We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 16
SECTION 707 – ALLOWABLE
STRESS DESIGN (ASD) OF
MASONRY 707.1 General 707.1.1 Scope The design of masonry structures using allowable stress design shall comply with the provisions of Section 706 and this section. Stresses in clay or concrete masonry under service loads shall not exceed the values given in this section. 707.1.2 Allowable Masonry Stresses When quality assurance provisions do not include requirements for special inspection as prescribed in Section 701, the allowable stresses for masonry in Section 707 shall be reduced by one half. When one half allowable masonry stresses are used in Seismic Zone 4, the value of f’m from Table 705-1 shall be limited to a maximum of 10 MPa for concrete masonry and 18 MPa for clay masonry unless the value of f’m is verified by tests in accordance with Section 705.3.4, Items 1 and 4 or 6. A letter of certification is not required. When one half allowable masonry stresses are used for design in Seismic Zones 4, the value of f’m shall be limited to 10 MPa for concrete masonry and 18 MPa for clay masonry for Section 705.3.2, Item 3, and Section 705.3.3, Item 5, unless the value of f’m is verified during construction by the testing requirements of Section 705.3.2, Item 2. A letter of certification is not required. 707.1.3 Minimum Dimensions for Masonry Structures Located in Seismic Zones 2 and 4 Elements of masonry structures located in Seismic Zones 2 and 4 shall be in accordance with this section. 707.1.3.1 Bearing Walls The nominal thickness of reinforced masonry bearing walls shall not be less than 150 mm except that nominal 100 mm load-bearing reinforced hollow-clay unit masonry walls may be used, provided net area unit strength exceeds 55 MPa, units are laid in running bond, bar sizes do not exceed 12 mm with no more than two bars or one splice in a cell, and joints are flush cut, concave or a protruding V section. 707.1.3.2 Columns The least nominal dimension of a reinforced masonry column shall be 300 mm except that, for ASD, if the allowable stresses are reduced by one half, the minimum nominal dimension shall be 200 mm. 707.1.4 Design Assumptions The working stress design procedure is based on working stresses and linear stress-strain distribution assumptions with all stresses in the elastic range as follows: 1. Plane sections before bending remain plane after bending. 2. Stress is proportional to strain. 3. Masonry elements combine to form a homogenous member. 707.1.5 Embedded Anchor Bolts 707.1.5.1 General Allowable loads for plate anchor bolts, headed anchor bolts and bent bar anchor bolts shall be determined in accordance with this section. 707.1.5.2 Tension Allowable loads in tension shall be the lesser value selected from Table 707-1 and 707-2 or shall be determined from the lesser of Formula (707-1) or Formula (707-2). Bt 0.042Ap f 'm (707-1) Bt = 0.2 Abfy (707-2) The area Ap shall be the lesser of Formula (707-3) or Formula (707-4) and where the projected areas of adjacent anchor bolts everlap, Ap of each anchor bolt shall be reduced by one half of the overlapping area. Ap = lb 2 (707-3) Ap = lbe 2 (707-4) 707.1.5.3 Shear Allowable loads in shear shall be the value selected from Table 707-3 or shall be determined from the lesser of Formula (707-5) or Formula (707-6). By 1070 4 f 'm Ab (707-5) Bv = 0.12 Abfy (707-6) Where the anchor bolt edge distance lbe in the direction of load is less than 12 bolt diameters, the value of Bv in Formula (707-5) shall be reduced by linear interpolation to zero at an lbe distance of 40 mm. Where adjacent anchors are spaced closer than 8db, the allowable shear of the adjacent anchors determined by Formula (707-5) shall be reduced by linear interpolation to 0.75 times the allowable shear value at a center-to-center spacing of four bolt diameters. 7-22 CHAPTER 7 - Masonry Association of Structural Engineers of the Philippines 707.1.5.4 Combined Shear and Tension Anchor bolts subjected to combined shear and tension shall be designed in accordance with: 1.0 v v t t B b B b (707-7) 707.1.6 Compression in Walls and Columns 707.1.6.1 Walls, Axial Loads Stresses due to compressive forces applied at the centroid of wall may be computed, assuming uniform distribution over the effective area, by fa = P/Ae (707-8) 707.1.6.2 Columns, Axial Loads Stresses due to compressive forces applied at the centroid of columns may be computed by Formula (707-8) assuming uniform distribution over the effective area. 707.1.6.3 Columns, Bending or Combined Bending and Axial Loads Stresses in columns due to combined bending and axial loads shall satisfy the requirements of Section 707.2.7 where fa/Fa is replaced by P/Pa. Columns subjected to bending shall meet all applicable requirements for flexural design. 707.1.7 Shear Walls, Design Loads When calculating shear or diagonal tension stresses, shear walls which resist seismic forces in Seismic Zone 4 shall be designed to resist 1.5 times the forces required by Section 208.5. 707.1.8 Design, Composite Construction 707.1.8.1 General The requirements of this section govern multiwythe masonry in which at least one wythe has strength or composition characteristics different from the other wythe or wythes and is adequately bonded to act as a single structural element. The following assumptions shall apply to the design of composite masonry: 1. Analysis shall be based on elastic transformed section of the net area. 2. The maximum computed stress in any portion of composite masonry shall not exceed the allowable stress for the material of that portion. 707.1.8.2 Determination of Modulus of Elasticity The modulus of elasticity of each type of masonry in composite construction shall be measured by tests if the modular ratio of the respective types of masonry exceeds 2 to 1 as determined by Section 706.2.12. 707.1.8.3 Structural Continuity 707.1.8.3.1 Bonding of Wythes All wythes of composite masonry elements shall be tied together as specified in Section 706.1.5.2 as a minimum requirement. Additional ties or the combination of grout and metal ties shall be provided to transfer the calculated stress. 707.1.8.3.2 Material Properties The effect of dimensional changes of the various materials and different boundary conditions of various wythes shall be included in the design. 707.1.8.4 Design Procedure, Transformed Sections In the design of transformed sections, one material is chosen as the reference material, and the other materials are transformed to an equivalent area of the reference material by multiplying the areas of the other materials by the respective ratios of the modulus of elasticity of the other materials to that of the reference material. Thickness of the transformed area and its distance perpendicular to a given bending axis remain unchanged. Effective height or length of the element remains unchanged. 707.1.9 Reuse of Masonry Units The allowable working stresses for reused masonry units shall not exceed 50 percent of those permitted for new masonry units of the same properties. 707.2 Design of Reinforced Masonry 707.2.1 Scope The requirements of this section are in addition to the requirements of Sections 706 and 707.1, and govern masonry in which reinforcement is used to resist forces. Walls with openings used to resist lateral loads whose pier and beam elements are within the dimensional limits of Section 708.2.6.1.2 may be designed in accordance with Section 708.2.6. Walls used to resist lateral loads not meeting the dimensional limits of Section 708.2.6.1.2 may be designed as walls in accordance with this section or Section 708.2.5. CHAPTER 7 - Masonry 7-23 National Structural Code of the Philippines Volume 1, 6th Edition 707.2.2 Reinforcement 707.2.2.1 Maximum Reinforcement Size The maximum size of reinforcement shall be 32 mm. Maximum reinforcement area in cells shall be 6 percent of the cell area without splices and 12 percent of the cell area with splices. 707.2.2.2 Cover All reinforcing bars, except joint reinforcement, shall be completely embedded in mortar or grout and have a minimum cover, including the masonry unit, of at least 20 mm, 40 mm of cover when the masonry is exposed to weather and 50 mm of cover when the masonry is exposed to soil. 707.2.2.3 Development Length The required development length ld for deformed bars or deformed wire shall be calculated by: ld = 0.29 db fs for bars in tension (707-9) ld = 0.22 db fs for bars in compression (707-10) Development length for smooth bars shall be twice the length determined by Formula (707-9). 707.2.2.4 Reinforcement Bond Stress Bond stress u in reinforcing bars shall not exceed the following: Plain Bars 410 kPa Deformed Bars 1370 kPa Deformed Bars without Special Inspection 690 kPa 707.2.2.5 Hooks 1. The term “standard hook” shall mean one of the following: 1.1 A 180-degree turn plus extension of at least 4 bar diameters, but not less than 63mm at free end of bar. 1.2 A 90-degree turn plus extension of at least 12 bar diameters at free end of bar. 1.3 For stirrup and tie anchorage only, either a 90- degree or a 135-degree turn, plus an extension of at least six bar diameters, but not less than 65 mm at the free end of the bar. 2. Inside diameter of bend of the bars, other than for stirrups and ties, shall not be less than that set forth in Table 707-4 3. Inside diameter of bend for 16 mm or smaller stirrups and ties shall not be less than four bar diameter. Inside diameter of bend for 16 mm or larger stirrups and ties shall not be less than that set forth in Table 707-4. 4. Hooks shall not be permitted in the tension portion of any beam, except at the ends of simple or cantilever beams or at the freely supported end of continuous or restrained beams. 5. Hooks shall not be assumed to carry a load which would produce a tensile stress in the bar greater than 52 MPa. 6. Hooks shall not be considered effective in adding to the compressive resistance of bars. 7. Any mechanical device capable of developing the strength of the bar without damage to the masonry may be used in lieu of a hook. Data must be presented to show the adequacy of such devices. 707.2.2.6 Splices The amount of lap of lapped splices shall be sufficient to transfer the allowable stress of the reinforcement as specified in Sections 706.3.4, 707.2.2.3 and 707.2.12. In no case shall the length of the lapped splice be less than 30 bar diameters for compression or 40 bar diameters for tension. Welded or mechanical connections shall develop 125 percent of the specified yield strength of the bar in tension. Exception: For compression bars in columns that are not part of the seismic-resisting system and are not subject to flexure, only the compressive strength need be developed. When adjacent splices in grouted masonry are separated by 76 mm or less, the required lap length shall be increased 30 percent. Exception: Where lap splices are staggered at least 24 bars diameters, no increase in lap length is required. See Section 707.2.12 for lap splice increases. 707.2.3 Design Assumptions The following assumptions are in addition to those stated in Section 707.1.4: 1. Masonry carries no tensile stress. 2. Reinforcement is completely surrounded by and bonded to masonry material so that they work together as a homogenous material within the range of allowable working stresses. 7-24 CHAPTER 7 - Masonry Association of Structural Engineers of the Philippines 707.2.4 Nonrectangular Flexural Elements Flexural elements of nonrectangular cross section shall be designed in accordance with the assumptions given in Sections 707.1.4 and 707.2.3. 707.2.5 Allowable Axial Compressive Stress and Force For members other than reinforced masonry columns, the allowable axial compressive stress Fa shall be determined as follows: ] 140 0.25 ' [1 ' 2 r F f h a m (707-11) for h’/ r 99 2 ' 70 ' 25 . 0 h F f r a m (707-12) for h’/r > 99 For reinforced masonry columns, the allowable axial compressive force Pa shall be determined as follows: ] 140 [0.25 ' 0.65 ][1 ' 2 r P f A A F h a m e s sc (707-13) for h’/r 99 ] ' [0.25 ' 0.65 ][70 h P f A A F r a m e s sc (707-14) for h’/r > 99 707.2.6 Allowable Flexural Compressive Stress The allowable flexural compressive stress Fb is: Fb 0.33 f 'm , 13.8 MPa maximum (707-15) 707.2.7 Combined Compressive Stresses, Unity Formula Elements subjected to combined axial and flexural stresses shall be designed in accordance with accepted principles of mechanics or in accordance with Formula (707-16): 1 b b a a F f F f (707-16) 707.2.8 Allowable Shear Stress in Flexural Members Where no shear reinforcement is provided, the allowable shear stress Fv in flexural members is: Fv 0.083 f 'm , 345 kPa maximum (707-17) Exception: For a distance of 1/16 the clear span beyond the point of inflection, the maximum stress shall be 140 kPa. Where shear reinforcement designed to take entire shear force is provided, the allowable shear stress, Fv in flexural members is: Fv 0.25 f 'm , 1.0 MPa maximum (707-18) 707.2.9 Allowable Shear Stress in Shear Walls Where inplane flexural reinforcement is provided and masonry is used to resist all shear, the allowable shear stress Fv in shear wall is: 1 36 (4 ) ' (80 45 ) Vd fM Vd F M v m maximum (707-19) For M Vd 1,Fv 1 12 f 'm , 240 kPa maximum (707-20) Where shear reinforcement designed to take all the shear is provided, the allowable shear stress Fv, in shear walls is: For M/Vd < 1, 1 24(4 ) ' , (120 45 ) Vd fM Vd F M v m maximum (707-21) M Vd 1, Fv 0.12 f 'm , 520 kPa maximum (707-22) 707.2.10 Allowable Bearing Stress When a member bears on the full area of a masonry element, the allowable bearing stress Fbr is: Fbr = 0.26 f’m (707-23) When a member bears on one third or less of a masonry element, the allowable bearing stress Fbr is: Fbr = 0.38 f’m (707-24) Formula (707-24) applies only when the least dimension between the edges of the loaded and unloaded areas is a minimum of one fourth of the parallel side dimension of the loaded area. The allowable bearing stress on a reasonably concentric area greater than one third but less than the full area shall be interpolated between the values of Formulas (707-23) and (707-24). CHAPTER 7 - Masonry 7-25 National Structural Code of the Philippines Volume 1, 6th Edition 707.2.11 Allowable Stresses in Reinforcement The allowable stresses in reinforcement shall be as follows: 1. Tensile Stress 1.1 Deformed bars, Fs = 0.5 fy , 165 MPa maximum (707-25) 1.2 Wire reinforcement, Fs = 0.5 fy , 200 MPa maximum (707-26) 1.3 Ties, anchors and smooth bars, Fs = 0.4 fy , 140 MPa maximum (707-27) 2. Compressive Stress 2.1 Deformed bars in columns, Fsc = 0.4 fy , 165 MPa maximum (707-28) 2.2 Deformed bars in flexural members, Fs = 0.5 fy , 165 MPa maximum (707-29) 2.3 Deformed bars in shear walls which are confined by lateral ties throughout the distance where compression reinforcement is required and where such lateral ties are not less than 6 mm in diameter and spaced not farther apart than 16 bar diameters or 48 tie diameters, Fsc = 0.4 fy , 165 MPa maximum (707-30) 707.2.12 Lap Splice Increases In regions of moment where the design tensile stresses in the reinforcement are greater than 80 percent of the allowable steel tensile stress Fs, the lap length of splices shall be increased not less than 50 percent of the minimum required length. Other equivalent means of stress transfer to accomplish the same 50 percent increase may be used. 707.2.13 Reinforcement for Columns Columns shall be provided with reinforcement as specified in this section. 707.2.13.1 Vertical Reinforcement The area of vertical reinforcement shall not be less than 0.005 Ae and not more than 0.04 Ae. At least four 10 mm bars shall be provided. The minimum clear distance between parallel bars in columns shall be two and one half times the bar diameter. 707.2.14 Compression in Walls and Columns 707.2.14.1 General Stresses due to compressive forces in walls and columns shall be calculated in accordance with Section 707.2.5. 707.2.14.2 Walls, Bending or Combined Bending and Axial Loads Stresses in walls due to combined bending and axial loads shall satisfy the requirements of Section 707.2.7 where fa is given by Formula (707-8). Walls subjected to bending with or without axial loads shall meet all applicable requirements for flexural design. The design of walls with an h’/t ratio larger than 30 shall be based on forces and moments determined from an analysis of the structure. Such analysis shall consider the influence of axial loads and variable moment of inertia on member stiffness and fixed-end moments, effect of deflections on moments and forces and the effects of duration of loads. 707.2.15 Flexural Design, Rectangular Flexural Elements Rectangular elements shall be designed in accordance with the following formulas or other methods based on the assumptions given in Sections 707.1.4, 707.2.3 and this section. 1. Compressive stress in the masonry: ( 2 ) bd 2 jk f M b (707-31) 2. Tensile stress in the longitudinal reinforcement: A jd fM s s (707-32) 3. Design coefficients: k (np)2 2np np (707-33) or b s nf kf 1 1 (707-34) 3 j 1 k (707-35) 707.2.16 Bond of Flexural Reinforcement In flexural members in which tensile reinforcement is parallel to the compressive face, the bond stress shall be computed by the formula: jd uV o (707-36) 707.2.17 Shear in Flexural Members and Shear Walls The shear stress in flexural members and shear walls shall