Impact of inverters on Transmission system
Impact of inverters on Transmission system
Abstract—This paper discusses the impact of inverter-based obtaining the negative-sequence component in
resources (IBRs) in traditional digital protection relays applied in electromechanical and solid-state relays requires complex and
the interconnection transmission line between the IBR and bulk
more expensive analog filters [7] [8]. These new functions
power system. Real events involving a photovoltaic (PV) power
plant are used to show the behavior of the fault currents, which is significantly improve the sensitivity, reliability, and security of
different from power systems with synchronous generators, transmission line protective functions and schemes, allowing
especially for negative-sequence components. The paper discusses for the secure detection of challenging line faults.
how to properly handle this kind of source by presenting modern This paper evaluates how nonconventional power sources
protective relays features, time-domain functions, and special affect the security and reliability of phasor-based transmission
settings for traditional protection intelligent electronic devices
line protection, especially the protective functions based on
(IEDs). The data of the real events were used to validate the
solutions proposed in this case study. The lessons learned will be symmetrical components. First, the paper briefly reviews the
applied in a new facility (a wind farm) that is currently in the short circuit contribution from nonconventional power sources,
design stage. focusing on the IBRs. The paper reviews the main transmission
line protective features based on negative-sequence
I. INTRODUCTION components and their benefits in terms of sensitivity, reliability,
Over the last decade, the renewable energy share of the and security.
electricity sector grew quickly. Renewable energy installations, A case study evaluating the performance of phasor-based
especially solar photovoltaic (PV) facilities and wind turbines, protective features in a 138 kV transmission line connecting a
are increasingly deployed today. The contribution of these 420 MW PV solar power plant to the bulk power system is
sources to the power system affects the performance of presented. Data from real fault events in this transmission
conventional protection systems, particularly for faults on system are used to evaluate the line protective functions’
transmission lines that connect such power sources to the bulk performance.
power system. Most of these renewable power sources are The paper evaluates the performance of improved phasor-
inverter-based, and their characteristics change according to based and time-domain protective functions that are designed
manufacturer design and specifications. The fault current to provide reliable performance of the transmission line
contribution from an inverter-based resource (IBR) is limited protection system connecting IBR to the grid. Data captured
by the current capacity of its power electronic components and from real fault events are used to test and assess the
its control functions. Typically, the maximum current capacity effectiveness and performance of the improved phasor-based
of these power components does not exceed 1.5 times the full- and time-domain protective features, and the results are
load current during the fault steady-state. Additionally, the presented and discussed.
IBRs do not have the same amount of rotational inertia as a Finally, the paper proposes protection philosophy
synchronous generator [1]. Usually, the IBR does not deliver combining phasor-based elements and time-domain
reliable negative-sequence and zero-sequence quantities, as the incremental quantities. It is based on the validation made with
synchronous generators would do. The IBR’s atypical behavior field data in this paper and previous papers’ conclusions.
and characteristics challenge the phasor-based protective Possible modifications in the phasor-based function setting to
functions when compared to synchronous generators, because improve security, as shown in [9], are also considered.
the assumptions made in their design are no longer valid,
especially assumptions about the fault current contribution II. IBR BEHAVIOR DURING POWER SYSTEM FAULTS
magnitude and associated negative-sequence behavior [1]. A. Dynamic Behavior of Wind Turbines During
Numerical relay benefits and advantages are well known in Short Circuits
the power industry, and the ease of obtaining the symmetrical Wind turbines are complex systems that transform the
components from the measured phase quantities is one of those kinetic energy of the wind into electrical energy, and wind
advantages. It allows the implementation of several new generation is already responsible for a significant portion of the
functions based on symmetrical components, especially the Brazilian energy matrix [10]. One of the specific features of
negative-sequence component [2] [3] [4] [5] [6], since wind generation is the high variability of wind strength, which
2
translates into variations in turbine rotations. For a generator, The PV modules are composed of a set of interconnected
varying rotation means a varying generated signal frequency. solar cells that transform energy. The cell connections are
Since there is a tendency for the frequency in the generator to directly related to the voltage and electric current that the
vary and a simultaneous need to keep the frequency of the module needs to supply to comply with the manufacturing
electrical system constant, several solutions have been design [16].
developed to allow coupling between the wind turbine and the PV generation systems consist of the connection of solar
power system. modules in series, in parallel, or as a combination of the two in
Wind turbines are commonly classified into different types, which each string is made up of a certain number of modules to
according to their operation and construction. Naturally, each obtain the desired voltage and current levels. Generally, power
type of generator contributes differently when there are faults is the technical specification most used to classify PV modules,
in the system. There are many studies that seek to find the best and the unit widely used is peak watt (Wp).
way to model the different types of machines to understand The complete system of a solar plant, at the generation level,
their behavior during system faults [11]. Good modeling allows is composed of the following equipment:
users to feel more confident when calculating generator • Solar modules
contributions for short circuit and yard equipment strength • Combiner box
studies. • Inverter
References [12] and [13] present the Type I and Type II • Step-up transformer
wind turbine characteristics and fault contributions, To produce the necessary power, the solar modules are
respectively. The contributions of Type III generators during interconnected and form strings. These strings are brought
faults can be divided into two behaviors, which depend on together in a combiner box, and the outputs of the combiner box
whether or not the crowbar is active. When the crowbar is are connected to the ac/dc inverters, which convert the dc
active, the power electronics do not control the field winding; voltage to ac voltage using a three-phase rectifier. The outputs
therefore, the behavior is similar to that of the induction of the inverters are linked to step-up transformers to connect the
generator. Also, when the generator with the activated crowbar energy at medium voltage level to a collector substation, which
is contributing, some components can have frequencies other then raises the voltage to make the generated energy available
than nominal frequency, since the axis rotation of the machine through the power system.
is not necessarily in sync with the network. The highest short Grid-connected solar power plants contribute to short circuit
circuit levels of the Type III wind turbine are obtained when the currents during a fault, modifying the short circuit characteristic
crowbar is active [14]. in the power system. The contribution to the short circuit
When the crowbar is not active and the network is under current depends on a variety of factors, including the maximum
fault conditions, wind turbine contributions are determined by current level supported by the inverter, inverter control systems,
the power electronics. In this situation, the control network environmental conditions, protection system, location, and type
developed by the manufacturer is largely responsible for of fault.
determining the dynamic response of the machine. We have
seen different responses among different manufacturers and III. FIELD CASE ANALYSIS
different wind turbines from the same manufacturer.
Fig. 1 shows the main features of the system used as a case
Type IV has its short circuit current fully controlled by the
study. The field case study is based on a solar PV power plant
power electronics. These devices are sized to carry a current
located in Brazil, which has an installed capacity of
level slightly above the nominal current, which limits the
approximately 420 MW. The PV is connected to Brazil’s
contribution of these generators to a range of 1.1 to 1.3 pu of
national interconnected system (GRID) through three
the nominal current for most of the time [1] [15]. Another
three-winding step-up transformers, as shown in Fig. 1:
characteristic is the low capacity to supply negative-sequence
• 34.5 kV sector—PV distribution voltage level with
current; the short circuit current of this type of generator tends
resistance-grounded and Y-connected step-up
to be balanced, even for unbalanced faults.
transformer winding. The inverters are connected to
B. Behavior of PV Power Plants During Short Circuits the 34.5 kV bus through 0.38/34.5 kV step-up
Generation of electrical energy through PV panels involves transformers, not shown in Fig. 1.
converting sunlight into electrical energy. This conversion • 138 kV sector—PV transmission voltage level with
occurs due to the semiconductor characteristics of the material solid-grounded and Y-connected transformer winding
(normally silicon), which is used in PV cells due to its for connection to the GRID through the 138 kV
commonality. transmission line with a length of 10.37 km
(6.44 miles).
• Delta (D) tertiary winding for harmonic filtering with
no load connected.
3
The applied intelligent electronic device (IED) is a Fig. 2. Oscillography records with current (amperes), voltage (kilovolts),
transmission line protective relay, and the main enabled and digital signals from the PV and GRID terminals for the external AG fault.
functions for circuit breaker (CB) tripping are as follows: The small dip in the A-phase voltage suggests that it was a
• Line differential protection—phase elements (87LA, short circuit in the grid relatively distant (electrically) from the
87LB and 87LC), negative-sequence element (87LQ), transmission line in question. Field personnel reports that the
and zero-sequence element (87LG) are enabled fault occurred approximately 200 km (124 miles) away from
• Phase and ground distance time-delayed elements the transmission line in question.
(Z2T)—Zone 1 is not enabled due to short line length Fig. 3 shows the waveforms for each phase and both
and PV fault contribution behavior terminals separately. This makes it easy to observe that the
• Directional comparison teleprotection scheme with current entering the line through the PV terminal is equal to the
permissive overreach transfer trip (POTT) by current leaving the line through the GRID terminal (the currents
overreaching distance (Z2) and neutral directional from both sides are in opposition of phase). This proves that it
overcurrent (67G2) element was an external fault to the line.
• Direct transfer trip (DTT)
• Emergency overcurrent protection (51E)—only
enabled in case of simultaneous loss-of-potential and
loss of differential channel communications
• Phase overvoltage protection (59P)
There is an AG fault in the grid, outside the 138 kV
interconnection transmission line. At the time of the fault, the
PV is connected generating energy; therefore, there is a
contribution from the PV to the fault.
Fig. 2 shows the currents and voltages during the AG fault
external to the transmission line. Users can conclude that it is
an AG short circuit due to the voltage sag in the A-phase and
the current increase in this phase at the beginning of the short
circuit. Current increases in the other phases and distortions in
the waveforms are a challenge for the protection schemes that
are currently employed.
For this fault, the 138 kV line protection should not cause
the opening of CBs. However, as Fig. 2 shows, the IED_GRID Fig. 3. Currents by phase (amperes) at both line terminals.
trips (2:TRIP). The current flowing through the IEDs at both
line terminals is the contribution of the PV, which has high The rest of this paper provides a more detailed analysis of
distortion and is not consistent with the contribution of a the behavior of the protection functions during this event.
synchronous machine to an AG fault.
4
Fig. 4. Relationship between I2 and I0 for AG, BG, CG, BCG, CAG, and
ABG faults.
overcurrent element (67G2), and this was the element I2R and V2 indicates a clear reverse fault (shown in Fig. 9b),
responsible for the POTT scheme operation. justifying the change of directionality determined by this relay.
In a traditional negative-sequence directional element, the
angular relationship between the negative-sequence voltage
(V2 and I2) determines the fault direction. For a forward fault,
I2 • 1<Z1ANG (I2R) is expected to be 180 degrees out with V2;
whereas, the reverse fault I2R is expected to be in-phase with V2
[17], as shown in Fig. 7. When setting V2 as the angular
reference, I2R is expected to be in the blue region for forward
faults and in the red region for reverse faults. The region in Fig. 8. Operating principles of element 32Q during a forward fault (a) and
black is where the direction is undefined. during a reverse fault (b).
Fig. 6. Oscillography records with current signals (amperes) and indications Fig. 9. Fault current (amperes) and relationship between I2R and V2 for the
of the protections activated on the PV and GRID terminals for the external IED_PV at different times during the fault.
AG fault.
For the IED_GRID, at the beginning of the fault, the
relationship between I2R and V2 is in an undefined region, and
the IED did not determine the fault to be in either direction
(shown in Fig. 10a). At a later time, the relationship between
I2R and V2 indicates a forward fault condition (shown in
Fig. 10b), justifying the IED’s determination that the direction
of the fault was forward.
Fig. 7. Relationship between V2 and I2R for forward and reverse faults.
Fig. 12. Fault current (amperes) and relationship between V0 and I0R for the
IED_GRID at different times during the fault.
In the external fault condition, despite the unstable behavior IV. EVALUATION OF NEW PROTECTIVE FEATURES
of the unconventional source, its contribution is a current In this section, the performance of new protection functions
passing through the line; therefore, this does not cause a for events in the system is evaluated. Both phasor-based
differential current in the phase, negative-sequence, and zero- protection functions were modified to better adapt to the
sequence elements. contribution of IBRs to faults, and new time-domain-based
For an internal fault in the protected line, the IED at the functions are evaluated.
GRID terminal measures the current contributed by the system,
while the IED at the PV terminal measures the current A. Incremental-Quantity Directional Element (TD32)
contributed by the PV plant. This is not a problem for the phase Reference [21] demonstrates the operational principle of the
and zero-sequence differential elements, given the TD32 element, which operates based on the incremental
characteristics of the system. For the negative-sequence voltage (∆v) and the incremental replica current (∆iZ).
differential element, it is not a problem at first, since the For a forward fault, the relationship between ∆v and ∆iZ is
contribution of the GRID is significantly greater than the the negative of the absolute value of the source impedance
contribution of the PV. As this paper is being written, no behind the relay (ZS), according to (1).
internal fault events on the line are available for analysis. ∆v =− ZS • ∆i Z (1)
Considering that the contribution to an internal fault at the
GRID terminal is much greater than that at the PV terminal, the For a reverse fault, the relationship between ∆v and ∆iZ is
87LQ element will also operate reliably under unbalanced the absolute value of the sum of the protected line impedance
internal faults. (ZL) with the source impedance of the remote terminal (ZR),
according to (2).
D. Distance Element (21)
There was no distance element pickup for this event because ∆v= ZL + ZR • ∆i Z (2)
the fault was far from the protected line. Fig. 14 shows the Mho The graphical representation of ∆v and ∆iZ during system
Zone 2 element characteristic and AG loop apparent faults helps us understand how the relationship between these
impedance. During the fault, the apparent impedance varies quantities indicates the fault direction (shown in Fig. 15) [21].
greatly.
In the case where the fault is within the overreaching zone,
this variation in apparent impedance during the fault could
cause the apparent impedance to move in and out of the zone,
preventing the element from operating and acting as a backup
for external faults in the system. References [1] and [20] show
how the behavior of unconventional sources affects distance
relays.
Fig. 15. Incremental voltage and incremental replica current for a forward
fault (a) and for a reverse fault (b).
In addition to S2 and S0, the logic also uses the positive- Given the applications and operating principle of this logic,
sequence voltage (V1) in determining the fault type when there it should work for faults in the forward direction.
is no ground involved and also to determine whether the fault We evaluated the performance of the improved
is, for example, CG or ABG. Fig. 20 shows the expected phasor-based fault-type identification logic and the
angular relationship between these quantities for each fault type incremental-quantity-based faulted phase selection logic for the
[22]. In Fig. 20, the fault is BCG, confirmed both by the events in Case 1 and Case 2, presented above.
relationship between S0 and S2 and by the relationship between In Fig. 21, events marked with “1” are from the GRID
S2 and V1. terminal and those marked with “2” are from the PV terminal.
The IED of the PV terminal correctly identifies the fault as AG
by using the improved phasor-based element (2:FIDAG) and
using the element based on incremental quantities (2:FSAG).
The IED of the GRID terminal correctly identifies the fault
using the element based on incremental quantities (1:FSAG),
and there is no indication of using the improved phasor element
(1:FIDAG), as expected, since the fault is in the reverse
direction.
Fig. 23 shows the performance of the faulted phase selection Fig. 24. Simplified single-line diagram of new EDF Renewables wind farm
and its connection with GRID.
logic for a CAG fault external to the protected line. For this
case, only the PV event is available. Both logic options A. Pilot Protection Scheme
correctly identify the phases under fault. Additionally, the The transmission lines connecting the wind farm with GRID
correct behavior of the TD32 element is shown. have an optical ground wire (OPGW). The POTT pilot
protection scheme will be adopted.
The following directional elements are available:
• Main 1 protection IED
− Directional element based on incremental
quantities (TD32)
− Directional element based on TWs (TW32)
− Negative-sequence impedance directional
element (32Q)
− Zero-sequence impedance directional
element (32V)
− Phase directional element (32P-1)
• Main 2 protection IED
− Negative-sequence impedance directional
element (32Q)
− Zero-sequence impedance directional
element (32V)
− Phase directional element (32P-2)
The phase directional elements (32P) in each IED are
classified with different codes as they have different operating
principles:
• 32P-1—phase directional element polarized with
Fig. 23. Fault current (amperes), voltage (kilovolts), performance of the positive-sequence voltage memory
improved phasor-based faulted phase selection logic (FIDCAG), incremental-
quantity-based faulted phase selection logic (FSCA), and TD32F for an
• 32P-2—phase directional element based on the
external CAG fault. positive-sequence impedance angle, obtained from the
relationship between the positive-sequence voltage
The improved method described was proven to be safer and
and positive-sequence current
more robust than the traditional method based only on
symmetrical component currents in the events evaluated.
12
1) Ground Faults strategy presented above, 32P-2 is also available for unbalanced
For faults involving ground, the TD32 and 32V elements phase-to-phase faults.
ensure reliable indication of the fault direction. These elements For three-phase faults (3P), the TD32, 32P-1 and 32P-2
have been shown to be safe for the events evaluated and have elements are available. Reference [1] shows that 32P may lose
high sensitivity for detecting high-impedance ground faults. security for 3P GRID faults and [9] suggests an enhanced 32P
The TD32 element is directly associated with the directional that can be implemented by current supervision and simple
comparison teleprotection scheme for sending the permissive logic. This enhanced 32P element is used to supervise all phase
signal. The POTT scheme uses a current-supervised TD32 elements.
element (TD67) for tripping. Likewise, the POTT scheme uses The POTT scheme uses current-supervised 32Q (67Q) and
a zero-sequence current-supervised 32V element (67G) to send 32P-1 or 32P-2 elements (67P) to send the permissive signal
permissive signal and for tripping. and for tripping. At the PV terminal, these elements do not
Even given the low fault contribution of the wind farm, the operate for a line fault with the 50FP setting strategic presented
connection of the wind farm’s step-up transformer above and trip at this terminal is based on weak infeed and
(34.5/500 kV) allows it to contribute with zero-sequence echo-converted-to-trip (ECTT) logic. In the Main 1 relay, the
current through the wind farm terminal for line faults. weak infeed logic can be triggered by phase undervoltage
(27P), negative-sequence overvoltage (59Q), or zero-sequence
2) Phase-to-Phase and Three-Phase Faults
For phase-to-phase faults (2P) without ground involvement, overvoltage (59G). In the Main 2 relay, phase-to-phase (27PP)
the TD32 element will also be employed to indicate the and 59G are available
direction of the faults. For both 2P and 3P elements, the TD32 element has the
As shown in Section III, the use of the negative sequence sensitivity to quickly identify and declare forward faults, even
can result in safety and reliability problems given the with the low magnitude of the IBR contribution, as discussed in
contribution of the IBR terminal, but its use is desirable for [20]. The way TD32 is implemented in the POTT scheme in
identification of the direction for faults between phases without [22] requires current supervision for TD32 (TD67) only for
ground involvement, since the 32V element is unavailable to tripping and not for sending the permissive signal. In the case
assist in this case. of an internal fault, both terminals will send the permissive
Reference [9] suggests a strategy for applying the 32Q signal; however, only the GRID side will have enough current
function in this type of system. This strategy consists of to trip by the POTT. To ensure a fast trip at the IBR side, it is
defining a setting for the forward and reverse fault supervision necessary to use a DTT.
overcurrent elements (50FP and 50RP, respectively) of the 32Q B. Line Current Differential Protection
function with a threshold high enough to guarantee the security The Main 2 relay has a line differential function based on
of these elements. the alpha plane, providing phase differential elements (87LA,
In this application, at the IBR terminal, 50FP and 50RP are 87LB, and 87LC), a negative-sequence differential element
set so that 32Q is enabled only for reverse faults. At the GRID (87LQ), and a zero-sequence differential element (87LG).
terminal, 50FP and 50RP are set so that 32Q is enabled for line As shown in Section III, all these elements remain safe for
faults. These settings allow the elements to be enabled by the external faults. Even with the unexpected behavior of I2 from
GRID contribution current only, where the relationship the IBR terminal, the same current passes through both line
between V2 and I2 is coherent with the fault direction. Since the terminals in the event of external faults. Thus, all differential
IBR contribution is limited, this strategy allows the function to elements can be enabled. Reference [9] also evaluates the
have the sensitivity to detect reverse unbalanced faults at the security and reliability of 87L function for IBR connecting
IBR terminal, increasing the security of the hybrid POTT transmission lines.
scheme that uses weak infeed and echo logic.
For the Main 2 relay, when 50FP is not activated, the fault- C. Distance and Step Distance Protection
type identification function stops comparing the phasors of I0 As mentioned previously, the application of the distance
and I2 and switches to a voltage-based faulted phase function at the wind farm terminal leads to safety and reliability
identification logic if the weak infeed logic is enabled, which is issues. An instantaneous Zone 1 element may overreach for
reliable for terminals with a weak source [9]. Therefore, proper external faults, and a time delay Zone 2 element may not be
setting of the 50FP is doubly beneficial in this IED. In addition able to provide backup for the system due to the variation in the
to fault location, fault-type signaling, and single-pole trip, FID apparent impedance.
logic in this IED also supervises distance elements. The enhanced 32P element can supervise phase distance
Additionally, the 32P-1 element works independently and is elements at both line terminals. Additionally, to prevent Zone 1
always available for phase-to-phase faults. As with the phase overreaching, the phase Zone 1 element can be limited using
directional element with a quadrature connection, there can be the distance element overcurrent supervision or adding a time
a conflict between 32P-1 elements of different phases in faults delay; these two conditions can also be combined in an OR gate.
like Case 2 of Section III. Adding 67G and 67Q supervision in Adding a dropout delay in the Zone 2 element can avoid
the pilot protection scheme improves security in this case. element dropout, providing dependable backup. All these
In the Main 2 IED, the 32Q element has priority over the solutions are suggested and detailed in [9].
32P-2 element. When 32Q is not enabled, per the setting
13
Since the connection between the wind farm and the GRID However, the termination of the line at the IBR is through a
is radial in this system, a distance element with an extended transformer, which means that ZT has a much higher value
Zone 1 can be applied to the GRID terminal relay, with a reach compared to ZC. This causes iR and iI to have opposite polarities
beyond the 500 kV bus of the wind farm, as shown in Fig. 25. and causes iTW to have a magnitude smaller than the incident
This increases instantaneous coverage for line faults, especially wave, which makes it difficult to detect.
in the event of communications channel failures. Additionally, Reference [25] shows actual records of current TWs in a
at the GRID terminal, the TD21 element can be applied with a transformer termination made by a TW-based fault-locating
reach near to the remote bus. device in a configuration similar to the system studied here. The
experience of this real system shows that, despite the
attenuation in the magnitude, detection is still possible. Since
the magnitude of the TW signal generated in the fault depends
on the voltage incidence angle, the signal attenuation at the
wind farm terminal reduces the sensitivity of TW-based
functions, especially for faults that occur far from the voltage
peak.
In the system in analysis, it will be applied using the
Fig. 25. Extended Zone 1 improves instantaneous coverage for line faults. following TW-based functions:
This strategy cannot be applied if more equipment • TW-based directional element (TW32)
(transmission lines or transformers) gets connected to the • TW-based line differential element (TW87)
500 kV bus of the wind farm terminal in the future. • TW-based fault location with data from two terminals
For these faults, the current that passes through the line (DETWFL) [25]
terminals is the current coming from the system, which is • Predictive line monitoring based on TWs [26]
mostly composed of synchronous machines; therefore, the In cases when the IBR terminal is connected to more
distance functions can operate normally. transmission lines, the low impedance increases the reliability
of the TW functions.
D. TW-Based Features
Faults in the transmission line generate voltage and current E. Line Protection System Reliability
transients that propagate toward the line terminals. When an Most of the protection strategies described are dependent on
incident wave (iI) reaches the line terminal, part is transmitted the availability of the communications channel between the line
(iT) and part is reflected (iR), as shown in Fig. 26 [24]. terminals, excluding the distance elements. Therefore, to ensure
the availability of the protection system, the means of
communication must be highly available and redundant.
This becomes even more critical in applications when other
transmission lines are connected to the IBR bus or more than
one transformer, since the strategy of extending the reach of
Zone 1 is not fully applicable.
The National Electric System Operator (ONS) of Brazilian
Fig. 26. Representation of incident (iI), reflected (iR), and transmitted (iT) grid requires, at a minimum, the total redundancy of the
waves at a transmission line terminal.
communications channel for all facilities with a voltage level
The portion of the wave that is reflected and transmitted equal to or greater than 230 kV.
depends on the ratio between the line’s characteristic Usually, transmission lines, especially newer ones, have an
impedance (ZC) and the equivalent terminal impedance (ZT), OPGW cable, which provides a reliable communications
which can be determined using (5) and (6). channel for both 87L protection and pilot protection schemes,
ZC − ZT either via direct fiber or through multiplexers.
iR = iI (5) To provide redundancy, an alternative route through nearby
ZC + ZT
substations is an option. In this case, for radially connected
2 ZC IBRs, alternative routes are unlikely to be available.
iT = iI (6) Communication redundancy can be obtained through a second
ZC + ZT
OPGW cable, power line carrier (PLC), or spread-spectrum
An IED that monitors the current signal at the line terminal radios for short lines. These last two means of communication
sees the sum of the incident and reflected currents (iTW) do not support or ideally meet the requirements of the
according to (7). 87L function [27], making it difficult to adopt the 87L function
i TW= i I + i R (7) with full redundancy.
Thus, pilot protection using a directional comparison
At the GRID terminal, two other transmission lines are
scheme is the natural alternative for these communications
connected, so ZT is smaller than ZC. This causes iR to have the
channels. The use of the TD32 function in the pilot protection
same polarity as iI and causes iTW to have a magnitude greater
than the incident wave, which makes it easier to detect.
14
[17] J. Roberts and A. Guzmán, “Directional Element Design and Paulo Lima received his BSEE in electrical engineering from Federal
Evaluation,” proceedings of the 21st Annual Western Protective Relay University of Itajubá, Brazil, in 2012. In 2013, he joined Schweitzer
Conference, Spokane, WA, October 1994. Engineering Laboratories, Inc. (SEL) as a protection application engineer in
[18] B. Fleming, “Negative-Sequence Impedance Directional Element,” Brazil. In 2018, he became an application engineering group coordinator, and
proceedings of the 10th Annual ProTest User Group Meeting, he has been the regional technical manager for Brazil since 2020. He has
experience in application, training, integration, and testing of digital protective
Pasadena, CA, February 1998.
relays. He also provides technical writing and training associated with SEL
[19] J. Roberts, D. Tziouvaras, G. Benmouyal, and H. Altuve, “The Effect of products and SEL University.
Multiprinciple Line Protection on Dependability and Security,”
proceedings of the 55th Annual Georgia Tech Protective Relaying
Fabio Lollo received his BSEE in electrical engineering from São Paulo State
Conference, Atlanta, GA, May 2001. University (Bauru campus), Brazil, in 1997. In 1998, he joined BMG
[20] B. Kasztenny, “Distance Elements for Line Protection Applications Engineering as an electrical engineer, working with protection and control
Near Unconventional Sources,” June 2021. Available: selinc.com. design and protection studies. In 2013, he joined Schweitzer Engineering
[21] E. O. Schweitzer, III, B. Kasztenny, A. Guzmán, V. Skendzic, and Laboratories, Inc. (SEL) as senior protection engineer in Brazil. In 2016, he
V. Mynam, “Speed of Line Protection – Can We Break Free of Phasor became design and studies group coordinator. Currently, he is a senior
Limitations?” proceedings of the 41st Annual Western Protective Relay protection engineer and supervises a group of project engineers with SEL
Conference, Spokane, WA, October 2014. Engineering Services, Inc. (SEL ES). He has experience in short circuit
calculation and protection settings for industrial and utility systems.
[22] SEL-T401L Ultra-High-Speed Line Relay Instruction Manual.
Available: selinc.com.
[23] E. O. Schweitzer, III, and B. Kasztenny, “Distance Protection: Why
Have We Started With a Circle, Does It Matter, and What Else Is Out
There?” proceedings of the 71st Annual Conference for Protective Relay
Engineers, College Station, TX, March 2018.
[24] A. Guzmán, B. Kasztenny, Y. Tong, and V. Mynam, “Accurate and
Economical Traveling-Wave Fault Locating Without
Communications,” proceedings of the 71st Annual Conference for
Protective Relay Engineers, College Station, TX, March 2018.
[25] E. O. Schweitzer, III, A. Guzmán, V. Mynam, V. Skendzic, B.
Kasztenny, and S. Marx, “Locating Faults by the Traveling Waves They
Launch,” proceedings of the 67th Annual Conference for Protective
Relay Engineers, College Station, TX, April 2014.
[26] B. Kasztenny, V. Mynam, T. Joshi, and D. Holmbo, “Preventing Line
Faults With Continuous Monitoring Based on Current Traveling
Waves,” proceedings of the 15th International Conference on
Developments in Power System Protection Liverpool, United Kingdom,
March 2020.
[27] B. Kasztenny, N. Fischer, K. Fodero, and A. Zvarych, “Communications
and Data Synchronization for Line Current Differential Schemes,”
proceedings of the 2nd Annual Protection, Automation, and Control
World Conference, Dublin, Ireland, June 2011.
IX. BIOGRAPHIES
Marcelo Bini received his BSEE in electrical engineering from Santa Catarina
State University (Joinville campus), Brazil, in 2006. In 2006, he joined Engevix
Engineering as an electrical engineer, working with hydroelectric power plant
projects with emphasis on protection, control, and measurement systems. In
2017, he joined Araxá Solar as a substation design engineer. In 2019, he joined
EDF Renewables as an electrical engineer, working with protection and control
design and other electrical projects involved in substations, transmission lines,
and medium voltage networks.