Mbpn-8nql8e R3 en
Mbpn-8nql8e R3 en
03/2018
www.schneider-electric.com
Legal Information
The Schneider Electric brand and any registered trademarks of Schneider Electric
Industries SAS referred to in this guide are the sole property of Schneider Electric
SA and its subsidiaries. They may not be used for any purpose without the owner's
permission, given in writing. This guide and its content are protected, within the
meaning of the French intellectual property code (Code de la propriété
intellectuelle français, referred to hereafter as "the Code"), under the laws of
copyright covering texts, drawings and models, as well as by trademark law. You
agree not to reproduce, other than for your own personal, noncommercial use as
defined in the Code, all or part of this guide on any medium whatsoever without
Schneider Electric's permission, given in writing. You also agree not to establish
any hypertext links to this guide or its content. Schneider Electric does not grant
any right or license for the personal and noncommercial use of the guide or its
content, except for a non-exclusive license to consult it on an "as is" basis, at your
own risk. All other rights are reserved.
Electrical equipment should be installed, operated, serviced, and maintained only
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
As standards, specifications, and designs change from time to time, please ask for
confirmation of the information given in this publication.
250–500 kVA 380/400/415 V UPS
Table of Contents
Important Safety Instructions — SAVE THESE
INSTRUCTIONS .........................................................................................5
Safety Precautions .....................................................................................6
Technical Data .............................................................................................8
Model list ...................................................................................................8
Input Power Factor .....................................................................................8
Efficiency ...................................................................................................8
Efficiency Curves ..................................................................................9
Derating due to Load Power Factor ............................................................10
Batteries ..................................................................................................10
Efficiency DC to AC.............................................................................10
End of Discharge Voltage .................................................................... 11
Compliance.............................................................................................. 11
Facility Planning ........................................................................................12
Input Specifications ..................................................................................12
Bypass Specifications ...............................................................................12
Output Specifications ................................................................................12
Battery Specifications ...............................................................................13
End of Discharge Current ....................................................................13
Recommended Cable Sizes ......................................................................13
Power Cables for Single UPS ..............................................................13
Power Cables for Parallel UPSs ...........................................................14
Connection Terminals..........................................................................16
Recommended Overcurrent Protection ......................................................16
Recommended Upstream and Downstream Protection ..........................16
Recommended Residual Current Protection .........................................18
Battery Breaker Box Configurations......................................................18
Environmental ..........................................................................................20
Heat Dissipation .................................................................................20
Weights and Dimensions...........................................................................20
Shipping Weights and Dimensions.............................................................20
Clearance ................................................................................................21
Default settings ........................................................................................22
Drawings ....................................................................................................23
Galaxy 7000 Single System.......................................................................24
Galaxy 7000 Single System with Transformer .............................................25
Options .......................................................................................................26
Hardware Options.....................................................................................26
Configuration Options ...............................................................................27
Parallel Capabilities ..................................................................................27
Limited Factory Warranty .........................................................................30
990–3887C-001 3
Important Safety Instructions — SAVE THESE
INSTRUCTIONS 250–500 kVA 380/400/415 V UPS
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment
damage.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.
Please Note
Electrical equipment should only be installed, operated, serviced, and maintained
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
990–3887C-001 5
Important Safety Instructions — SAVE THESE
250–500 kVA 380/400/415 V UPS INSTRUCTIONS
Safety Precautions
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• The product must be installed according to the specifications and
requirements as defined by Schneider Electric. It concerns in particular the
external and internal protections (upstream circuit breakers, battery circuit
breakers, cabling, etc.) and environmental requirements. No responsibility is
assumed by Schneider Electric if these requirements are not respected.
• After the UPS system has been electrically wired, do not start up the system.
Start-up must only be performed by Schneider Electric.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS System must be installed according to local and national regulations.
Install the UPS according to:
• IEC 60364 (including 60364–4–41- protection against electric shock, 60364–
4–42 - protection against thermal effect, and 60364–4–43 - protection against
overcurrent), or
• NEC NFPA 70
depending on which one of the standards apply in your local area.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Install the UPS system in a temperature controlled area free of conductive
contaminants and humidity.
• Install the UPS system on a non-inflammable, level, and solid surface (e.g.
concrete) that can support the weight of the system.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS is not designed for and must therefore not be installed in the following
unusual operating environments:
• Damaging fumes
• Explosive mixtures of dust or gases, corrosive gases, or conductive or radiant
heat from other sources
• Moisture, abrasive dust, steam or in an excessively damp environment
• Fungus, insects, vermin
• Salt-laden air or contaminated cooling refrigerant
• Pollution degree higher than 2 according to IEC 60664-1
• Exposure to abnormal vibrations, shocks, and tilting
• Exposure to direct sunlight, heat sources, or strong electromagnetic fields
Failure to follow these instructions will result in death or serious injury.
6 990–3887C-001
Important Safety Instructions — SAVE THESE
INSTRUCTIONS 250–500 kVA 380/400/415 V UPS
NOTICE
RISK OF OVERHEATING
Respect the clearance requirements around the UPS system and do not cover
the product’s ventilation openings when the UPS system is in operation.
Failure to follow these instructions can result in equipment damage.
NOTICE
RISK OF EQUIPMENT DAMAGE
Do not connect the UPS output to regenerative load systems including
photovoltaic systems and speed drives.
Failure to follow these instructions can result in equipment damage.
990–3887C-001 7
250–500 kVA 380/400/415 V UPS Technical Data
Technical Data
Model list
The Galaxy 7000 UPS is available in the following models:
• Galaxy 7000 250 kVA 380/400/415 V
• Galaxy 7000 300 kVA 380/400/415 V
• Galaxy 7000 400 kVA 380/400/415 V
• Galaxy 7000 500 kVA 380/400/415 V
Efficiency
The table below provides average system efficiencies on a double conversion
single unit with a balanced linear load, PF 0.9, AC input voltage 400 V / AC output
voltage 400 V.
Efficiency on load PF 0.8 or for other input or output AC voltages is very close to
the values given below for PF 0.9, voltage input / 400 V output. Difference is less
than + / -0.2%.
Minimum system efficiency is very close to average system efficiency. The
difference is 0.2% maximum.
All these measures are coming from the production line ATE statistics performed
on over 200 units.
8 990–3887C-001
Technical Data 250–500 kVA 380/400/415 V UPS
Efficiency Curves
250 kVA 400 V
990–3887C-001 9
250–500 kVA 380/400/415 V UPS Technical Data
Batteries
Efficiency DC to AC
Efficiency in Battery Mode
Efficiency during discharge (output voltage 380 V or 400 V, inductive load PF 0.8 or
0.9 )
10 990–3887C-001
Technical Data 250–500 kVA 380/400/415 V UPS
DC Power in kW — PF 0.8
DC Power in kW — PF 0.9
Compliance
Directives for CE marking
990–3887C-001 11
250–500 kVA 380/400/415 V UPS Facility Planning
Facility Planning
Input Specifications
250 kVA 300 kVA 400 kVA 500 kVA
Voltage (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
Nominal input 369 351 337 319 441 420 403 382 586 558 536 507 735 700 672 636
current (A)1
Frequency (Hz) 45 to 66
Bypass Specifications
250 kVA 300 kVA 400 kVA 500 kVA
380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
Nominal input 379 361 347 328 455 433 417 393 607 577 556 524 759 722 695 656
current (A)
Frequency (Hz) 45 to 66
Output Specifications
250 kVA 300 kVA 400 kVA 500 kVA
Voltage (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
Nominal output 379 361 347 328 455 433 417 393 607 577 556 524 759 722 695 656
current (A)
Output voltage ± 1%
regulation
Crest factor 2.7 2.9 3.0 3.3 2.3 2.4 2.5 2.8 2.3 2.4 2.5 2.8 2.6 2.7 2.8 3.0
1. For 400 V interphase voltages and a load with a power factor of 0.9.
12 990–3887C-001
Facility Planning 250–500 kVA 380/400/415 V UPS
Battery Specifications
Type Sealed lead-acid Vented lead-acid Ni-Cad
Min./Max. floating voltage (V) 600 / 654 581 / 634 600 / 655
NOTE: The battery current is an average current Pn with a power factor of 0.9
990–3887C-001 13
250–500 kVA 380/400/415 V UPS Facility Planning
AC cable sizes are determined for the TNS system and for the following cable
characteristics:
• copper single-core cables, type U1000 R02V
• maximum length 100 m with a line voltage drop <3%
• installation on perforated cable trays
• XLPE-type insulation, single-layer trefoil formation
• THDI between 15% and 33%
• 35°C, at 400 V
• grouped by four cables.
Battery cable sizes are determined for:
• installation on perforated metallic grounded cable trays,
• copper, single-core cables, type U1000 R02V,
• maximum length 25 m with a line voltage drop <1%.
NOTE: Important: For > 200 kVA UPS, the output cables must be at least 6
metres long (L ≥ 6 m).
UPS rating Number of UPSs Total power rating Current on AC bypass Minimum size for AC
(kVA) or load (A) bypass or load (mm²)
Frequency Converters
UPS rating Number of UPSs Total power rating Current on AC bypass Minimum size for load
(kVA) or load (A) (mm²)
NOTE: The power cables between the UPS units and the upstream protective
devices must be of the same size and length.
NOTE: The power cables between the UPS units and the load must be of the
same size and length.
14 990–3887C-001
Facility Planning 250–500 kVA 380/400/415 V UPS
UPS rating Number of Total power Current on AC bypass or load (A) Minimum size for load (mm²)
UPSs rating (kVA)4
NOTE: The power cables between the UPS units and the upstream protective
devices must be of the same size and length.
NOTE: The power cables between the UPS units and the load must be of the
same size and length.
UPS rating Number Total power Current on AC bypass or load (A) Minimum size for load (mm²)
of UPS rating4 (kVA)
NOTE: The power cables between the UPS units and the upstream protective
devices must be of the same size and length.
NOTE: The power cables between the UPS units and the load must be of the
same size and length.
990–3887C-001 15
250–500 kVA 380/400/415 V UPS Facility Planning
Connection Terminals
UPS Cabinets
800 kVA 13 13
1200 kVA 13 13
2000 kVA 13 and 17 13
16 990–3887C-001
Facility Planning 250–500 kVA 380/400/415 V UPS
Line-current Values
Input current at 1.25 In overload limited to 10 minutes 441 530 706 881
(A)
Input current at 1.5 In overload limited to 30 seconds 530 636 848 1058
(A)
Normal AC NSX 630N Micrologic NSX 630N Micrologic NS 800N 3P Micrologic NS 800N 3P Micrologic
source 3P 2.3 3P 2.3 2.0 5.0
Bypass AC NSX 630N Micrologic NSX 630N Micrologic NS 800N 4P Micrologic NS 800N 4P Micrologic
source 4P 2.3 4P 2.3 2.0 5.0
Output NSX 100 N TM D 80 NSX 100 N TM D 80 NSX 100 N TM D 100 C125N D 125
C120N C80 C120N C80 NG 125N C 125 NSX 160N TM 160D
C120N B 125 C120N B 125 C125H C 125 NG125N D125
Icw 8(kA) 26.7 22
7. RMS current limit when inverter is coupled and bypass AC source is out of tolerances
8. RMS shortime current value that can be carried without damage under condition defined by the standard IEC 62040-1.
990–3887C-001 17
250–500 kVA 380/400/415 V UPS Facility Planning
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The battery breaker box must only be used with the Galaxy 7000 UPS.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD OF FIRE OR ARC FLASH
• The battery breaker box must be connected as described in this manual.
• The undervoltage coil must be wired to the UPS as shown on the diagrams.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
The below battery solutions can be made of several strings in parallel. All strings
must be identical: same element block and the same number of blocks.
The below battery configurations and settings are based on nominal power at a
power factor of 0.9 and 264 lead battery cells. For other battery configurations
please contact Schneider Electric.
18 990–3887C-001
Facility Planning 250–500 kVA 380/400/415 V UPS
Battery Thermal/
Strings Magnetic
UPS Battery Backup Time Minutes Setting (A)
QF1-1 QF1-2
(NSX500S TM-DC) (NSX500S TM-DC)
6 3 500/1250 3 500/1250
300 kVA Any 2 1 500/1250 1 500/1250
3 2 500/1250 1 500/1250
4 2 500/1250 2 500/1250
5 3 500/1250 2 500/1250
6 3 500/1250 3 500/1250
400 kVA < 90 2 1 500/1250 1 500/1250
4 2 500/1250 2 500/1250
6 3 500/1250 3 500/1250
500 kVA < 20 2 1 500/1250 1 500/1250
4 2 500/1250 2 500/1250
6 3 500/1250 3 500/1250
990–3887C-001 19
250–500 kVA 380/400/415 V UPS Facility Planning
Environmental
Operating temperature 0 - 40 °C
Heat Dissipation
Active power 112 225 135 270 180 360 225 450
(kW)
Heat losses (kW) 8.2 14.9 9.4 18.6 11.3 22.6 13.6 27.2
Heat losses 1962 3554 2243 4449 2697 5395 3250 6501
(calories/s)
20 990–3887C-001
Facility Planning 250–500 kVA 380/400/415 V UPS
Clearance
NOTE: Clearance dimensions are published for airflow and service access
only. Consult with the local safety codes and standards for additional
requirements in your local area.
NOTE: The UPS system can be placed up against the wall. It is preferable to
leave some space for easier maintenance.
NOTICE
HAZARD OF OVERHEATING
• Leave nothing on top of the UPS.
• Maintain 500 mm of free space above the UPS.
• Ensure that the UPS cabinet rests on its four cylindrical feet, (six feet for 500
kVA UPS).
• Ensure that the distance between the UPS rear panel and the floor is less
than 10 mm.
Failure to follow these instructions can result in equipment damage.
NOTE: Leave one meter of free space in front of the UPS for door opening.
990–3887C-001 21
250–500 kVA 380/400/415 V UPS Facility Planning
Default settings
System Settings (only updated when in load disconnect) Default setting
Frequency range 45 Hz to 66 Hz
Other settings
Battery present No
Display settings
Temperature unit °C
22 990–3887C-001
Drawings 250–500 kVA 380/400/415 V UPS
Drawings
NOTE: A comprehensive set of drawings is available on the engineering
website at engineer.apc.com.
NOTE: These drawings are for reference ONLY — subject to change without
notice.
990–3887C-001 23
250–500 kVA 380/400/415 V UPS Drawings
24 990–3887C-001
Drawings 250–500 kVA 380/400/415 V UPS
990–3887C-001 25
250–500 kVA 380/400/415 V UPS Options
Options
Hardware Options
Battery Cabinets
• Galaxy 7000 Empty Battery Cabinet 700 mm
Auxiliary Cabinets
• Galaxy 7000 Empty Auxiliary Cabinet
• Galaxy 7000 Empty Auxiliary Cabinet 700 mm
• Galaxy 7000 400 V Top Connection
External Bypass
• Galaxy 7000 External Bypass
Management Cards
• Network management card with ModBus/Jbus
• Network management teleservice card
• Environment sensor for network management cable
26 990–3887C-001
Options 250–500 kVA 380/400/415 V UPS
Configuration Options
• Connection through the top
• Isolation/Voltage matching transformer
• Synchronisation module
• B2000 or Cellwatch battery-monitoring system for block by block management
• Lightning arrestor (built into the UPS cabinet)
• Backfeed protection
• Jbus/Modbus + Ethernet 10/100
• Multi-standard communication cards
• Jbus/Modbus + Ethernet 10/100 + Modem
• Two ports with dry contacts and/or remote shutdown
• Battery circuit breaker unit
• Supervision and shutdown software
• Enterprise Power Manager V.2
Parallel Capabilities
Integrated Parallel UPSs
1
Q3BP
Byp as AC Q4S D
Normal AC Q1 Q5N
A B
C
2
+ QF1
990–3887C-001 27
250–500 kVA 380/400/415 V UPS Options
1
Q3BP
Byp as AC Q4S D
Normal AC Q1 Q5N
A B
C
2
+ QF1
1
Static-switch on AC bypass
line (D)
Normal AC
Q 1 Q 5 N
A B
2
+ QF1 Q F 1 + -
Normal AC
Q 1 Q 5 N
A B
C
2
+ QF1
28 990–3887C-001
Options 250–500 kVA 380/400/415 V UPS
Normal AC
Q 1 Q 5 N
A B
2
+ QF1 Q F 1 + -
Normal AC
Q 1 Q 5 N
A B
C
2
+ QF1
2
+ QF1
1
Normal AC C
Q1 Q5N
A B
990–3887C-001 29
250–500 kVA 380/400/415 V UPS Limited Factory Warranty
Terms of Warranty
Schneider Electric warrants that the product shall be free from defects in materials
and workmanship for a period of one year from the date of product start-up when
start-up is performed by Schneider Electric-authorized service personnel and
occurs within six months of the Schneider Electric shipment date. This warranty
covers repairing or replacing any defective parts including on-site labor and travel.
In the event that the product fails to meet the foregoing warranty criteria, the
warranty covers repairing or replacing defective parts at the sole discretion of
Schneider Electric for a period of one year from the shipment date. For Schneider
Electric cooling solutions, this warranty does not cover circuit breaker resetting,
loss of refrigerant, consumables, or preventive maintenance items. Repair or
replacement of a defective product or part thereof does not extend the original
warranty period. Any parts furnished under this warranty may be new or factory-
remanufactured.
Non-transferable Warranty
This warranty is extended to the first person, firm, association or corporation
(herein referred to by “You” or “Your”) for whom the Schneider Electric product
specified herein has been purchased. This warranty is not transferable or
assignable without the prior written permission of Schneider Electric.
Assignment of Warranties
Schneider Electric will assign you any warranties which are made by
manufacturers and suppliers of components of the Schneider Electric product and
which are assignable. Any such warranties are assigned “AS IS” and Schneider
Electric makes no representation as to the effectiveness or extent of such
warranties, assumes no responsibility for any matters which may be warranted by
such manufacturers or suppliers and extends no coverage under this Warranty to
such components.
Drawings, Descriptions
Schneider Electric warrants for the warranty period and on the terms of the
warranty set forth herein that the Schneider Electric product will substantially
conform to the descriptions contained in the Schneider Electric Official Published
Specifications or any of the drawings certified and agreed to by contract with
Schneider Electric if applicable thereto (“Specifications”). It is understood that the
Specifications are not warranties of performance and not warranties of fitness for a
particular purpose.
Exclusions
Schneider Electric shall not be liable under the warranty if its testing and
examination disclose that the alleged defect in the product does not exist or was
30 990–3887C-001
Limited Factory Warranty 250–500 kVA 380/400/415 V UPS
caused by end user or any third person misuse, negligence, improper installation
or testing. Further, Schneider Electric shall not be liable under the warranty for
unauthorized attempts to repair or modify wrong or inadequate electrical voltage or
connection, inappropriate on-site operation conditions, corrosive atmosphere,
repair, installation, start-up by non-Schneider Electric designated personnel, a
change in location or operating use, exposure to the elements, Acts of God, fire,
theft, or installation contrary to Schneider Electric recommendations or
specifications or in any event if the Schneider Electric serial number has been
altered, defaced, or removed, or any other cause beyond the range of the intended
use.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF
LAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED
UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. SCHNEIDER
ELECTRIC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY,
SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER
ELECTRIC EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED,
OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF,
SCHNEIDER ELECTRIC RENDERING OF TECHNICAL OR OTHER ADVICE OR
SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING
WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER
WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE
CONSTITUTE SCHNEIDER ELECTRIC SOLE LIABILITY AND PURCHASER’S
EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES.
SCHNEIDER ELECTRIC WARRANTIES RUN ONLY TO PURCHASER AND ARE
NOT EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL SCHNEIDER ELECTRIC, ITS OFFICERS, DIRECTORS,
AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT,
SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE
USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH
DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT,
NEGLIGENCE OR STRICT LIABILITY OR WHETHER SCHNEIDER ELECTRIC
HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH
DAMAGES, SPECIFICALLY, SCHNEIDER ELECTRIC IS NOT LIABLE FOR ANY
COSTS, SUCH AS LOST PROFITS OR REVENUE, LOSS OF EQUIPMENT,
LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA,
COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NO SALESMAN, EMPLOYEE OR AGENT OF SCHNEIDER ELECTRIC IS
AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY.
WARRANTY TERMS MAY BE MODIFIED, IF AT ALL, ONLY IN WRITING SIGNED
BY AN SCHNEIDER ELECTRIC OFFICER AND LEGAL DEPARTMENT.
Warranty Claims
Customers with warranty claims issues may access the SCHNEIDER ELECTRIC
worldwide customer support network through the SCHNEIDER ELECTRIC web
site: http://www.schneider-electric.com. Select your country from the country
selection pull-down menu. Open the Support tab at the top of the web page to
obtain contact information for customer support in your region.
990–3887C-001 31