Nader NDM2 63 MCCB
Nader NDM2 63 MCCB
ND M---- 2- 63 / 4 3 00 63A
Page 1 of 9
Note 1: The rated current is: 10A, 12.5A, 16A, 20A, 25A, 32A, 40A, 50A 63A;
Note 2: The neutral pole-N-pole type of the 4P product is divided into three types:
Type A: The N-pole isn't installed with an overcurrent tripper, but always connected;
Type B: The N-pole isn't installed with an overcurrent tripper, but on-off with the other three poles;
Type C: The N-pole is installed with an overcurrent tripper, and on-off with the other three poles.
Note 3: Application code: No code is available for the circuit breaker for distribution; the protection motor type is represented as
2;
Note 4: Release code;
0: Tripper (none)
2: Instantaneous tripper only
3: Complex tripper
Note 5: No code is available for the direct handle-operated mode; P: Motor-operated; Z: Rotation handle-operated
Table 1: Comparison Table of Accessory Code:
Handle Legend
Single auxiliary contact
Dual-auxiliary contact
Alarm contact
Shunt release
Under-voltage release
Auxiliary contact (a single accessory
Left installation Right installation
integrates the auxiliary and alarm
functions)
Accessory Number
code Accessory name of poles
None
Shunt release
Dual-auxiliary contact
Under-voltage release
Alarm contact
Page 2 of 9
4、 Main Technical Parameters
Model
Usage category
Number of poles
Rated limit
short-circuit breaking
capacity Icu (kA)
Rated limit
short-circuit breaking
capacity level Ics
(kA)
Electrical life
Operating
performance(Number
of times) Mechanical
life
Outline dimensions
Page 3 of 9
5、 Connection capacity:
Rated current A 10, 12.5 16, 20 25 32 40, 50 63
Wire 1.5 2.5 4.0 6.0 10 16
cross-section
area mm2
Page 4 of 9
Derating Factor Table of Temperature Change for NDM2 Series Molded Case Circuit Breaker
SN Product Derating factor of product temperature change
model
1 NDM2-63 Temperature 40℃ 45℃ 50℃ 55℃ 60℃ 65℃ 70℃
Derating 1 0.979 0.958 0.937 0.915 0.893 0.871
factor
7、 Tripping Characteristics
NDM2-63 Time/Current Characteristic Curve:
Action time
Rated current(100%)
Page 5 of 9
8. Outline and Installation Dimensions
Under-voltage
Mounting Plate
Model
Page 6 of 9
8.1 Insulation distance mounted in the metal cabinet (unit: mm), as shown below:
NDM2-63 25 65 30 30
8.2 Minimum center distance between rowed circuit breakers
NDM2-63 90 90
Note:
1. Cable insulating connection
2. Connection without insulation
3. Check whether the 0 arcing cover or phase partition is assembled
properly before products are energized.
Page 7 of 9
9. Installation Mode
Installation Direction
For vertical installation of the product, the gradient between the installation surface and the vertical plane is no more than ±22.5°.
Horizontal installation of the product
12. Precautions
▲ Various characteristics and accessories of the circuit breaker are set in the factory, which shall not be
adjusted randomly;
▲ The circuit breaker handle can be located in three positions, indicating three states: on, off and free tripping.
When the handle is in the free tripping position, pull the handle in the off direction when the circuit breaker is
connected and on.
Page 8 of 9
Page 9 of 9