Document ID: TE/QMS/F/02

Rev. No. : 03 Issued Date : 21/11/2023

Technical Data Sheet of 19/33 kV Three Core Cables

S.No Particulars 3 X 300


1 Name of Manufacturer Polycab India Ltd
2 Type of Cable A2XFY
3 Voltage Grade kV 19/33 KV (E)
4 No of cores X size in sqmm 3 X 300
Maximum conductor temperature under normal
5 a) 90°C
operating conditions
Maximum conductor temperature at the termination of
b) 250°C
short circuit
6 a) Permissible Voltage Variation ± 10%
b) Permissible Frequency Variation ± 5%
c) Combined Voltage & Frequency variation ± 10%
7 Conductor
a) Material H4 Grade Aluminium as per Class 2 of IS: 8130/2013, latest
Maximum d.c. resistance of conductor at 20° C
b) 0.100
(ohm/km)
c) Shape Stranded Compacted Circular
8 Conductor Screening
a) Material Extruded Semi-conducting Compound
b) Nominal thickness (mm) 0.3
9 Insulation
a) Material XLPE as per IS 7098(Pt-2)/2011
b) Nominal thickness (mm) 8.8
c) Core identification By Coloured strips (Red,Yellow,Blue)
10 Insulation Screening
(i) Non - Metallic
a) Material Extruded Semi-conducting Compound
b) Nominal thickness (mm) 0.3
(ii) Metallic
a) Material Single Layer of Copper Tape
b) Approximate thickness (mm) 0.04
11 Inner Sheath
a) Material Extruded PVC Type 'ST2' as per IS:5831, latest
b) Minimum thickness (mm) 0.7
c) Inner Sheath Colour Black
12 Armouring
a) Material Gal.Steel
b) Type of armouring Flat Strip
c) Nominal size of armour (mm) 4.0 x 0.8
d) Tolerance on armour dimensions ± 10%
13 Outer Sheath
(i) Material Extruded PVC Type 'ST2' as per IS:5831, latest
(ii) Thickness (mm) 3.00 (Min.)
(iii) Colour of sheath Black
14 Electrical Parameters
a) Max. a.c. resistance of conductor at 90° C (ohm/km) 0.130
b) Approx. Cable Capacitance (mfd/km) 0.22
c) Approx. Cable reactance (ohm/km) 0.104
d) Impedance of cable (ohm/km) 0.166
15 Continuous Current carrying capacities :-
(a) In Ground at 30°C (A) 351
(b) In Air at 40°C (A) 448
Short Circuit rating of conductor for the duration of 1
16 28.35
sec (kA)
IS 7098 Part 2/2011, IS 8130, IS 5831, IS 3975 etc. with latest up
17 Standard to which the cables confirm
to date amendments
18 Approx. Overall diameter (mm) 94.0 ± 3.0
19 Embossing YEAR POLYCAB ELECTRIC 19/33 KV (E) GRADE XLPE
YEAR POLYCAB ELECTRIC 19/33 KV (E) GRADE XLPE CABLE
20 Printing SIZE CABLE TYPE WITH SEQUENTIAL MARKING at every one
meter interval.
21 Standard Drum Length (Mtr.) 500 ± 5%
Maximum 5% of order quantity & Individual Non-standard drum
22 Non- Standard Drum Length (Mtr.)
length minimum 200 Mtrs
Note:-The values given above are subject to tolerances as per
the relevant standards.
Incase of any Typographical error /Discrepancy, relevant
standards shall be prevailed.
RD.S-17-120824-Q-0824-159384-V1-ECOREN
Document ID: TE/QMS/F/02

Rev. No. : 01 Issued Date : 10/06/2021

Technical Data Sheet of Solar Cable

Sr.No. Description Unit 1C X 6 Sq.mm


1 Manufacturer Name POLYCAB INDIA LTD
2 Brand Name POLYCAB
3 Rated a.c. Voltage kV 1.0/1.0
Nominal d.c. Voltage kV 1.5
4 CONDUCTOR
Annealed Tinned Flexible copper conductor as
a) Material
per Class 5 of BS EN 60228
b) Conductor Size Sq.mm 6
c) Max. D.C Cond. Resistance at 20 Deg. C. Ohm/km 3.39
5 INSULATION
E-Beam Cross linkable LSOH Compound
a) Material (Polyolefin Type) as per Annexure B Table
B.1 of BS EN 50618
b) Nominal Thickness mm 0.7
c) Colour of insulation Black | Red
6 Sheath
E-Beam Cross linkable LSOH (Polyolefin
a) Material Type) Compound as per Annexure B Table
B.1 of BS EN 50618
b) Nominal Thickness mm 0.8
c) Colour of outer sheath Black | Black with red strip
7 Overall Diameter ( Approx) mm 6.3 ± 0.4 mm
Current rating (upto 60°C) at two loaded cables
8 Amp 57
touching, on a surface

9 Current rating of single cable free in air Amp 70

10 (a) Lower ambient temperature °C -25


b) Upper ambient temperature °C 90
Max. conductor temp. under normal operating
11 °C 120°C
conditions
Max. conductor temp at the termination of short
12 °C 250°C for 5seconds
circuit

Solar DC Cable as per BS EN 50618 (H1Z2Z2-


13 Cable type and Applicable Standard (Cable Code)
K)

14 Recommended minimum bending radius in mm 8 - 10 times the overall diameter of the cable

“YEAR POLYCAB 1.5 KV DC SOLAR CABLE


'H1Z2Z2-K' CABLE SIZE EBXL TUV
15 Printing
RHEINLAND EN 50618:2014 CE WITH
SEQUENTIAL METER MARKING”
Note:-The values given above are subject to tolerances as per the relevant standards.
Document ID: TE/QMS/F/02
Rev. No. : 00 |Issued Date : 02/04/2018

Technical Data Sheet of Flexible Cables

Cable Code LDIS09CYUAY1003C2.5S


Sr.No. Description Unit 3C X 2.5 Sq.mm
1 Manufacturer Name Polycab India Limited
2 Brand Name POLYCAB
3 Rated Voltage Volts 1100
4 CONDUCTOR
Plain annealed high conductivity
a) Material Flexible copper conductor as per Class
5 of IS 8130/2013 latest
b) Conductor Size Sq.mm 2.5
Max. D.C Cond. Resistance at 20
c) Ohm/km 7.98
Deg. C.
d) Shape of Conductor Bunched Circular
5 INSULATION
a) Material PVC Type 'D'
b) Nominal Thickness in mm. mm 0.7
c) Core Identification Red, Black & Yellow/Green
6 Sheath
Extruded PVC Type 'ST3' as per
a) Material
IS:5831/84
b) Nominal Thickness in mm. mm 1.0
c) Sheath Colour Black
7 Maximum Overall Diameter mm 10.9
8 Current rating Amps 22
Max. conductor temp. under
9 °C 70
normal operating conditions
Max conductor temp at the
10 °C 160
termination of short circuit
Standards to which the cables As per IS 8130/2013,IS 694/2010,
11
confirm etc. with latest up to date amendments
Recommended minimum bending 8 times the overall diameter of the
12
radius in mm cable
Max. Tensile strength when
13 Kg 38
pulled with pulling eye
POLYCAB 1100 V
14 Printing
NO.OF CORE X SQ.MM
Note:-The values given above are subject to
tolerances as per the relevant standards.
Document ID: TE/QMS/F/02
Rev. No. : 01 | Issued Date : 10/06/2021

Technical Data of LT XLPE Cables

S.No Particulars 3 X 2.5


1 Name of Manufacturer Polycab India Ltd
2 Type of cable 2XWY
3 Voltage Grade (V) 1100
4 No of cores X size in sqmm 3 X 2.5
5 Conductor

a) Material Plain annealed Copper as per Class 2 of IS:8130, latest

b) Max. d.c. resistance of conductor at 20° C (ohm/km) 7.41


c) Shape of the conductor Stranded Circular
6 Insulation
a) Material Extruded XLPE as per IS 7098(Pt-1)/88, Latest
b) Nominal thickness (mm) 0.7
c) Core identification Red , Yellow & Blue
7 Inner Sheath
a) Material Extruded PVC Type 'ST2' as per IS:5831, Latest
b) Minimum thickness (mm) 0.3
c) Colour of Inner sheath. Black
8 Armouring
a) Material Galvanised Steel
b) Type of armouring Round Wire
c) Nominal size of armour (mm) 1.40
d) Tolerance on armour dimensions ± 0.040 mm
9 Outer Sheath
a) Material Extruded PVC Type 'ST2' as per IS:5831, Latest
b) Thickness (mm) 1.24 (Min.)
c) Colour of outer sheath. Black
10 Electrical Parameters
a) Max. a.c. resistance of conductor at 90° C (ohm/km) 9.45
b) Calculated Cable reactance (ohm/km) 0.0989
c) Impedance of cable (ohm/km) 9.45
d) Approx. Cable Capacitance (mfd/km) 0.21
Maximum conductor temperature under normal operating
11 90°C
conditions
Maximum conductor temperature at the termination of short
12 250°C
circuit

13 Short Circuit rating of conductor for the duration of 1 sec (kA) 0.36

Continuous Current carrying capacities for standard


14
conditions :-
(a) In Ground at 30°C (A) 34
(b) In Air at 40°C (A) 29
IS 7098 Part I/88, IS 8130, IS 5831, IS 3975 etc. with
15 Applicable Standard
latest up to date amendments
16 Approx. overall diameter of the cable in (mm) 13.5 ± 2 mm
17 Minimum bending radius 12 times Overall diameter
18 Max. Tensile strength
(i) for Cables pulled with stocking (Newtons) 9 x D², D is the cable OD in mm
ii) for Cables pulled with pulling eyes (N) 375
19 Embossing POLYCAB ELECTRIC 1100 VOLTS GRADE XLPE
YEAR POLYCAB ELECTRIC 1100 VOLTS GRADE XLPE
20 Printing CABLE SIZE CABLE TYPE WITH SEQUENTIAL MARKING
at every one meter interval.
21 Standard Drum Length (Mtr.) 1000 ± 5%
Maximum 5% of order quantity & Individual Non-standard
22 Non- Standard Drum Length (Mtr.)
drum length minimum 200m
Note:-The values given above are subject to tolerances as per the
relevant standards.
Incase of any Typographical error /Discrepancy, relevant standards
shall be prevailed.
Document ID: TE/QMS/F/02
Rev. No. : 01 | Issued Date : 10/06/2021

Technical Data of LT XLPE Cables

S.No Particulars 3X4


1 Name of Manufacturer Polycab India Ltd
2 Type of cable 2XWY
3 Voltage Grade (V) 1100
4 No of cores X size in sqmm 3X4
5 Conductor

a) Material Plain annealed Copper as per Class 2 of IS:8130, latest

b) Max. d.c. resistance of conductor at 20° C (ohm/km) 4.61


c) Shape of the conductor Stranded Circular
6 Insulation
a) Material Extruded XLPE as per IS 7098(Pt-1)/88, Latest
b) Nominal thickness (mm) 0.7
c) Core identification Red , Yellow & Blue
7 Inner Sheath
a) Material Extruded PVC Type 'ST2' as per IS:5831, Latest
b) Minimum thickness (mm) 0.3
c) Colour of Inner sheath. Black
8 Armouring
a) Material Galvanised Steel
b) Type of armouring Round Wire
c) Nominal size of armour (mm) 1.40
d) Tolerance on armour dimensions ± 0.040 mm
9 Outer Sheath
a) Material Extruded PVC Type 'ST2' as per IS:5831, Latest
b) Thickness (mm) 1.24 (Min.)
c) Colour of outer sheath. Black
10 Electrical Parameters
a) Max. a.c. resistance of conductor at 90° C (ohm/km) 5.88
b) Calculated Cable reactance (ohm/km) 0.0930
c) Impedance of cable (ohm/km) 5.88
d) Approx. Cable Capacitance (mfd/km) 0.25
Maximum conductor temperature under normal operating
11 90°C
conditions
Maximum conductor temperature at the termination of short
12 250°C
circuit

13 Short Circuit rating of conductor for the duration of 1 sec (kA) 0.57

Continuous Current carrying capacities for standard


14
conditions :-
(a) In Ground at 30°C (A) 45
(b) In Air at 40°C (A) 41
IS 7098 Part I/88, IS 8130, IS 5831, IS 3975 etc. with
15 Applicable Standard
latest up to date amendments
16 Approx. overall diameter of the cable in (mm) 15.0 ± 2 mm
17 Minimum bending radius 12 times Overall diameter
18 Max. Tensile strength
(i) for Cables pulled with stocking (Newtons) 9 x D², D is the cable OD in mm
ii) for Cables pulled with pulling eyes (N) 600
19 Embossing POLYCAB ELECTRIC 1100 VOLTS GRADE XLPE
YEAR POLYCAB ELECTRIC 1100 VOLTS GRADE XLPE
20 Printing CABLE SIZE CABLE TYPE WITH SEQUENTIAL MARKING
at every one meter interval.
21 Standard Drum Length (Mtr.) 1000 ± 5%
Maximum 5% of order quantity & Individual Non-standard
22 Non- Standard Drum Length (Mtr.)
drum length minimum 200m
Note:-The values given above are subject to tolerances as per the
relevant standards.
Incase of any Typographical error /Discrepancy, relevant standards
shall be prevailed.
Document ID: TE/QMS/F/02
Rev. No. : 01 | Issued Date : 10/06/2021

Technical Data of LT XLPE Cables

S.No Particulars 3 X 35
1 Name of Manufacturer Polycab India Ltd
2 Type of cable A2XFY
3 Voltage Grade (V) 1100
4 No of cores X size in sqmm 3 X 35
5 Conductor
a) Material H2/H4 Grade Aluminium as per Class 2 of IS: 8130, latest
b) Max. d.c. resistance of conductor at 20° C (ohm/km) 0.868
c) Shape of the conductor Stranded Compacted Sector
6 Insulation
a) Material Extruded XLPE as per IS 7098(Pt-1)/88, Latest
b) Nominal thickness (mm) 0.9
c) Core identification Red , Yellow & Blue
7 Inner Sheath
a) Material Extruded PVC Type ST2 as per IS:5831 ,Latest
b) Minimum thickness (mm) 0.3
c) Colour of Inner sheath. Black
8 Armouring
a) Material Galvanised Steel
b) Type of armouring Flat Strip
c) Nominal size of armour (mm) 4.0 x 0.8
d) Tolerance on armour dimensions ± 10%
9 Outer Sheath
a) Material Extruded PVC Type ST2 as per IS:5831 ,Latest
b) Thickness (mm) 1.40 (Min.)
c) Colour of outer sheath. Black
10 Electrical Parameters
a) Max. a.c. resistance of conductor at 90° C (ohm/km) 1.11
b) Calculated Cable reactance (ohm/km) 0.0787
c) Impedance of cable (ohm/km) 1.11
d) Approx. Cable Capacitance (mfd/km) 0.50
Maximum conductor temperature under normal operating
11 90°C
conditions
Maximum conductor temperature at the termination of short
12 250°C
circuit

13 Short Circuit rating of conductor for the duration of 1 sec (kA) 3.31

Continuous Current carrying capacities for standard


14
conditions :-
(a) In Ground at 30°C (A) 114
(b) In Air at 40°C (A) 114
IS 7098 Part I/88, IS 8130, IS 5831, IS 3975 etc. with
15 Applicable Standard
latest up to date amendments
16 Approx. overall diameter of the cable in (mm) 22.5 ± 2.0
17 Minimum bending radius 12 times Overall diameter
18 Max. Tensile strength
(i) for Cables pulled with stocking (Newtons) 9 x D², D is the cable OD in mm
ii) for Cables pulled with pulling eyes (N) 3,150
19 Embossing POLYCAB ELECTRIC 1100 VOLTS GRADE XLPE
YEAR POLYCAB ELECTRIC 1100 VOLTS GRADE XLPE
20 Printing CABLE SIZE CABLE TYPE WITH SEQUENTIAL MARKING
at every one meter interval.
21 Standard Drum Length (Mtr.) 1000 ± 5%
Maximum 5% of order quantity & Individual Non-standard
22 Non- Standard Drum Length (Mtr.)
drum length minimum 200m
Note:-The values given above are subject to tolerances as per the
relevant standards.
Incase of any Typographical error /Discrepancy, relevant standards
shall be prevailed.
Document ID: TE/QMS/F/02
Rev. No. : 01 | Issued Date : 10/06/2021

Technical Data of LT XLPE Cables

S.No Particulars 3 X 50
1 Name of Manufacturer Polycab India Ltd
2 Type of cable A2XFY
3 Voltage Grade (V) 1100
4 No of cores X size in sqmm 3 X 50
5 Conductor
a) Material H2/H4 Grade Aluminium as per Class 2 of IS: 8130, latest
b) Max. d.c. resistance of conductor at 20° C (ohm/km) 0.641
c) Shape of the conductor Stranded Compacted Sector
6 Insulation
a) Material Extruded XLPE as per IS 7098(Pt-1)/88, Latest
b) Nominal thickness (mm) 1.0
c) Core identification Red , Yellow & Blue
7 Inner Sheath
a) Material Extruded PVC Type ST2 as per IS:5831 ,Latest
b) Minimum thickness (mm) 0.3
c) Colour of Inner sheath. Black
8 Armouring
a) Material Galvanised Steel
b) Type of armouring Flat Strip
c) Nominal size of armour (mm) 4.0 x 0.8
d) Tolerance on armour dimensions ± 10%
9 Outer Sheath
a) Material Extruded PVC Type ST2 as per IS:5831 ,Latest
b) Thickness (mm) 1.40 (Min.)
c) Colour of outer sheath. Black
10 Electrical Parameters
a) Max. a.c. resistance of conductor at 90° C (ohm/km) 0.822
b) Calculated Cable reactance (ohm/km) 0.0780
c) Impedance of cable (ohm/km) 0.826
d) Approx. Cable Capacitance (mfd/km) 0.53
Maximum conductor temperature under normal operating
11 90°C
conditions
Maximum conductor temperature at the termination of short
12 250°C
circuit

13 Short Circuit rating of conductor for the duration of 1 sec (kA) 4.72

Continuous Current carrying capacities for standard


14
conditions :-
(a) In Ground at 30°C (A) 134
(b) In Air at 40°C (A) 138
IS 7098 Part I/88, IS 8130, IS 5831, IS 3975 etc. with
15 Applicable Standard
latest up to date amendments
16 Approx. overall diameter of the cable in (mm) 25.5 ± 2.0
17 Minimum bending radius 12 times Overall diameter
18 Max. Tensile strength
(i) for Cables pulled with stocking (Newtons) 9 x D², D is the cable OD in mm
ii) for Cables pulled with pulling eyes (N) 4,500
19 Embossing POLYCAB ELECTRIC 1100 VOLTS GRADE XLPE
YEAR POLYCAB ELECTRIC 1100 VOLTS GRADE XLPE
20 Printing CABLE SIZE CABLE TYPE WITH SEQUENTIAL MARKING
at every one meter interval.
21 Standard Drum Length (Mtr.) 1000 ± 5%
Maximum 5% of order quantity & Individual Non-standard
22 Non- Standard Drum Length (Mtr.)
drum length minimum 200m
Note:-The values given above are subject to tolerances as per the
relevant standards.
Incase of any Typographical error /Discrepancy, relevant standards
shall be prevailed.
Document ID: TE/QMS/F/02
Rev. No. : 01 Issued Date : 10/06/2021

Technical Data Sheet of 1.9/3.3 kV Single Core Cables

S.No Particulars 1 Core X 400 Sq.mm


1 Name of Manufacturer Polycab India Ltd
2 Type of cable A2XFaY
3 Voltage Grade kV 1.9/3.3 (E)
4 No of cores X size in sq.mm 1 Core X 400 Sq.mm
5 Conductor
H2/H4 Grade Aluminium as per Class 2 of IS:
a) Material
8130/2013,latest
Max. d.c. resistance of conductor at 20° C
b) 0.0778
(ohm/km)
c) Shape of the conductor Stranded Compacted Circular
6 Insulation
a) Material XLPE as per IS 7098(Pt-2)/2011
b) Nominal thickness (mm) 2.6
c) Core identification Natural
7 Armouring
a) Material Aluminium
b) Type of armouring Flat Strip
c) Nominal size of armour (mm) 4.0 x 0.8
d) Tolerance on armour dimensions ± 10%
8 Outer Sheath
a) Material Extruded FR-LSH PVC Type 'ST2' as per IS:5831/84
b) Thickness (mm) 1.56 (Min.)
c) Colour of outer sheath. Black
9 Electrical Parameters
Max. a.c. resistance of conductor at 90° C
a) 0.102
(ohm/km)
b) Calculated Cable reactance (ohm/km) 0.0879
c) Impedance of cable (ohm/km) 0.135
d Approx. Cable Capacitance (mfd/km) 0.68
Maximum conductor temperature under normal
10 90°C
operating conditions
Maximum conductor temperature at the
11 250°C
termination of short circuit
Short Circuit rating of conductor for the duration
12 37.79
of 1 sec (kA)
13 Continuous Current carrying capacities :-
(a) In Ground at 30°C (A) 412
(b) In Air at 40°C (A) 593
IS 7098 Part 2/2011, IS 8130/2013, IS 5831/84 etc. with
14 Applicable Standard
latest up to date amendments
15 Approx. overall diameter of the cable in mm 33.0 ± 3.0
16 Minimum bending radius 15 times Overall diameter
17 Max. Tensile strength
(i) for Cables pulled with stocking (Newtons) 9 x D², D is the cable OD in mm
(ii) for Cables pulled with pulling eyes (N) 12,000
18 Embossing POLYCAB ELECTRIC 1.9/3.3 KV (E) GRADE XLPE FR-LSH
YEAR POLYCAB ELECTRIC 1.9/3.3 KV (E) GRADE XLPE FR-
19 Printing LSH CABLE SIZE CABLE TYPE WITH SEQUENTIAL
MARKING at every one meter interval.
20 FR-LSH Properties
a) Oxygen Index Min. 29% as per ASTM D- 2863
b) Temperature Index Min. 250 Deg.C as per ASTM D- 2863
c) Smoke Density Rating Max. 60% as per ASTM D- 2843
d) Acid Gas Generation Max. 20% as per IEC- 754- 1
e) Flammability Test As per IEC:332-I
20 Standard Drum Length (Mtr.) 1000 ± 5%
5% of order quantity & Individual Non-standard drum length
21 Non- Standard Drum Length (Mtr.)
minimum 200 Mtrs
Note:-The values given above are subject to tolerances
as per the relevant standards.
Incase of any Typographical error /Discrepancy,
relevant standards shall be prevailed.
Document ID: TE/QMS/F/02
Rev. No. : 01 | Issued Date : 10/06/2021

Technical Data of LT XLPE Cables

S.No Particulars 12 Core X 2.5 SQ.MM


1 Name of Manufacturer Polycab India Ltd.
2 Type of cable 2XFY
3 Voltage Grade (V) 1100
4 No of cores X size in sqmm 12 Core X 2.5 SQ.MM
5 Conductor
a) Material Plain annealed Copper as per Class 2 of IS:8130/84
b) Max. d.c. resistance of conductor at 20° C (ohm/km) 7.41
c) Shape of the conductor Stranded Circular
6 Insulation
a) Material XLPE as per IS 7098(Pt-1)/88, Latest
b) Nominal thickness (mm) 0.7
c) Core identification All cores Grey with number printing
7 Inner Sheath
a) Material Extruded PVC Type ST2 as per IS:5831/84
b) Minimum thickness (mm) 0.3
c) Colour of Inner sheath. Black
8 Armouring
a) Material Galvanised Steel
b) Type of armouring Flat Strip
c) Nominal size of armour (mm) 4.0 x 0.8
d) Tolerance on armour dimensions ± 10%
9 Outer Sheath
a) Material Extruded PVC Type ST2 as per IS:5831/84
b) Thickness (mm) 1.40 (Min.)
c) Colour of outer sheath. Black
10 Electrical Parameters
a) Max. a.c. resistance of conductor at 90° C (ohm/km) 9.45
b) Calculated Cable reactance (ohm/km) 0.0989
c) Impedance of cable (ohm/km) 9.45
d) Approx. Cable Capacitance (mfd/km) 0.21
Maximum conductor temperature under normal operating
11 90°C
conditions
Maximum conductor temperature at the termination of short
12 250°C
circuit
13 Short Circuit rating of conductor for the duration of 1 sec (kA) 0.36
Continuous Current carrying capacities for standard
14
conditions :-
(a) In Ground at 30°C (A) 20
(b) In Air at 40°C (A) 18
IS 8130/2013,IS 7098 Part I/88, IS 5831/84, IS
15 Applicable Standard
3975/1999 etc. with latest up to date amendments
16 Approx. overall diameter of the cable in (mm) 20.0 ± 2.0
17 Minimum bending radius 12 times Overall diameter
18 Max. Tensile strength
(i) for Cables pulled with stocking (Newtons) 9 x D², D is the cable OD in mm
ii) for Cables pulled with pulling eyes (N) 1,500
19 Embossing POLYCAB ELECTRIC 1100 VOLTS GRADE XLPE
YEAR POLYCAB ELECTRIC 1100 VOLTS GRADE XLPE
20 Printing CABLE SIZE CABLE TYPE WITH SEQUENTIAL MARKING
at every one meter interval.
21 Standard Drum Length (Mtr.) 1000 ± 5%
Maximum 5% of order quantity & Individual Non standard
22 Non- Standard Drum Length (Mtr.)
drum length minimum 200
Note:-The values given above are subject to tolerances as per the
relevant standards.
Incase of any Typographical error /Discrepancy, relevant standards
shall be prevailed.
Document ID: TE/QMS/F/02
Rev. No. : 03 | Issued Date : 21/11/2023

Technical Data of LT XLPE Cables

S.No Particulars 4 Core X 10 Sq.mm


1 Name of Manufacturer Polycab India Ltd
2 Type of cable A2XFY
3 Voltage Grade (V) 1100
4 No of cores X size in sqmm 4 Core X 10 Sq.mm
5 Conductor
H2/H4 Grade Aluminium as per Class 2 of IS: 8130/2013,
a) Material
latest
b) Max. d.c. resistance of conductor at 20° C (ohm/km) 3.08
c) Shape of the conductor Stranded Circular
6 Insulation
a) Material XLPE as per IS 7098(Pt-1)/88, Latest
b) Nominal thickness (mm) 0.7
c) Core identification Red,Yellow,Blue,Black
7 Inner Sheath
a) Material Extruded PVC Type ST2 as per IS:5831 / 84
b) Minimum thickness (mm) 0.3
c) Colour of Inner sheath. Black
8 Armouring
a) Material Galvanised Steel
b) Type of armouring Flat Strip
c) Nominal size of armour (mm) 4.0 x 0.8
d) Tolerance on armour dimensions ± 10%
9 Outer Sheath
a) Material Extruded PVC Type 'ST2' as per IS:5831/ 84
b) Thickness (mm) 1.24 (Min.)
c) Colour of outer sheath. Black
10 Electrical Parameters
a) Max. a.c. resistance of conductor at 90° C (ohm/km) 3.95
b) Calculated Cable reactance (ohm/km) 0.0840
c) Impedance of cable (ohm/km) 3.95
d) Approx. Cable Capacitance (mfd/km) 0.36
Maximum conductor temperature under normal operating
11 90°C
conditions
Maximum conductor temperature at the termination of short
12 250°C
circuit
13 Short Circuit rating of conductor for the duration of 1 sec (kA) 0.94
Continuous Current carrying capacities for standard
14
conditions :-
(a) In Ground at 30°C (A) 57
(b) In Air at 40°C (A) 54
Gen. IS 7098 Part I/88, IS 8130/2013, IS 5831/84, IS
15 Applicable Standard
3975/1999 etc. with latest up to date amendments
16 Approx. overall diameter of the cable in (mm) 17.0 +/- 2.0
17 Minimum bending radius 12 times Overall diameter
18 Max. Tensile strength
(i) for Cables pulled with stocking (Newtons) 9 x D², D is the cable OD in mm
ii) for Cables pulled with pulling eyes (N) 1,200
19 Embossing POLYCAB ELECTRIC 1100 VOLTS GRADE XLPE
YEAR POLYCAB ELECTRIC 1100 VOLTS GRADE XLPE
20 Printing CABLE SIZE CABLE TYPE WITH SEQUENTIAL MARKING
at every one meter interval.
21 Standard Drum Length (Mtr.) 1000 Mtr. ±5%
Maximum 5% of order quantity and Individual Non-
22 Non- Standard Drum Length (Mtr.)
standard drum length minimum 200m.
Note:-The values given above are subject to tolerances as per the
ISI marking not Applicable
relevant standards.
Incase of any Typographical error /Discrepancy, relevant standards
shall be prevailed.
Document ID: TE/QMS/F/02
Rev. No. : 03 Issued Date : 21/11/2023

Technical Data Sheet of Flexible Cables

Sr.No. Description Unit 1C X 2.5 Sq.mm


1 Manufacturer Name Polycab India Limited
2 Brand Name POLYCAB
3 Rated Voltage Volts 1100
4 CONDUCTOR
Plain annealed high conductivity Flexible
a) Material copper conductor as per Class 5 of IS
8130/2013 latest
b) Conductor Size Sq.mm 2.5
Max. D.C Cond. Resistance at 20
c) Ohm/km 7.98
Deg. C.
d) Shape of Conductor Bunched Circular
5 INSULATION
a) Material PVC Type 'D'
b) Thickness - Nominal mm 0.7
c) Core Identification Green
6 Maximum Overall Diameter mm 4.1
0
7 Current rating at 40 C Amps 22
Max. conductor temp. under
8 °C 70
normal operating conditions
Max conductor temp at the
9 °C 160
termination of short circuit
Standards to which the cables As per IS 8130/2013,IS 694/2010, etc.
10
confirm with latest up to date amendments
Recommended minimum bending
11 8 times the overall diameter of the cable
radius in mm
Max. Tensile strength when
12 Kg 13
pulled with pulling eye

13 Printing POLYCAB 1100 V SQ.MM

Note:-The values given above are subject to


tolerances as per the relevant standards.

TDS-17-121224-159384
Document ID: TE/QMS/F/02
Rev. No. : 03 Issued Date : 21/11/2023

Technical Data Sheet of Flexible Cables

Sr.No. Description Unit 1C X 16 Sq.mm


1 Manufacturer Name Polycab India Limited
2 Brand Name POLYCAB
3 Rated Voltage Volts 1100
4 CONDUCTOR
Plain annealed high conductivity
a) Material Flexible copper conductor as per Class
5 of IS 8130/2013 latest
b) Conductor Size Sq.mm 16
Max. D.C Cond. Resistance at 20
c) Ohm/km 1.21
Deg. C.
d) Shape of Conductor Bunched Circular
5 INSULATION
a) Material PVC Type 'D'
b) Thickness - Nominal mm 1.0
c) Core Identification Green
6 Maximum Overall Diameter mm 8.1
0
7 Current rating at 40 C Amps 68
Max. conductor temp. under
8 °C 70
normal operating conditions
Max conductor temp at the
9 °C 160
termination of short circuit
Standards to which the cables As per IS 8130/2013,IS 694/2010, etc.
10
confirm with latest up to date amendments
Recommended minimum bending
11 8 times the overall diameter of the cable
radius in mm
Max. Tensile strength when
12 Kg 82
pulled with pulling eye

13 Printing POLYCAB 1100 V SQ.MM

Note:-The values given above are subject to


tolerances as per the relevant standards.

TDS-17-121224-159384
Document ID: TE/QMS/F/02
Rev. No. : 01 Issued Date : 10/06/2021

Technical Data Sheet of 1.9/3.3 kV Single Core Cables

S.No Particulars 1 Core X 400 Sq.mm


1 Name of Manufacturer Polycab India Ltd
2 Type of cable A2XFaY
3 Voltage Grade kV 1.9/3.3 (E)
4 No of cores X size in sq.mm 1 Core X 400 Sq.mm
5 Conductor
H2/H4 Grade Aluminium as per Class 2 of IS:
a) Material
8130/2013,latest
Max. d.c. resistance of conductor at 20° C
b) 0.0778
(ohm/km)
c) Shape of the conductor Stranded Compacted Circular
6 Insulation
a) Material XLPE as per IS 7098(Pt-2)/2011
b) Nominal thickness (mm) 2.6
c) Core identification Natural
7 Armouring
a) Material Aluminium
b) Type of armouring Flat Strip
c) Nominal size of armour (mm) 4.0 x 0.8
d) Tolerance on armour dimensions ± 10%
8 Outer Sheath
a) Material Extruded FR-LSH PVC Type 'ST2' as per IS:5831/84
b) Thickness (mm) 1.56 (Min.)
c) Colour of outer sheath. Black with Red strip
9 Electrical Parameters
Max. a.c. resistance of conductor at 90° C
a) 0.102
(ohm/km)
b) Calculated Cable reactance (ohm/km) 0.0879
c) Impedance of cable (ohm/km) 0.135
d Approx. Cable Capacitance (mfd/km) 0.68
Maximum conductor temperature under normal
10 90°C
operating conditions
Maximum conductor temperature at the
11 250°C
termination of short circuit
Short Circuit rating of conductor for the duration
12 37.79
of 1 sec (kA)
13 Continuous Current carrying capacities :-
(a) In Ground at 30°C (A) 412
(b) In Air at 40°C (A) 593
IS 7098 Part 2/2011, IS 8130/2013, IS 5831/84 etc. with
14 Applicable Standard
latest up to date amendments
15 Approx. overall diameter of the cable in mm 33.0 ± 3.0
16 Minimum bending radius 15 times Overall diameter
17 Max. Tensile strength
(i) for Cables pulled with stocking (Newtons) 9 x D², D is the cable OD in mm
(ii) for Cables pulled with pulling eyes (N) 12,000
18 Embossing POLYCAB ELECTRIC 1.9/3.3 KV (E) GRADE XLPE FR-LSH
YEAR POLYCAB ELECTRIC 1.9/3.3 KV (E) GRADE XLPE FR-
19 Printing LSH CABLE SIZE CABLE TYPE WITH SEQUENTIAL
MARKING at every one meter interval.
20 FR-LSH Properties
a) Oxygen Index Min. 29% as per ASTM D- 2863
b) Temperature Index Min. 250 Deg.C as per ASTM D- 2863
c) Smoke Density Rating Max. 60% as per ASTM D- 2843
d) Acid Gas Generation Max. 20% as per IEC- 754- 1
e) Flammability Test As per IEC:332-I
20 Standard Drum Length (Mtr.) 1000 ± 5%
5% of order quantity & Individual Non-standard drum length
21 Non- Standard Drum Length (Mtr.)
minimum 200 Mtrs
Note:-The values given above are subject to tolerances
as per the relevant standards.
Incase of any Typographical error /Discrepancy,
relevant standards shall be prevailed.

You might also like