Product Specification of NDM2-63

Product Name:Molded Case Circuit


Breaker
Product Model:NDM2-63
NDM2-63
1、 Application Scope and Purpose
NDM2 series of molded case circuit breakers (referred to as circuit breakers) apply to infrequent switching of
circuits with the 50/60Hz, the rated working voltage of AC690V and rated working current of 800A as well as
infrequent motor starting. With the overload, short circuit and undervoltage protection functions, the circuit
breaker can protect lines and power equipment from damage. Products are widely used in the new energy,
power, industrial control, real estate, electric power, telecom, rail transportation, project (public) construction
and etc.
2. Picture of the Product

3. Specification and Model Description

ND M---- 2- 63 / 4 3 00 63A

Rated current of the circuit breaker (Note 1)


Neutral pole-N-pole type of the 4P product (Note 2)

Application code (Note 3)


Accessory code (Table 1)
Release code (Note 4)
Number of poles: 4
Operation mode (Note 5)
Rated current of frame: 63A
Design code
Molded case circuit breaker (MCCB)
“Nader” brand low-voltage apparatus

Page 1 of 9
Note 1: The rated current is: 10A, 12.5A, 16A, 20A, 25A, 32A, 40A, 50A 63A;
Note 2: The neutral pole-N-pole type of the 4P product is divided into three types:
Type A: The N-pole isn't installed with an overcurrent tripper, but always connected;
Type B: The N-pole isn't installed with an overcurrent tripper, but on-off with the other three poles;
Type C: The N-pole is installed with an overcurrent tripper, and on-off with the other three poles.
Note 3: Application code: No code is available for the circuit breaker for distribution; the protection motor type is represented as
2;
Note 4: Release code;
0: Tripper (none)
2: Instantaneous tripper only
3: Complex tripper
Note 5: No code is available for the direct handle-operated mode; P: Motor-operated; Z: Rotation handle-operated
Table 1: Comparison Table of Accessory Code:
Handle Legend
Single auxiliary contact
Dual-auxiliary contact
Alarm contact
Shunt release
Under-voltage release
Auxiliary contact (a single accessory
Left installation Right installation
integrates the auxiliary and alarm
functions)

Installation position Model

Accessory Number
code Accessory name of poles

None

Shunt release

Dual-auxiliary contact

Single auxiliary contact

Under-voltage release

Shunt release, dual-auxiliary contact

Shunt release, single auxiliary contact

Shunt release, under-voltage release

Two sets of dual auxiliary contacts

Two sets of single auxiliary contacts

Dual-auxiliary contact, single auxiliary contact

Under-voltage release, dual-auxiliary contact

Under-voltage release, single auxiliary contact

Alarm contact

Shunt release, alarm contact

Dual-auxiliary contact, alarm contact

Under-voltage release, alarm contact

Shunt release, auxiliary alarm contact

Auxiliary alarm contact

Dual-auxiliary contact, auxiliary alarm contact

Under-voltage release, auxiliary alarm contact

Page 2 of 9
4、 Main Technical Parameters

Model

Rated current of frame Inm (A)

Rated current In (A)

Rated insulation voltage Ui (V)

Rated impulse withstand voltage Uimp (V)

Power frequency withstand voltage (1min) (V)

Usage category

Number of poles

Rated limit short-circuit breaking capacity


level

Rated limit
short-circuit breaking
capacity Icu (kA)

Rated limit
short-circuit breaking
capacity level Ics
(kA)

Electrical life
Operating
performance(Number
of times) Mechanical
life

Outline dimensions

Flashover distance (mm)

Wiring mode General, P, Z1,Z2Q, Z2H

Page 3 of 9
5、 Connection capacity:
Rated current A 10, 12.5 16, 20 25 32 40, 50 63
Wire 1.5 2.5 4.0 6.0 10 16
cross-section
area mm2

SN Rated current of frame Thread diameter Torque value (N)


(A)
1 63 M5 4

SN Rated current of frame Mounting thread Torque value (N)


(A) diameter
1 63 M3 1

6. Normal Working Environment


 Operating Ambient Temperature
-35℃~+70℃; the average within 24 h shall not be more than +35℃. If the temperature is higher than +40℃,
the user needs to reduce the capacity. See the "Derating Factor Table of Temperature Change for NDM2Z
Series Molded Case Circuit Breakers" for the derating factor.
 Storage Temperature
-40℃~+75℃
 Altitude
The altitude of the installation site doesn't exceed 2,000m. See the "Derating Factor Table of Temperature
Change for NDM2Z Series Molded Case Circuit Breakers" for the derating factor at the altitude;
 Operating/Storage Relative Humidity
The relative humidity at an ambient temperature of +40℃ should not exceed 50%. A higher relative humidity
is allowed at a lower temperature. For example, the relative humidity at 20℃ can reach 90%. For frost due to
temperature change, the corresponding measures should be taken.
 Pollution Level
Level 3
 Installation Category
The installation category of the circuit breaker connected to the main loop is: Ⅲ (power distribution and
control level);
The installation category of the circuit breaker not connected to the main loop is: Ⅱ (load level).
 Installation Environment
The product should be installed in places that are free from explosive media, media corrosive to metal,
insulation damaging gas, and conductive dust, which should be also avoided from snow and rain.

Page 4 of 9
 Derating Factor Table of Temperature Change for NDM2 Series Molded Case Circuit Breaker
SN Product Derating factor of product temperature change
model
1 NDM2-63 Temperature 40℃ 45℃ 50℃ 55℃ 60℃ 65℃ 70℃
Derating 1 0.979 0.958 0.937 0.915 0.893 0.871
factor

High-altitude Derating Factor Table of Molded Case Circuit Breaker

Altitude H Rated working current Ultimate Rated working


Altitude (km) working voltage frequency withstand
voltage
2 In Ue U
2.5 In Ue U
3 0.98In 0.83Ue 0.89U
3.5 0.97 In 0.77 Ue 0.85U
4 0.96In 0.71Ue 0.80U
4.5 0.95 In 0.67 Ue 0.77U
5 0.94In 0.63Ue 0.73U

7、 Tripping Characteristics
NDM2-63 Time/Current Characteristic Curve:
Action time

Rated current(100%)

Page 5 of 9
8. Outline and Installation Dimensions

Under-voltage

Add a 142'' terminal cover (optional); no terminal cover is available


for 4P products

Hole Dimensions of Front-plate Connection

Mounting Plate

Model

Page 6 of 9
8.1 Insulation distance mounted in the metal cabinet (unit: mm), as shown below:

A (inlet wire end to the


Mounting distance
cabinet face) C (outlet
B (distance
wire end to
from side to
the cabinet
With a 0 cabinet)
Without a 0 face)
Specification arcing
arcing cover
cover

NDM2-63 25 65 30 30
8.2 Minimum center distance between rowed circuit breakers

Width of circuit breaker


Specification
(mm) Center distance (mm)

3 poles-3P 4 poles-4P 3 poles-3P 4 poles-4P


NDM2-63 78 103 108 133
Note: Check the connected busbar or cable during rowing or stacking of the circuit br eaker to ensure that the
air insulation distance won't be reduced
8.3 Minimum center distance between stacked circuit breakers
H (distance of circuit breaker from bottom)
Specification
With a 0 arcing cover Without a 0 arcing cover

NDM2-63 90 90

Note:
1. Cable insulating connection
2. Connection without insulation
3. Check whether the 0 arcing cover or phase partition is assembled
properly before products are energized.

Page 7 of 9
9. Installation Mode
Installation Direction

For vertical installation of the product, the gradient between the installation surface and the vertical plane is no more than ±22.5°.
Horizontal installation of the product

Vertical Installation Horizontal Installation

10. Packaging and Storage


Minimum packaging quantity: 1 piece/box. The packaged products should be stored in a warehouse with
the ambient temperature of -45℃~75 ℃ and the corresponding relative humidity below 80% without acidic,
alkali or other corrosive gas in the surrounding air. Under the conditions above, the storage period shall be no
more than 36 months since the manufacturing date.

11. List of Accessories and Installation

SN Name Specification Quantity/Set


Cross small pan-head
1 M3X35 6
screws
2. Plain washer 3 6
3 Spring washer 3 6
4 Hexagon nut M3 6
5 Phase partition —— 6

12. Precautions
▲ Various characteristics and accessories of the circuit breaker are set in the factory, which shall not be
adjusted randomly;
▲ The circuit breaker handle can be located in three positions, indicating three states: on, off and free tripping.
When the handle is in the free tripping position, pull the handle in the off direction when the circuit breaker is
connected and on.

Page 8 of 9