Galaxy 7000

250–500 kVA 380/400/415 V UPS


Technical Specifications

03/2018

www.schneider-electric.com
Legal Information
The Schneider Electric brand and any registered trademarks of Schneider Electric
Industries SAS referred to in this guide are the sole property of Schneider Electric
SA and its subsidiaries. They may not be used for any purpose without the owner's
permission, given in writing. This guide and its content are protected, within the
meaning of the French intellectual property code (Code de la propriété
intellectuelle français, referred to hereafter as "the Code"), under the laws of
copyright covering texts, drawings and models, as well as by trademark law. You
agree not to reproduce, other than for your own personal, noncommercial use as
defined in the Code, all or part of this guide on any medium whatsoever without
Schneider Electric's permission, given in writing. You also agree not to establish
any hypertext links to this guide or its content. Schneider Electric does not grant
any right or license for the personal and noncommercial use of the guide or its
content, except for a non-exclusive license to consult it on an "as is" basis, at your
own risk. All other rights are reserved.
Electrical equipment should be installed, operated, serviced, and maintained only
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
As standards, specifications, and designs change from time to time, please ask for
confirmation of the information given in this publication.
250–500 kVA 380/400/415 V UPS

Table of Contents
Important Safety Instructions — SAVE THESE
INSTRUCTIONS .........................................................................................5
Safety Precautions .....................................................................................6
Technical Data .............................................................................................8
Model list ...................................................................................................8
Input Power Factor .....................................................................................8
Efficiency ...................................................................................................8
Efficiency Curves ..................................................................................9
Derating due to Load Power Factor ............................................................10
Batteries ..................................................................................................10
Efficiency DC to AC.............................................................................10
End of Discharge Voltage .................................................................... 11
Compliance.............................................................................................. 11
Facility Planning ........................................................................................12
Input Specifications ..................................................................................12
Bypass Specifications ...............................................................................12
Output Specifications ................................................................................12
Battery Specifications ...............................................................................13
End of Discharge Current ....................................................................13
Recommended Cable Sizes ......................................................................13
Power Cables for Single UPS ..............................................................13
Power Cables for Parallel UPSs ...........................................................14
Connection Terminals..........................................................................16
Recommended Overcurrent Protection ......................................................16
Recommended Upstream and Downstream Protection ..........................16
Recommended Residual Current Protection .........................................18
Battery Breaker Box Configurations......................................................18
Environmental ..........................................................................................20
Heat Dissipation .................................................................................20
Weights and Dimensions...........................................................................20
Shipping Weights and Dimensions.............................................................20
Clearance ................................................................................................21
Default settings ........................................................................................22
Drawings ....................................................................................................23
Galaxy 7000 Single System.......................................................................24
Galaxy 7000 Single System with Transformer .............................................25
Options .......................................................................................................26
Hardware Options.....................................................................................26
Configuration Options ...............................................................................27
Parallel Capabilities ..................................................................................27
Limited Factory Warranty .........................................................................30

990–3887C-001 3
Important Safety Instructions — SAVE THESE
INSTRUCTIONS 250–500 kVA 380/400/415 V UPS

Important Safety Instructions — SAVE THESE


INSTRUCTIONS
Read these instructions carefully and look at the equipment to become familiar with
it before trying to install, operate, service or maintain it. The following safety
messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or simplifies a
procedure.

The addition of this symbol to a “Danger” or “Warning” safety


message indicates that an electrical hazard exists which will result in
personal injury if the instructions are not followed.

This is the safety alert symbol. It is used to alert you to potential


personal injury hazards. Obey all safety messages with this symbol
to avoid possible injury or death.

DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.

WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment
damage.

NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.

Please Note
Electrical equipment should only be installed, operated, serviced, and maintained
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.

990–3887C-001 5
Important Safety Instructions — SAVE THESE
250–500 kVA 380/400/415 V UPS INSTRUCTIONS

Safety Precautions

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• The product must be installed according to the specifications and
requirements as defined by Schneider Electric. It concerns in particular the
external and internal protections (upstream circuit breakers, battery circuit
breakers, cabling, etc.) and environmental requirements. No responsibility is
assumed by Schneider Electric if these requirements are not respected.
• After the UPS system has been electrically wired, do not start up the system.
Start-up must only be performed by Schneider Electric.
Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS System must be installed according to local and national regulations.
Install the UPS according to:
• IEC 60364 (including 60364–4–41- protection against electric shock, 60364–
4–42 - protection against thermal effect, and 60364–4–43 - protection against
overcurrent), or
• NEC NFPA 70
depending on which one of the standards apply in your local area.
Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Install the UPS system in a temperature controlled area free of conductive
contaminants and humidity.
• Install the UPS system on a non-inflammable, level, and solid surface (e.g.
concrete) that can support the weight of the system.
Failure to follow these instructions will result in death or serious injury.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS is not designed for and must therefore not be installed in the following
unusual operating environments:
• Damaging fumes
• Explosive mixtures of dust or gases, corrosive gases, or conductive or radiant
heat from other sources
• Moisture, abrasive dust, steam or in an excessively damp environment
• Fungus, insects, vermin
• Salt-laden air or contaminated cooling refrigerant
• Pollution degree higher than 2 according to IEC 60664-1
• Exposure to abnormal vibrations, shocks, and tilting
• Exposure to direct sunlight, heat sources, or strong electromagnetic fields
Failure to follow these instructions will result in death or serious injury.

6 990–3887C-001
Important Safety Instructions — SAVE THESE
INSTRUCTIONS 250–500 kVA 380/400/415 V UPS

NOTICE
RISK OF OVERHEATING
Respect the clearance requirements around the UPS system and do not cover
the product’s ventilation openings when the UPS system is in operation.
Failure to follow these instructions can result in equipment damage.

NOTICE
RISK OF EQUIPMENT DAMAGE
Do not connect the UPS output to regenerative load systems including
photovoltaic systems and speed drives.
Failure to follow these instructions can result in equipment damage.

990–3887C-001 7
250–500 kVA 380/400/415 V UPS Technical Data

Technical Data
Model list
The Galaxy 7000 UPS is available in the following models:
• Galaxy 7000 250 kVA 380/400/415 V
• Galaxy 7000 300 kVA 380/400/415 V
• Galaxy 7000 400 kVA 380/400/415 V
• Galaxy 7000 500 kVA 380/400/415 V

Input Power Factor


For linear and non-linear load
Load 25% 50% 75% 100%
Power Factor ≥ 0.95 > 0.99 > 0.99 > 0.99

Efficiency
The table below provides average system efficiencies on a double conversion
single unit with a balanced linear load, PF 0.9, AC input voltage 400 V / AC output
voltage 400 V.
Efficiency on load PF 0.8 or for other input or output AC voltages is very close to
the values given below for PF 0.9, voltage input / 400 V output. Difference is less
than + / -0.2%.
Minimum system efficiency is very close to average system efficiency. The
difference is 0.2% maximum.
All these measures are coming from the production line ATE statistics performed
on over 200 units.

System 25% load 50% load 75% load 100% load

250 kVA 89.7 93.2 93.8 93.8


300 kVA 90.5 93.5 93.9 93.6
400 kVA 92.2 94.1 94.3 94.1

500 kVA 91.4 94.3 94.5 94.3

8 990–3887C-001
Technical Data 250–500 kVA 380/400/415 V UPS

Efficiency Curves
250 kVA 400 V

300 kVA 400 V

400 kVA 400 V

990–3887C-001 9
250–500 kVA 380/400/415 V UPS Technical Data

500 kVA 400 V

Derating due to Load Power Factor

Batteries
Efficiency DC to AC
Efficiency in Battery Mode

Efficiency during discharge (output voltage 380 V or 400 V, inductive load PF 0.8 or
0.9 )

% load 250 kVA 300 kVA 400 kVA 500 kVA

25 90.2 91.0 92.7 91.9


50 93.7 94.0 94.6 94.8
75 94.3 94.4 94.8 95.0
100 94.3 94.1 94.6 94.8

10 990–3887C-001
Technical Data 250–500 kVA 380/400/415 V UPS

DC Power in kW — PF 0.8

% load 250 kVA 300 kVA 400 kVA 500 kVA

25 55.4 65.9 86.3 108.8


50 106.7 127.6 169.1 211.0
75 159.1 190.7 253.2 315.8
100 212.1 255.0 338.3 422.0

DC Power in kW — PF 0.9

% load 250 kVA 300 kVA 400 kVA 500 kVA

25 62.3 74.1 97.1 122.4


50 120.0 143.6 190.2 237.4
75 179.0 214.5 284.9 355.3
100 238.6 286.9 380.6 474.8

End of Discharge Voltage

I batt(A) = battery current at the beginning of discharge. C10(Ah)= battery capacity


in 10 hours
Between 0.1 <alpha<0.97, equation of battery shutdown voltage level is : U batt
mini(V/ cell) = (- 0.3x alpha) + 1.93
Example alpha = 0.5 Ubatt mini = 1.78V/ cell

Compliance
Directives for CE marking

Low voltage directive 2006/95/CEE

EMC directive 2004/108/CEE


Safety standard of UPS CEI/EN 62040-1 edition 2008/2008

EMC standard of UPS CEI/EN 62040–2 edition 2005/2006

Declaration of conformity with UPS harmonised standards and directives IEC


62040-1 (Safety) and IEC 62040-2 (EMC) are available on demand.

990–3887C-001 11
250–500 kVA 380/400/415 V UPS Facility Planning

Facility Planning
Input Specifications
250 kVA 300 kVA 400 kVA 500 kVA

Voltage (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440

Nominal input 369 351 337 319 441 420 403 382 586 558 536 507 735 700 672 636
current (A)1

Connections L1, L2, L3

Frequency (Hz) 45 to 66

Total Harmonic < 5% at full load


Distortion (THDI)

Input power factor > 0.99 at load > 50%


correction

Bypass Specifications
250 kVA 300 kVA 400 kVA 500 kVA

380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440

Nominal input 379 361 347 328 455 433 417 393 607 577 556 524 759 722 695 656
current (A)

Connections 4-wire (L1, L2, L3 + N + PE)

Frequency (Hz) 45 to 66

Output Specifications
250 kVA 300 kVA 400 kVA 500 kVA

Voltage (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440

Nominal output 379 361 347 328 455 433 417 393 607 577 556 524 759 722 695 656
current (A)

Connections 4-wire (L1, L2, L3 + N + PE)

Output capacity 150% for 30 seconds (normal operation)


125% for 10 minutes (normal operation)

Output frequency 50/60 ± 0.1


(sync to mains)
(Hz)

Slew rate (Hz/ 2


Sec)

Total Harmonic < 2% ph/ph


Distortion (THDU)

Output power 0.9


factor
Dynamic load ± 1%
response

Output voltage ± 1%
regulation

Crest factor 2.7 2.9 3.0 3.3 2.3 2.4 2.5 2.8 2.3 2.4 2.5 2.8 2.6 2.7 2.8 3.0

1. For 400 V interphase voltages and a load with a power factor of 0.9.

12 990–3887C-001
Facility Planning 250–500 kVA 380/400/415 V UPS

Battery Specifications
Type Sealed lead-acid Vented lead-acid Ni-Cad

Min./Max. number of cells 264 / 288 264 / 288 422 / 468


Floating voltage per cell (V) 2.27 2.2 1.4

Min./Max. floating voltage (V) 600 / 654 581 / 634 600 / 655

Equalising voltage per cell (V) Not applicable 2.4 1.5

Boost voltage per cell (V) Not applicable 2.25 1.45

Min. voltage per cell (V) 1.65 to 1.9 1.65 to 1.9 1

Recharge current 0.1 x C10 0.1 x C10 0.2 C5

End of Discharge Current

Sealed lead-acid Vented lead-acid Ni-Cad


250 kVA 548/502 548/502 566/509
300 kVA 659/604 659/604 680/612
400 kVA 874/801 874/801 902/812
500 kVA 1090/999 1090/999 1125/1012

NOTE: The battery current is an average current Pn with a power factor of 0.9

Recommended Cable Sizes


Power Cables for Single UPS
AC cable sizes are determined for the TNS system and for the following cable
characteristics:
• copper single-core cables, type U1000 R02V
• maximum length 100 m with a line voltage drop <3%
• installation on perforated cable trays
• XLPE-type insulation, single-layer trefoil formation
• THDI between 15% and 33%
• 35°C, at 400 V
• grouped by four cables.
Battery cable sizes are determined for:
• installation on perforated metallic grounded cable trays,
• copper, single-core cables, type U1000 R02V,
• maximum length 25 m with a line voltage drop <1%.

UPS rating Minimum size (mm²)

Normal AC line Bypass AC line Load Battery

250 kVA 1 x 150 1 x 150 1 x 150 1 x 150


300 kVA 1 x 240 1 x 240 1 x 240 1 x 185
400 kVA 2 x 150 2 x 150 2 x 150 1 x 240
500 kVA 2 x 240 2 x 240 2 x 240 2 x 1502

2. Per battery cabinet.

990–3887C-001 13
250–500 kVA 380/400/415 V UPS Facility Planning

Power Cables for Parallel UPSs


Normal AC Line and Battery

AC cable sizes are determined for the TNS system and for the following cable
characteristics:
• copper single-core cables, type U1000 R02V
• maximum length 100 m with a line voltage drop <3%
• installation on perforated cable trays
• XLPE-type insulation, single-layer trefoil formation
• THDI between 15% and 33%
• 35°C, at 400 V
• grouped by four cables.
Battery cable sizes are determined for:
• installation on perforated metallic grounded cable trays,
• copper, single-core cables, type U1000 R02V,
• maximum length 25 m with a line voltage drop <1%.
NOTE: Important: For > 200 kVA UPS, the output cables must be at least 6
metres long (L ≥ 6 m).

UPS rating Minimum size (mm²)

Normal AC line Battery

250 kVA 1 x 150 1 x 150


300 kVA 1 x 240 1 x 185
400 kVA 2 x 150 1 x 240
500 kVA 2 x 240 2 x 1503

Bypass AC Line and Load

UPS rating Number of UPSs Total power rating Current on AC bypass Minimum size for AC
(kVA) or load (A) bypass or load (mm²)

250 kVA 2 250 361 1 x 150


300 kVA 2 300 433 1 x 240
400 kVA 2 400 577 2 x 150
500 kVA 2 500 722 2 x 240

Frequency Converters

UPS rating Number of UPSs Total power rating Current on AC bypass Minimum size for load
(kVA) or load (A) (mm²)

250 kVA 2 250 361 1 x 150


300 kVA 2 300 433 1 x 240
400 kVA 2 400 577 2 x 150
500 kVA 2 500 722 2 x 240

NOTE: The power cables between the UPS units and the upstream protective
devices must be of the same size and length.
NOTE: The power cables between the UPS units and the load must be of the
same size and length.

3. Per battery cabinet.

14 990–3887C-001
Facility Planning 250–500 kVA 380/400/415 V UPS

Integrated Parallel UPS Units with External Bypass Cabinet

UPS rating Number of Total power Current on AC bypass or load (A) Minimum size for load (mm²)
UPSs rating (kVA)4

250 kVA 2 500 722 2 x 185


3 750 1083 3 x 300
4 1000 1443 4 x 240
300 kVA 2 600 866 2 x 240
3 900 1300 4 x 240
4 1200 1732 4 x 300
400 kVA 2 400 1154 4 x 185
3 1200 1732 4 x 300
4 1600 2308 4 x 500
500 kVA 2 500 1433 4 x 240
3 1500 2165 4 x 500
4 2000 2886 Consult us5

NOTE: The power cables between the UPS units and the upstream protective
devices must be of the same size and length.
NOTE: The power cables between the UPS units and the load must be of the
same size and length.

Parallel UPS Units with Static-Switch Cabinet (SSC)

UPS rating Number Total power Current on AC bypass or load (A) Minimum size for load (mm²)
of UPS rating4 (kVA)

250 kVA 2 500 722 2 x 185


3 750 1083 3 x 300
4 1000 1443 4 x 240
300 kVA 2 600 866 2 x 240
3 900 1300 4 x 240
4 1200 1732 4 x 300
400 kVA 2 400 1154 4 x 185
3 1200 1732 4 x 300
4 1600 2308 4 x 500
500 kVA 2 500 1433 4 x 240
3 1500 2165 4 x 500
4 2000 2886 Consult us5

NOTE: The power cables between the UPS units and the upstream protective
devices must be of the same size and length.
NOTE: The power cables between the UPS units and the load must be of the
same size and length.

4. Not including redundant UPS units.


5. Standard NFC15–100 limits the number of cables to four.

990–3887C-001 15
250–500 kVA 380/400/415 V UPS Facility Planning

Connection Terminals
UPS Cabinets

Phase terminal Earth terminal Battery terminal

UPS rating Type of stud Number of holes x diameter (mm)

250 — 400 kVA 2 x M106 1 x 10 5 x 13 3 x 13


500 kVA N/A 4 x 13 5 x 13 3 x 13

SSC, SSC Maintenance, External Bypass Cabinets

Cabinets Phase terminal Earth terminal


Hole diameter (mm)

800 kVA 13 13
1200 kVA 13 13
2000 kVA 13 and 17 13

Recommended Overcurrent Protection


Recommended Upstream and Downstream Protection
Selection of Protection Devices

Time/current Curves for UPS input and Output Fuses

6. Maximum tightening torque 25 Nm.

16 990–3887C-001
Facility Planning 250–500 kVA 380/400/415 V UPS

UPS Output Current

UPS 250 kVA 300 kVA 400 kVA 500 kVA


In at 400 V (A) 361 433 577 722

Ioutput maximum7 (A) 1030 1030 1374 1975

Ioutput minimum7 (A) 793 793 1140 1470

Line-current Values

UPS 250 kVA 300 kVA 400 kVA 500 kVA


Continuous input current (A) 368 442 587 735

Input current at 1.25 In overload limited to 10 minutes 441 530 706 881
(A)

Input current at 1.5 In overload limited to 30 seconds 530 636 848 1058
(A)

Input / output fuse ratings (A) 630 630 800 1000

For U=400V and power factor=0.9.

Power Circuit Protection

UPS 250 kVA 300 kVA 400 kVA 500 kVA


CB Trip Unit CB Trip Unit CB Trip Unit CB Trip Unit

Normal AC NSX 630N Micrologic NSX 630N Micrologic NS 800N 3P Micrologic NS 800N 3P Micrologic
source 3P 2.3 3P 2.3 2.0 5.0
Bypass AC NSX 630N Micrologic NSX 630N Micrologic NS 800N 4P Micrologic NS 800N 4P Micrologic
source 4P 2.3 4P 2.3 2.0 5.0

Output NSX 100 N TM D 80 NSX 100 N TM D 80 NSX 100 N TM D 100 C125N D 125
C120N C80 C120N C80 NG 125N C 125 NSX 160N TM 160D
C120N B 125 C120N B 125 C125H C 125 NG125N D125
Icw 8(kA) 26.7 22

NOTE: If these downstream protection recommendations are not followed, a


short-circuit on an output circuit can result in a break in power longer than 20
ms on all the other output circuits.

Permissible UPS overloads as a Function of Time

Normal Mode Operation

7. RMS current limit when inverter is coupled and bypass AC source is out of tolerances
8. RMS shortime current value that can be carried without damage under condition defined by the standard IEC 62040-1.

990–3887C-001 17
250–500 kVA 380/400/415 V UPS Facility Planning

Bypass AC Mode or Static Switch Operation

Recommended Residual Current Protection


Requirements for residual current protection:
For single mains:
• The same residual current protection can be used for input and bypass.
For dual mains:
• A transformer is required upstream of either the input or bypass.
• Equip each source with a circuit breaker or switch with residual current
protection.
The recommended minimum residual current protection is 3 A, provided the
conditions defined in IEC60364-4-61 are complied with.

Battery Breaker Box Configurations

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The battery breaker box must only be used with the Galaxy 7000 UPS.
Failure to follow these instructions will result in death or serious injury.

WARNING
HAZARD OF FIRE OR ARC FLASH
• The battery breaker box must be connected as described in this manual.
• The undervoltage coil must be wired to the UPS as shown on the diagrams.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.

The below battery solutions can be made of several strings in parallel. All strings
must be identical: same element block and the same number of blocks.
The below battery configurations and settings are based on nominal power at a
power factor of 0.9 and 264 lead battery cells. For other battery configurations
please contact Schneider Electric.

18 990–3887C-001
Facility Planning 250–500 kVA 380/400/415 V UPS

Battery Configurations with One Battery Breaker (QF1)

QF1 (NSX500S TM-DC)

Battery Thermal/
Strings Magnetic
UPS Battery Backup Time Minutes Setting (A)

250 kVA < 90 1 500/1250


300 kVA < 10 1 500/1250

Battery Configurations with Two Battery Breakers (QF1)

QF1-1 QF1-2
(NSX500S TM-DC) (NSX500S TM-DC)

Battery Thermal/ Battery Thermal/


Battery Backup Time Total Number of Strings Magnetic Strings Magnetic
UPS Minutes Battery Strings Setting (A) Setting (A)

250 kVA Any 2 1 500/1250 1 500/1250


3 2 500/1250 1 500/1250
4 2 500/1250 2 500/1250
5 3 500/1250 2 500/1250

6 3 500/1250 3 500/1250
300 kVA Any 2 1 500/1250 1 500/1250
3 2 500/1250 1 500/1250
4 2 500/1250 2 500/1250
5 3 500/1250 2 500/1250
6 3 500/1250 3 500/1250
400 kVA < 90 2 1 500/1250 1 500/1250
4 2 500/1250 2 500/1250
6 3 500/1250 3 500/1250
500 kVA < 20 2 1 500/1250 1 500/1250
4 2 500/1250 2 500/1250
6 3 500/1250 3 500/1250

Battery Configurations with Three Battery Breakers (QF1)

QF1-1 QF1-2 QF1-3


(NSX500S TM-DC) (NSX500S TM-DC) (NSX500S TM-DC)
Battery Total
Backup Number of Battery Thermal/ Battery Thermal/ Battery Thermal/
Time Battery Strings Magnetic Strings Magnetic Strings Magnetic
UPS Minutes Strings Setting (A) Setting (A) Setting (A)

400 kVA Any 3 1 500/1250 1 500/1250 1 500/1250


5 2 500/1250 2 500/1250 1 500/1250
500 kVA Any 3 1 500/1250 1 500/1250 1 500/1250
5 2 500/1250 2 500/1250 1 500/1250

6 2 500/1250 2 500/1250 2 500/1250

990–3887C-001 19
250–500 kVA 380/400/415 V UPS Facility Planning

Environmental
Operating temperature 0 - 40 °C

Storage temperature with or without batteries -25 - 45 °C dry heat

Operating relative humidity 20- 95%, non-condensing

Storage relative humidity 20- 95%, non-condensing

Operating elevation 0–1500 m: 85% load


1500–2000 m: 79% load
2000–2300 m: 75% load
2300–3000 m: 69% load
3000–4000 m: 59% load

Storage elevation 0-10000 meters

Audible noise according to ISO 3746 (NFS 31 027)


250-400 kVA 380/400/415/440 V 75 dBA
500 kVA 380/400/415/440 V 75 dBA

Protection class From IP20 to IP32


Colour Pearl dark grey (RAL 9023)

Heat Dissipation

250 kVA 300 kVA 400 kVA 500 kVA


Batteries Batteries Batteries Batteries Batteries Batteries Batteries Batteries
fully charging fully charging fully charging fully charging
charged charged charged charged

Active power 112 225 135 270 180 360 225 450
(kW)

Efficiency 93.2 93.8 93.5 93.6 94.1 94.1 94.3 94.3

Heat losses (kW) 8.2 14.9 9.4 18.6 11.3 22.6 13.6 27.2

Heat losses 1962 3554 2243 4449 2697 5395 3250 6501
(calories/s)

Weights and Dimensions


UPS rating Weight (kg) Height (mm) Width (mm) Depth (mm)

250 kVA 990 1900 1412 855


300 kVA 990 1900 1412 855
400 kVA 1140 1900 1412 855
500 kVA 1500 1900 1812 855

Shipping Weights and Dimensions


UPS Weight (kg) Height (mm) Width (mm) Depth (mm)

160 kVA 860 2030 1525 970


200 kVA 860 2030 1525 970
250 kVA 1010 2030 1525 970
300 kVA 1010 2030 1525 970
400 kVA 1160 2030 1525 970
500 kVA 1520 2030 1925 970

20 990–3887C-001
Facility Planning 250–500 kVA 380/400/415 V UPS

Clearance
NOTE: Clearance dimensions are published for airflow and service access
only. Consult with the local safety codes and standards for additional
requirements in your local area.
NOTE: The UPS system can be placed up against the wall. It is preferable to
leave some space for easier maintenance.

NOTICE
HAZARD OF OVERHEATING
• Leave nothing on top of the UPS.
• Maintain 500 mm of free space above the UPS.
• Ensure that the UPS cabinet rests on its four cylindrical feet, (six feet for 500
kVA UPS).
• Ensure that the distance between the UPS rear panel and the floor is less
than 10 mm.
Failure to follow these instructions can result in equipment damage.

NOTE: Leave one meter of free space in front of the UPS for door opening.

990–3887C-001 21
250–500 kVA 380/400/415 V UPS Facility Planning

Default settings
System Settings (only updated when in load disconnect) Default setting

Nominal output rated voltage (ph-ph) 400 V (380, 400, or 415)

Frequency 50 Hz (50 or 60 Hz)

Frequency range 45 Hz to 66 Hz

Automatic start Forbidden


Rate of synchronization with AC Bypass source 1 Hz/s

Transfer to Bypass AC Allowed

AC bypass overload control active

AC Bypass frequency threshold tolerance 8%

AC Bypass Static Switch operation when EPO Close

Shutdown mode (can only be set from service port) Never

PFC current ramp enable Yes

Break duration 100 ms


Remote command enabled No
Shutdown setting

Shutdown mode (can only be set from service port) Never

Other settings

Battery present No

Battery-test interval 1 month

Low battery warning voltage threshold 20 %

Low battery warning time threshold 1 minute

Deep battery discharge Forbidden

Display settings

Display language English

Date format mm/dd/yyyy

Temperature unit °C

Main screen Welcome screen


Password OOO

22 990–3887C-001
Drawings 250–500 kVA 380/400/415 V UPS

Drawings
NOTE: A comprehensive set of drawings is available on the engineering
website at engineer.apc.com.
NOTE: These drawings are for reference ONLY — subject to change without
notice.

990–3887C-001 23
250–500 kVA 380/400/415 V UPS Drawings

Galaxy 7000 Single System

24 990–3887C-001
Drawings 250–500 kVA 380/400/415 V UPS

Galaxy 7000 Single System with Transformer

990–3887C-001 25
250–500 kVA 380/400/415 V UPS Options

Options
Hardware Options
Battery Cabinets
• Galaxy 7000 Empty Battery Cabinet 700 mm

Auxiliary Cabinets
• Galaxy 7000 Empty Auxiliary Cabinet
• Galaxy 7000 Empty Auxiliary Cabinet 700 mm
• Galaxy 7000 400 V Top Connection

External Bypass
• Galaxy 7000 External Bypass

Battery Circuit Breaker Boxes


• Galaxy 7000 Battery Circuit Breaker Box 200 kVA 400 V
• Galaxy 7000 Auxiliaries 250 kVA
• Galaxy 7000 Auxiliaries 300 kVA
• Galaxy 7000 Auxiliaries 400 kVA
• Galaxy 7000 Auxiliaries 500 kVA

Protection and Cover Features


• Galaxy 7000 Transversal Auxiliaries
• Galaxy 7000 400 V IP Cover

Static Switch Cabinets


• Galaxy 7000 Static Bypass Switch

Management Cards
• Network management card with ModBus/Jbus
• Network management teleservice card
• Environment sensor for network management cable

26 990–3887C-001
Options 250–500 kVA 380/400/415 V UPS

Configuration Options
• Connection through the top
• Isolation/Voltage matching transformer
• Synchronisation module
• B2000 or Cellwatch battery-monitoring system for block by block management
• Lightning arrestor (built into the UPS cabinet)
• Backfeed protection
• Jbus/Modbus + Ethernet 10/100
• Multi-standard communication cards
• Jbus/Modbus + Ethernet 10/100 + Modem
• Two ports with dry contacts and/or remote shutdown
• Battery circuit breaker unit
• Supervision and shutdown software
• Enterprise Power Manager V.2

Parallel Capabilities
Integrated Parallel UPSs

UPS cabinet (1)


1 PFC rectifier module (A)
Q3BP
Byp as AC Inverter module (B)
Q4S D
Battery chopper (C)
Normal AC Q1 Q5N Static-switch on AC bypass
A B
line (D)
C
Batteries (2)
2
–
+ QF1

1
Q3BP
Byp as AC Q4S D

Normal AC Q1 Q5N
A B
C

2
–
+ QF1

990–3887C-001 27
250–500 kVA 380/400/415 V UPS Options

Integrated Parallel UPSs with external bypass cabinet

UPS cabinet (1)


3
Byp as AC Q3BP e xt PFC rectifier module (A)
Inverter module (B)
1
Q3BP Battery chopper (C)
Byp as AC Q4S D Static-switch on AC bypass
line (D)
Normal AC Q1 Q5N
A B Batteries (2)
C
External bypass cabinet (3)
2 –
+ QF1 Q5N
e xt

1
Q3BP
Byp as AC Q4S D

Normal AC Q1 Q5N
A B
C

2 –
+ QF1

Parallel UPSs with SSC (Static-Switch Cabinet)


Up to eight UPS units can be connected in parallel with a Static-Switch Cabinet.

UPS 1 cabinet (1)


3 PFC rectifier module (A)
Q3BP
Inverter module (B)
Byp as AC
Q4S Q 5 N Battery chopper (C)
D
Batteries (2)
SSC (3)

1
Static-switch on AC bypass
line (D)
Normal AC
Q 1 Q 5 N
A B

2
–
+ QF1 Q F 1 + -

Normal AC
Q 1 Q 5 N
A B
C

2
–
+ QF1

28 990–3887C-001
Options 250–500 kVA 380/400/415 V UPS

Parallel UPSs with SSC and SSC maintenance cabinet


UPS 1 cabinet (1)
3 PFC rectifier module (A)
Q3BP
Inverter module (B)
Byp as AC
Q4S Q 5 N
D Battery chopper (C)
Batteries (2)
SSC (3)
4
Static-switch on AC bypass
line (D)
QN QM
SSC maintenance cabinet
(4)
1

Normal AC
Q 1 Q 5 N
A B

2
–
+ QF1 Q F 1 + -

Normal AC
Q 1 Q 5 N
A B
C

2
–
+ QF1

Parallel UPSs set up as frequency converters

UPS cabinet (1)


2 PFC rectifier module (A)
–
+ QF1
Inverter module (B)
Battery chopper (C)
1
Normal AC C
Batteries (2)
Q1 Q5N
A B

2
–
+ QF1

1
Normal AC C
Q1 Q5N
A B

990–3887C-001 29
250–500 kVA 380/400/415 V UPS Limited Factory Warranty

Limited Factory Warranty


One-Year Factory Warranty
The limited warranty provided by Schneider Electric in this Statement of Limited
Factory Warranty applies only to products you purchase for your commercial or
industrial use in the ordinary course of your business.

Terms of Warranty
Schneider Electric warrants that the product shall be free from defects in materials
and workmanship for a period of one year from the date of product start-up when
start-up is performed by Schneider Electric-authorized service personnel and
occurs within six months of the Schneider Electric shipment date. This warranty
covers repairing or replacing any defective parts including on-site labor and travel.
In the event that the product fails to meet the foregoing warranty criteria, the
warranty covers repairing or replacing defective parts at the sole discretion of
Schneider Electric for a period of one year from the shipment date. For Schneider
Electric cooling solutions, this warranty does not cover circuit breaker resetting,
loss of refrigerant, consumables, or preventive maintenance items. Repair or
replacement of a defective product or part thereof does not extend the original
warranty period. Any parts furnished under this warranty may be new or factory-
remanufactured.

Non-transferable Warranty
This warranty is extended to the first person, firm, association or corporation
(herein referred to by “You” or “Your”) for whom the Schneider Electric product
specified herein has been purchased. This warranty is not transferable or
assignable without the prior written permission of Schneider Electric.

Assignment of Warranties
Schneider Electric will assign you any warranties which are made by
manufacturers and suppliers of components of the Schneider Electric product and
which are assignable. Any such warranties are assigned “AS IS” and Schneider
Electric makes no representation as to the effectiveness or extent of such
warranties, assumes no responsibility for any matters which may be warranted by
such manufacturers or suppliers and extends no coverage under this Warranty to
such components.

Drawings, Descriptions
Schneider Electric warrants for the warranty period and on the terms of the
warranty set forth herein that the Schneider Electric product will substantially
conform to the descriptions contained in the Schneider Electric Official Published
Specifications or any of the drawings certified and agreed to by contract with
Schneider Electric if applicable thereto (“Specifications”). It is understood that the
Specifications are not warranties of performance and not warranties of fitness for a
particular purpose.

Exclusions
Schneider Electric shall not be liable under the warranty if its testing and
examination disclose that the alleged defect in the product does not exist or was

30 990–3887C-001
Limited Factory Warranty 250–500 kVA 380/400/415 V UPS

caused by end user or any third person misuse, negligence, improper installation
or testing. Further, Schneider Electric shall not be liable under the warranty for
unauthorized attempts to repair or modify wrong or inadequate electrical voltage or
connection, inappropriate on-site operation conditions, corrosive atmosphere,
repair, installation, start-up by non-Schneider Electric designated personnel, a
change in location or operating use, exposure to the elements, Acts of God, fire,
theft, or installation contrary to Schneider Electric recommendations or
specifications or in any event if the Schneider Electric serial number has been
altered, defaced, or removed, or any other cause beyond the range of the intended
use.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF
LAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED
UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. SCHNEIDER
ELECTRIC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY,
SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER
ELECTRIC EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED,
OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF,
SCHNEIDER ELECTRIC RENDERING OF TECHNICAL OR OTHER ADVICE OR
SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING
WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER
WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE
CONSTITUTE SCHNEIDER ELECTRIC SOLE LIABILITY AND PURCHASER’S
EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES.
SCHNEIDER ELECTRIC WARRANTIES RUN ONLY TO PURCHASER AND ARE
NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL SCHNEIDER ELECTRIC, ITS OFFICERS, DIRECTORS,
AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT,
SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE
USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH
DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT,
NEGLIGENCE OR STRICT LIABILITY OR WHETHER SCHNEIDER ELECTRIC
HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH
DAMAGES, SPECIFICALLY, SCHNEIDER ELECTRIC IS NOT LIABLE FOR ANY
COSTS, SUCH AS LOST PROFITS OR REVENUE, LOSS OF EQUIPMENT,
LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA,
COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NO SALESMAN, EMPLOYEE OR AGENT OF SCHNEIDER ELECTRIC IS
AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY.
WARRANTY TERMS MAY BE MODIFIED, IF AT ALL, ONLY IN WRITING SIGNED
BY AN SCHNEIDER ELECTRIC OFFICER AND LEGAL DEPARTMENT.

Warranty Claims
Customers with warranty claims issues may access the SCHNEIDER ELECTRIC
worldwide customer support network through the SCHNEIDER ELECTRIC web
site: http://www.schneider-electric.com. Select your country from the country
selection pull-down menu. Open the Support tab at the top of the web page to
obtain contact information for customer support in your region.

990–3887C-001 31
Printed in.
Schneider Electric

Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
www.schneider-electric.com

As standards, specifications, and design change from time to time,


please ask for confirmation of the information given in this publication.

© 2011 – 2018 Schneider Electric. All rights reserved.


990–3887C-001

You might also like