0% found this document useful (0 votes)
12 views

CIFX-RE_usermanual_en

Uploaded by

kuka
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
12 views

CIFX-RE_usermanual_en

Uploaded by

kuka
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 94

User Manual

CIFX Cards Real Time Ethernet

Installation, Operation and Hardware Description

Language: English

www.hilscher.com
Communication Interface Hilscher cifX-RE Table of Contents • 2

Table of Contents
1 INTRODUCTION.........................................................................................................6
1.1 About the User Manual ...............................................................................................6
1.1.1 List of Revisions ...................................................................................................7
1.1.2 Reference on Hardware and Software .................................................................8
1.1.3 Conventions in this Manual ..................................................................................8
1.2 Contents of the Product CD........................................................................................9
1.2.1 Directory Structure of the CD ...............................................................................9
1.2.2 Documentations cifX Cards................................................................................10
1.3 Legal Notes...............................................................................................................11
1.3.1 Guarantee...........................................................................................................11
1.3.2 Registered Trademarks......................................................................................11
1.4 Licenses....................................................................................................................11

2 SAFETY ....................................................................................................................12
2.1 Intended Use ............................................................................................................12
2.2 Personnel Qualification.............................................................................................13
2.3 Labeling of Safety Instructions..................................................................................13
2.4 Safety Instructions ....................................................................................................14
2.4.1 Electrical Current ................................................................................................14
2.4.2 Electrostatic Discharge.......................................................................................14
2.5 Safety Instructions USA............................................................................................15
2.5.1 Electrical Current ................................................................................................15
2.5.2 Electrostatic Discharge.......................................................................................15

3 DESCRIPTION AND REQUIREMENTS ...................................................................16


3.1 Description................................................................................................................16
3.2 System Requirements ..............................................................................................17
3.3 Requirements for Operation .....................................................................................18
3.3.1 cifX Slave Device................................................................................................18
3.3.2 cifX Master Device..............................................................................................18

4 GETTING STARTET .................................................................................................19


4.1 Steps how to install and configure cifX Slave Devices .............................................19
4.2 Steps how to install and configure cifX Master Devices ...........................................20

5 INSTALLING CIFX CARD .........................................................................................21


5.1 Safety Advices ..........................................................................................................21
5.1.1 Safety Advices USA ...........................................................................................21
5.2 CIFX 50-RE and CIFX 50E-RE.................................................................................22
5.2.1 Fix Front Plate Sticker ........................................................................................23

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 8 – UM:CIFX-RE#EN – 2008/05
Communication Interface Hilscher cifX-RE Table of Contents • 3
5.3 CIFX 80-RE ..............................................................................................................24
5.3.1 Fix Front Plate Sticker ........................................................................................25
5.4 CIFX 90-RE ..............................................................................................................26
5.5 CIFX 104C-RE and CIFX 104C-RE-R ......................................................................27
5.6 CIFX 104C-RE\F and CIFX 104C-RE-R\F................................................................27

6 INSTALLING SOFTWARE ........................................................................................28


6.1 Installing cifX Device Driver ......................................................................................28
6.2 Installing the netX Configuration and Diagnostic Utility ............................................33
6.3 Installing SYCON.net................................................................................................33

7 NETX CONFIGURATION AND DIAGNOSTIC UTILITY............................................34


7.1 Configuration Steps cifX Card ..................................................................................34
7.2 Starting netX Configuration and Diagnostic Utility ....................................................35
7.3 Introduction to the Dialog Structure ..........................................................................35
7.3.1 General Buttons..................................................................................................37
7.3.2 Help ....................................................................................................................37
7.3.3 Status Line..........................................................................................................38
7.4 Working with netX Configuration and Diagnostic Utility ............................................39
7.4.1 Selecting Language / Firmware, downloading Firmware ...................................40
7.4.2 Configuration ......................................................................................................41
7.4.3 Diagnostics .........................................................................................................43

8 TROUBLESHOOTING ..............................................................................................47

9 DEVICE DRAWINGS AND CONNECTIONS ............................................................48


9.1 Device Drawing CIFX 50-RE ....................................................................................48
9.2 Device Drawing CIFX 50E-RE ..................................................................................48
9.3 Device Drawing CIFX 80-RE ....................................................................................49
9.4 Device Drawing CIFX 90-RE ....................................................................................49
9.5 Device Drawing CIFX 104C-RE................................................................................50
9.6 Device Drawing CIFX 104C-RE-R ............................................................................50
9.7 Device Drawing CIFX 104C-RE\F ............................................................................51
9.8 Device Drawing CIFX 104C-RE-R\F.........................................................................51
9.9 Device Drawing Connection Interface AIFX-RE .......................................................52
9.10 Device Drawing Diagnosis Interface AIFX-DIAG ......................................................52
9.11 Ethernet Interface .....................................................................................................53
9.11.1 Ethernet pinning at the RJ45 Socket..................................................................53
9.11.2 Ethernet Connection Data ..................................................................................53
9.11.3 Use of Hubs and Switches .................................................................................54
9.12 Mini-B USB Connector (5 Pin) ..................................................................................55
9.13 Rotary Switch for Slot Number .................................................................................55

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Table of Contents • 4
9.14 Cable Connector.......................................................................................................56
9.14.1 Pinning for Cable Connector Ethernet................................................................56
9.14.2 Pinning for Cable Connector DIAG ....................................................................57
9.14.3 Pinning for SYNC Connector, X51 .....................................................................57

10 LED ...........................................................................................................................58
10.1 LED Real Time Ethernet Systems ............................................................................58
10.1.1 LED Names for each Real Time Ethernet System.............................................58
10.1.2 LED EtherCAT Master........................................................................................59
10.1.3 LED EtherCAT Slave..........................................................................................60
10.1.4 LED EtherNet/IP Scanner (Master) ....................................................................61
10.1.5 LED EtherNet/IP Adapter (Slave).......................................................................62
10.1.6 LED Open Modbus/TCP.....................................................................................63
10.1.7 LED Powerlink Controlled Node / Slave.............................................................64
10.1.8 LED PROFINET IO-RT Controller......................................................................65
10.1.9 LED PROFINET IO-RT-Device ..........................................................................66
10.1.10 LED SERCOS III Slave ......................................................................................67

11 TECHNICAL DATA ...................................................................................................68


11.1 Technical Data cifX Real-Time Ethernet Cards ........................................................68
11.1.1 CIFX 50-RE ........................................................................................................68
11.1.2 CIFX 50E-RE......................................................................................................69
11.1.3 CIFX 80-RE ........................................................................................................70
11.1.4 CIFX 90-RE ........................................................................................................71
11.1.5 CIFX 104C-RE, CIFX 104C-RE-R, CIFX 104C-RE\F, CIFX 104C-RE-R\F .....72
11.1.6 AIFX-RE .............................................................................................................73
11.1.7 AIFX-DIAG..........................................................................................................73
11.2 Protocols...................................................................................................................74
11.2.1 EtherCAT Master................................................................................................74
11.2.2 EtherCAT Slave..................................................................................................74
11.2.3 EtherNet/IP Scanner (Master) ............................................................................75
11.2.4 EtherNet/IP Adapter (Slave)...............................................................................76
11.2.5 Open Modbus/TCP.............................................................................................77
11.2.6 Powerlink Controlled Node / Slave.....................................................................77
11.2.7 PROFINET IO-RT-Controller..............................................................................78
11.2.8 PROFINET IO-RT-Device ..................................................................................79
11.2.9 SERCOS III Slave ..............................................................................................80

12 CONFIGURATION PARAMETERS...........................................................................81
12.1.1 EtherCAT Slave Parameters ..............................................................................81
12.1.2 EtherNet/IP Adapter Parameters........................................................................82
12.1.3 Open Modbus/TCP Parameters .........................................................................84
12.1.4 Powerlink Controlled Node / Slave Parameters .................................................86
12.1.5 PROFINET IO-Device Parameters.....................................................................88
12.1.6 SERCOS III Slave Parameters...........................................................................89

13 LISTS ........................................................................................................................90
13.1 List of Figures ...........................................................................................................90

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Table of Contents • 5
13.2 List of Tables ............................................................................................................91

14 GLOSSARY...............................................................................................................93

15 CONTACTS...............................................................................................................94

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Introduction • 6

1 Introduction
1.1 About the User Manual
This user manual contains descriptions of the installation, operation and
hardware of Real Time Ethernet cifX cards under Windows ®
2000/Windows®.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Introduction • 7

1.1.1 List of Revisions


Index Date Chapter Revisions
1 17 May all created
2006
2 13 June 2, 4, 7 actualized according to ANSI Z 535.6,
2007 LED description actualized
1, 3, 4, 7, Descriptions for the cards CIFX 50E-RE, CIFX 90-RE,
8 CIFX 104C-RE, CIFX 104C-RE-R, CIFX 104C-RE\F, CIFX 104C-RE-R\F completed,
Descriptions for SERCOS III Slave added
3 27.06.07 7.1.3 Description MS and NS LED EtherNet/IP Adapter (Slave) adapted
4 01.08.07 all EtherCAT Master, EtherNet/IP Scanner (Master) added,
3.4 – 3.11 Notice to LED at RJ45 socket added
5 15.08.07 1.2, 1.3, Information and description to the System configurator SYCON.net added,
1.8, 3.1,
3.3, 5.1, 6
1.8 Information for Master license added,
2.1., 7.1.1, Information for PROFINET IO-RT-Controller added,
8.1, 8.2.1,
8.2.2
8.2.3 Protocol data for EtherCAT-Master added.
6 15.02.08 All Descriptions, data and drawings for the CIFX 80-RE card Descriptions
1 Chapter „Introduction“ actualized,
2.1 Section „Intended Use“ actualized,
2.4 Section „Safety Instructions“ actualized,
3 Chapter „Description and Requirements“ adapted,
4 Chapter „Getting Startet“ added,
5.4 Section “CIFX 104C-RE and CIFX 104C-RE-R” adapted,
6 Chapter „Installing Software“ descriptions to the cifX Device Driver and cifX Driver
Setup inserted,
7 Chapter „Troubleshooting “actualized,
8 Chapter „Device Drawings and Connections“ here inserted and actualized,
9.1.1 Section „LED PROFINET IO-RT Controller“ adapted.
9.1.2 Section „ LEDs PROFINET IO-RT-Device “ actualized.
10.2 Section „Protocols“ actualized,
7 05.05.08 All Descriptions for Powerlink, Open Modbus/TCP and SERCOS III Slave added;
Descriptions to the cifX Driver Setup erased,
Descriptions to the netX Configuration and Diagnostic Utility inserted,
1 Chapte „Introductionl“ actualized,
2.1 Section „Intended Use“ actualized,
3 Chapter „Description and Requirements“ actualized,
4 Chapter „Getting startet“ actualized,
5 Chapter „Installing CIFX Cards“ actualized,
6 Chapter „Installing Software“ actualized,
7 Chapter „netX Configuration and Diagnostic Utility“ added and actualized.
11 Chapter „Technical Data“ actualized,
12 Chapter „Configuration Parameter“ added and actualized.
14 Glossary added
8 21.05.08 1 Chapte „Introductionl“ actualized,
3 Chapter „Description and Requirements“ actualized,
4 Chapter „Getting startet“ actualized,
5 Chapter „Installing CIFX Cards“ actualized,
6 Chapter „Installing Software“ actualized,
7 Chapter „netX Configuration and Diagnostic Utility“ added and actualized.
10 Chapter „LED“ actualized
9 09.06.08 4.2 Section “Steps how to install and configure cifX Master Devices” actualized,
9.11.3 Section “Use of Hubs and Switches” actualized,
10.1.7 Section “LED Powerlink Controlled Node / Slave” actualized,
11.2 Section “Protocols” actualized,
12 Configuration parameters Real-Time-Ethernet-Systems actualized.,
Table 1: List of Revisions

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Introduction • 8

1.1.2 Reference on Hardware and Software


Card Type Device
CIFX 50-RE Revision 2
CIFX 50E-RE Revision 1
CIFX 80-RE Revision 1
CIFX 90-RE Revision 2
CIFX 104C-RE Revision 3
CIFX 104C-RE-R Revision 3
CIFX 104C-RE\F Revision 3
CIFX 104C-RE-R\F Revision 3
AIFX-RE Revision 2
AIFX-DIAG Revision 1
Table 2: Reference on Hardware

Software

Software Software Version


netX Configuration and Diagnostic Utility-Setup:
netXSetup.exe 1.1.0.49
Table 3: Reference on Software

1.1.3 Conventions in this Manual


Operating Instructions, a result of an operation step or notes are marked as
follows:

Operating Instructions:
¾ <instruction>

Or

1. <instruction>
2. <instruction>

Results:
° <result>

Notes:

Note: <note>

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Introduction • 9

1.2 Contents of the Product CD


The Product CD for the Communication InterFaces cifX contains:
• cifX Device Driver
• netX Configuration and Diagnostic Utility setup including the
loadable Firmware
• System configurator SYCON.net
• Device Description Files (GSDML, EDS, XML, XDD)
• Documentation

1.2.1 Directory Structure of the CD


All manuals on this CD are delivered in the Adobe Acrobat® Reader format
(PDF).

Directory Name Description


API Toolkit, Header Files and cifX32DLL.lib
Documentation Documentation in the Acrobat® Reader Format (PDF)
Driver cifX Device Driver
EDS Device Description File
Firmware Loadable Firmware
Software cifX Configuration and Diagnostic Utility,
System Configurator SYCON.net (configuration and diagnostic
program)
Table 4: Directory Structure of the CD

1.2.1.1 Device Description Files


The CD Rom includes the device description files for the following Slave
devices:

Real Time Ethernet Name / Extension


EtherCAT Slave DDF, XML
EtherNet/IP Adapter (Slave) EDS
Powerlink Controlled Node / Slave XDD
PROFINET IO-RT-Device GSDML/XML
Table 5: Device Description Files

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Introduction • 10

1.2.2 Documentations cifX Cards


The following documentation overview gives information, for which items
you can find further information in which manual.

Manual Contents Document name


User Manual, Installation, Operation and Hardware CIFX-RE_usermanual_en.pdf
CIFX Cards Real Time Description
Ethernet
Operating Instruction Manual SYCON.net Frame Application SYCONnet_netFrame_en.pdf
Operating Instruction Manual FDT Container SYCONnet_netDevice_en.pdf
Operating Instruction Manual DTM for EtherCAT Master EtherCAT_Master_DTM_en.pdf*
Operating Instruction Manual Generic EtherCAT Slave DTM EtherCAT_Slave_DTM_en.pdf*
for EtherCAT Slave Devices
Operating Instruction Manual DTM for EtherNet/IP Scanner Devices EtherNetIP_Scanner_DTM_en.pdf
Operating Instruction Manual DTM for EtherNet/IP Adapter Devices EtherNetIP_Adapter_DTM_en.pdf
Operating Instruction Manual Generic EtherNet/IP Adapter DTM for EtherNetIP_GenericAdapter_DTM_en.pdf
EtherNet/IP Adapter Devices and Modular
Generic EtherNet/IP Adapter DTM for
modular EtherNet/IP Adapter Devices
Operating Instruction Manual DTM for Hilscher PROFINET IO-Controller PROFINET_IO_Controller_DTM_en.pdf
Operating Instruction Manual DTM for Hilscher PROFINET IO-Devices PROFINET_IO_Device_DTM_en.pdf
Operating Instruction Manual Generic DTM for PROFINET IO Devices PROFINET_IO_GenericDevice_DTM_en.pdf
Table 6: Documentations cifX Devices Real Time Ethernet

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Introduction • 11

1.3 Legal Notes


1.3.1 Guarantee
Although the cifX cards CIFX 50-RE, CIFX 50E-RE, CIFX 80-RE, CIFX 90-
RE, the devices of the family CIFX 104C-RE and the AIFX-RE and AIFX-
DIAG interfaces as well as the driver program have been developed with
great care and has been thoroughly tested, Hilscher Gesellschaft für
Systemautomation mbH cannot guarantee the suitability of these boards for
any purpose not confirmed by us in writing.
Guarantee claims shall be limited to the right to require rectification. Liability
for any damage which may have arisen from the use of this hard and
software or its documentation shall be limited to cases of intent.

1.3.2 Registered Trademarks


Windows® 2000 / Windows® XP are registered trademarks of Microsoft
Corporation.

1.4 Licenses
If a cifX card is used as a slave, neither for the firmware nor for the
configurator SYCON.net a license is required.
Licenses are required, if the cifX card is used with
• a firmware with master functionality*,
• an OPC server.
* The master license includes the card operating as master and the license
for the configurator SYCON.net for the respective card.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Safety • 12

2 Safety
2.1 Intended Use
The cifX cards
• CIFX 50-RE, CIFX 50E-RE
• CIFX 80-RE
• CIFX 90-RE
• CIFX 104C-RE, CIFX 104C-RE-R
• CIFX 104C-RE\F, CIFX 104C-RE-R\F
described in this user manual are PC cards for real-time Ethernet
communication. Depending from the loaded firmware, the real time
Ethernet systems listed hereafter can be realized using the cifX card:
• EtherCAT Master
• EtherCAT Slave
• EtherNet/IP Scanner (Master)
• EtherNet/IP Adapter (Slave)
• Open Modbus/TCP
• Powerlink Controlled Node / Slave
• PROFINET IO-RT-Controller
• PROFINET IO-RT-Device
• SERCOS III Slave
The interfaces
• AIFX-RE
• AIFX-DIAG
are used for connection to the CIFX 90-RE card or the devices of the family
CIFX 104C-RE.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Safety • 13

2.2 Personnel Qualification


The cifX card must only be installed, configured and removed by qualified
personnel.

2.3 Labeling of Safety Instructions


The safety instructions are pinpointed particularly. The instructions are
highlighted with a specific safety symbol, a warning triangle and a signal
word according to the degree of endangerment. Inside the note the danger
is exactly named. Instructions to a property damage message do not
contain a warning triangle.

Symbol Sort of Warning or Principle


Safety symbol for the warning to personal injury

Warning of danger by electrical current

Warning of damages by electrostatic discharge

Table 7: Safety Symbols and Sort of Warning or Principle

2.3.1.1 Signal Words


Signal Word Meaning
DANGER indicates a direct hazard with high risk, which will have as consequence
death or grievous bodily harm if it isn't avoided.
The use of this signal word shall be restricted to extremely hazard.
Remark: The signal word may not be used in case of danger of pure
property damages.
WARNING indicates a possible hazard with medium risk, which will have as
consequence death or (grievous) bodily harm if it isn't avoided.
Remark: The signal word may not be used in case of danger of pure
property damages.
CAUTION indicates a minor hazard with medium risk, which could have as
consequence simple battery if it isn't avoided.
Note Indicates an important note in the manual.
Table 8: Signal Words

2.3.1.2 Signal Words USA


Signal Word Meaning
DANGER Indicates a Hazardous Situation Which, if not Avoided, will Result in Death
or Serious Injury.
WARNING Indicates a Hazardous Situation Which, if not Avoided, could Result in
Death or Serious Injury.
CAUTION Indicates a Hazardous Situation Which, if not Avoided, may Result in
Minor or Moderate Injury.
NOTICE Indicates a Property Damage Message.
Note Indicates an Important Note in the Manual.
Table 9: Signal Words according to ANSI
Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim
Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Safety • 14

2.4 Safety Instructions


This manual contains instructions which must be observed to ensure your
own personal safety and to avoid damage to devices.

2.4.1 Electrical Current


Electrocution
ƒ Disconnect the power plug of the PC and make sure, that the PC is
WARNING! current-free.
ƒ Only after disconnecting power open the PC cabinet and install or
remove the cifX card.

Device Destruction!
ƒ Use only 3.3 V for power supply to operate the card.
CAUTION! Operation with 5 V power supply leads to device destruction.
Also all I/O signals are only 3.3V tolerant.

The cifX card may not be powered by a 5 V power supply! The cifX card
may only be powered by a 3.3 V power supply. The use of a higher supply
voltage than 3.3V may result in severe damage to the cifX card! Further, all
signal pins require 3.3V signaling voltage and are not 5 V tolerant!

2.4.2 Electrostatic Discharge


Adhere to the necessary safety precautions for components that are
vulnerable with electrostatic discharge (EN 61340-5-1 und EN 61340-5-2
as well as IEC 61340-5-1 und IEC 61340-5-2).

Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which cause
CAUTION! internal damage and affect normal operation. Follow guidelines when you
handle this equipment:
ƒ Touch a grounded object to discharge potential static.
ƒ Wear an approved grounding wriststrap.
ƒ Do not touch connectors or pins on component boards.
ƒ Do not touch circuit components inside the equipment.
ƒ If available, use a static-safe workstation.
ƒ When not in use, store the equipment in appropriate static-safe
packaging.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Safety • 15

2.5 Safety Instructions USA


This manual contains instructions which must be observed to ensure your
own personal safety and to avoid damage to devices.

2.5.1 Electrical Current

Electrocution
ƒ Disconnect the power plug of the PC and make sure, that the PC is
current-free.
ƒ Only after disconnecting power open the PC cabinet and install or
remove the cifX card.

Device Destruction!
ƒ Use only 3.3 V for power supply to operate the card.
Operation with 5 V power supply leads to device destruction.
Also all I/O signals are only 3.3V tolerant.

The cifX card may not be powered by a 5 V power supply! The cifX card
may only be powered by a 3.3 V power supply. The use of a higher supply
voltage than 3.3V may result in severe damage to the cifX card! Further, all
signal pins require 3.3V signaling voltage and are not 5 V tolerant!

2.5.2 Electrostatic Discharge


Adhere to the necessary safety precautions for components that are
vulnerable with electrostatic discharge (EN 61340-5-1 und EN 61340-5-2
as well as IEC 61340-5-1 und IEC 61340-5-2).

Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which cause
internal damage and affect normal operation. Follow guidelines when you
handle this equipment:
ƒ Touch a grounded object to discharge potential static.
ƒ Wear an approved grounding wriststrap.
ƒ Do not touch connectors or pins on component boards.
ƒ Do not touch circuit components inside the equipment.
ƒ If available, use a static-safe workstation.
ƒ When not in use, store the equipment in appropriate static-safe
packaging.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Description and Requirements • 16

3 Description and Requirements


3.1 Description
The cifX devices described in this user manual are PC cards for real-time
Ethernet communication. Depending of the loaded firmware, the cifX card
proceeds the communication of one of the following real time Ethernet
systems:
• EtherCAT Master
• EtherCAT Slave
• EtherNet/IP Scanner (Master)
• EtherNet/IP Adapter (Slave)
• Open Modbus/TCP
• Powerlink Controlled Node / Slave
• PROFINET IO-RT-Controller
• PROFINET IO-RT-Device
• SERCOS III Slave
The cifX handles the complete data exchange between the connected
Ethernet devices and the PC. The data exchange is proceeded via dual-
port memory.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Description and Requirements • 17

3.2 System Requirements


1. Windows® 2000 / Windows® XP
2. PC with PCI connector (3.3 V)

Type of Card PCI Connector


CIFX 50-RE PCI slot (3,3 V)
CIFX 50E-RE PCI Express X1 slot (3,3 V),
X1 = Single Lane
CIFX 80-RE Compact PCI (3,3 V)
CIFX 90-RE Mini PCI Socket (3,3 V), Type III System Connector
CIFX 104C-RE PCI Slot for PC/104 cards (3,3 V)
CIFX 104C-RE-R
CIFX 104C-RE\F
CIFX 104C-RE-R\F

Table 10: PCI Connector for cifX cards

3. CD ROM drive
4. Graphic resolution: min. 1024 x 768 pixel or higher
5. Keyboard and Mouse

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Description and Requirements • 18

3.3 Requirements for Operation


3.3.1 cifX Slave Device
For cifX Slave device operation the following requirements must be fulfilled:

Protocols EtherCAT-Slave,
EtherNet/IP-Adapter (Slave),
Open Modbus/TCP,
Powerlink Controlled Node / Slave,
PROFINET IO-Device,
SERCOS III-Slave
Software 1. The cifX Device Driver must be installed (from V0.933).
Installation 2. The netX Configuration and Diagnostic Utility program must be
installed.
Firmware- 3. Using the netX Configuration and Diagnostic Utility program,
Download the user must select the firmware which is to be loaded to the cifX
Slave device.
Parameter Setting 4. The cifX Slave device must be parameterized using one of the
following options:
• netX Configuration and Diagnostic Utility program
• Application program (programming required)
Communication 5. For the communication a Master for the respective communication
system is required.

Table 11: Requirements for cifX Slave Device Operation

3.3.2 cifX Master Device


For cifX Master device operation the following requirements must be
fulfilled:

Protocols EtherCAT-Master,
EtherNet/IP-Scanner (Master),
PROFINET IO-Controller
Software 1. The cifX Device Driver must be installed (from V0.933).
Installation
Firmware- 3. Using the system configurator SYCON.net, the user must select
Download the firmware which is to be loaded to the cifX Master device.
Configuration 4. The cifX Master device must be configured using one of the
following options:
• System configurator SYCON.net
• Application program (programming required)
Communication For communication slave devices for the used communcation system
are required.

Table 12: Preconditions for cifX Master Device Operation

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Getting Startet • 19

4 Getting Startet
4.1 Steps how to install and configure cifX Slave Devices
The following table describes the steps to configure a cifX Slave device as
it is typical for many cases.

# Step Description For detailed information Page


see section
1 Hardware Installation Installing cifX Slave device: Installing cifX Card 21
Disconnect the power plug of the PC.
Open the cabinet of the PC.
If necessary, glue enclosed sticker on the front
plate.
Plug in and mount the cifX Slave device.
If necessary, connect a connection or a
diagnosis interface.
Close the PC casing.
Connect the PC to the power supply and switch
on the PC.
2 cifX Device Driver Windows® recognizes a new hardware and Installing cifX Device Driver 28
Installation requires the device driver, which is on the CD-
ROM cifX.
Enter the CD-ROM cifX in the PC and follow to
the instructions of the installation wizard, to
install the driver.
3 netX Configuration and Start the netX Utility setup program to install Installing the netX 33
Diagnostic Utility the netX Configuration and Diagnostic Configuration and
Installation Utility. Diagnostic Utility
4 Setting cifX Slave In the netX Configuration and Diagnostic Configuration Steps cifX 34
Device Parameters Utility: Card
- Select the language,
- Select and download the firmware,
- Setting the cifX Slave Device parameters.
Table 13: Installation and Configuration Steps cifX Slave Device

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Getting Startet • 20

4.2 Steps how to install and configure cifX Master Devices


The following table describes the steps to configure a cifX Master device as
it is typical for many cases.

# Step Description For detailed information Page


see section
1 Hardware Installation Installing cifX Master device: Installing cifX Card 21
Disconnect the power plug of the PC.
Open the cabinet of the PC.
If necessary, glue enclosed sticker on the front
plate.
Plug in and mount the cifX Master device.
If necessary, connect a connection or a
diagnosis interface.
Close the PC casing.
Connect the PC to the power supply and switch
on the PC.
2 cifX Device Driver Windows® recognizes a new hardware and Installing cifX Device Driver 28
Installation requires the device driver, which is on the CD-
ROM cifX.
Enter the CD-ROM cifX in the PC and follow to
the instructions of the installation wizard.
3 SYCON.net Installation Run the SYCON.net-Setup. Installing SYCON.net 33
4 Firmware Download - Start system configurator SYCON.net. See corresponding user 10
- Select driver and assign device. manual under
- Select and download the firmware. Documentations cifX Cards
5 Configuration - Configure the cifX Master device.
cifX Master device
6 Download Configuration - Download the configuration to the cifX Master
device *.
(*EtherCAT-Master, EtherNet/IP-Scanner
(Master), PROFINET IO-Controller)
7 Diagnostic - Righclick on device symbol.
- Select context menu entry Diagnosis,
- then select Diagnosis > Station Diagnosis
- or Master Diagnosis.
8 I/O Monitor - Righclick on device symbol.
- Select context menu entry Diagnosis,
- then Additional Tools > IO Monitor.
- Check the input or output data.
Table 14: Installation and Configuration Steps cifX Master Device

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Installing cifX Card • 21

5 Installing cifX Card


5.1 Safety Advices
Obey to the following safety advices, when installing the cifX card.

Electrocution
ƒ Disconnect the power plug of the PC and make sure, that the PC is
WARNING! current-free.
ƒ Only after disconnecting power open the PC cabinet and install or
remove the cifX card.

Device Destruction!
ƒ Use only 3.3 V for power supply to operate the card.
CAUTION! Operation with 5 V power supply leads to device destruction.
Also all I/O signals are only 3.3V tolerant.

Damage from electrostatic Discharge


ƒ To prevent damage to the PC and the cifX, make sure, that the cifX card
CAUTION! is grounded via the endplate and the PC and make sure, that you are
discharged when you mount/demount the cifX card.

5.1.1 Safety Advices USA


Obey to the following safety advices, when installing the cifX card.

Electrocution
ƒ Disconnect the power plug of the PC and make sure, that the PC is
current-free.
ƒ Only after disconnecting power open the PC cabinet and install or
remove the cifX card.

Device Destruction!
ƒ Use only 3.3 V for power supply to operate the card.
Operation with 5 V power supply leads to device destruction.
Also all I/O signals are only 3.3V tolerant.

Damage from electrostatic Discharge


ƒ To prevent damage to the PC and the cifX, make sure, that the cifX card
is grounded via the endplate and the PC and make sure, that you are
discharged when you mount/demount the cifX card.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Installing cifX Card • 22

5.2 CIFX 50-RE and CIFX 50E-RE


For installation of the CIFX 50-RE or CIFX 50E-RE card handle as follows:
1. Use the sticker according to the firmware and glew it on the front of the
CIFX 50-RE or CIFX 50E-RE card (see section Fix Front Plate Sticker
on page 23).
2. Disconnect the power plug of the PC.
3. Open the cabinet of the PC.
4. Plug in the CIFX 50-RE card on a free PCI slot,
or plug in the CIFX 50E-RE card on a free PCI express slot.
5. Fix the CIFX 50-RE or CIFX 50E-RE card using the hole intended.
6. Close the PC casing.
7. Connect the PC to the power supply and switch on the PC.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Installing cifX Card • 23

5.2.1 Fix Front Plate Sticker


Note: Your cifX card set contains a set of front plate stickers (6 different
stickers). Depending from the loaded firmware the label on each sticker
indicates the names of the respective system and communication status
LED or of the LED of the RJ45 Ethernet female connector. (Further
information to this question you find also in section LED Real Time
Ethernet Systems beginning from page 58.)

Front Plate Stickers for CIFX 50-RE and CIFX 50E-RE:

Figure 1: Front Plate Stickers for CIFX 50-RE and CIFX 50E-RE for the labeling of the card
LED or of the LED of the Ethernet female connector

PROFINET IO
Modbus/TCP
EtherNet/IP

SERCOS III
Powerlink
EtherCAT

EtherCAT

cifX-LED
Master

Slave

Open

SYS (yellow / green) SYS SYS SYS SYS SYS SYS SYS
COM 0 (red/ green) RUN RUN MS BS RUN SF STA
COM 2 (red/ green) ERR ERR NS BE ERR BF ERR
RJ45 green LINK L/A IN LINK L/A LINK LINK L/A
Ch0
yellow ACT - ACT - ACT RX/TX -
RJ45 green - L/A OUT LINK L/A LINK LINK L/A
Ch1
yellow - - ACT - ACT RX/TX -
Table 15: cifX LED Labeling depending of the loaded Firmware

¾ Use the sticker according to the firmware and glew it on the front of the
CIFX 50-RE or CIFX 50E-RE card.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Installing cifX Card • 24

5.3 CIFX 80-RE


For installation of the CIFX 80-RE card handle as follows:
1. Use the sticker according to the firmware and glew it on the front of the
CIFX 80-RE card (see section Fix Front Plate Sticker on page 25).
2. Disconnect the power plug of the PC.
3. Open the cabinet of the PC and remove blank plate.
4. Put down the ejection lever at the CIFX 80-RE card.
5. Plug in the CIFX 80-RE card to a free compact PCI slot.
6. Fasten the CIFX 80-RE card.
¾ Tip up the lever and click in.
¾ Screw the CIFX 80-RE card with two screws onto the wholes above and
below.
7. Close the PC casing.
8. Connect the PC to the power supply and switch on the PC.

Note: To remove the CIFX 80-RE card from the compact PCI slot, first
press the grey button at the ejection lever and then press the ejection lever
downwards.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Installing cifX Card • 25

5.3.1 Fix Front Plate Sticker


Note: Your cifX card set contains a set of front plate stickers (6 different
stickers). Depending from the loaded firmware the label on each sticker
indicates the names of the respective system and communication status
LED or of the LED of the RJ45 Ethernet female connector. (Further
information to this question you find also in section LED Real Time
Ethernet Systems beginning from page 58.)

PROFINET IO
Modbus/TCP
EtherNet/IP

SERCOS III
Powerlink
EtherCAT

EtherCAT
cifX-LED
Master

Slave

Open
SYS (yellow / green) SYS SYS SYS SYS SYS SYS SYS
COM 0 (red/ green) RUN RUN MS BS RUN SF STA
COM 1 (red/ green) ERR ERR NS BE ERR BF ERR
RJ45 green LINK L/A IN LINK L/A LINK LINK L/A
Ch0
yellow ACT - ACT - ACT RX/TX -
RJ45 green - L/A OUT LINK L/A LINK LINK L/A
Ch1
yellow - - ACT - ACT RX/TX -
Table 16: cifX LED Labeling depending of the loaded Firmware

¾ Use the sticker according to the firmware and glew it on the front of the
CIFX 80-RE card.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Installing cifX Card • 26

5.4 CIFX 90-RE


For installation of the CIFX 90-RE card handle as follows:
1. Disconnect the power plug of the PC.
2. Open the cabinet of the PC.
3. Plug in the CIFX 90-RE card in the Mini PCI socket (Type III System
Connector) on the mainboard.
4. Press the clamps at the Mini PCI socket until they snap in, to fasten the
CIFX 90-RE card to the mainboard.
To connect the AIFX-RE connection interface:
5. Connect the cable connector X1 on the AIFX-RE connection interface
with the cable.
6. Connect the cable connector X4 on the CIFX 90-RE card with the cable.
7. Mount the AIFX-RE on the PC cabinet.
Only then:
8. Close the PC casing.
9. Connect the PC to the power supply and switch on the PC.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Installing cifX Card • 27

5.5 CIFX 104C-RE and CIFX 104C-RE-R


For installation of the CIFX 104C-RE card handle as follows:
1. Disconnect the power plug of the PC.
2. Open the cabinet of the PC.
3. Plug in the CIFX 104C-RE card on a free PCI slot for PC 104 cards.
4. Fix the CIFX 104C-RE card to the mainboard using 4 spacing bolts and
screws intended. The scope of delivery does not include spacing bolts
and screws.
5. Close the PC casing.
6. Connect the PC to the power supply and switch on the PC.

5.6 CIFX 104C-RE\F and CIFX 104C-RE-R\F


For installation of the CIFX 104C-RE card handle as follows:
1. Disconnect the power plug of the PC.
2. Open the cabinet of the PC.
3. Plug in the CIFX 104C-RE card on a free PCI slot for PC 104 cards.
4. Fix the CIFX 104C-RE card to the mainboard using 4 spacing bolts and
screws intended. The scope of delivery does not include spacing bolts
and screws.
To connect the connection interface AIFX-RE:
5. Connect the cable connector Ethernet X 1 on the connection interface
AIFX-RE with the cable.
6. Connect the cable connector Ethernet X 4 (or X304) on the CIFX 104C-
RE card with the cable.
7. Mount the AIFX-RE on the PC cabinet.
To connect the Diagnosis Interface AIFX-DIAG:
8. Connect the cable connector DIAG X 1 on the Diagnosis Interface
AIFX-DIAG with the cable.
9. Connect the cable connector DIAG X 3 (or X303) on the CIFX 104C-RE
card with the cable.
10. Mount the AIFX-DIAG on the PC cabinet.
After that:
11. Close the PC casing.
12. Connect the PC to the power supply and switch on the PC.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Installing Software • 28

6 Installing Software
6.1 Installing cifX Device Driver
To install the cifX Device Driver proceed as described hereafter:
1. After installation of the cifX card restart your PC.
Windows® 2000 / Windows® XP recognize the cifX card automatically.
° The message Found New Hardware is displayed and the Found new
Hardware Wizard is started.
2. Select Install from a list or specific location (Advanced).

Figure 2: Found new Hardware Wizard - Indicate Software Source

3. Insert the installation CD now.


4. Click to the button Next >.
° The Found new Hardware Wizard asks you to select the research-
and installation options.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Installing Software • 29

Figure 3: Found new Hardware Wizard - Select research- and installation options

5. Select Search for the best driver in these locations.


6. Activate the checkbox Search removable media (floppy, CD-ROM...).
7. Click to the button Next >.
° The driver software for the cifX Device Driver gets installed.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Installing Software • 30

Figure 4: Found new Hardware Wizard - Software gets installed

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Installing Software • 31
° The Found new Hardware Wizard indicates the cifX PCI/PCIe Device
software installation is complete.

Figure 5: Found new Hardware Wizard - Software installation has been completed

8. Click in Found new Hardware Wizard > Completing the Found new
Hardware Wizard to the button Finish.
° The installation of the cifX Device Driver is complete.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Installing Software • 32
9. Check in the Computer Manager, if your cifX card installed correctly.
¾ Therefore open the Computer Manager as follows: Desktop symbol
My Computer > rightclick Properties > window System Properties >
tab Hardware > button Computer Manager.
¾ Check, if the view of your Computer Manager corresponds to the
marked area in the view hereafter.

Figure 6: Device Manager > cifXPCI/PCIe Device - correctly installed

Note: The cifX card has to be configured.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Installing Software • 33

6.2 Installing the netX Configuration and Diagnostic Utility


After the cifX Device Driver is installed start the netX Utility setup program
to install the netX Configuration and Diagnostic Utility:
Therefore:
¾ Close all application programs on the system!
¾ Insert the cifX CD to the local CD ROM drive.
¾ Start in the directory Software the netX Utility setup program and
execute the installation steps according to the instructions at the
screen.
Or:
¾ Select netX Configuration and Diagnostic Utility of the autostart
menu.

6.3 Installing SYCON.net


To install the system configurator SYCON.net:
¾ Close all application programs on the system!
¾ Insert the cifX CD to the local CD ROM drive.
¾ Start in the directory Software the SYCON.net setup program
SYCONnet netX setup.exe.
Or:
¾ Select SYCON.net of the autostart menu.

Note: Administrator privileges are required on Windows® 2000/ Windows®


XP systems for installation!

¾ Choose System Installation from the start screen.


° The installation program asks for the components to be installed.
¾ Answer these questions with Yes or No.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE netX Configuration and Diagnostic Utility • 34

7 netX Configuration and Diagnostic Utility


7.1 Configuration Steps cifX Card
The chapter netX Configuration and Diagnostic Utility provides
information on how to configure the device parameters of a real-time
Ethernet or a fieldbus Slave and what can be read from the diagnostic
window.

Configuration Steps
The following table describes the main steps how to configure a cifX device
if the cifX device driver is already installed.

# Action Short Description For detailed information Page


see section
1 Starting the netX Utility Start the netX Configuration and Diagnostic Starting netX Configuration 35
Utility. and Diagnostic Utility
2 Selecting the Language Select the language of the netX Configuration Selecting Language / 40
and Diagnostic Utility graphical user interface. Firmware, downloading
Firmware
3 Selecting the Firmware Select the firmware protocol. Selecting Language / 40
Protocol and Download the firmware via Apply. Firmware, downloading
downloading the Firmware
Firmware
4 Set and download the Set the configuration parameters for the Slave Configuration 41
Parameters to be used and download this one to the cifX
card.
5 cifX Diagnosis Check cifX communication. Diagnostics 43
Table 17: Configuration Steps / USB Device Driver already installed

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE netX Configuration and Diagnostic Utility • 35

7.2 Starting netX Configuration and Diagnostic Utility


¾ Start the netX Configuration and Diagnostic Utility via Start >
Programs > netX Setup > netX Setup Program.
° The utility detects the type of the connected cifX, for Real-Time-
Ethernet or for fieldbusses.
To read more on how to configure the cifX and to use its diagnostic
features refer to the descriptions hereafter.

7.3 Introduction to the Dialog Structure


The graphical user interface of the netX Configuration and Diagnostic
Utility is divided in five main areas:
• A header with the Select Network and Language Bar
• A second header with the Device Identification
• The Navigation Area (left side)
• The Configuration Window (middle)
• The Diagnostic Window (right side)

Select Network and Language Bar

Device Identification

Navi- Configuration Diagnostic


gation Window Window
Area

OK Cancel Apply Help


Status Line

Figure 7: Dialog Structure of netX Configuration and Diagnostic Utility

Additional information e. g. online-state of the netX Configuration and


Diagnostic Utility can be found in the Status Line.
Explanations to general dialog elements like buttons can be found in the
subsection General Buttons on page 37.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE netX Configuration and Diagnostic Utility • 36

Select Network / Language Icon Bar

Figure 8: Select Network Icon Bar

Figure 9: Select Language Icon Bar (only English yet)

Device Identification
The Device Identification shows the information about the connected cifX.

Parameter Meaning
IO Device Name of the device
Vendor Vendor name of the device
Firmware Name of the currently loaded firmware
Device ID Identification number of the device
Vendor ID Identification number of the vendor
Version Version of the currently loaded firmware
Table 18: Device Identification

Navigation Area, Configuration and Diagnostic Window


The Navigation Area at the left side of the netX Configuration and
Diagnostic Utility shows the installed drivers and devices as a folder
structure. The Navigation Area can be hidden via the symbol or it can
be displayed again via the symbol .
The actual parameters of the currently loaded firmware are displayed in the
Configuration window of the netX Configuration and Diagnostic Utility
and can be edited there.
In the Diagnostic window system and communication diagnosis is
displayed. With the Start COM button the communication to the Master can
be started respectively can be stopped with the Stop COM button. The
device can also be reset with the Reset button.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE netX Configuration and Diagnostic Utility • 37

7.3.1 General Buttons


The table below explains the general buttons in the netX Configuration
and Diagnostic Utility user interface.

Button Meaning
OK 1. Configuration modified - The firmware and Configuration are
downloaded: If the configuration has been changed and you click to the
OK button, the firmware/configuration is downloaded to the cifX.
2. Configuration has not been modified - If the configuration has not been
changed and you click to the OK button, you are asked if you want to
download the firmware/configuration, if you want to quit the netX
Configuration and Diagnostic Utility or if you want to cancel.
Cancel If the configuration has been changed and you click to the Cancel button,
you are asked if you want to save the configuration. If you answer this
question with yes, the configuration will be saved but it will not been
downloaded to the cifX.
Apply If the configuration has been changed and you click to the Apply button,
the firmware/configuration is directly downloaded to the cifX and the Apply
button is greyed out again.
The Apply button is greyed out, if the offline and the online configuration
are identical.
Help To open the netX Configuration and Diagnostic Utility online help, click on
the Help button.
Table 19: General Buttons

7.3.2 Help
¾ To open the help in netX Configuration and Diagnostic Utility, click
on the Help button or press the F1 key.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE netX Configuration and Diagnostic Utility • 38

7.3.3 Status Line


The Status Line displays information about the current state of the netX
Configuration and Diagnostic Utility. The download or any other activity is
signaled in the status line.

Figure 10: Status Line – Status Fields 1 to 6

Number Meaning Icon


1 Connection State:
Icon going closed = Device is going online
Icon closed = Device is online
Icon going opened = Device is going offline
Icon opened = Device is offline
Icon with lightening = Device communication disturbed

2 Data Source States


The displayed data are read out from the instance data set (database).

The displayed data are read out from the instance data set (database).
Database is locked with password.
The displayed data are read out from the device.

The displayed data are read out from the device.


Device is locked with password.
3 States of the instance Data Set
All data loaded -
Valid Modified = Parameter is changed (not equal) to data source.

Invalid Modified = Invalid value (e. g. not plausible)

Initial data set = Parameter value is equal to data source value (data -
base or fieldbus device).
4 Changes directly made on the Device
Changes have only an impact on the device and not on the instance data
set. Instance data set and device may not be consistent any more.
Load Configure and Diagnosis Parameters

Table 20: Status Line Icons

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE netX Configuration and Diagnostic Utility • 39

7.4 Working with netX Configuration and Diagnostic Utility


After the netX Configuration and Diagnostic Utility has been started, the
Select Network / Language Icon Bar is activated. All the other firmware /
language buttons are greyed out. The Device Identification shows the
information about the connected cifX.

Figure 11: netX Configuration and Diagnostic Utility

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE netX Configuration and Diagnostic Utility • 40

7.4.1 Selecting Language / Firmware, downloading Firmware


1. In the Select Language Icon Bar select the language icon for the
language in which the graphical user interface shall be displayed.

Icon Language
English
Japanese
Italian
French
German
Chinese

Table 21: Select Language Icon Bar (only English yet)

° The graphical user interface of the netX Configuration and


Diagnostic Utility is displayed in the corresponding language.
2. Selecting Firmware Protocol.
Real-Time Ethernet Fieldbus
Firmware Firmware Firmware Firmware
Button Button
EtherNet/IP-Adapter PROFIBUS DP-Slave
(Slave)
Powerlink Controlled Node CC-Link Slave
/ Slave
PROFINET IO-Device DeviceNet Slave

EtherCAT-Slave CANopen Slave

SERCOS III Slave

Open Modbus/TCP

Table 22: Select Network Icon Bar: Firmware Buttons Real-Time Ethernet and Fieldbus
System

¾ Select in the Select Network Icon Bar the firmware button for the
Slave device you intend to use with the cifX.
3. Set parameters.
4. Download Firmware.
¾ Activate the Apply button.
° The selected firmware/configuration is directly downloaded to the cifX
device. The download is signaled in the status line.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE netX Configuration and Diagnostic Utility • 41

7.4.2 Configuration
The actual parameters of the selected firmware protocol are displayed in
the Configuration window. The configuration parameters can be edited.
With the Default button the parameters can be reset to the default state.
¾ Click to the Configuration window to put the focus on it.

Figure 12: Configuration Window

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE netX Configuration and Diagnostic Utility • 42

Note: For the description of the single parameters refer to section Fehler!
Verweisquelle konnte nicht gefunden werden. on page Fehler!
Textmarke nicht definiert..

Section Subsection Manual


Page
Fehler! EtherCAT Slave Parameters 81
Verweisquelle
EtherNet/IP Adapter Parameters 82
konnte nicht
gefunden werden. Open Modbus/TCP Parameters 84
Powerlink Controlled Node / Slave Parameters 86
PROFINET IO-Device Parameters 88
SERCOS III Slave Parameters 89
T able 23: Descriptions Configuration Windows

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE netX Configuration and Diagnostic Utility • 43

7.4.3 Diagnostics
The Diagnostic window displays:
• System and Communicating status information,
• 16 Bit Input / Output data,
• the SYS and COM LED status,
• and the buttons for the functions: Start COM Start Communication, Stop
COM Stop Communication and Reset Reset Device.

¾ Click to the Diagnostic window to put the focus on it.

Figure 13: Diagnostic Window

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE netX Configuration and Diagnostic Utility • 44

7.4.3.1 Diagnostic: System

Figure 14: Diagnostic Window > System

Display Meaning
Ready Indicates, that the firmware has been started correctly. The firmware
waits for a configuration.

Error Indicates, that the firmware reports an error.

Change of State The system change of state field contains information of the current
operating status of the communication channel.
State The system status field holds information regarding netX operating
system rcX. The value indicates the current state the rcX has.
Error The system error field holds information about the general status of the
netX firmware stacks. An error code of zero indicates a faultless
system.
Table 24: Diagnostic Window > System

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE netX Configuration and Diagnostic Utility • 45

7.4.3.2 Diagnostic: Communication

Figure 15: Diagnostic Window > Communication

Display Meaning
Communicating Indicates, that the cifX takes part in the network communication.

Error Indicates, that the firmware reports an error.

Change of State The communication change of state register contains information about
the current operating status of the communication channel and its
firmware.
State The communication state field contains information regarding the
current network status of the communication channel.
Error This field holds the current error code of the communication channel. If
the cause of error is resolved, the communication error field is set to
zero again.
Table 25: Diagnostic Window > System, Communication

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE netX Configuration and Diagnostic Utility • 46

7.4.3.3 Diagnostic: Input / Output, SYS / COM

Input / Output
Under Input / Output the state of the respective input or output signal is
displayed for the first two Byte of the transmitted data.
¾ To set the inputs, click to the corresponding input symbol.
° The input symbol is displayed in the corresponding color.
If the Master sends data, the outputs are set.

Figure 16: Diagnostic Window > Input, Output, Start COM, Stop COM, Reset

SYS / COM
Under SYS / COM the state of the respective LED is displayed.
Further information to this you find in section LED Real Time Ethernet
Systems beginning from page 58

7.4.3.4 Diagnostic: Start COM, Stop COM, Reset


Button Meaning
With the Start COM button the
communication to the Master can be
started.

With the Stop COM button the


communication to the Master can be
stopped.

With the Reset button the device can


be reset.

Table 26: Start COM, Stop COM, Reset

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Troubleshooting • 47

8 Troubleshooting
General
¾ Check, if the requirements for cifX card operation are served:
Further information to this you find in section Requirements for Operation
on page 18.

LINK-LED
¾ Check using the LINK LED status, if a connection to the Ethernet is
established.
Further information to this you find in chapter LED Real Time Ethernet
Systems on page 58.

Cable
¾ Check that the pin occupation of the used cable is correct.

Configuration
¾ Check the configuration in the Master and the Slave device. The
configuration has to match.

Diagnostic using the netX Configuration and Diagnostic Utility (Slave)


With the menu netX Configuration and Diagnostic Utility > Diagnostics
the diagnosis information of the Slave device is shown. The shown
diagnostic information depends on the used protocol.

Diagnostic using the System Configurator SYCON.net (Master)


With the menu Online > Diagnosis the diagnosis information of the Master
device is shown. The shown diagnostic information depends on the used
protocol.

Note: More information about the device diagnosis and its functions you
find in the operating manual of the corresponding Real Time Ethernet
system. Therefore refer to section Documentations cifX Cards on page
10.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Device Drawings and Connections • 48

9 Device Drawings and Connections


9.1 Device Drawing CIFX 50-RE
Note:
Device
supports Auto
Crossover
Function
Note:
With loaded
EtherNet/IP-
Adapter,
Scanner or
EtherCAT
Master
firmware only
channel 0 can
be used,
channel 1 is
deactivated.

Figure 17: Device Drawing CIFX 50-RE

The meaning of the yellow and green LED at the RJ45 socket depends
from the loaded firmware. See section LED Real Time Ethernet Systems
beginning from page 58.

9.2 Device Drawing CIFX 50E-RE


Note:
Device
supports Auto
Crossover
Function
Note:
With loaded
EtherNet/IP-
Adapter,
Scanner or
EtherCAT
Master
firmware only
channel 0 can
be used,
channel 1 is
deactivated.

Figure 18: Device Drawing CIFX 50E-RE

The meaning of the yellow and green LED at the RJ45 socket depends
from the loaded firmware. See section LED Real Time Ethernet Systems
beginning from page 58.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Device Drawings and Connections • 49

9.3 Device Drawing CIFX 80-RE

Note: Device supports Auto Crossover Function


Note: With loaded EtherNet/IP-Adapter, Scanner or EtherCAT Master firmware only channel 0 can be used, channel 1 is
deactivated.
Figure 19: Device Drawing CIFX 80-RE

The meaning of the yellow and green LED at the RJ45 socket depends
from the loaded protocol. See section LED Real Time Ethernet Systems
beginning from page 58.

9.4 Device Drawing CIFX 90-RE

Figure 20: Device Drawing CIFX 90-RE

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Device Drawings and Connections • 50

9.5 Device Drawing CIFX 104C-RE


Note:
Device supports
Auto Crossover
Function
Note:
With loaded
EtherNet/IP-
Adapter, Scanner
or EtherCAT
Master firmware
only channel 0
can be used,
channel 1 is
deactivated.

Figure 21: Device Drawing CIFX 104C-RE

The meaning of the yellow and green LED at the RJ45 socket depends
from the loaded firmware. See section LED Real Time Ethernet Systems
beginning from page 58.

9.6 Device Drawing CIFX 104C-RE-R


Note:
Device supports
Auto Crossover
Function
Note
With loaded
EtherNet/IP-
Adapter, Scanner
or EtherCAT
Master firmware
only channel 0
can be used,
channel 1 is
deactivated.

Figure 22: Device Drawing CIFX 104C-RE-R

The meaning of the yellow and green LED at the RJ45 socket depends
from the loaded firmware. See section LED Real Time Ethernet Systems
beginning from page 58.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Device Drawings and Connections • 51

9.7 Device Drawing CIFX 104C-RE\F

Figure 23: Device Drawing CIFX 104C-RE\F

9.8 Device Drawing CIFX 104C-RE-R\F

Figure 24: Device Drawing CIFX 104C-RE-R\F

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Device Drawings and Connections • 52

9.9 Device Drawing Connection Interface AIFX-RE


Only for CIFX 104C-RE\F, CIFX 104C-RE-R\F and CIFX 90-RE.
Note:
Device supports Auto
Crossover Function
Note
With loaded
EtherNet/IP-Adapter,
Scanner or EtherCAT
Master firmware only
channel 0 can be
used, channel 1 is
deactivated.
Figure 25: Device Drawing Connection Interface AIFX-RE

The meaning of the yellow and green LED at the RJ45 socket depends
from the loaded firmware. See section LED Real Time Ethernet Systems
beginning from page 58.

9.10 Device Drawing Diagnosis Interface AIFX-DIAG


Only for CIFX 104C-RE\F and CIFX 104C-RE-R\F.

Figure 26: Device Drawing Diagnosis Interface AIFX-DIAG

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Device Drawings and Connections • 53

9.11 Ethernet Interface


For the Ethernet interface use RJ45 plugs and twisted pair cable of
category 5 (CAT5) or higher, which consists of 4 twisted cores and has a
maximum transmission rate of 100 MBit/s (CAT5).

9.11.1 Ethernet pinning at the RJ45 Socket


Note: The device supports the Auto Crossover function. Due to this fact
RX and TX can be switched. The following figure shows the RJ45
standard pinning.

Device supports
Auto Crossover
Function Pin 1: TX+
Pin 2: TX-
Pin 3: RX+
Pin 4: Term 1

Pin 5: Term 1
Pin 6: RX-
Pin 7: Term 2
Pin 8: Term 2

Figure 27: Ethernet pinning at the RJ45 Socket

Pin Signal Meaning


1 TX+ Transmit Data +
2 TX– Transmit Data –
3 RX+ Receive Data +
4 Term 1 Connected to each other and
terminated to PE through RC circuit*
5 Term 1
6 RX– Receive Data –
7 Term 2 Connected to each other and
terminated to PE through RC circuit*
8 Term 2
* Bob Smith Termination
Table 27: Ethernet pinning at the RJ45 Socket

9.11.2 Ethernet Connection Data


Medium 2 x 2 Twisted-Pair cupric cable, CAT5 (100 MBit/s)
Length of cable max. 100 m
Transmission rate 10 MBit/s / 100 MBit/s
Table 28: Ethernet Connection Data

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Device Drawings and Connections • 54

9.11.3 Use of Hubs and Switches


For the corresponding communication systems the use of hubs and
switches is forbidden or applicable. The following table shows the use of
hubs and switches by communication system:
Communication System Hub Switch
EtherCAT forbidden applicable only between Master and
1. participant
PROFINET IO forbidden applicable only, if the switch supports
‘priority tagging’
(100 MBit/s, Full duplex)
EtherNet/IP allowed applicable
(10 MBit/s / 100 MBit/s,
Full or Half Duplex, Auto-Negotiation)
SERCOS III forbidden forbidden
Table 29: Use of Hubs and Switches

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Device Drawings and Connections • 55

9.12 Mini-B USB Connector (5 Pin)


Only for CIFX 80-RE, CIFX 104C-RE, CIFX 104C-RE-R.
For CIFX 104C-RE\F, CIFX 104C-RE-R\F when using the AIFX-DIAG.

Figure 28: Mini-B USB Connector (5 Pin), S302

Pin Name Description


1 USB_EXT USB Bus Power (+5 V, supplied externally)
2 D- Data -
3 D+ Data +
4 ID Not connected
5 GND Ground
Table 30: Pin out, S302

9.13 Rotary Switch for Slot Number


Only for CIFX 104C devices
The Rotary Switch for Slot Number is used for setting the physical slot
number. Max. 4 modules can be plugged on each other. Each slot setting
can be used only one time. The module next to the host controller gets the
CLK 0, the following modules get the next higher CLK number.

Switch Module No. CLK ID Select INT


Position Slot
0, 4, 8 1 CLK 0 IDSEL 0 INTA
1, 5, 9 2 CLK 1 IDSEL 1 INTB
2, 6 3 CLK 2 IDSEL 2 INTC
3, 7 4 CLK 3 IDSEL 3 INTD
Table 31: Rotary Switch for Slot Number, S1

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Device Drawings and Connections • 56

9.14 Cable Connector


9.14.1 Pinning for Cable Connector Ethernet
Only for CIFX 104C-RE\F (X304), CIFX 104C-RE-R\F (X4) and
CIFX 90-RE (X4).
Pin Signal
1 GND
2 +3V3 Analog
3 STA0_green
4 STA0_red
5 XM0_TX
6 STA1_green
7 CH0_LINKn
8 CH0_ACTIVITY
9 AIFINIT
10 STA1_red
11 CH0_TXP
12 CH0_TXN
13 CH0_RXP
14 CH0_RXN
15 CH1_TXP
16 CH1_TXN
17 CH1_RXP
18 CH1_RXN
19 CH1_LINKn
20 CH1_ACTIVITY
Table 32: Pinning for Cable Connector Ethernet X4 or X304 –
Cable 20 pin Ethernet + Status LED

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Device Drawings and Connections • 57

9.14.2 Pinning for Cable Connector DIAG


Only for CIFX 104C-RE\F (X303), CIFX 104C-RE-R\F (X3).

Pin Signal
1 GND
2 +3V3
3 STA2
4 STA3
5 USB_POS
6 USB_NEG
7 RDYn
8 RUNn
9 STA0_green
10 STA0_red
11 STA1_green
12 STA1_red
Table 33: Pinning for Cable connector DIAG X3 or X303 -
Cable 12 pin USB + Status LED

9.14.3 Pinning for SYNC Connector, X51


Only for CIFX 80-RE, CIFX 90-RE, CIFX 104C-RE, CIFX 104C-RE-R, CIFX
104C-RE\F, CIFX 104C-RE-R\F.

Pin Signal
1 GND
2 IO_0 XMAC3
3 IO_1 XMAC3
Table 34: Pinning for SYNC Connector, X51

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE LED • 58

10 LED
10.1 LED Real Time Ethernet Systems

10.1.1 LED Names for each Real Time Ethernet System


Note: Depending from the loaded cifX firmware the cifX LED are
configured to the corresponding real-time Ethernet system.

PROFINET IO
Modbus/TCP
EtherNet/IP

SERCOS III
Powerlink
EtherCAT

cifX-LED EtherCAT
Master

Slave

Open
SYS (yellow / green) SYS SYS SYS SYS SYS SYS SYS
COM 0 (red/ green) RUN RUN MS BS RUN SF STA
COM 1 (red/ green) ERR ERR NS BE ERR BF ERR
RJ45 green LINK L/A IN LINK L/A LINK LINK L/A
Ch0
yellow ACT - ACT - ACT RX/TX -
RJ45 green - L/A OUT LINK L/A LINK LINK L/A
Ch1
yellow - - ACT - ACT RX/TX -
Table 35: LED Names for each Real Time Ethernet System

LED Name Meaning


System Status SYS System
RUN Run
ERR Error
STA Status
SF System Failure
Communication Status BF Bus Failure
MS Module Status
NS Network Status
BS Bus Status
BE Bus Error
LINK, L Link
ACT, A Activity
RJ45 L/A Link/Activity
L/A IN Link/Activity Input
L/A OUT Link/Activity Output
Table 36: Meaning LED Names

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE LED • 59

10.1.2 LED EtherCAT Master


LED Color State Meaning

SYS green On Operating System running


yellow Flashing cyclic Device indicates boot error
with 1Hz
yellow static Bootloader is waiting for booting procedure
- Off Power supply for the device is missing or hardware defect

RUN - Off INIT: The device is in state INIT


green Blinking PRE-OPERATIONAL: The device is in state PRE-
OPERATIONAL
green Flickering BOOT: Device is in Boot mode
green Single Flash SAFE-OPERATIONAL: The device is in state SAFE-
OPERATIONAL
green On OPERATIONAL: The device is in state OPERATIONAL

ERR - Off Master has no errors

red On Master has detected a communication error. The error is


indicated in the DPM

LINK / green On A link is established


RJ45 Ch0
& Ch1 - Off No link established
ACT / yellow Flashing The device sends/receives Ethernet frames
RJ45 Ch0
& Ch1

Table 37: EtherCAT Master

RUN and ERR LED Indicator States EtherCAT Master:


Indicator state Definition
On The indicator is constantly on.
Off The indicator is constantly off.
Blinking The indicator turns on and off phase with a frequency of
2,5 Hz: on for 200 ms followed by off for 200 ms.
Flickering The indicator turns on and off phase with a frequency of
approximately 10 Hz: on for approximately 50 ms followed by off
for 50 ms.
Single Flash The indicator shows one short flash (200 ms) followed by a
long off phase (1,000 ms).
Double Flash The indicator shows a sequence of two short flashes (each
200 ms), separated by a short off phase (200 ms). The
sequence is finished by a long off phase (1,000 ms).
Table 38: Indicator States EtherCAT Master

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE LED • 60

10.1.3 LED EtherCAT Slave


LED Color State Meaning

SYS green On Operating System running


yellow Flashing cyclic Device indicates boot error
with 1Hz
yellow static Bootloader is waiting for booting procedure
- Off Power supply for the device is missing or hardware defect

RUN - Off INIT: The device is in state INIT


green Blinking PRE-OPERATIONAL: The device is in state PRE-
OPERATIONAL
green Single Flash SAFE-OPERATIONAL: The device is in state SAFE-
OPERATIONAL
green On OPERATIONAL: The device is in state OPERATIONAL

ERR - Off No error: The EtherCAT communication of the device is in


working condition
red Blinking Invalid Configuration: General Configuration Error
(Example: State change commanded by master is impossible
due to register or object settings.)
red Single Flash Unsolicited State Change: Slave device application has
changed the EtherCAT state autonomously: Parameter
"Change" in the AL status register is set to 0x01:change/error
(Example: Synchronization Error, device enters Safe-
Operational automatically.)
red Double Flash Application Watchdog Timeout: An application watchdog
timeout has occurred.
(Example: Sync Manager Watchdog timeout)
red On PDI Watchdog Timeout: A PDI Watchdog timeout has
occurred
(Example: Application controller is not responding any more)

L/A IN / green On A link is established


RJ45 Ch0
& Ch1 green Flashing The device sends/receives Ethernet frames
- Off No link established
L/A OUT / yellow - -
RJ45 Ch0
& Ch1

Table 39: EtherCAT Slave

RUN and ERR LED Indicator States EtherCAT Slave:


Indicator state Definition
On The indicator is constantly on.
Off The indicator is constantly off.
Blinking The indicator turns on and off phase with a frequency of
2,5 Hz: on for 200 ms followed by off for 200 ms.
Single Flash The indicator shows one short flash (200 ms) followed by a
long off phase (1,000 ms).
Double Flash The indicator shows a sequence of two short flashes (each
200 ms), separated by a short off phase (200 ms). The
sequence is finished by a long off phase (1,000 ms).
Table 40: Indicator States EtherCAT Slave
Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim
Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE LED • 61

10.1.4 LED EtherNet/IP Scanner (Master)


LED Color State Meaning

SYS green On Operating System running.


yellow Flashing cyclic Device indicates boot error.
with 1Hz
yellow static Bootloader is waiting for booting procedure.
- Off Power supply for the device is missing or hardware defect.

MS green On Device operational: If the device is operating correctly, the


module status indicator shall be steady green.
green Flashing Standby: If the device has not been configured, the module
status indicator shall be flashing green.
red On Major fault: If the device has detected a non-recoverable
major fault, the module status indicator shall be steady red.
red Flashing Minor fault*: If the device has detected a recoverable minor
fault, the module status indicator shall be flashing red. NOTE:
An incorrect or inconsistent configuration would be considered
a minor fault. (*for future use )
red / Flashing Self-test: While the device is performing its power up testing,
green the module status indicator shall be flashing green / red.
- Off No power: If no power is supplied to the device, the module
status indicator shall be steady off.

NS green On Connected: If the device has at least one established


connection (even to the Message Router), the network status
indicator shall be steady green.
green Flashing No connections: If the device has no established
connections, but has obtained an IP address, the network
status indicator shall be flashing green.
red On Duplicate IP*: If the device has detected that its IP address is
already in use, the network status indicator shall be steady
red. (*For future use )
red Flashing Connection timeout: If one or more of the connections in
which this device is the target has timed out, the network
status indicator shall be flashing red. This shall be left only if
all timed out connections are reestablished or if the device is
reset.
red / Flashing Self-test: While the device is performing its power up testing,
green the network status indicator shall be flashing green / red.
- Off Not powered, no IP address: If the device does not have an
IP address (or is powered off), the network status indicator
shall be steady off.

LINK / green On A connection to the Ethernet exists


RJ45 Ch0
& Ch1 - Off The device has no connection to the Ethernet

ACT / yellow Flashing The device sends/receives Ethernet frames


RJ45 Ch0
& Ch1

Table 41: EtherNet/IP Scanner (Master)

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE LED • 62

10.1.5 LED EtherNet/IP Adapter (Slave)


LED Color State Meaning

SYS green On Operating System running.


yellow Flashing cyclic Device indicates boot error.
with 1Hz
yellow static Bootloader is waiting for booting procedure.
- Off Power supply for the device is missing or hardware defect.

MS green On Device operational: If the device is operating correctly, the


module status indicator shall be steady green.
green Flashing Standby: If the device has not been configured, the module
status indicator shall be flashing green.
red On Major fault: If the device has detected a non-recoverable
major fault, the module status indicator shall be steady red.
red Flashing Minor fault*: If the device has detected a recoverable minor
fault, the module status indicator shall be flashing red.
NOTE: An incorrect or inconsistent configuration would be
considered a minor fault. (* For future use)
red / Flashing Self-test: While the device is performing its power up
green testing, the module status indicator shall be flashing green /
red.
- Off No power: If no power is supplied to the device, the module
status indicator shall be steady off.

NS green On Connected: If the device has at least one established


connection (even to the Message Router), the network
status indicator shall be steady green.
green Flashing No connections: If the device has no established
connections, but has obtained an IP address, the network
status indicator shall be flashing green.
red On Duplicate IP*: If the device has detected that its IP address
is already in use, the network status indicator shall be
steady red. (* For future use)
red Flashing Connection timeout: If one or more of the connections in
which this device is the target has timed out, the network
status indicator shall be flashing red. This shall be left only if
all timed out connections are reestablished or if the device is
reset.
red / Flashing Self-test: While the device is performing its power up
green testing, the network status indicator shall be flashing green /
red.
- Off Not powered, no IP address: If the device does not have
an IP address (or is powered off), the network status
indicator shall be steady off.

LINK / green On A connection to the Ethernet exists


RJ45 Ch0
& Ch1 - Off The device has no connection to the Ethernet

ACT / yellow Flashing The device sends/receives Ethernet frames


RJ45 Ch0
& Ch1

Table 42: EtherNet/IP Adapter (Slave)

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE LED • 63

10.1.6 LED Open Modbus/TCP


LED Color State Meaning

SYS green On Operating System running.


yellow Flashing cyclic Device indicates boot error.
with 1Hz
yellow static Bootloader is waiting for booting procedure.
- Off Power supply for the device is missing or hardware defect.

RUN - Off Not Ready


OMB task is not ready
green Flashing cyclic Ready, not configured yet
with 1Hz OMB task is ready and not configured yet
green Flashing cyclic Waiting for Communication:
with 5Hz OMB task is configured
green On Connected:
OMB task has communication – at least one TCP
connection is established

ERR - Off No communication error

red Flashing cyclic System error


with 2Hz
(On/Off Ratio =
25 %)

red On Communication error active

LINK / green On A connection to the Ethernet exists


RJ45 Ch0
& Ch1 - Off The device has no connection to the Ethernet

ACT / yellow Flashing The device sends/receives Ethernet frames


RJ45 Ch0
& Ch1

Table 43: LED Open Modbus/TCP

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE LED • 64

10.1.7 LED Powerlink Controlled Node / Slave


LED Color State Meaning

SYS green On Operating System running.


yellow Flashing cyclic Device indicates boot error.
with 1Hz
yellow static Bootloader is waiting for booting procedure.
- Off Power supply for the device is missing or hardware defect.

BS - Off Slave initializing


green Flickering Slave is in Basic Ethernet state
Single Flash Slave is in Pre-Operational 1
Double Flash Slave is in Pre-Operational 2
Triple Flash Slave is in ReadyToOperate
On Slave is Operational
Blinking Slave is Stopped

BE - Off Slave has no error

red On Slave has detected an error

L/A / green On Link: A connection to the Ethernet exists


RJ45 Ch0
& Ch1 green Flashing Activity: The device sends/receives Ethernet frames
- Off The device has no connection to the Ethernet
RJ45 Ch0 yellow - -
& Ch1

Table 44: LED Powerlink Controlled Node / Slave

RUN / ERR LED Indicator Powerlink Controlled Node / Slave:

Indicator state Definition


On The indicator is constantly on.
Off The indicator is constantly off.
Flickering The indicator turns on and off phase with a frequency of
approximately 10 Hz: on for approximately 50 ms followed by off
for 50 ms. Red and green LED shall be on alternately.
Blinking The indicator turns on and off phase with a frequency of
approximately 2,5 Hz: on for approximately 200 ms followed by
off for 200 ms. Red and green LED shall be on alternately.
Single Flash The indicator shows one short flash (approximately 200 ms)
followed by a long off phase (approximately 1,000 ms).
Double Flash The indicator shows a sequence of two short flashes (each
approximately 200 ms), separated by a short off phase
(approximately 200 ms). The sequence is finished by a long off
phase (approximately 1,000 ms).
Triple Flash The indicator shows a sequence of three short flashes (each
approximately 200 ms), separated by a short off phase
(approximately 200 ms). The sequence is finished by a long off
phase (approximately 1,000 ms).
Table 45: Indicator States Powerlink Controlled Node / Slave

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE LED • 65

10.1.8 LED PROFINET IO-RT Controller


LED Color State Meaning

SYS green On Operating System running


yellow Flashing cyclic at Device indicates boot error
1Hz
yellow Static Bootloader is waiting for booting procedure
- Off Power supply for the device is missing or hardware defect

SF red On (together with BF „red ON“)


No valid Master license
red Flashing cyclic at System error: Invalid configuration
2 Hz
- Off No error

BF red On No Connection: No Link.


or (together with SF „red ON“)
No valid Master license
red Flashing cyclic at Configuration fault: not all configured IO-Devices are
2 Hz connected.
- Off No error

LINK / green On A connection to the Ethernet exists


RJ45 Ch0
& Ch1 - Off The device has no connection to the Ethernet

RX/TX / yellow Flashing The device sends/receives Ethernet frames


RJ45 Ch0
& Ch1

Table 46: PROFINET IO-RT Controller

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE LED • 66

10.1.9 LED PROFINET IO-RT-Device


LED Color State Meaning

SYS green On Operating System running


yellow Flashing cyclic at Device indicates boot error
1Hz
yellow static Bootloader is waiting for booting procedure
- Off Power supply for the device is missing or hardware defect

SF red On Watchdog timeout; channel, generic or extended diagnosis


present; system error
red Flashing cyclic at DCP signal service is initiated via the bus
2 Hz (for 3 sec.)
- Off No error
BF red On No configuration; or low speed physical link; or no physical
link
red Flashing cyclic at No data exchange
2 Hz
- Off No error
LINK / green On A connection to the Ethernet exists
RJ45 Ch0
& Ch1 - Off The device has no connection to the Ethernet

RX/TX / yellow Flashing The device sends/receives Ethernet frames


RJ45 Ch0
& Ch1

Table 47: PROFINET IO-RT-Device

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE LED • 67

10.1.10 LED SERCOS III Slave


LED Color State Meaning

SYS green On Operating System running.


yellow Flashing cyclic Device indicates boot error.
with 1Hz
yellow static Bootloader is waiting for booting procedure.
- Off Power supply for the device is missing or hardware defect.

STA green Blinking CP0: Communication phase 0


green Single Flash CP1: Communication phase 1
green Double Flash CP2: Communication phase 2
green Triple Flash CP3: Communication phase 3
green On CP4: Communication phase 4
- Off NRT: Non Real-time Mode

ERR red On Error


- Off No error

L/A / green On Link: A connection to the Ethernet exists


RJ45 Ch0
& Ch1 green Flashing Activity: The device sends/receives Ethernet frames
- Off The device has no connection to the Ethernet
RJ45 Ch0 yellow - -
& Ch1

Table 48: SERCOS III Slave

RUN and STA LED Indicator States SERCOS III Slave:


Indicator state Definition
On The indicator is constantly on.
Off The indicator is constantly off.
Blinking The indicator turns on and off phase with a frequency of
2,5 Hz: on for 200 ms followed by off for 200 ms.
Single Flash The indicator shows one short flash (200 ms) followed by a
long off phase (1,000 ms).
Double Flash The indicator shows a sequence of two short flashes (each
200 ms), separated by a short off phase (200 ms). The
sequence is finished by a long off phase (1,000 ms).
Triple Flash The indicator shows a sequence of three short flashes (each
200 ms), separated by a short off phase (200 ms). The
sequence is finished by a long off phase (1,000 ms).
Table 49: Indicator States SERCOS III Slave

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Technical Data • 68

11 Technical Data
11.1 Technical Data cifX Real-Time Ethernet Cards
Note: All technical data are temporarily and can be altered without notice.

11.1.1 CIFX 50-RE


Item CIFX 50-RE
System Interface PCI, 32-Bit Dual-Port Memory
Dual-Port Memory Size 64 KBytes
Function Real-Time-Ethernet
Communication Determined by the loaded firmware
Protocols EtherCAT-Master, EtherCAT-Slave,
EtherNet/IP-Scanner (Master), EtherNet/IP-Adapter (Slave),
Open Modbus/TCP,
Powerlink Controlled Node / Slave,
PROFINET IO-Controller, PROFINET IO-Device,
SERCOS III-Slave
Ethernet Frame Types Ethernet II
Processor netX 500
LED SYS, COM 0, COM 1, 2x Link, 2x Activity
GUI cifX netX Configuration and Diagnostic Utility
Transmission Rate 10/100 MBit/s, Auto-Negotiation, Cross-Over,
Halfduplex/Fullduplex (100 MBit/s)
Depending on used firmware
Ethernet Interface RJ45 Socket, 10 Base-T, 100 Base-TX, potential free
Power Supply +3,3 V ±5 % / 600 mA
Dimensions 120,0 x 73,2 x 18,5 mm
(L x W x D)
Operating Temperature 0 °C ... 55 °C
Table 50: Technical Data CIFX 50-RE

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Technical Data • 69

11.1.2 CIFX 50E-RE


Item CIFX 50E-RE
System Interface PCI-Express, Single-Lane Port, 32-Bit Dual-Port Memory
Dual-Port Memory Size 64 KBytes
Function Real-Time-Ethernet
Communication Determined by the loaded firmware
Protocols EtherCAT-Master, EtherCAT-Slave,
EtherNet/IP-Scanner (Master), EtherNet/IP-Adapter (Slave),
Open Modbus/TCP,
Powerlink Controlled Node / Slave,
PROFINET IO-Controller, PROFINET IO-Device,
SERCOS III-Slave
Ethernet Frame Types Ethernet II
Processor netX 500
LED SYS, COM 0, COM 1, 2x Link, 2x Activity
GUI cifX netX Configuration and Diagnostic Utility
Transmission Rate 10/100 MBit/s, Auto-Negotiation, Cross-Over,
Halfduplex/Fullduplex (100 MBit/s)
Depending on used firmware
Ethernet Interface RJ45 Socket, 10 Base-T, 100 Base-TX, potential free
Power Supply +3,3 V ±5 % / 600 mA
Dimensions 120,0 x 77,6 x 18,5 mm
(L x W x D)
Operating Temperature 0 °C ... 55 °C
Table 51: Technical Data CIFX 50E-RE

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Technical Data • 70

11.1.3 CIFX 80-RE


Item CIFX 80-RE
System Interface Compact PCI (3,3 V)
Dual-Port Memory Size 64 KBytes
Function Real-Time-Ethernet
Communication Determined by the loaded firmware
Protocols EtherCAT-Master, EtherCAT-Slave,
EtherNet/IP-Scanner (Master), EtherNet/IP-Adapter (Slave),
Open Modbus/TCP,
Powerlink Controlled Node / Slave,
PROFINET IO-Controller, PROFINET IO-Device,
SERCOS III-Slave
Ethernet Frame Types Ethernet II
Processor netX 500
LED SYS, COM 0, COM 1, 2x Link, 2x Activity
GUI cifX netX Configuration and Diagnostic Utility
Transmission Rate 10/100 MBit/s, Auto-Negotiation, Cross-Over,
Halfduplex/Fullduplex (100 MBit/s)
Ethernet Interface RJ45 Socket, 10 Base-T, 100 Base-TX, potential free
Power Supply +3,3 V ±5 % / 600 mA
Dimensions 100,0 x 160,0 x 9,4 mm
(L x W x D)
Operating Temperature -20 °C ... 55 °C
Table 52: Technical Data CIFX 80-RE

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Technical Data • 71

11.1.4 CIFX 90-RE


Item CIFX 90-RE
System Interface Mini-PCI-Socket (3,3 V), Type III System Connector
Dual-Port Memory Size 64 KBytes
Function Real-Time-Ethernet
Communication Determined by the loaded firmware
Protocols EtherCAT-Master, EtherCAT-Slave,
EtherNet/IP-Scanner (Master), EtherNet/IP-Adapter (Slave),
Open Modbus/TCP,
Powerlink Controlled Node / Slave,
PROFINET IO-Controller, PROFINET IO-Device,
SERCOS III-Slave
Ethernet Frame Types Ethernet II
Processor netX 500
LED SYS
GUI cifX netX Configuration and Diagnostic Utility
Transmission Rate 10/100 MBit/s, Auto-Negotiation, Cross-Over,
Halfduplex/Fullduplex (100 MBit/s)
Depending on used firmware
Interface AIFX-RE Cable Connector Ethernet
for connecting connection interface AIFX-RE
Power Supply +3,3 V ±5 % / 600 mA
Dimensions 60,0 x 44,6 x 9,4 mm
(L x W x D)
Operating Temperature -20 °C ... 70 °C
Table 53: Technical Data CIFX 90-RE

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Technical Data • 72

11.1.5 CIFX 104C-RE, CIFX 104C-RE-R,


CIFX 104C-RE\F, CIFX 104C-RE-R\F
Item CIFX 104C-RE, CIFX 104C-RE-R,
CIFX 104C-RE\F, CIFX 104C-RE-R\F
System Interface PCI Slot for PC/104 cards (3,3 V)
Dual-Port Memory Size 64 KBytes
Function Real-Time-Ethernet
Communication Determined by the loaded firmware
Protocols EtherCAT-Master, EtherCAT-Slave,
EtherNet/IP-Scanner (Master), EtherNet/IP-Adapter (Slave),
Open Modbus/TCP,
Powerlink Controlled Node / Slave,
PROFINET IO-Controller, PROFINET IO-Device,
SERCOS III-Slave
Ethernet Frame Types Ethernet II
Processor netX 500
LED SYS, COM 0, COM 1, 2x Link, 2x Activity
GUI cifX netX Configuration and Diagnostic Utility
Transmission Rate 10/100 MBit/s, Auto-Negotiation, Cross-Over,
Halfduplex/Fullduplex (100 MBit/s)
Depending on used firmware
Ethernet Interface For CIFX 104C-RE, CIFX 104C-RE-R :
RJ45 Socket, 10 Base-T, 100 Base-TX, potential free
Interface AIFX-RE For CIFX 104C-RE\F, CIFX 104C-RE-R\F :
Cable Connector Ethernet for connecting AIFX-RE
Diagnostic Interface For CIFX 104C-RE\F, CIFX 104C-RE-R\F :
Cable Connector DIAG
Power Supply +3,3 V ±5 % / 600 mA
Dimensions 96,0 x 90,2 x 26,5 mm
(L x W x D)
Operating Temperature -20 °C ... 55 °C
Table 54: Technical Data CIFX 104C-RE, CIFX 104C-RE-R, CIFX 104C-RE\F,
CIFX 104C-RE-R\F

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Technical Data • 73

11.1.6 AIFX-RE
Item AIFX-RE
Function Connection Interface Ethernet
Interface For CIFX 90-RE, CIFX 104C-RE\F, CIFX 104C-RE-R\F :
cifX-RE Cards Cable Connector Ethernet for connecting AIFX-RE
Ethernet Interface RJ45 Socket, 10 Base-T, 100 Base-TX, potential free
Transmission Rate 10/100 MBit/s, Auto-Negotiation, Cross-Over,
Halfduplex/Fullduplex (100 MBit/s)
Depending on used firmware
Dimensions (L x W x D) 42,5 x 30,6 x 18,5 mm
Operating Temperature -20 °C ... 70 °C
Table 55: Technical Data AIFX-RE

11.1.7 AIFX-DIAG
Item AIFX-DIAG
Function Diagnostic Interface
Diagnostic Interface For CIFX 104C-RE\F, CIFX 104C-RE-R\F :
Cable Connector DIAG
Dimensions 53,5 x 23,3 x 14,7 mm
(L x W x D)
Operating Temperature -20 °C ... 70 °C
LED SYS, COM 0, COM 1, COM 2, COM 3, ON
Table 56: Technical Data AIFX-DIAG

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Technical Data • 74

11.2 Protocols

11.2.1 EtherCAT Master


Parameter Description
Maximum number of cyclic input data 5760 bytes
Maximum number of cyclic output data 5760 bytes
Minimum bus cycle time 500 microseconds
Acyclic communication CoE (CANopen over EtherCAT)
CoE-Upload, CoE-Download
max. 1500 bytes
Functions Get OD List
Emergency
Slave diagnostics
Topology Line
Baud rate 100 MBit/s
Data transport layer Ethernet II, IEEE 802.3
Configuration File Max. 1 MByte
Table 57: EtherCAT Master

11.2.2 EtherCAT Slave


Parameter Description
Maximum number of cyclic input data 400 bytes (netX 100/netX 500)
Acyclic communication SDO
SDO Master-Slave
SDO Slave-Slave (depending on Master capability)
Type Complex Slave
Functions Emergency
FMMUs 3 (netX 100/netX 500)
SYNC Manager 4 (netX 100/500)
Baud rate 100 MBit/s
Data transport layer Ethernet II, IEEE 802.3
Table 58: EtherCAT Slave

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Technical Data • 75

11.2.3 EtherNet/IP Scanner (Master)


Parameter Description
Maximum number of total cyclic input 5760 bytes
data
Maximum number of total cyclic output 5760 bytes
data
Maximum number of supported 64 connections for implicit and explicit
connections
Maximum number of cyclic input data 504 bytes/slave/telegram
Maximum number of cyclic output data 504 bytes/slave/telegram
IO Connection type Cyclic, minimum 2 ms *
Maximum number of unscheduled data 1400 bytes per telegram
UCMM, Class 3 supported
Explicit Messages, Client and Server Get_Attribute_Single/All
Services Set_Attribute_Single/All
Predefined standard objects Identity Object
Message Route Object
Assembly Object
Connection Manager
Ethernet Link Object
TCP/IP Object
Maximal number of user specific objects 20
DHCP supported
BOOTP supported
Baud rates 10 and 100 MBit/s
Data transport layer Ethernet II, IEEE 802.3
* depending on used number of connections and used number of input and output data
Table 59: EtherNet/IP Scanner (Master)

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Technical Data • 76

11.2.4 EtherNet/IP Adapter (Slave)


Parameter Description
Maximum number of input data 504 bytes
Maximum number of output data 504 bytes
IO Connection 1 explicit owner, up to 2 listen only
IO Connection type Cyclic, minimum 2 ms
Explicit Messages Get_Attribute, Set_Attribute
UCMM supported
Max. number of user specific objects 20
Max. number of connections 8, explicit and implicit connections
Predefined standard objects Identity Object
Message Route Object
Assembly Object
Connection Manager
Ethernet Link Object
TCP/IP Object
DHCP supported
BOOTP supported
Baud rates 10 and 100 MBit/s
Data transport layer Ethernet II, IEEE 802.3
Table 60: EtherNet/IP Adapter (Slave)

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Technical Data • 77

11.2.5 Open Modbus/TCP


Parameter Description
Maximum number of input data 5760 bytes
Maximum number of output data 5760 bytes
Acyclic communication Read/Write Register, Max. 125 Registers per Read
Telegram (FC 3, 4, 23), Max. 121 Registers per Write
Telegram (FC 23), Max. 123 Registers per Write Telegram
(FC 6)
Read/Write Coil, Max. 2000 Coils per Read Telegram (FC 1,
2), Max. 1968 Coils per Write Telegram (FC 15)
Modbus Function Codes 1, 2, 3, 4, 5, 6, 7, 15, 16, 23
Mode Message Mode: Client, Server (I/O data area is not used in
this mode)
I/O Mode: Server
Baud rates 10 and 100 MBit/s
Data transport layer Ethernet II, IEEE 802.3
Table 61: Open Modbus/TCP

11.2.6 Powerlink Controlled Node / Slave


Parameter Description
Maximum number of cyclic input data 1490 bytes
Maximum number of cyclic output data 1490 bytes
Acyclic data transfer SDO Upload/Download
Functions: SDO over ASND and UDP
Baud rate 100 MBit/s, half-duplex
Data transport layer Ethernet II, IEEE 802.3
Ethernet Powerlink version V2
Table 62: Powerlink Controlled Node / Slave

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Technical Data • 78

11.2.7 PROFINET IO-RT-Controller


Parameter Description
Maximum number of total cyclic input data 3072 bytes
Maximum number of total cyclic output 3072 bytes
data
Maximum number of cyclic input data 1024 bytes per device (= IOCR data length)
Maximum number of cyclic output data 1024 bytes per device (= IOCR data length)
Maximum number of configured devices 128
Acyclic communication Read/Write Record
Limited to 1392 bytes per telegram
Limited to 4096 bytes per request
Alarm processing yes
DCP supported
Context management by CL-RPC
Minimum cycle time 1ms
Different IO-Devices can be configured with different cycle
times
Baud rate 100 MBit/s
Full-Duplex mode
Data transport layer Ethernet II, IEEE 802.3
Configuration File Max. 1 MByte
Limitations RT over UDP not supported
Multicast communication not supported
DHCP is not supported (neither for PROFINET IO-
Controller nor for the IO-Devices)
Only one IOCR per IO-Device
Using cycle time of less than 4ms reduces the maximum
amount of connected devices to 25
NameOfStation of IO-Controller CANNOT be set using the
DCP SET NameOfStation service but only at start-up while
configuring the IO-Controller
SNMP not supported
LLDP not supported

Table 63: PROFINET IO-RT-Controller

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Technical Data • 79

11.2.8 PROFINET IO-RT-Device


Parameter Description
Maximum number of cyclic input data 1024 bytes
Maximum number of cyclic output data 1024 bytes
Maximum number of all submodules 80
Maximum slot address 300
Maximum subslot address 100
Acyclic communication Read/Write Record, max. 1024 bytes/telegram
Alarm Types Process Alarm, Diagnostic Alarm, Return of SubModule,
Plug Alarm, Pull Alarm
DCP supported
Used Protocols (subset) UDP, IP, ARP, ICMP (Ping)
Topology recognition LLDP, SNMP V1, MIB2, physical device
VLAN- and priority tagging yes
Context Management by CL-RPC
Minimum cycle time 1ms
IO-Device can be configured with different cycle times
Baud rate 100 MBit/s
Data transport layer Ethernet II, IEEE 802.3
Table 64: PROFINET IO-RT-Device

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Technical Data • 80

11.2.9 SERCOS III Slave


Parameter Description
Maximum number of cyclic input data 200 bytes (including Device Control, Connection Control)
Maximum number of cyclic output data 200 bytes (including Device Status, Connection Control)
Maximum number of applicable device 1
addresses
Minimum cycle time 250µs
Topology Line and ring
Acyclic communication (Service Channel) Read/Write/Standard Commands
NRT Channel supported yes
Communication phases NRT, CP0, CP1, CP2, CP3, CP4
Baud rate 100 MBit/s
Data transport layer Ethernet II, IEEE 802.3
Supported SERCOS III version: Communication Specification Version 1.1
Supported SERCOS Communication SCP_VarCFG, SCP_NRT, SCP_Sync
Profiles
Table 65: SERCOS III Slave

Note: The Firmware is based on the SERCOS III specification V1.1.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Configuration Parameters • 81

12 Configuration Parameters
12.1.1 EtherCAT Slave Parameters
Parameter Meaning Range of Value /
Value
Interface
Bus Startup Communication start application controlled or automatic Application controlled,
Automatic
Watchdog Time Watchdog time within which the device watchdog must be [0, 20 … 65535] ms,
[ms] retriggered from the application program while the application default = 1000 ms,
program monitoring is activated. When the watchdog time value is 0 = Off
equal to 0 the watchdog respectively the application program
monitoring is deactivated.
I/O Data Status Status of the input or the output data. None, (1 Byte, 4 Byte)
For each input and output date the following status information (in
Byte) is memorized in the dual-port memory:
Status 0 = None (default)
Status 1 = 1 Byte (for future use)
Status 2 = 4 Byte (for future use)
Ident
Vendor ID Identification number of the manufacturer 0 … (232 - 1),
Hilscher:
044 (hex)
Product Code Product code of the device 0 … (232 - 1),
Default:
CIFX RE ECS:
0x00000001
NXSTK 50-RE ECS:
0x00000008
Revision Revision number of the device 0 … (232 - 1),
Number Default:
CIFX RE ECS:
0x00020000
NXSTK 50-RE ECS:
0x00000000
Serial Number Serial number of the device 0 … (232 - 1)
Data
Input Length Length of the input data in Byte 0 … 400* Byte
Default: 4 Byte
Output Length Length of the output data in Byte 0 … 400* Byte
Default: 4 Byte
* Sum: The length of input and of output is equal 400 Bytes,
Table 66: EtherCAT Slave Parameters

Note: To configure the Master a XML file (device description file) is


required. The settings in the used Master must comply with the settings in
the Slave, to establish a communication. Important parameters are:
Vendor ID, Product Code, Serial Number, Revision Number, Output and
Input length.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Configuration Parameters • 82

12.1.2 EtherNet/IP Adapter Parameters


Parameter Meaning Range of Value /
Value
Interface
Bus Startup Communication start application controlled or automatic Application controlled,
Automatic
Watchdog Time Watchdog time within which the device watchdog must be [0, 20 … 65535] ms,
[ms] retriggered from the application program while the application default = 1000 ms,
program monitoring is activated. When the watchdog time value is 0 = Off
equal to 0 respectively the application program monitoring is
deactivated.
I/O Data Status Status of the input or the output data. None, (1 Byte, 4 Byte)
For each input and output date the following status information (in
Byte) is memorized in the dual-port memory:
Status 0 = None (default)
Status 1 = 1 Byte (for future use)
Status 2 = 4 Byte (for future use)
Ident
Vendor ID Identification number of the manufacturer 283
Product Type Communication Adapter 12
Product Code Product code of the device CIFX RE EIS:
101 (hex), 257
NXSTK 50-RE:
101 (hex), 257
Major Rev Major Revision 1
Minor Rev Minor Revision 1
Device name Device name of the device station, Character string,
e. g. EtherNet/IP Adapter (Slave) 0 - 31 characters
Bus
IP Address IP address for the device
Netmask Network mask for the device
Gateway Gateway address for the device
Flags BootP: Default: DHCP
If set, the device obtains its IP Address, Netmask, Gateway
Address from a BOOTP server.
DHCP:
If set, the device obtains its IP Address, Netmask, Gateway
Address from a DHCP server.
100Mbit: Speed Selection,
If set, the device will operate at 100 Mbit/s, else at 10 Mbit/s. This
parameter will not be in effect, when auto-negotiation is active.
FullDuplex: Duplex Operation,
If set, full-duplex operation will be used. The device will operate in
half-duplex mode, if this parameter is set to zero. This parameter
will not be in effect, when auto-negotiation is active.
Auto-neg.: Auto-Negotiation,
If set, the device will auto-negotiate link parameters with the
remote hub or switch.
Data
Input Length Length of the input data in Byte 0 … 504 Byte
Default: 2 Byte
Output Length Length of the output data in Byte 0 … 504 Byte
Default: 2 Byte
Table 67: EtherNet/IP Adapter Parameters

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Configuration Parameters • 83

Note: To configure the Scanner/Master an EDS file (device description


file) is required. The settings in the used Scanner/Master must comply
with the settings in the Adapter/Slave, to establish a communication.
Important parameters are: Input, Output length, Vendor ID, Product Type,
Product Code, Major Rev, Minor Rev, IP Address and Netmask.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Configuration Parameters • 84

12.1.3 Open Modbus/TCP Parameters


Parameter Meaning Range of Value /
Value
Interface
Bus Startup Communication start application controlled or automatic Application controlled,
Automatic
Watchdog Time Watchdog time within which the device watchdog must be [0, 20 … 65535] ms,
[ms] retriggered from the application program while the application default = 1000 ms,
program monitoring is activated. When the watchdog time value is 0 = Off
equal to 0 the watchdog respectively the application program
monitoring is deactivated.
Mode Mode of data exchange. 0 ... 1
0: Message-Mode
1: IO-Mode
Swap Data-storage mode 0 ... 1
0: Data will not be swapped.
1: Data will be swapped.
Bus
Open Server Server Connections 0 ... 4 ... 16
Sockets Number of sockets to provide for server requests*
*A value of 0 means that the Open Modbus/TCP task exclusive works as Client,
while a Value of 16 means that the Open Modbus/TCP task exclusive works as
Server in Message-Mode.
The parameters Send Timeout, Connect Timeout and Close Timeout are for the
Timeout between the Open Modbus/TCP Task and the TCP Task.

Omb Open Connection remain open time 1 ... 10 ... 60000


Time Only for client jobs in message-mode. The connection to the
destination-device stays open, until timeout is expired. Value is
multiplied with 100 ms.
Note: This timeout starts, after receiving the answer to a
command
Answer Telegram Timeout 1 ... 20 ... 60000
Timeout Only for client jobs in message-mode. After expiration of this time,
the job will be canceled and an error is send to the application.
Value is multiplied with 100 ms.
Note: This timeout starts after command is send to the destination
device via TCP
Send Timeout TCP Task SendTimeout Parameter 0 ...
Parameter for TCP task (in milliseconds) . Used OMB task 2.000.000.000
internal. It specifies the timeout for trying to send messages via
TCP/IP
0 is the default value of 31000 milliseconds
Connect TCP Task Connect Timeout Parameter 0 ...
Timeout Parameter for TCP task (in milliseconds). Used OMB task 2.000.000.000
internal. It specifies the timeout for trying to establish a
connection with the TCP task.
0 is the default value of 31000 milliseconds
Close Timeout TCP Task Close Timeout Parameter 0 ...
Parameter for TCP task (in milliseconds). Used OMB task 2.000.000.000
internal. It specifies the timeout for trying to close a connection
with the TCP task.
0 is the default Value of 13000 milliseconds
IP Address IP address for the device. Valid IP address
For more see next page

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Configuration Parameters • 85

Parameter Meaning Range of Value /


Value
Net Mask Netmask for the subnet of the device. Valid netmask
Gateway IP address of the default gateway. Valid IP address
Flags BootP: 0 … 63
If set, the device obtains its IP Address, Netmask, Gateway
Address from a BOOTP server.
DHCP:
If set, the device obtains its IP Address, Netmask, Gateway
Address from a DHCP server.
Table 68: Open Modbus/TCP Parameters

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Configuration Parameters • 86

12.1.4 Powerlink Controlled Node / Slave Parameters


Parameter Meaning Range of Value /
Value
Interface
Bus Startup Communication start application controlled or automatic Application controlled,
Automatic
Watchdog Time [ms] Watchdog time within which the device watchdog must be [0, 20 … 65535] ms,
retriggered from the application program while the default = 1000 ms,
application program monitoring is activated. When the 0 = Off
watchdog time value is equal to 0 the watchdog respectively
the application program monitoring is deactivated.
I/O Data Status Status of the input or the output data. None, (1 Byte, 4 Byte)
For each input and output date the following status
information (in Byte) is memorized in the dual-port memory:
Status 0 = None (default)
Status 1 = 1 Byte (for future use)
Status 2 = 4 Byte (for future use)
Disable Host- Bit 0 of the stack configuration flags controls the host- Default: Host-
Triggered Input Data triggered input data exchange: Triggered Update
Exchange 0 = Host-Triggered Update enabled enabled

1 = Host-Triggered Update disabled


Disable Host- Bit 1 of the stack configuration flags controls the host- Default: Host-
Triggered Output triggered output data exchange: Triggered Update
Data Exchange 0 = Host-Triggered Update enabled enabled

1 = Host-Triggered Update disabled


Ident
Vendor ID Identification number of the manufacturer 44 hex
Serial Number Serial number of the device CIFX-RE:
0x00000000-
0xFFFFFFFF
Default: 0
Product Code Product code of the device CIFX RE PLS:
0x00000000-
0xFFFFFFFF,
Default:1
Revision Number Revision number of the device as specified by the CIFX RE PLS:
manufacturer 0x00000000-
0xFFFFFFFF
Default: 0
Bus
Node Id EPL Node ID (EPL = Ethernet Powerlink) 1...239
DNS Node Name DNS-compatible name of the Powerlink Controlled Node /
Slave
Gateway Address Gateway address for IP stack
For more see next page

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Configuration Parameters • 87

Parameter Meaning Range of Value /


Value
Data
Input Data Bytes Length of the input data in byte 1… 1490 Byte,
Default: 4 Byte
Output Data Bytes Length of the output data in byte 1… 1490 Byte,
Default: 4 Byte
Disable Bit 4 of the stack configuration flags controls whether the Default: Do not check
PdDOMapping mapping version field in the PReq will be checked: PReq PDO mapping
Version Check 0 = Check PReq PDO mapping version version

1 = Do not check PReq PDO mapping version


Configure Default Bit 2 of the stack configuration flags controls whether the Default: Create default
Objects default objects have to be configured: objects
0 = Do not create default objects
1 = Create default objects
If the objects will be created, the old set of previously
existing objects will be cleared
Delete Application Bit 3 of the stack configuration flags controls whether all Default: Delete
Objects application objects are to be deleted. application specific
0 = Do not delete application objects objects

1 = Delete application-specific objects


Table 69: Powerlink Controlled Node / Slave Parameters

Note: To configure the Managing Node/Master a XDD file (device


description file) is required. The settings in the used Managing
Node/Master must comply with the settings in the Controlled Node/Slave,
to establish a communication. Important parameters are: Vendor ID,
Product Code, Serial Number, Revision Number, Node ID, Output and
Input length.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Configuration Parameters • 88

12.1.5 PROFINET IO-Device Parameters


Parameter Meaning Range of Value /
Value
Interface
Bus Startup Communication start application controlled or automatic Application controlled,
Automatic
Watchdog Time [ms] Watchdog time within which the device watchdog must be [0, 20 … 65535] ms,
retriggered from the application program while the default = 1000 ms,
application program monitoring is activated. When the 0 = Off
watchdog time value is equal to 0 respectively the
application program monitoring is deactivated.
I/O Data Status Status of the input or the output data. None, (1 Byte, 4 Byte)
For each input and output date the following status
information (in Byte) is memorized in the dual-port memory:
Status 0 = None (default)
Status 1 = 1 Byte (for future use)
Status 2 = 4 Byte (for future use)
Ident
Vendor ID Identification number of the manufacturer, assigned by 0 … (232 - 1), Hilscher:
PROFIBUS Nutzerorganisation e. V. 011E (hex)
Device ID Identification number of the device, freely eligibly by the 0 … (216 - 1),
manufacturer, fixed for every device. CIFX RE PNS:
103 (hex), Dez 259
NXSTK 50-RE PNS:
105 (hex), Dez 261
Device Type Description of the device type, freely eligible Character string,
0 - 25 characters
Order ID Hilscher device number ( e. g. 1610 100) or order Character string,
description of the customer for its device 0 - 20 characters
Name of Station Station name of the PROFINET IO-Device station. It has to Character string,
match the station name configured in the PROFINET IO- 1 - 240 characters,
Controller for this device. Must be DNS compatible name. Default:
See GSDML-File
Type of Station Type name of the PROFINET station; name can be Character string,
assigned freely. 1 - 240 characters
Default:
See GSDML-File
Data
Input Data Length Length of the input data in Byte 0 … 1024 Byte
Default: 2 Byte
Output Data Length Length of the output data in Byte 0 … 1024 Byte
Default: 2 Byte
Table 70: PROFINET IO-Device Parameters

Note: To configure the Controller a GSDML file (device description file) is


required. The settings in the used Controller must comply with the settings
in the Device, to establish a communication. Important parameters are:
Station Name, Vendor ID, Device ID, Input and Output data length.

Note: Under Name of Station the name must be typed in, which was also
used in the configuration file of the master of this device. If no name
chosen freely is used in the configuration file, then the name from the
GSDML file is used.

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Configuration Parameters • 89

12.1.6 SERCOS III Slave Parameters


Parameter Meaning Range of Value /
Value
Bus Startup Communication start application controlled or automatic Application controlled,
Automatic
Watchdog Time Watchdog time within which the device watchdog must be [0, 20 … 65535] ms,
[ms] retriggered from the application program while the application default = 1000 ms,
program monitoring is activated. When the watchdog time value is 0 = Off
equal to 0 respectively the application program monitoring is
deactivated.
I/O Data Status Status of the input or the output data. None, 1 Byte, 4 Byte
For each input and output date the following status information (in
Byte) is memorized in the dual-port memory:
Status 0 = None
Status 1 = 1 Byte
Status 2 = 4 Byte
Device Address Address for the SERCOS III Slave. [1 … 127]
The address range is from 1 to 127.
Object Location of the Object Dictionary for Service Channel: local or local, Host
Dictionary Host 0= local
1= Host (not supported
yet)
Default = 0
IP Address Flag for IP address of the SERCOS III Slave station Default: none
Netmask Flag for Network mask of the SERCOS III Slave station Default: none
Gateway Flag for Gateway address of the SERCOS III Slave station Default: none
Flags BootP: Default: none
If set, the device obtains its configuration from a BOOTP server.
DHCP:
If set, the device obtains its configuration from a DHCP server.
Table 71: SERCOS III Slave Parameters

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Lists • 90

13 Lists
13.1 List of Figures
Figure 1: Front Plate Stickers for CIFX 50-RE and CIFX 50E-RE for the labeling of the card LED or of the
LED of the Ethernet female connector 23
Figure 2: Found new Hardware Wizard - Indicate Software Source 28
Figure 3: Found new Hardware Wizard - Select research- and installation options 29
Figure 4: Found new Hardware Wizard - Software gets installed 30
Figure 5: Found new Hardware Wizard - Software installation has been completed 31
Figure 6: Device Manager > cifXPCI/PCIe Device - correctly installed 32
Figure 7: Dialog Structure of netX Configuration and Diagnostic Utility 35
Figure 8: Select Network Icon Bar 36
Figure 9: Select Language Icon Bar (only English yet) 36
Figure 10: Status Line – Status Fields 1 to 6 38
Figure 11: netX Configuration and Diagnostic Utility 39
Figure 12: Configuration Window 41
Figure 13: Diagnostic Window 43
Figure 14: Diagnostic Window > System 44
Figure 15: Diagnostic Window > Communication 45
Figure 16: Diagnostic Window > Input, Output, Start COM, Stop COM, Reset 46
Figure 17: Device Drawing CIFX 50-RE 48
Figure 18: Device Drawing CIFX 50E-RE 48
Figure 19: Device Drawing CIFX 80-RE 49
Figure 20: Device Drawing CIFX 90-RE 49
Figure 21: Device Drawing CIFX 104C-RE 50
Figure 22: Device Drawing CIFX 104C-RE-R 50
Figure 23: Device Drawing CIFX 104C-RE\F 51
Figure 24: Device Drawing CIFX 104C-RE-R\F 51
Figure 25: Device Drawing Connection Interface AIFX-RE 52
Figure 26: Device Drawing Diagnosis Interface AIFX-DIAG 52
Figure 27: Ethernet pinning at the RJ45 Socket 53
Figure 28: Mini-B USB Connector (5 Pin), S302 55

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Lists • 91

13.2 List of Tables


Table 1: List of Revisions 7
Table 2: Reference on Hardware 8
Table 3: Reference on Software 8
Table 4: Directory Structure of the CD 9
Table 5: Device Description Files 9
Table 6: Documentations cifX Devices Real Time Ethernet 10
Table 7: Safety Symbols and Sort of Warning or Principle 13
Table 8: Signal Words 13
Table 9: Signal Words according to ANSI 13
Table 10: PCI Connector for cifX cards 17
Table 11: Requirements for cifX Slave Device Operation 18
Table 12: Preconditions for cifX Master Device Operation 18
Table 13: Installation and Configuration Steps cifX Slave Device 19
Table 14: Installation and Configuration Steps cifX Master Device 20
Table 15: cifX LED Labeling depending of the loaded Firmware 23
Table 16: cifX LED Labeling depending of the loaded Firmware 25
Table 17: Configuration Steps / USB Device Driver already installed 34
Table 18: Device Identification 36
Table 19: General Buttons 37
Table 20: Status Line Icons 38
Table 21: Select Language Icon Bar (only English yet) 40
Table 22: Select Network Icon Bar: Firmware Buttons Real-Time Ethernet and Fieldbus System 40
T able 23: Descriptions Configuration Windows 42
Table 24: Diagnostic Window > System 44
Table 25: Diagnostic Window > System, Communication 45
Table 26: Start COM, Stop COM, Reset 46
Table 27: Ethernet pinning at the RJ45 Socket 53
Table 28: Ethernet Connection Data 53
Table 29: Use of Hubs and Switches 54
Table 30: Pin out, S302 55
Table 31: Rotary Switch for Slot Number, S1 55
Table 32: Pinning for Cable Connector Ethernet X4 or X304 – Cable 20 pin Ethernet + Status LED 56
Table 33: Pinning for Cable connector DIAG X3 or X303 - Cable 12 pin USB + Status LED 57
Table 34: Pinning for SYNC Connector, X51 57
Table 35: LED Names for each Real Time Ethernet System 58
Table 36: Meaning LED Names 58
Table 37: EtherCAT Master 59
Table 38: Indicator States EtherCAT Master 59
Table 39: EtherCAT Slave 60
Table 40: Indicator States EtherCAT Slave 60
Table 41: EtherNet/IP Scanner (Master) 61
Table 42: EtherNet/IP Adapter (Slave) 62
Table 43: LED Open Modbus/TCP 63
Table 44: LED Powerlink Controlled Node / Slave 64
Table 45: Indicator States Powerlink Controlled Node / Slave 64
Table 46: PROFINET IO-RT Controller 65
Table 47: PROFINET IO-RT-Device 66
Table 48: SERCOS III Slave 67
Table 49: Indicator States SERCOS III Slave 67
Table 50: Technical Data CIFX 50-RE 68
Table 51: Technical Data CIFX 50E-RE 69
Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim
Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Lists • 92
Table 52: Technical Data CIFX 80-RE 70
Table 53: Technical Data CIFX 90-RE 71
Table 54: Technical Data CIFX 104C-RE, CIFX 104C-RE-R, CIFX 104C-RE\F, CIFX 104C-RE-R\F 72
Table 55: Technical Data AIFX-RE 73
Table 56: Technical Data AIFX-DIAG 73
Table 57: EtherCAT Master 74
Table 58: EtherCAT Slave 74
Table 59: EtherNet/IP Scanner (Master) 75
Table 60: EtherNet/IP Adapter (Slave) 76
Table 61: Open Modbus/TCP 77
Table 62: Powerlink Controlled Node / Slave 77
Table 63: PROFINET IO-RT-Controller 78
Table 64: PROFINET IO-RT-Device 79
Table 65: SERCOS III Slave 80
Table 66: EtherCAT Slave Parameters 81
Table 67: EtherNet/IP Adapter Parameters 82
Table 68: Open Modbus/TCP Parameters 85
Table 69: Powerlink Controlled Node / Slave Parameters 87
Table 70: PROFINET IO-Device Parameters 88
Table 71: SERCOS III Slave Parameters 89

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Glossary • 93

14 Glossary
CIFX
Communication InterFace based on netX
DPM
Dual-Port Memory
EDS
Electronic Data Sheet
XML based device description file.
GSDML
General Station Description Markup Language
XML based device description file.
netX Configuration and Diagnostic Utility
The netX Configuration and Diagnostic Utility allows to operate cifX or
netX based devices in different networks. Its graphical user interface serves
as configuration tool for the installation, configuration and diagnosis of the
devices.
netX
networX on chip, next generation of communication controllers

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06
Communication Interface Hilscher cifX-RE Contacts • 94

15 Contacts

Headquarter

Germany
Hilscher Gesellschaft für
Systemautomation mbH
Rheinstrasse 15
65795 Hattersheim
Phone: +49 (0) 6190 9907-0
Fax: +49 (0) 6190 9907-50
E-Mail: [email protected]
Support
Phone: +49 (0) 6190 9907-99
E-Mail: [email protected]

Subsidiaries

China Japan
Hilscher Ges.f.Systemaut. mbH Hilscher Japan KK
Shanghai Representative Office Tokyo, 160-0022
200010 Shanghai Phone: +81 (0) 3-5362-0521
Phone: +86 (0) 21-6355-5161 E-Mail: [email protected]
E-Mail: [email protected] Support
Support Phone: +81 (0) 3-5362-0521
Phone: +86 (0) 21-6355-5161 E-Mail: [email protected]
E-Mail: [email protected]

Switzerland
France Hilscher Swiss GmbH
Hilscher France S.a.r.l. 4500 Solothurn
69500 Bron Phone: +41 (0) 32 623 6633
Phone: +33 (0) 4 72 37 98 40 E-Mail: [email protected]
E-Mail: [email protected] Support
Support Phone: +49 (0) 6190 9907-99
Phone: +33 (0) 4 72 37 98 40 E-Mail: [email protected]
E-Mail: [email protected]

USA
Italy Hilscher North America, Inc.
Hilscher Italia srl Lisle, IL 60532
20090 Vimodrone (MI) Phone: +1 630-505-5301
Phone: +39 02 25007068 E-Mail: [email protected]
E-Mail: [email protected] Support
Support Phone: +1 630-505-5301
Phone: +39 / 02 25007068 E-Mail: [email protected]
E-Mail: [email protected]

Hilscher Gesellschaft für Systemautomation mbH – Rheinstr. 15 – D 65795 Hattersheim


Edition 9 – UM:CIFX-RE#EN – 2008/06

You might also like