1 General 1-1
3 General operation
The decentralized architecture of the ABB As an example the central unit may be connected to
Procontic CS 31 system offers a superior solution to remote units distributed along a process line.
control system requirements:
A cost reduction in wiring is possible upto 80% with the
– The central unit can be mounted within the control implementation of the CS 31 system.
panel.
– The input/output units can be mounted local to the
sensors and actuators.
LY
T
PP
N
INPU
RU
SU
62,00 01 02 03 04 05 06 07 08 09 10 11
T
PU
OUT
07KR31 24VDC 5W
CENTRAL UNIT ABB Procontic CS 31
RUN
COM 1
STOP
Central Unit
07 KR 91
RS 485
(twisted pair)
I/O unit
07 KR 31 slave CPU
C 228
as intelligent I/O unit
Example of configuration
for simple process
with intelligent I/O units
"Master" CPU
07 KR 31
RS 485
(twisted pair)
I/O Unit
07 KR 31 slave CPU
C 228
Plug-in base
ECZ Plug-in base for I/O units 07 KR 31/07 KT 31 FPR 370 0001 R0001
DIN rail or screw fixing
07 KP 90 CS 31 RCOM coupler
used with 07 KT 92, 07 KR 91 R 0252, 07 KT 93
1 serial interface EIA RS232
24 VDC power supply GJR 525 1000 R0202
07 KP 92 CS 31 coupler
used with 07 KT 92, 07 KR 91 R 0252, 07 KT 93
Freely programmable in C language, stored in flash EPROM
2 serial interfaces EIA R232, EJA RS422 or EIA RS485
24 VDC power supply GJR 525 1500 R101
Cable Sub D9 For programming and test FPTN 404 948 R0002
Cable Sub D25 For programming and test FPTN 404 948 R0005
Cable Sub D9 For ASCII or MODBUS communication FPTN 404 948 R0006
Cable Sub D25 For ASCII or MODBUS communication FPTN 404 948 R0001
Spare parts
5V battery for external power supply of TCZ FPTN 404 949 R0003
● Serial interfaces
● Insulation test voltages
– for connection of the RS485,
central unit to using screw terminals the insulation test voltages
the remote units are according to IEC 1131-2
– radiated electromagnetic
field immunity test according to
IEC 1000-4-3
field strength 10 V/m
(severity level 3)
frequency range 27 MHz to 1000 MHz
sweep speed 1.5 x 10E-3
decade/s
3.1 CPU communication with remote units 3.2 Addressing of the remote units
Communication between the central units and the remote All system bus request telegrams have an address. The
units requires no user intervention as it is carried out by a remote unit which has the same address as the telegram
dedicated serial interface. receives and responds to the data.
The dual port RAM of the central unit enables data transfer The address of the remote unit is set using the DIL
between the user program processor and the dedicated switches of the plug-in base.
serial interface.
The inputs and outputs have the following address
structure: yy, xx
Twisted pair The I/O channels are simply addressed from 03, 00 to
bus (RS 485) 03, 07 within the user program of the central unit, as
though they were centralized.
Remote Remote
unit unit 3.3 System bus
C 223 D
Similarly, data is transfered from the dual port RAM to the Isolation opto-couplers
remote units via the dedicated serial interface and bus for
the write cycle. Material twisted pair
C 002 D
● Installation of the bus
correct wiring
The CS 31 bus is a RS 485 serial line and a schield
twisted pair.
The CS 31 bus is a master slave bus. Only one master
can be present on the bus.
The maximum length between the both extremities is
500 metres.
The master should be :
C 003 D
– a central unit : 07 KR 31, 07 KT 31, 07 KR 91,
wrong wiring
07 KT 92, 07 KT 93, PCZB, UCZA/UCZB
– a PLC coupler : 07 CS 61 and 07 CS 91 for the ABB
Procontic T 200 and T 300
– a PC board : 07 CM 90 "Star connection of the bus is forbidden !"
● Characteristics of the bus' cable
The CS 31 bus is a shield twisted pair RS 485
Master Remote Remote Remote
– cross 0.22 ... 0.8 mm2 central unit unit unit unit
– twists > 10 per metre
– resistance 100/km 07 KR 31
PCZB
– impedance UCZA/UCZB
– characteristics 100 to 150
07 KR 91/07 KT 92/93 Remote Remote
07 CM 90 unit unit
– capacitance < 150 nF/km 35 CS 91
07 CS 61 C 004 GB/D
– schield
– termination 120 , 1/4 Watt resistor allowed wiring
connected at the ends of the
bus
forbidden wiring
correct wrong
120 Ω 120 Ω
1/4 W 1/4 W
1 2 3 1 2 3 1 2 3
Remote Remote
ld
ld
ld
2
1
Master
ie
ie
ie
s
s
bu
bu
bu
bu
bu
bu
sh
sh
sh
unit unit
18 18 18
C 006 GB/D
The bus must be terminated with a 120 , 1/4 Watt resistor, this must be connected at the ends of the bus.
The central units UCZA/UCZB, the couplers 07 CS 61 and 35 CS 91 have to be connected at an end of the bus.
The resistor 120 is integrated.
The other central units and the PC board should be connected everywhere on the bus.
The shield of the bus must be connected to the earth near the master.
120 Ω 120 Ω
1/4 W 1/4 W
1 2 3 1 2 3 1 2 3
Remote Remote
ld
ld
ld
2
1
2
1
2
1
Master
ie
ie
ie
s
s
s
s
s
s
bu
bu
bu
bu
bu
bu
sh
sh
sh
unit unit
18 18 18
C 104 GB/D
When noisy elements are in the area of the cabinet, it is better to connect the bus' shield to the ground via a capacitor
1 nF class Y directly at the access of the cabinet according the following diagram.
1 nF 1 2 3
class Y Remote
ld
2
1
ie
s
s
bu
bu
sh
unit
18
C 105 GB/D
common +
common –
When the remote units are outside the cabinet, they N = Neutral
must be connected to the nearest earth. ICSK 20 F1
The connection to the earth has to be as short as
161718192021 282930
possible (shorter than 25 cm).
L1
N Valve
24VDC
Valve
230VAC
+
230VAC/24VDC
C 0010 GB/D
–
ON
12345678
16 17 18
1 2 3 1 2 3
Master Remote
unit
L1 = phase 9
N = Neutral
The capacitor is integrated in the plug-in base.
ICSK 20 F1
When the cabinets are close from each others, the
161718192021 28
different earths have to be connected together with a
230VAC/24VDC
cable with a cross section of at least 16 mm2.
L1 +
N – Valve
230VAC
Valve
24VDC
C 009 GB/ D
noisy element HT L1
L2
L3
Cabinet Cabinet M
1 2 N
Impedance
Z = 1000 Ω
C 103 GB/D
advised connection
C 015 GB/D
unit is in an other cabinet
noisy elements
earth
C 012 GB/D
to avoid
HT L1
L2
L3
N
Unit 1 Unit 2
One single CPU is the master on the bus, all of the other The refresh time depends on the configuration of the
remote units or CPU are considered to be slaves. system, number and type of remote units.
The master CPU manages up to a maximum of 31 remote
units on one bus. The example below is for a system of remote units type
All messages are terminated with an error check (CRC8). ICSC 08 L1.
C 226 D
During initialization, the central unit interrogates all of the
remote units in succession, thus building an image of the The user program and the bus refresh cycle are executed
system configuration. in serie with the 07 KR/KT 31, 07 KR 91 and 07 KT 92/93
central units. The time event diagram is shown below :
On each cycle of the bus all of the remote units are
interrogated.
External
evenement
This updates all diagnosis information and recognizes Reading
of input
additional remote units.
Input delay: 2 to 32 ms
Bus
If the CPU or one of the remote units receives a message transmission
with a (CRC8) error, it is ignored. 1.5 to 12 ms (binary module)
After ten consecutive transmission errors, an error "Bus Program
execution
error" is generated on the remote units and within the Max. 2 cycles
programmed
diagnostics of the central unit. Bus
transmission
C 227
1.5 to 12 ms (binary module)
ICSI 08 D1 323 µs
ICSI 08 E1 323 µs
ICSI 08 E3/E4 323 µs
ICSI 16 D1 387 µs
ICSI 16 E1 387 µs
ICSO 08 R1 260 µs
ICSO 08 Y1 260 µs
ISCO 16 N1 340 µs
ICSC 08 L1 387 µs
ICFC 16 L1 516 µs
ICSK 20 F1 452 µs
ICSK 20 N1 452 µs
ICDG 32 L1 516/590 µs
following the configuration
ICPI 08 D1 323 µs
ICPI 16 D1 387 µs
ICPO 08 H1 260 µs
ICPO 16 H1 340 µs
with :
– T offset = 2 000 µs
– T communication time : see table
– n = number of slaves on the bus
Example of calculation
Configuration :
1 "Master" CPU ......... 2 000 µs
1 ICSK 20 F1 ................ 452 µs
1 ICSO 08 R1 ............... 260 µs
1 ICSI 16 E1 ................. 387 µs
1 ICFC 16 L1 ................ 516 µs
1 ICSC 08 L1 ................ 387 µs