Hazard
of detonation, combustion, or Storage and Industrial occupancies based on: speed at SBC
deflagration hazard. In IBC, which contents are likely to burn hazardous contents
hazard level of contents does exceeding Maximum Allowable Quantities established in
impact construction NFPA 30.
requirements.
Code The provisions relevant to an The most stringent requirements of all occupancies in
Requirement occupancy only pertain to that the building apply throughout the building.
Provision occupancy area and not to the NFPA
rest of the building.
Shaft Requires that duct and air Do not include any similar provision
Enclosures transfer penetrations at shaft
enclosures be protected with SBC
listed fire and smoke dampers.
Title SBC NFPA 101 Preferred Code
(SBC/NFPA)
Level of Discharge That portion of a means The story that is either (1) the lowest story
of egress system from which not less than 50% of the
between the termination required number of exits and not less than
of an exit and a public 50% of the required egress capacity from
way." i.e. exterior such a story discharge directly outside at
sidewalk to public way) the finished ground level; or (2) where no
story meets the conditions of item (1), the
story that is provided with one or more
exits that discharge directly to the outside
to the finished ground level via the
smallest elevation change NFPA
Ceiling Min. ceiling height: 7' - Min. ceiling height: 7' - 6"
Height/Head 6" Min. headroom at protruding objects: 6' -
Clearance Min. headroom at 8" SBC or NFPA
protruding objects: 6' -
8"
Title SBC NFPA 101 Preferred Code
(SBC/NFPA)
Ceiling Height/Head No more than 50% of the Not More than 1/3 (33%) of the ceiling
Clearance ceiling area of a means of area of a means of egress shall be
egress shall be reduced in reduced in height by protruding SBC
height by protruding objects objects.
more
Occupant Load Table 1004.5 Table 7.3.1.2
Dead End Corridor Max. 20 feet except business Max. 30 feet NFPA
occupancies (50 feet)
Vertical Exit Requires a smoke proof enclosure for Requires a smoke proof NFPA
Enclosure stairways at both some high rise and enclosure at underground
underground structure structures only
Panic Hardware
Requirements
SBC or NFPA
Preferable Selection of Code at
Various Stages of Project
Workflow
Project Development
Starting with SBC & developing Using NFPA
Process