DL05 I/O Specifications


D0-05DR $212.00
Wiring diagram and specifications

D0-05DR Specifications
AC Power Supply 95–240 VAC
Voltage Range C3
Specifications (30VA)
Number of Input Pts. 8 (sink/source)
Number of Commons 2 (isolated)
Input Voltage Range 12–24 VDC
Power
(X0-X2) 1.8K @ input wiring
12–24 VDC 95-240
Input Impedance VAC
(X3-X7) 2.8K @
12–24 VDC 6-240 VAC
or
On Current/ 12-24 6-27 VDC
DC Input >5mA/10VDC VDC Source Sink
Voltage Level
Specifications Input point wiring Output point wiring
OFF Current/
<0.5 mA/<2VDC
Voltage Level
Response Time X0-X2 X3-X7
OFF to ON Equivalent input circuit,
<100µs <8ms high-speed inputs (X0-X2)
Response
ON to OFF
<100µs <8ms
Response
Fuses None 
9'&
Number of
6 6RXUFH 6LQN
Output Points
Number of Commons 2 (isolated)
6–240 VAC,
Output Voltage Range 47–63 Hz
6–27 VDC Equivalent input circuit,
Maximum Voltage 264VAC,30VDC standard inputs (X3-X7)

2A/point
Maximum Current
Relay Output 6A/common
Specifications Maximum 0.1 mA @
Leakage Current 246VAC 
9'&
Smallest
5mA @ 5VDC 6RXUFH 6LQN
Recommended Load
OFF to ON Response <15ms
ON to OFF Response <10ms
Status Indicators Logic side
Derating chart for relay outputs Equivalent output circuit
None (external
Fuses
recommended)

Typical Relay Life (Operations) at Room


Temperature
Load Current
Voltage and Type of Load
1A 2A
24 VDC Resistive 600K 270K
24 VDC Solenoid 150K 60K
110 VAC Resistive 900K 350K
110 VAC Solenoid 350K 150K
220 VAC Resistive 600K 250K
220 VAC Solenoid 200K 100K

www.automationdirect.com DL05 / DL06 PLCs tDL5-21


For the latest prices, please check AutomationDirect.com.
1-800-633-0405

Features at a Glance
The DL05 and DL06 micro PLCs are
complete self-contained systems.
DL05 CPU Specifications DL06 CPU Specifications
The CPU, power supply, and I/O are System capacity System capacity
all included inside the same housing. Total memory available (words)……………………....... 6K Total memory available (words)…………………..... 14.8K
Option modules are available to expand Ladder memory (words)…………………………...........2048 Ladder memory (words)…………………………...........7680
V-memory (words)……………………………..................4096 V-memory (words)………………………………................7616
the capability of each PLC family for User V-memory………………………………....................3968 .User V-memory………………………………...............7488
more demanding applications. The .Non-volatile user V-memory……………………...........128 .Non-volatile user V-memory……………………......128
standard features of these PLCs are Battery backup………………………………….................... Yes1 Built-in battery backup (D2-BAT-1)………………….... Yes
extraordinary and compare favorably Total built-in I/O…………………………………...................... 14 Total I/O…………………………………………...........................36
.Inputs…………………………………………................................. 8 . Inputs…………………………………………............................20
with larger and more expensive PLCs. .Outputs………………………………………….............................. 6 . Outputs………………………………………........................... 16
The specification tables to the right are I/O expansion……………………………………................... Yes1 I/O expansion…………………………………...................... Yes1
meant for quick reference only. Detailed Performance Performance
Contact execution (Boolean)……………………....... 0.7 µs Contact execution (Boolean)................................0.6 µs
specifications and wiring information for )
Typical scan (1K Boolean 2…………………........ 1.5-3 ms. Typical scan (1K Boolean)2 ……………………........1-2 ms.
each model of the DL05 and DL06 PLCs
can be found in those specific sections. Instructions and diagnostics Instructions and diagnostics
RLL ladder style.............................................................. Yes RLL ladder style…………………………………..................... Yes
RLLPLUS/flowchart style (Stages).................... Yes/256 RLLPLUS/flowchart style (Stages)…………….. Yes/1024

Program capacity
Run-time editing............................................................ Yes Run-time editing………………………………….................. Yes
Supports Overrides....................................................... Yes Supports Overrides………………………………................. Yes
Scan............................................................... Variable/fixed Scan……………………………………................... Variable/fixed
Most boolean ladder instructions require Number of Instructions 133 Number of Instructions……………………………........... 229
a single word of program memory. Types of Instructions:
Control relays..................................................................512 Types of Instructions:
Other instructions, such as timers, Timers................................................................................128 .Control relays………………………………........................ 1024
.Timers………………………………………............................... 256
counters, etc., require two or more Counters...........................................................................128
.Counters……………………………………..............................128
words. Data is stored in V‑memory in Immediate I/O................................................................ Yes
.Immediate I/O…………………………………...................... Yes
Subroutines..................................................................... Yes
16-bit registers. For/next loops................................................................ Yes .Subroutines……………………………………......................... Yes
Timed interrupt.............................................................. Yes .For/next loops…………………………………....................... Yes
Performance .Table functions………………………………......................... Yes
Integer math................................................................... Yes
The performance characteristics shown Floating-point math...................................................... No .Timed interrupt………………………………........................ Yes
in the tables represent the amount of PID...................................................................................... Yes .Integer math………………………………….......................... Yes
.Trigonometric functions………………………….............. Yes
time required to read the inputs, solve Drum sequencers.......................................................... Yes
.Floating-point math……………………………................... Yes
Bit of word....................................................................... Yes
the Relay Ladder Logic program and .PID…………………………………………................................... Yes
ASCII print........................................................................ Yes
update the outputs. Real-time clock/calendar.......................................... Yes1 .Drum sequencers……………………………….................... Yes
Internal diagnostics....................................................... Yes .Bit of word……………………………………........................... Yes
Instructions Password security.......................................................... Yes .Number type conversion………………………............... Yes
A complete list of instructions is System and user error log.......................................... No .ASCII in, out, print……………………………...................... Yes
available at the end of this section. Communications
.LCD instruction………………………………......................... Yes
Real-time clock/calendar…………………………............. Yes
Built-in ports.Two RS-232C
Communications Internal diagnostics………………………………................ Yes
Protocols supported:
The DL05 and DL06 offer powerful . -sequence (proprietary protocol)………………....... Yes
K
Password security……………………………….................... Yes
System and user error log...........…………………………No
communication features normally found .DirectNet Client/Server…………………………................ Yes
only on more expensive PLCs. .Modbus RTU Client/Server………………………............ Yes Communications
.ASCII out…………………………………….............................. Yes Built-in ports:
One RS-232C
Special features Baud rate
Port 1 .................................................9,600 baud (fixed) One multi-function RS232C/RS422/RS485
The DC input and DC output PLCs offer Port 2.............................................selectable 300-38,400
high-speed counting or pulse output. baud (default 9,600) NOTE: RS485 is for MODBUS RTU only.
Protocols sup56ported:
Option module slots allow for discrete Specialty Features . -sequence (proprietary protocol)………………....... Yes
K
Filtered inputs……………………………………...................Yes
I/O expansion, analog I/O, or additional .DirectNet Client/Server…………………………................ Yes
3

Interrupt input……………………………………...................Yes3 .Modbus RTU Client/Server………………………............ Yes


communication options. High speed counter………………………….........Yes, 5kHz3 .ASCII in/out…………………………………............................ Yes
Pulse output……………………………….................Yes, 7kHz3 Baud rate
Pulse catch input………………………………….................Yes3 . Port 1………………………….......................,600 baud
(fixed)
1- These features are available with use of . Port 2.........…………………selectable 300-38,400
certain option modules. Option module specifications are baud
located later in this section. . .............…………………………(default 9,600)
2- Our 1K program includes contacts, coils, and scan Specialty Features
overhead. If you compare our products to others, make Filtered inputs……………………………………..................Yes3
sure you include their scan overhead. Interrupt input……………………………………..................Yes3
High speed counter…………………………........Yes, 7kHz3
3- Input features only available on units with DC inputs and Pulse output………………………………..............Yes, 10kHz3
output features only available on units with DC outputs. Pulse catch input…………………………………................Yes3
1- These features are available with use of
certain option module. Option module specifications are
located later in this section.
2- Our 1K program includes contacts, coils, and scan
overhead. If you compare our products to others, make
sure you include their scan overhead.
3- Input features only available on units with DC inputs and
output features only available on units with DC outputs.

www.automationdirect.com DL05 / DL06 PLCs tDL5-3


For the latest prices, please check AutomationDirect.com.
1-800-633-0405

Features at a Glance
DirectSOFT software
The DL05 and DL06 PLCs use the same
familiar DirectSOFT programming
Communication Output status
software that our larger PLCs use. A FREE Mounting tab Input status
ports indicators
indicators Mode switch
version of DirectSOFT gives you all the
great features of the full version, but
with a 100-word PLC program download
limitation. For programs larger than
100 words, the full package is required.
The FREE PC-DS100 software may be
sufficient to program the DL05 and
DL06. If you are programming with a Mode status
indicators
full package version prior to v6.0, you
will need v2.4 or later for the DL05 Communication
PLCs and v4.0 or later for the DL06. We status indicators
always recommend the latest version
for the most robust features. See the
DirectLOGIC Overview section DL in
this catalog for a complete description Removable
terminal
of DirectSOFT including features, part block
numbers of programming packages and
upgrades.
Programming
Handheld programmer....D2-HPP $590.00
DirectSOFT Programming for Windows
External power inputs Discrete input terminals Discrete output terminals Option module slot
PC-DSOFT6 $462.00
PC-DS100 Free
PC-R60-U (upgrade) $291.00
Hardware features diagrams

External power inputs Discrete output terminals Removable Option module slots
terminal
block

Mode status
Output status indicators indicators

Input status indicators Communicat-


ion status
indicators

Mode switch

Discrete input terminals Removable Communication ports Mounting tab


terminal
block

www.automationdirect.com DL05 / DL06 PLCs tDL5-4


For the latest prices, please check AutomationDirect.com.
1-800-633-0405

Product Dimensions and Installation


It is important to understand the
installation requirements for your DL05
or DL06 system. Your knowledge of these
requirements will help ensure that your
system operates within its environmental
and electrical limits.
Note: There is a minimum clearance requirement
Plan for safety of 2” (51mm) between the panel door
(or any devices mounted in the panel door)
This catalog should never be used as and the nearest DL05 component.
a replacement for the user manual.
You can purchase, download free,
or view online the user manuals for
these products. The D0-USER-M is the Temperature probe
publication for the DL05 PLCs, and the 2"
D0-06USER-M is the publication for the 50mm
DL06 PLCs. The D0-OPTIONS-M is the min

user manual for the option modules.


These user manuals contain important
safety information that must be
followed. The system installation should Power source
comply with all appropriate electrical 2"
codes and standards. 50mm
min

Unit dimensions and 2"


Panel ground 50mm
terminal min
Bus
bar

Ground braid Earth


Panel
copper lugs ground

Panel or
single point
Star ground
Star washers See the Enclosure
washers
section to find an enclosure that
Temperature probe fits your application

1.5"
38mm
min

Power source Environmental Specifications


for DL05 and DL06
-4º F-158ºF
1.5" Storage Temperature
38mm
(-20ºC to 70ºC)
min Ambient Operating 32ºF-131ºF
Panel ground Temperature (0º to 55ºC)
terminal 5 to 95% relative
Bus Ambient Humidity humidity
bar 1.5" (non-condensing)
38mm
Earth min MIL STD 810C
Vibration Resistance
ground Method 514.2
MIL STD 810C
Shock Resistance
Method 516.2
Note: T here is a minimum clearance requirement of 1.5” (38mm)
between the panel door (or any devices mounted in the Noise Immunity NEMA (ICS3-304)
panel door) and the nearest DL06 component. Atmosphere No corrosive gases

www.automationdirect.com DL05 / DL06 PLCs tDL5-5


For the latest prices, please check AutomationDirect.com.
1-800-633-0405

Product Dimensions and Installation


Mounting Orientation
DL05 and DL06 PLCs must be mounted
properly to ensure ample airflow for
cooling purposes. It is important to
follow the unit orientation requirements
and to verify that the PLC’s dimensions
are compatible with your application.
Notice particularly the grounding
requirements and the recommended
cabinet clearances.

Mounting orientation

Mounting orientation

www.automationdirect.com DL05 / DL06 PLCs tDL5-6


For the latest prices, please check AutomationDirect.com.
1-800-633-0405

Ports, Status Indicators, and Modes


Port 1 Port 2 DL05 and DL06
Port 1 is a 6-pin, fixed configuration port Port 2 is a configurable port on both status indicators
and has the same pin assignments on the DL05 and the DL06 PLCs. The DL05
the DL05 and the DL06. Please refer to PLC uses a 6-pin modular connector
the table and diagrams on this page. This and offers RS-232 communications
Status Indicators
port can be used to connect to an HPP, only. The DL06 PLC uses a 15-pin Indicator Status Meaning
DirectSOFT, an operator interface, or other HD-sub connector and offers RS-232, ON Power good
external device. Features include: RS-422, or RS-485 communications. PWR
OFF Power failure
• 9600 baud Please refer to the table and diagrams
ON CPU is in Run Mode
• 8 data bits
on this page for more information. This
port can be used to connect to an HPP, RUN CPU is in Stop or Program
OFF
• Odd parity DirectSOFT, an operator interface, or Mode
• 1 start bit, 1 stop bit other external device. Features of port ON CPU self diagnostics error
CPU
• Station address of 1 2 include: OFF CPU self diagnostics good
• Asynchronous, half-duplex, DTE •3 00, 600, 1200, 2400, 4800, 9600 (default), Data is being transmitted by
ON
Protocols supported (as Server): 19,200, 38,400 baud the CPU-Port 1
TX1
• K sequence, DirectNET, Modbus RTU • 8 data bits No data is being transmitted
OFF
• Odd (default), even, or no parity by the CPU-Port 1

DL05 & DL06 Port 1 Pin Descriptions • 1 start bit, 1 stop bit ON
Data is being received by the
CPU-Port 1
- Station address: RX1
1 0V Power (-) connection (GND) 1 (default) No data is being received by
OFF
2 5V Power (+) connection 1-90 DirectNET, K sequence the CPU-Port 1
3 RXD Receive data (RS-232C) 1-247 Modbus RTU Data is being transmitted by
ON
• Asynchronous, half-duplex, DTE the CPU-Port 2
4 TXD Transmit data (RS-232C) TX2
5 5V Power (+) connection Protocols supported: OFF
No data is being transmitted
by the CPU-Port 2
6 0V Power (-) connection (GND) • K sequence (Server), DirectNET
(Client/Server), Modbus (Client/Server) Data is being received by the
ON
CPU-Port 2
RX2
No data is being received by
OFF
DL05 Port 2 Pin Descriptions the CPU-Port 2

1 0V Power (-) connection (GND) DL05 and DL06


2 5V Power (+) connection mode switches
3 RXD Receive data (RS-232C)
4 TXD Transmit data (RS-232C) Mode
5 RTS Ready to send
Switch CPU Action
DL05 6 0V Power (-) connection (GND)
Position
CPU is forced into the RUN mode
DL06 Port 2 Pin Descriptions RUN (Run if no errors are encountered. No
Program) program changes are allowed by the
6-pin Female Modular Connector
1 5V Power (+) connection programming/monitoring device.
2 TXD Transmit data (RS-232C) RUN PROGRAM and the TEST
3 RXD Receive data (RS-232C) TERM modes are available. Mode and
(Terminal) program changes are allowed by the
4 RTS Ready to send (RS232C) programming/monitoring device.
5 CTS Clear to send (RS232C) CPU is forced into the STOP mode.
6 RXD- Receive data (-) (RS-422/485) STOP No changes are allowed by the
programming/monitoring device.
7 0V Power (-) connection (GND)
8 0V Power (-) connection (GND) Use the optional low profile 15-pin adapter to make option
9 TXD+ Transmit data (+) (RS-422/485 module wiring easier.
10 TXD- Transmit data (-) (RS-422/485)
11 RTS+ Ready to send (+) (RS-422/485) D0-06ADPTR
DL06 12 RTS- Ready to send (-) (RS-422/485)
13 RXD+ Receive data (+) (RS-422/485)
14 CTS+ Clear to send (+) (RS-422/485)
15 CTS- Clear to send (-) (RS-422/485)
6-pin Female 15-pin Female
Modular D-sub Connector
Connector

www.automationdirect.com DL05 / DL06 PLCs tDL5-10