JKF8-Intelligent Low Volatage Reactive Power Automatic Compensating Controller-Catalog
JKF8-Intelligent Low Volatage Reactive Power Automatic Compensating Controller-Catalog
2. Type designation
JK F 8- , (50Hz or 60Hz)
Rated voltage:380V,440V,220V,240V
Low-Voltage
Reactive Power Compensation Controller Series
3. Features
JKF8 Intelligent Low-Voltage 3.4 In case the voltage of the electrical power network is lower
Reactive Power than 300 V, or exceeds the preset over-voltage protection value,the
connected capacitor banks will be automatically and rapidly(5 sec.)
Compensation Controller disconnected in steps, and the voltage value will be displayed.
3.5 In case the signal from the secondary coil of the current
1. General transformer is smaller than 150 m A, the controller will prevent
any more capacitor from being connected, in the mean time,
JKF8 Intelligent Low-Voltage
automatically and rapidly (5 sec.)disconnect the connected capacitor
Reactive Power Compensation Controller (hereinafter referred to as
banks step-wise.
'controller' ) is a dedicated controller which can make compensations
for the reactive power of low voltage distribution system.
3.6 Switching (opening/closing control of the contactor) prevention
time for the same group of capacitors is 3 minutes(capacitor
discharge duration)
4. Operating conditions
5. Technical data
Parameters Technical Specifications
Low-current capacitor
connection prevention ≤150 mA
Full automation mode (displayed code F-0: 1): no need to set the capacitor connection threshold
or the capacitor disconnection threshold.
Preset mode Manual setup mode(displayed code F-0: 0): need to set the capacitor connection threshold and
the capacitor disconnection threshold manually.
Capacitor connection Full automation mode: capacitor banks in the smallest step
threshold Manual mode: preset value for reactive power: 1~120 kvar (preset value in factory: 10kvar)
Capacitor disconnection threshold Power factor, 0.85 ~ -0.95 continuously adjustable (preset value in factory: 1.00)
Over-voltage threshold 400 V~456 V (preset value in factory: 430 V), 230V~270V (preset value in factory: 250 V)
6. Wiring diagram
10 ls1
8
A B C N
7 Us1
6 Us2
5 H
Low voltatge side
3 COM L
1 11
5A 1A 1A
P P
J1 J12
To load control panel
6.1 Connection terminal US1 and US2 are to be connected to the sampling voltage. AC 400 V or AC 220V shall be connected.
6.2 Terminal IS1 and IS2 are to be connected to the sampling current, which shall be sampled from the transformed current generated by the current
transformer for the load, and which shall not be in-phase with US1 and US2(if A is for current, then B and C are for voltage).
6.3 Terminal COM is the common shared terminal to be connected to number 1 to 12 relays in the output lines of the controller, and each of the
terminals 1~12 is to be connected to the output control line to control the respective contactor in the respective compensation loop of the capacitor
panel.
6.4 If the coil voltage of the contactor J is 230 V, then Point P is connected to Phase N. If the coil voltage of the contactor Jis 400 V, then Point P is
connected to Phase C(as long as it is not in-phase with terminal COM).
6.5 FU1~3 are to be connected to fusers which are supplied by the user.
7. Description of parameters
7.1 Description of dynamic parameters
If the measured value is out of the display range, the approximate value
Q Reactive power kVar
will be displayed,e.g,1360 Kvar is displayed as E14.
If the measured value is out of the display range, the approximate value
P Active power kW
will be displayed,e.g,1360 kW is displayed as E14.
1 full automation
F-0 Preset mode 1or0 1 -
0 manual setup
F-2 Target power factor 0.85~-0.95 1.00 0.01 "-"stands for system capacity
120mm
113mm±0.5mm
120mm
130mm 113mm±0.5mm
Boring dimension
9. Ordering information
On ordering, please clarify rated voltage, number of phase, frequency, etc of the products;
and associated conditions at the mounting place.