PROJECT:

PROJECT OWNER: SIDAMO ELTO FARMERS COOPERATIVE UNION

ELECTRICAL DESIGN REPORT

(DESIGN EXECUTED AS PER ES 3961:2015)

-1- December ,2022


PROJECT:
PROJECT OWNER: SIDAMO ELTO FARMERS COOPERATIVE UNION

Contents
1. Generalities...........................................................................................................................................3
1.1 Power Supply Characteristics..........................................................................................................3
1.2 Distribution Characteristics.............................................................................................................3
1.3 Low Voltage System Earthing.........................................................................................................4
2 Power Supply..........................................................................................................................................4
2.1 M a i n Power Supply.......................................................................................................................4
2.2 Emergency Power supply................................................................................................................6
3. Low Voltage Power Cables..................................................................................................................6
4. LV Circuits and Distribution boards sizing...........................................................................................6
5. Cables and Conductor sizing................................................................................................................7
6. Lighting.................................................................................................................................................7
7. Telephone System.................................................................................................................................9
8. Integrated Reception TV System.........................................................................................................10
9. Lightning Protection System...............................................................................................................10

TECHNICAL REPORT

-2- December ,2022


PROJECT:
PROJECT OWNER: SIDAMO ELTO FARMERS COOPERATIVE UNION

1. Generalities

A Factor Building for PP PLASTIC FACTORY is to be constructed at Hawassa in


Wondo Tika.

The following points are part of the design:


 Normal power supplies;
 Electrical earthing and bonding;
 Emergency power supplies (electric generator backed);
 Cable, and cable containment;
 Main and sub distribution boards;
 Lighting equipment;
 wiring devices;
 Lightning protection,
 Satellite Master Antenna TV system
 Fire Alarm System,

1.1 Power Supply Characteristics

Nominal characteristics of power supply and distribution will be as follows:


 Medium Voltage 15 kV, 3 phases
(MV):
 Low voltage (LV): 400 V/240 V, 3 phase, solidly grounded neutral, earthing
arrangement
 Frequency: (TNS)
50Hz

1.2 Distribution Characteristics

Electric power supply to the building considered to be distributed from the LV


switchboard defined as the Main Distribution Board- MDB, which in turn is fed
from a distribution transformer capacity of 630KVA, and 400KVA stand-by diesel
generator set via an Automatic Transfer Switch.

Power risers to every floor are furnished in single duct. Final installation location
of these panels (MDB) shall be decided at later stage.
The low voltage LV distribution system shall be 3-phase + Neutral + Earth. All
Distribution Boards to be 3-phase 400/240V for lighting / main motors and for
power final or branch circuits/ motors unless specifically stated otherwise.
Voltage drop limits:
 A maximum total of 10% voltage drop from the main supply
"Transformer" up to the farthest point of the network: 2% feeders,
6% branch circuits.

1.3 Low Voltage System Earthing

-3- December ,2022


PROJECT:
PROJECT OWNER: SIDAMO ELTO FARMERS COOPERATIVE UNION

To ensure safe operation, equipotential bonding and lightning protection shall


include all installations.
The earthing configuration shall be TN-S type, and will comply with IEE
regulations. Transformer neutrals will be connected to the main earth source.
All equipment and facilities are to be earthed and equipotential bonded
appropriately to the relevant standards. Several equipotential earth bars will be
installed in main electrical, low current, mechanicals rooms, loading station and in
the pumping station to ensure easy access for connection and earthing of all
electrical conducting equipment. Each equipotential bar will be connected in loop
configuration via buried bare copper conductor.
Conductor bonded to an earth rod is terminated on a main system earth bar at
the MDB room.

All local bonding is made to this main earth bar. All other system-bonding
conductors are also terminated here, which include lightning arrester system
earthing, data/telecom system, etc. The anticipated earth resistance is five ohms
max.
The low voltage system on the client side is earthed at the MDBs earth terminals
inside the boards. In all other sub-distribution boards the neutral and earth
terminals shall be isolated.
The sub main distribution boards are bonded through earth bonding conductors
equal in size with the neutral conductors derived from the MDBs earth terminal.
All other sub-distribution boards shall be bonded through earth continuity
conductors derived from their respective power source panel.
If the feeder cable size is less than or equal to 25mm² the earth conductor is part
of the cable. In all other cases, the earth conductor is run parallel to the power
cable.

2 Power Supply

2.1 M a i n Power Supply

The building power supply will be achieved by low voltage 630KVA CSS
(compact sub-station), delta-stars with solidly earthed neutral. Transformer
should be manufactured and tested in compliance with IEC 60076, and
CENELEC HD398-1 to HD398-5.

The Low Voltage Switchgear shall meet the IEC 60947 requirements. The LV
switchboard designated as the main distribution Board (MDB) shall be of the
cubicle type suitable for front access and for use on 400V, 3-phases, 50Hz.
The Main MDB (CMDB) shall be provided with an ammeter and voltmeter with
phase selection switches, power factor meters and protection fuses.

-4- December ,2022


PROJECT:
PROJECT OWNER: SIDAMO ELTO FARMERS COOPERATIVE UNION

The low voltage power distribution system throughout the building shall be via
PVC sheathed PVC insulated power cables of 0.6/1KV insulation strength except
the main cable feeder from the transfer switch in the generator set room up-to
the main distribution boards MDB is PVC sheathed and XLPE insulated. Cable
runs from the main floor distribution board’s up-to the various sub-distribution
boards shall be mainly inside vertical riser ducts fixed to the duct walls on cable
ladder fixed by clamps at 50cm span.

Sub Distribution Boards (SDBs) are situated in suitable location in the on every
floor. Specialized services like lifts and pumps are provided with their own sub-
distribution panels through Main board MDB-GF located on the ground floor.

All sub distribution boards (SDBs) will be installed in accessible locations for
safety and operational requirements. They are fed from the MDB (MDB) in hot
dip galvanized cable trays minimum size of 300 x 60mm. The SDBs should be
made of sheet steel front doors and IP43 minimum protection with doors closed
and IP40 with doors open.

Further all final circuits are fed through PVC insulated HOV5-U conductors inside
PVC conduits of 16mm, 19mm, 21mm diameters as appropriate and as shown
on the drawings. Mostly single socket and partially twin socket outlets of
10/16A with grounding contact are provided in shops, commercial, bars, and
restaurants. All office areas furnished with twin socket and single socket outlets
of 10/16A screw fixed to 60mm diameter recess boxes.

The CMDB circuit breaker shall be equipped with long, short, and ground fault
protection; the branch circuit breakers shall have an instantaneous trip in
addition to those listed for the mains.
The Low Voltage switchgear bus and circuit breakers shall be rated for a short-
circuit fault level as required by to the incoming service.

The circuit breakers types shall be in accordance with the following standards:
 Less than 1000 Amps- Molded Case Circuit Breaker (MCCB) as per IEC
60947-2
 Less than 60 Amps - Miniature Circuit Breakers (MCB) as per IEC 60947-2.
Bus bars and Bus bars’ connection shall be constructed in accordance with IEC
standards. Bus bars must be of rectangular section hard drawn high
conductivity copper, adequately rated and supported by Porcelain or molded
insulators spaced at suitable intervals. Bus bars shall be rated for a maximum
operating temperature of 90°C.

All over-current protection shall be made by circuit breakers.


For each DB, the main circuit breaker shall be MCCB (molded case circuit
breaker) type as per IEC 60947-2. Circuit breakers for branch circuits rated up to
60amps shall be MCB (miniature circuit breakers) as per IEC 60947-2. Breakers
for circuits with loads beyond 60 amps shall also be molded case type.

-5- December ,2022


PROJECT:
PROJECT OWNER: SIDAMO ELTO FARMERS COOPERATIVE UNION

2.2 Emergency Power supply

400KVA diesel-generating set with automatic starting, made of soundproof


canopy, residential type will be used to supply standby power to the building in
the case of utility power failure. The standby (emergency) power system is
envisaged to support the full load of the entire building. The generating set
shall automatically take over the electrical load in case of power failure, and it
shall be installed at the generator room in the power house at the outdoor area.
The system shall be fully sized to operate under full load, at the site conditions,
to deliver prime power in case of extended power outages.

3. Low Voltage Power Cables


LV power cables shall be color-coded in accordance with the IEC standard
method. Power cables shall have a minimum conductor size of 2.5 mm2,
lighting minimum conductors’ size shall be 1.5 mm2. Size shall be indicated in
mm² with insulation colour code in accordance with IEC.

Cables shall be suitable for installation indoors and outdoors in metal trays,
conduits and underground conduit cache, in wet and dry locations.

Cables shall be rated for use at 75°C in wet locations and 90°C in dry locations.
Cables shall be clearly marked on the overall jacket, at maximum
intervals of 0.6m with the manufacturer’s name, year of manufacture,
voltage class, number and size of conductors and the serial number.

The feeders shall be single core or multi-core cables lay in galvanized steel
cable trays or in under floor conduits.

All cable penetrations through fire separation zones will be capped off
with fire stopping material.

4. LV Circuits and Distribution boards sizing


Each lighting point is considered with its actual power consumption,
including ballast loss if any.

o Socket outlets are attributed with 200W load each.


o Motors and other loads are considered with their estimated loads.
o Light points are grouped into final circuits not to exceed 10A single-phase
circuit breakers at the maximum in the majority of cases.
o Socket outlets not exceeding eight in numbers are grouped into one circuit
with 16A single-phase circuit breakers. -Motor and power outlets are each
put in a circuit protected by appropriately sized circuit breakers.
o Each distribution panel is sized after summing all the loads connected to it,
and depending on the size of the board 70 to 80 percent, diversity is
allowed.

-6- December ,2022


PROJECT:
PROJECT OWNER: SIDAMO ELTO FARMERS COOPERATIVE UNION

5. Cables and Conductor sizing

CURRENT CARRYING CAPACITY


-Load current of each circuit is calculated by;
Ib=P/Vcosø for single phase and
Ib= P/√3Vcosø for three phase
Where; Ib is the load current in amperes
P is the connected load in watts , V is the phase voltage in volts
Cosø is the power factor of the current
The current carrying capacity of the cable is determined from standard tables
according to IEC 60364, which take into consideration the conductor type,
insulation and sheath type, and method of installation.
Cables are installed on cable tray, on vertical riser duct, and inside PVC conduit
recessed inside slab and/or wall. Appropriate current carrying capacity tables give
current carrying capacity of cables. The ambient temperature is taken to be 30°C
and cables are not bunched together inside a conduit.

The basic criterion is;


Ib ≤ Iz Where; Ib is the load current and Iz is the current carrying capacity of
the cable under specified condition.
-Circuit breakers overload protection is decided by the criterion;
Ib ≤ In ≤ Iz Where, In is the rated current of the circuit breaker
If ≤ 1.45Iz, If is the current that insures circuit breaker operation in standard
condition.

6. Lighting

Lighting installation is done with PVC insulated conductor of 2.5sqmm in rigid


thermoplastic conduit (that confirm to DIN 49017) of not less than 16mm
diameter under plastered wall or slab and/or ceiling. Plastic type Flush mounted
junction boxes are used where necessary. Every circuit shall have its own neutral
wire and the live wire shall be connected to the switch. Switches for flush and
surface mounting in lighting circuit shall be rated for 10A, 240V AC and shall
conform to ES 3961:2015.

-7- December ,2022


PROJECT:
PROJECT OWNER: SIDAMO ELTO FARMERS COOPERATIVE UNION

The interior lighting is designed to provide general illumination levels (average


maintained lux) to be achieved for different areas.

Type of Area
Illumination (lux)

A. Circulation Area 100 lux

B. Kitchen 500 lux

C. Bath room 100 lux

D. Office 300 lux

E. Row material store 1000 lux

F. Production Area 1000 lux

Light fittings of the low energy consumption type are used wherever possible.
Lighting control generally will be by localized switches.

6.1. LUMINARIES AND LAMPS


Enclosure to luminaries shall provide a minimum degree of protection of IP20
when located within the residence and can go up to IP66 when located in toilets
and for external purpose. Terminal blocks for connection of the supply cables shall
be adequate for the size of conductors forming the loop-in wiring.

Light fittings and lamps used for this project are summarized below:
Type 1, Luminous flux 5200lm with LED 48W lamp (Office).
Type 2, Luminous flux 12800lm with LED 97W lamp (Factory).
Type 3, Luminous flux 1500lm with LED 15W lamp (Lobby and Corridor).
Type 4, Luminous flux 1200lm with LED 12W lamp (Toilet).
Type 5, Luminous flux 1350lm with LED 15W lamp (Toilet mirror).
Type 6, Luminous flux 1800lm with LED 20W lamp (Store).
Type 7, Luminous flux 5200lm with LED 48W lamp (Kitchen).
Type 8, Luminous flux 2400lm with LED 25W lamp (Cafe).

-8- December ,2022


PROJECT:
PROJECT OWNER: SIDAMO ELTO FARMERS COOPERATIVE UNION

Type 9, Luminous flux 6500lm with LED 56W lamp (Tank Farm).

Type 11, Luminous flux 620lm with LED 18W lamp (External wall light).
Type 12, Luminous flux 10000lm with LED 100W lamp (Flood light).

6.2 NUMBER OF LIGHT FITTINGS

To calculate the number of lamps from the requested average lighting level the formula below is used.
No.of Lamps = (Eavg x Area) / (UF x DF x ɸ)
Eavg = Average lighting level
Area = Area of room (m2)
U F = Utilization factor
DF = Distribution factor
ɸ = Luminous flux per lamp (lumen)

7. Telephone System

Telecom system provisions is made in the form of UTP, 4 pair, CAT 6 cabling from
tele/data boxes complete with wiring accessories. The provision will make
telephone connection at any place fast and simple. The telephone outlets are RJ-
11 type.
DATA CABLE INSIDE PVC CONDUITS
NO. ITEM DIA CSA NO OF SPACING FACTOR
(mm) (mm²) CABLES
1 UTP 4 PAIR 11 95.03 1 -
CABLE
2 CONDUIT 16 201.1 1 0.47
3 CONDUIT 20 314.2 2 0.61

The telephone cable installed from riser shaft are laid on cable trays before
reaching their nod terminated inside PVC conduits of minimum size of 16mm
diameter.

8. Integrated Reception TV System

-9- December ,2022


PROJECT:
PROJECT OWNER: SIDAMO ELTO FARMERS COOPERATIVE UNION

An Integrated Reception TV system is a Satellite reception system is the basic


system for residential type of buildings Television programs transmission
provision.

The IRS system design is achieved by simply installing not more than three or
four Satellite dishes and one Terrestrial Antenna per building, connected to
signal amplifiers, and multi switches terminated to end TV socket- outlets
through splitters.

Wiring through coaxial cabling for standard transmission system. The design
begins from selecting its antenna system installation position and it shall be
installed with PVC insulated RG-59/U coaxial cable inside a minimum conduit
size of 19mm diameter, terminated to junction boxes at every floor.

Further the television system points distributed with the use of appropriate
numbers of splitters, which shall be installed as shown on the drawings with
PVC insulated RG6/U coaxial cables terminating each point in side PVC conduits
of minimum size of 16mm diameter.

9. Lightning Protection System

A lightning protection system based on Early Streamer Emission System air


terminal in accordance to the NF C 17-102 and similar ESE standards shall be
implemented for this project.

The working principle of the system is that during Thunder storm conditions when
the lightning down-leader is approaching ground level, an upward leader may be
created by any conducive surface in case of passive lighting rod, the upward
leader propagate only after a long period of change reorganization in the case of
INTERCEPTION SI ESE, the initiation time of upward leader is greatly reduced.

The INTERCEPTOR SI ESE generates controlled magnitude and frequency pulses


at the tip of the terminal during high static field characteristic prior to a lighting
discharge.
This enables the creation of an upward leader from the terminal that propagates
towards down earth leader coming from the thundercloud.

SYSTEM REQUIRMENTS

The design and installation of the terminals should be completed in compliance


with the requirements of the French standard NF C 17-102. In addition to terminal
placement requirements, the standard requires two down conductors per terminal
to be installed on opposite walls. A down conductor cross-sectional area of ≥
70mm2 is specified. The down conductors are to be secured at three points per
meter with equipotential bonding made to nearby metallic items.

Each down conductor requires a test clamp and dedicated earth system of 10
ohm or less. Should 10 ohms not be achievable, then 100m of buried conductor

-10- December ,2022


PROJECT:
PROJECT OWNER: SIDAMO ELTO FARMERS COOPERATIVE UNION

with no single vertical or horizontal element exceeding 20m is acceptable. The


lighting protection ground should not be connected to the main building ground
and any nearby buried metallic items.

-11- December ,2022