Static vs Dynamic Contact Resistance
Static vs Dynamic Contact Resistance
Page 2
What is a circuit breaker?
Ideal switch
© OMICRON
According to IEC 62271-100 and ANSI C37.100-1992 a circuit breaker is a mechanical switching device,
capable of making, carrying and breaking currents under normal circuit conditions and also making, carrying
for a specified time and breaking currents under specified abnormal conditions such as short circuit.
Page 3
What is a circuit breaker?
Static behavior
Carry operational currents
Insulating HV parts to ground
Isolating faulted parts to the grid (in case the breaker is open)
Dynamic behavior
Breaking and making operational currents
Breaking and making fault currents (fault clearance)
© OMICRON
The main task of a circuit breaker is to interrupt operational + fault currents and to isolate faulty parts such as
overhead lines, cables, transformers, generators, etc. from the system. Hence a circuit breaker has a dynamic
behavior (breaking and making operational and fault currents) and a static behavior (carry operational currents
and insulating HV parts to ground).
In regards to the current the wording "break" and "make" is used whereas in regards to the action "open" and
"close" is used.
A circuit breaker is controlled by the protection device of the corresponding asset and the SCADA system
which allows controlling the grid by remote.
Page 4
Overview components
Interrupter unit(s)
Breaking chamber, interrupter chamber,
interrupter housing, etc.
Contains interrupter, interrupting medium
Support insulator
Line-to-ground insulator
Contains insulated pull-rod,
mechanical linkage, insulating
medium
© OMICRON
Depending on location of in the electrical network, network design and region several design of circuit
breakers are common – which is discussed in later more in detail. All of them consist of following three main
components
Interrupter unit(s)
Support insulator
Operating mechanism & control unit
Page 5
Circuit breaker components
Components
Interrupter
Mechanical
linkage
Control Operating
mechanism
© OMICRON
The trip or close command from any control device is forwarded to the circuit breakers' main contacts via the
functional chain. The functional chain consists of the following parts:
Control: This is the control device of the circuit breaker, e.g. the protection device. For HV circuit breakers this
part is not included directly in the circuit breaker. But some MV breakers are equipped with the protection
device itself.
Operating mechanism: Coils, armatures and the drive itself (spring, hydraulic, pneumatic, magnetic)
Mechanical linkage: Linkage between the drive and the interrupter. In order to obtain synchronicity of the
breaker's main contacts the mechanical linkage can be tuned via screws.
Interrupter: Main contacts of the circuit breaker
Page 6
Typical test on circuit breakers?
Interrupter
Under- & overvoltage tests
Pick-up tests
Mechanical
linkage
Control Operating
mechanism
© OMICRON
Page 7
Typical test on circuit breakers?
Interrupter
Current trace
Inrush current
Charging time
Under- & overvoltage tests
Mechanical
linkage
Control Operating
mechanism
© OMICRON
Page 8
Typical test on circuit breakers?
Interrupter
Contact travel (motion) of main contacts
Mechanical
linkage
Control Operating
mechanism
© OMICRON
Page 9
Typical test on circuit breakers?
Interrupter
Dynamic Contact Resistance
Mechanical
linkage
Control Operating
mechanism
© OMICRON
Page 10
Contact wear and tear of main contacts
© OMICRON
One very common and “simple” test is the static contact resistance test.
It is done to check the status of the main contact (and/or also bus bar junctions)
The test is done when breaker is closed using the four-point resistance measurement method. This is done to
exclude the resistance from test leads in the end value.
For the analysis, the resistance value is checked against the manufacturer specifications, comparing the
values between the phases and with the previous results if available.
Page 11
Contact wear and tear of main contacts
Measurement method
Inject a high current
Measure small voltage in a
noisy environment
Use 4-wire technique for
connection
© OMICRON
Principle
The principle of contact resistance measurement (µΩ meter test) is to measure the resistance in static
position: breaker closed.
A high current is injected between the breaking elements (direction of line) and measure the voltage drop
(line-ground). As the contact resistance is in µΩ- range a 4-wire measurement has to be applied, as otherwise
the resistance of the test leads (mΩ- range) falsify the results.
Conventional method
Disadvantage of using conventional units is the confusingly wiring effort for breakers with several interrupting
units. Connection mistakes are highly possible. Furthermore the measurement can be affected due to long
connection leads → inductive loop (antenna).
Page 12
Performance of trip and close components
Page 13
Contact wear and tear of main contacts
6 5 4
7 3
8 2
9
1
© OMICRON
What are arguments for performing a Dynamic Resistance Measurement (DRM) instead of a conventional
Static Contact Resistance measurement? Well it may become quite obvious comparing the sequences of a
circuit breaker operation with the jump of a motocross racer in the picture shown above.
Static Contact Resistance does only provide us an insight of the main contacts condition (resistance) in
defined open and close state. Represented by picture 1 = takeoff (open) and picture 9 = landing (close).
Dynamic Contact Resistance allows us to have a better insight of the main contacts condition (resistance)
during whole process of the movement. This allows us to see the condition of the arcing but also main
contacts providing information of resistance, timing and motion/travel (represented by picture 1+ picture 2 + ...
picture 9).
Page 14
Contact wear and tear of main contacts
© OMICRON
A dynamic contact resistance measurement is a commonly used method, because it determines the contact
length without having to disassemble the circuit breaker.
When the arcing contact becomes shorter than the minimum requirement specified by the circuit breaker
manufacturer, a safe operation can no longer be guaranteed and the interrupter unit needs to be maintained
properly.
In order to apply that method it is important to know the components of an SF6 circuit breaker interrupter unit
and how the current is interrupted during an open operation
Principle
The principle of Dynamic Resistance measurement (DRM) is to combine all information contact resistance,
timing, coil currents and travel (motion) into one diagram for the different operations. Thereby the whole
operation can be analyzed to find out arcing problems (e.g. bouncing), contact finger problems.
Page 15
Contact wear and tear of main contacts
© OMICRON
Page 16
Contact wear and tear of main contacts
© OMICRON
When the main contact is already opened but the arcing contact stays closed, the current injected will flow
through the arcing contact.
Tungsten copper (WCu) materials are used for arcing contacts in SF6 circuit breakers for high and medium
voltage applications. At the heart of the switching chamber, WCu arcing contacts are exposed to extreme
mechanical and thermal stresses, with temperatures ≥ 20,000 K being reached during arcing.
Tungsten-copper has unique material properties. A high level of temperature resistance is one of the most
important advantages of tungsten, while the copper content increases the electrical and thermal conductivity.
Page 17
Contact wear and tear of main contacts
Source: SIEMENS
© OMICRON
Above example shows a Dynamic Resistance Measurement on Open [O] operation. Overlaying the
information of contact resistance and travel (motion) over time allows to refer to the arcing contact length.
Page 18
Contact wear and tear of main contacts
Source: SIEMENS
© OMICRON
Page 19
Contact wear and tear of main contacts
© OMICRON
Page 20
CIBANO 500: 3-in-1 circuit breaker test system
Digital
Timing and
micro-ohm-meter
travel analyzer
Coil and
motor supply of 2.4 kW
© OMICRON
With CIBANO 500, OMICRON has introduced the first ever 3-in-1 test system that can be used to test all
types of circuit breakers: medium- and high-voltage breakers with live- or dead-tank design. CIBANO 500
is unique in that it combines a micro-ohmmeter, timing analyzer, and circuit breaker supply in just one system.
This enables both standard tests, such as contact resistance measurement and switching time
analysis, as well as advanced tests, such as motion analysis and dynamic resistance measurement, to be
carried out with ease.
Thanks to the integrated circuit breaker supply, the user is able to freely adjust DC voltage with CIBANO 500
as well as simulate a circuit breaker supply with undervoltage without having to change the cabling. Thus it is
possible to test the circuit breaker during the commissioning of switchgear systems where no station battery is
available.
© OMICRON Academy
Page 20
07a-Hardware-CIBANO-500+accessories
Page 21
CIBANO 500 Hardware Overview
Functional scheme
CB MC2
CIBANO 500
Digital
transmission
© OMICRON
The accessories main contact module CB MC2 and transducer node CB TN3 are powered via PoE+ (Power
over Ethernet) by the main device CIBANO 500. Over the EtherCAT® interface power supply and data
commination realized where a number of units can be connected as the based on serial bus technology.
© OMICRON Academy
Page 21
07a-Hardware-CIBANO-500+accessories
Page 22
Main contact module CB MC2
© OMICRON
The idea of main contact module CB MC2 is too minimize the wiring effort by using one module for each
phase of circuit breaker. By having 2 current output and 2 voltage measurement inputs using short cables can
be used to measure contact resistance, dynamic resistance measurement and timing tests.
The main advantage is that for all test no re-wiring is required and all wires are clearly visible arranged.
© OMICRON Academy
Page 22
07a-Hardware-CIBANO-500+accessories
Page 23
Main contact module CB MC2
2x 100 A DC
current output to
interrupting unit Visualization LED
status indication
2x voltage/
binary input
voltage inputs
© OMICRON
Voltage input 2x voltage input, one for each interrupter unit of a CB with two interrupter
units
Visualization LED Indicating the status to identify which unit connected to which phase
EtherCAT® interface power supply and data communication with CIBANO 500 main device
© OMICRON Academy
Page 23
06a-Performing-MV-HV-breakers
Page 24
Connection concept
CB MC2
CB MC2
CB MC2
CB MC2
Grounding on both sides of the interrupter unit
CIBANO 500 + 3 x CB MC2 : all tests on 3-phase circuit breakers with one or two interrupters
CIBANO 500
© OMICRON Page 24
Here a standard connection example of 3-phase SF6 Live-Tank Circuit breaker (ganged operation) shown.
Important: first always ground all interrupter units from both sides (to busbar and asset to be protected). For
each phase (with two interrupter units) on CB MC2 is connected. Use one CB TN3 and connect all 3
transducers (rotary/linear).
Connections of trip/close coils, motor and auxiliary has to be done depending on the wiring diagram of the
circuit breaker control.
© OMICRON Academy
Page 24
12a-Case-study-DRM-HV-breaker
Page 26
Details about breaker
© OMICRON
Inspection was scheduled for this 315kV Live-tank SF6 breaker during maintenance. Both measurement files
are in the chapter 10. Practical exercises:
2014-09-10_DRM-Norway-before-maintenance.ptm
2014-09-15_DRM-Norway-after-maintenance.ptm
Page 27
Function principle
© OMICRON
Page 28
Condition assessment // 2014-09-10
© OMICRON
The results of contact resistance measurement doesn’t provided much insight in the condition of the main &
arcing contacts. Just a deviation of the resistances in close position observed between the phases L1, L2, L3.
But no further assumptions can be made based on this results.
Page 29
Condition assessment // 2014-09-10
© OMICRON
First timing measurement for Close operation doesn’t provide much information so far.
Page 30
Condition assessment // 2014-09-10
© OMICRON
Page 31
Condition assessment // 2014-09-10
© OMICRON
Another DRM measurement on open sequence indicates that the second interrupter unit in shows
discontinuity of the arcing contacts which would lead to heavy arcing.
Page 32
Before maintenance
Main contacts
© OMICRON
As a result of the DRM results it was decided to take the interrupter unit to the workshop for inspection and
maintenance. Especially on the right picture heavy arcing can be observed on the main contacts at the
location of the contact fingers.
Page 33
Before maintenance
Arcing contact
© OMICRON
Page 34
After maintenance
© OMICRON
Main contact was completely renewed and the arcing contact polished.
Page 35
After maintenance // 2014-09-15
© OMICRON
After re-building the interrupter units and assembling back the breaker the measurement was repeated. The
contact resistance measurement shows now equal resistance in close positon after maintenance in all 3 poles.
Page 36
After maintenance // 2014-09-15
© OMICRON
Repeating the DRM measurements in open position show proper performance when the arcing contact is
taking over the current flow from the main contact. No interruption any more!
Page 37
After maintenance // 2014-09-15
© OMICRON
Same measurement with view of currents over time instead of contact resistance.
38
Assessment examples
Time-optimized circuit breaker diagnostics with CIBANO 500
© OMICRON
© OMICRON
© OMICRON
© OMICRON
This dynamic resistance measurement during opening of the circuit breaker shows that the main contact could
have something. Normally when the movement starts there will be a small change in the resistance due to
friction and a bigger increase of the resistance when the transaction from main contact to arcing contact takes
place, but in this case the bigger change is taking place immediately when the contact travel starts. This
indicates that there is either a contact problem i.e. loose main contacts (fingers) or the main contact has
contamination on the surface due to wear. But it could also be that the clamps are not correct mounted and
are moving due to the vibration during operation.
© OMICRON
© OMICRON
The dynamic resistance measurement during closing of the circuit breaker shows that the contamination of the
main contact surface can be excluded as the behavior is continuing also after that the main contact has reach
it end position. This indicates more in direction loose main contacts (fingers) or badly mounted clamps.
© OMICRON
This dynamic resistance measurement during opening of the circuit breaker shows that the main contact for
phase LB has something. In this measurement the resistance change is small when the contact travel starts
(due to friction), which is okay, but when the transaction from main contact to arcing contact takes place the
resistance value starts to have high peaks until the arcing contact is opened. This indicates that there is
probably a contact problem e.g. arcing contact in bad condition due to wear. The next slides shows the same
even clearer when the current trace is enabled instead.
discontinuity
on red phase
© OMICRON
Above DRM measurement on a SF6 MV Circuit breaker shows a good example of discontinuity of one phase.
For a short moment the main contact losses continuity before the arcing contact is taking over which can lead
to serious arcing and heavy wear off the main contacts.
Measurement of contact resistance in both states open-close would show any problem.
travel (mm)
DRM (Ω)
© OMICRON
Above shows the same before on an Open sequence and corresponding DRM measurement but just
animated.