Slide 4
Slide 4
pass himself.
—G. Herbert
a A
Vp + ZL1
n N
Vp + ZL Vp + ZL2
b B
(a) (b)
Three-
phase b c
output
b N a Stator
c
Rotor
a S b
A three-phase generator.
Van Vbn Vcn windings or coils with terminals a-a , b-b , and c-c are physically
placed 120 apart around the stator. Terminals a and a , for example,
stand for one of the ends of coils going into and the other end coming
0
out of the page. As the rotor rotates, its magnetic field “cuts” the flux
120 240 t from the three coils and induces voltages in the coils. Because the coils
are placed 120 apart, the induced voltages in the coils are equal in
magnitude but out of phase by 120 (Fig. 12.5). Since each coil can be
regarded as a single-phase generator by itself, the three-phase genera-
The generated voltages are 120 apart tor can supply power to both single-phase and three-phase loads.
from each other. A typical three-phase system consists of three voltage sources con-
nected to loads by three or four wires (or transmission lines). (Three-
phase current sources are very scarce.) A three-phase system is
equivalent to three single-phase circuits. The voltage sources can be
either wye-connected as shown in Fig. 12.6(a) or delta-connected as in
Fig. 12.6(b).
a a
+ Van
n Vca + Vab
Vcn Vbn
b + b
Vbc
c c
(a) (b)
Vcn
Let us consider the wye-connected voltages in Fig. 12.6(a) for
now. The voltages V , V , and V are respectively between lines a, b,
120 and c, and the neutral line n. These voltages are called phase voltages.
120
If the voltage sources have the same amplitude and frequency and
Van are out of phase with each other by 120 , the voltages are said to be
120 balanced. This implies that
V V V 0 (12.1)
Vbn
V V V (12.2)
(a)
Thus,
Vbn
.
120
120
Since the three-phase voltages are 120 out of phase with each
Van other, there are two possible combinations. One possibility is shown in
120 Fig. 12.7(a) and expressed mathematically as
Vcn
V V 0
(b) V V 120 (12.3)
V V 0
V V 120 (12.4)
V V 240 V 120
This is called the acb sequence or negative sequence. For this phase
sequence, V leads V , which in turn leads V . The acb sequence is
produced when the rotor in Fig. 12.4 rotates in the clockwise direction.
It is easy to show that the voltages in Eqs. (12.3) or (12.4) satisfy
Eqs. (12.1) and (12.2). For example, from Eq. (12.3),
V V V V 0 V 120 V 120
V (1.0 0.5 j0.866 0.5 j0.866) (12.5)
0
Zl
a A
Zs
ZL
Van + Zn
n N
Vcn + + Vbn ZL ZL
Zs Zs
b C B
c
Zl
Zl
Van + In ZY
Z and Z are often very small compared with Z , so one can assume
that Z Z if no source or line impedance is given. In any event, by n N
lumping the impedances together, the Y-Y system in Fig. 12.9 can be Vcn + + Vbn ZY ZY
simplified to that shown in Fig. 12.10.
c Ib
Assuming the positive sequence, the phase voltages (or line-to- C B
neutral voltages) are Ic b
V V 0
(12.10)
V V 120 , V V 120 Balanced Y-Y connection.
The line-to-line voltages or simply line voltages V , V , and V are
related to the phase voltages. For example,
V V V V V V 0 V 120
1 3 (12.11a)
V 1 j ) 3V 30
2 2
Similarly, we can obtain
V V V 3V 90 (12.11b)
V V V 3V 210 (12.11c)
Thus, the magnitude of the line voltages V is 3 times the magnitude
of the phase voltages V , or
V 3V (12.12)
where
V V V V (12.13)
and
V V V V (12.14)
Also the line voltages lead their corresponding phase voltages by 30 .
Figure 12.11(a) illustrates this. Figure 12.11(a) also shows how to
determine V from the phase voltages, while Fig. 12.11(b) shows the
same for the three line voltages. Notice that V leads V by 120 , and
V leads V by 120 , so that the line voltages sum up to zero as do
the phase voltages.
Vnb Vab = Van + Vnb Applying KVL to each phase in Fig. 12.10, we obtain the line cur-
Vcn rents as
30 V V V 120
Van I , I I 120
Z Z Z
(12.15)
V V 240
I I 240
Vbn Z Z
(a) We can readily infer that the line currents add up to zero,
Vca Vcn Vab I I I 0 (12.16)
so that
I (I I I) 0 (12.17a)
Van
or
Vbn V ZI 0 (12.17b)
that is, the voltage across the neutral wire is zero. The neutral line can
thus be removed without affecting the system. In fact, in long distance
Vbc power transmission, conductors in multiples of three are used with the
(b)
earth itself acting as the neutral conductor. Power systems designed in
this way are well grounded at all critical points to ensure safety.
Phasor diagrams illustrating the relation- While the line current is the current in each line, the phase current
ship between line voltages and phase is the current in each phase of the source or load. In the Y-Y system, the
voltages. line current is the same as the phase current. We will use single subscripts
for line currents because it is natural and conventional to assume that line a
Ia
A
currents flow from the source to the load.
An alternative way of analyzing a balanced Y-Y system is to do Van + ZY
so on a “per phase” basis. We look at one phase, say phase a, and ana-
lyze the single-phase equivalent circuit in Fig. 12.12. The single-phase
n N
analysis yields the line current I as
A single-phase equivalent circuit.
V
I (12.18)
Z
From I , we use the phase sequence to obtain other line currents. Thus,
as long as the system is balanced, we need only analyze one phase.
We may do this even if the neutral line is absent, as in the three-wire
system.
Calculate the line currents in the three-wire Y-Y system of Fig. 12.13.
5 – j2 A
a
+ 110 0 V
10 + j8
10 + j8
5 – j2 C
110 0
I 6.81 21.8 A
16.155 21.8
Since the source voltages in Fig. 12.13 are in positive sequence, the
line currents are also in positive sequence:
I I 120 6.81 141.8 A
I I 240 6.81 261.8 A 6.81 98.2 A
A Y-connected balanced three-phase generator with an impedance of
0.4 j0.3 per phase is connected to a Y-connected balanced load
with an impedance of 24 j19 per phase. The line joining the gen-
erator and the load has an impedance of 0.6 j0.7 per phase.
Assuming a positive sequence for the source voltages and that V
120 30 V, find: (a) the line voltages, (b) the line currents.
Van +
n A
I AB
Z
Vcn + + Vbn
Z ICA
Ib Z
b B
c C
Ic I BC
Balanced Y- connection.
Another way to get these phase currents is to apply KVL. For
example, applying KVL around loop aABbna gives
V Z I V 0
or
V V V V
I (12.22)
Z Z Z
which is the same as Eq. (12.21). This is the more general way of find-
ing the phase currents.
The line currents are obtained from the phase currents by apply-
ing KCL at nodes A, B, and C. Thus,
I I I , I I I , I I I (12.23)
Since I I 240 ,
I I I I (1 1 240 )
I (1 0.5 j0.866) I 3 30 (12.24)
showing that the magnitude I of the line current is 3 times the mag-
nitude I of the phase current, or
I 3I (12.25)
where
Ic
I I I I (12.26)
and
I CA 30
I I I I (12.27)
Also, the line currents lag the corresponding phase currents by 30 , I AB
assuming the positive sequence. Figure 12.15 is a phasor diagram illus- 30
trating the relationship between the phase and line currents.
30 Ia
An alternative way of analyzing the Y- circuit is to transform
the -connected load to an equivalent Y-connected load. Using the -Y Ib I BC
transformation formula in Eq. (12.8),
Phasor diagram illustrating the relationship
between phase and line currents.
Z
Z (12.28)
3
Ia
After this transformation, we now have a Y-Y system as in Fig. 12.10.
The three-phase Y- system in Fig. 12.14 can be replaced by the single- Z
Van +
phase equivalent circuit in Fig. 12.16. This allows us to calculate only 3
the line currents. The phase currents are obtained using Eq. (12.25) and
utilizing the fact that each of the phase currents leads the correspon- A single-phase equivalent circuit of a bal-
ding line current by 30 . anced Y- circuit.
V V 3 30 100 3 10 30 V
or
V 173.2 40 V
The phase currents are
V 173.2 40
I 19.36 13.43 A
Z 8.944 26.57
I I 120 19.36 106.57 A
I I 120 19.36 133.43 A
The line currents are
I I 3 30 3(19.36) 13.43 30
33.53 16.57 A
I I 120 33.53 136.57 A
I I 120 33.53 103.43 A
12 60 A, 12 180 A, 12 60 A, 20.79 90 A,
20.79 150 A, 20.79 30 A.
A balanced - connection.
ZY
Vca + Vab N
+
ZY ZY
Ib
c + C
b B
Vbc Ic
A balanced -Y connection.
But I lags I by 120 , since we assumed the abc sequence; that is,
I I 120 . Hence,
I I I (1 1 120 )
1 3 (12.36)
I 1 j I 3 30
2 2
Substituting Eq. (12.36) into Eq. (12.35) gives
V 3 30
I (12.37)
Z
From this, we obtain the other line currents I and I using the posi-
tive phase sequence, i.e., I I 120 , I I 120 . The phase
currents are equal to the line currents.
Another way to obtain the line currents is to replace the delta-
connected source with its equivalent wye-connected source, as shown
in Fig. 12.19. In Section 12.3, we found that the line-to-line voltages a
of a wye-connected source lead their corresponding phase voltages by
30 . Therefore, we obtain each phase voltage of the equivalent wye- + V
an
connected source by dividing the corresponding line voltage of the +
Vca + n Vab
delta-connected source by 3 and shifting its phase by 30 . Thus,
the equivalent wye-connected source has the phase voltages + Vbn +
Vcn
V c + b
V 30
3 Vbc
(12.38)
V V
V 150 , V 90 Transforming a -connected source to an
3 3 equivalent Y-connected source.
If the delta-connected source has source impedance Z per phase, the
equivalent wye-connected source will have a source impedance of Z 3
per phase, according to Eq. (9.69).
Once the source is transformed to wye, the circuit becomes a wye-
wye system. Therefore, we can use the equivalent single-phase circuit Ia
shown in Fig. 12.20, from which the line current for phase a is
Vp 30
+ ZY
V 3 30 3
I (12.39)
Z
which is the same as Eq. (12.37). The single-phase equivalent circuit.
Alternatively, we may transform the wye-connected load to an
equivalent delta-connected load. This results in a delta-delta system,
which can be analyzed as in Section 12.5. Note that
V
V I Z 30
3 (12.40)
V V 120 , V V 120
As stated earlier, the delta-connected load is more desirable than
the wye-connected load. It is easier to alter the loads in any one phase
of the delta-connected loads, as the individual loads are connected
directly across the lines. However, the delta-connected source is hardly
used in practice, because any slight imbalance in the phase voltages
will result in unwanted circulating currents.
Table 12.1 presents a summary of the formulas for phase cur-
rents and voltages and line currents and voltages for the four con-
nections. Students are advised not to memorize the formulas but to
understand how they are derived. The formulas can always be
V 121.2 30
I 2.57 62 A
Z 47.12 32
I I 120 2.57 178 A
I I 120 2.57 58 A
which are the same as the phase currents.