The ABCs of DOAS - Dedicated Outdoor Air Systems
The ABCs of DOAS - Dedicated Outdoor Air Systems
org)
Reprinted by permission from ASHRAE Journal, May 2003. This article may not be copied nor distributed in either
paper or digital form without ASHRAE's permission.
By Wayne Morris, Associate Member ASHRAE a thermostat that matches the sensible-
cooling capacity of the coil with the sen-
o curb the initial cost of a building’s mechanical systems, designers
T
sible-cooling load in the space.
have expended much time and effort to use a single HVAC unit to Equipment cooling capacity, both sen-
sible and latent, decreases as the space
handle ventilation as well as mechanical cooling. High-occupancy spaces, sensible-cooling load drops. In most cli-
such as classrooms, pose a particular challenge. This article explores the mates, the combination of less latent-
cooling capacity and a lower space SHR
benefits of “splitting” the cooling load, that is, using a dedicated outdoor-
elevates the relative humidity in the
air unit to treat high latent-cooling load of outdoor air and zone-mounted space at part-load conditions.
terminal units to treat high sensible-cooling load of indoor air. Treating An “off-the-shelf,” packaged unitary air
conditioner may further aggravate this
outdoor air separately makes it easy to verify sufficient ventilation airflow
situation. Such equipment is designed to
and enforces the maximum limit for relative humidity in occupied zones. operate with a supply-airflow-to-cooling-
capacity ratio of 350 to 400 cfm/ton (47
This article also explores techniques tent-cooling loads on the cooling equip- to 54 L/s per kW). In hot, humid climates,
to minimize inefficient reheating and ment do not peak at the same time. When offsetting the ventilation load for high-
recooling of the outdoor air while sim- it’s hot outside, sensible-cooling load can occupancy spaces may require that the
plifying the system and maximizing ther- exceed latent-cooling load. By contrast, unit deliver no more than 200 to 250 cfm/
mal comfort. when it’s cool and rainy outside, latent- ton (27 to 34 L/s per kW) to achieve the
cooling load can approach or even ex- dew point of 45°F to 50°F (7°C to 10°C)
Defining the Challenge ceed sensible cooling load. needed for adequate dehumidification.
Why is it so difficult to provide ad- Constant-volume, mixed-air HVAC
equate dehumidification with a constant- units traditionally are selected with suf- About the Author
volume, mixed-air system? The answer ficient cooling capacity to handle the Wayne Morris is an applications engineer for
lies in the fact that the sensible- and la- dry-bulb design load and controlled by Trane, Global Unitary Systems, in Macon, Ga.