Performance Requirements of
Performance Requirements of
Performance Requirements of
Lighting and Light-Signaling Devices
for Motor Vehicle having more than
Three Wheels, Trailer and
Semi-Trailer
PRINTED BY:
ON BEHALF OF:
AUTOMOTIVE INDUSTRY STANDARDS COMMITTEE
UNDER
CENTRAL MOTOR VEHICLES RULES – TECHNICAL STANDING COMMITTEE
SET-UP BY
MINISTRY OF ROAD TRANSPORT & HIGHWAYS
GOVERNMENT OF INDIA
December 2004
I
AIS-012
Status chart of the Standard to be used by the purchaser
for updating the record
General Remarks :
II
AIS-012
INTRODUCTION
The Government of India felt the need for a permanent agency to expedite the
publication of standards and development of test facilities in parallel when the
work on the preparation of the standards is going on, as the development of
improved safety critical parts can be undertaken only after the publication of the
standard and commissioning of test facilities. To this end, the Ministry of Surface
Transport (MOST) vide order No. RT-11028/11/97-MVL dated September
15,1997.The standard prepared by AISC will be approved by the permanent
CMVR Technical Standing Committee (CTSC). After approval, the Automotive
Research Association of India,(ARAI), Pune , being the Secretariat of the AIS
Committee, has published this standard . For better dissemination of this
information ARAI may publish this document on their Web site.
Considerable assistance has been taken from the following ECE Regulations in
preparing this standard:
III
AIS-012
- The new and old colour coordinates of ECE regulations have been retained as
alternatives;
- The size of number plate for checking the registration plate (mark) illuminating
lamp has been changed to the size prescribed in CMVR ;
IV
AIS-012
1.0 SCOPE
2.0 REFERENCE
4.0 DEFINITIONS
4.1.1 “Lens” means the outermost component of the headlamp (unit), which
transmits light through the illuminating surface;
1/205
AIS-012
4.1.5. “Ballast” means the electrical supply of the gas-discharge light source.
This ballast may be partly or completely inside or outside the
headlamp.
4.1.6. “Matched pair” means the set of lamps of the same function on the left
and right-hand side of the vehicle;
4.1.9. “Front fog lamps of different types” are front fog lamps which differ
in such essential respects as;
2/205
AIS-012
4.1.10. “Front and rear position (side) lamps, stops lamps and end-outline
marker lamps of different types” means lamps which differ in each
side category in such essential respects as;
4.1.10.3. The system used to reduce illumination at night-in the case of stop-
lamps with two levels of intensity.
4.1.13. “Parking lamps of different types” are parking lamps which differ in
such essential respects as;
3/205
AIS-012
4.1.13.2. The characteristics of the optical system;
4.1.15. “Rear fog lamps of different types” are rear fog lamps, which differ in
such essential respects as
4.1.16.3 The angle of incidence of the light on the surface of the plate.
5.1 Main beam headlamp and dipped beam Annex: A1, A2, A3
headlamp
5.2 Gas discharge headlamp Annex: B1 , B2. B3
5.3 Front fog lamp Annex:C1, C2, C3
5.4 Front and rear position lamp, stop lamp Annex: D1, D2, D3
and end-out line marker lamp
5.5 Direction indicator lamp and hazard Annex: E1, E2, E3
warning lamp
5.6 Reversing lamp Annex: F1, F2, F3
5.7 Parking lamp Annex: G1, G2, G3
5.8 Side marker lamp Annex: H1, H2, H3
5.9 Rear fog lamp Annex: J1, J2, J3
5.10 Rear registration plate (mark) illuminating Annex: K1, K2, K3
device
4/205
AIS-012
5.11 In the case of devices designed for use with replaceable filament lamp
or gas-discharge light source, they shall be of category listed in AIS-
034 or corresponding standard applicable at the time of Type Approval
of device or those permitted in standard considered to be alternate as
per rule 92(3) of CMVR. The lamp holders of such devices shall be
suitable for cap of such filament lamps or gas-discharge light sources
5.12 In the case of devices with non-replaceable light source or light source
module, the non-replaceable light source or light source module shall
comply with the requirement given to Annex :M
6.1 The applicable tests to the lighting and light-signaling devices are
shown in the Table-1
7.1 For photometric and colorimetric tests two samples – one L/H and
one R/H- shall meet the specified requirements. The samples tested
for photometric tests may be further used for colorimetric tests
7.2 For all other environmental tests a separate sample shall be tested.
However tests can be combined as per manufacturers’ option.
7.3 For the test of plastic material of which the lenses of headlamp are
made the following samples shall also be submitted:
7.3.3 Every such lens or sample of material shall be produced by the method
to be used in mass production;
5/205
AIS-012
7.3.4 A reflector to which the lenses can be fitted in accordance with the
manufacturer's instructions.
7.3.5 The materials making up the lenses and coatings, if any, shall be
accompanied by the test report of the characteristics of these materials
and coatings if they have already been tested.
7.3.6.1. One sample each of the relevant material as being used in the
headlamp or one headlamp sample containing these. Each material
sample shall have the same appearance and surface treatment - if any -
as intended for use in the headlamp to be approved.
8.2 The test agency may at any time verify the conformity control methods
applied in each production facility. The normal frequency of these
verifications shall be once every two years.
8.3. Penalties for noncompliance of conformity of production shall be as
detailed in AIS-037
6/205
AIS-012
10.1.1 the model with the changed specifications still complies with
provisions;
or,
10.1.2 any further verification is required to establish compliance.
10.3. In case of 10.1.2, tests for only those parameters which are affected by
the modifications need be carried out
Till the details are finalized, the Criteria shall be as agreed between the
test agency and manufacturer.
12. MARKING
12.1 The devices shall have, in a legible and indelible way, the following
markings:
Note: This is not applicable, if the devices are fitted with non-
replaceable light sources.
12.4 On the prototype for type approval the marking may be provided by
suitable temporary methods and need not necessary be obtained from
the tools used for series production.
7/205
AIS-012
12.7 In case of front and rear position lamp, stop lamp and end-out line
marker lamps operating at other than the nominal rated voltages of
6V, 12V or 24 V respectively, by the application of an additional
supply system or having secondary mode, must bear a marking
denoting the rated secondary design voltage , if the additional supply
is not part of the device.
Table: 1
(See para 6.1)
LIST OF APPLICABLE TESTS
2 Colorimetry
3 Vibration Test
6 Dust Test
7 Moisture Test
8/205
AIS-012
Table: 2
(See para 9.1)
TECHNICAL INFORMATION TO BE SUBMITTED BY THE
MANUFACTURER FOR TYPE- APPROVAL
10/205
AIS-012
12.4.6 In the case of a Category S3 stop lamp which is intended to be mounted inside
the vehicle, a sample plate or sample plates (in case of different possibilities)
having the equivalent optical properties corresponding to those of the actual
rear window(s).
12.5 Direction Indicator lamp
12.5.1 Category or to which of the Categories 1, 1a, 1b, 2a, 2b, 3, 4, 5 or 6
according to Appendix-1 to Annex: E2 the direction indicator belongs and,
if it belongs to Category 2, whether it has one level of intensity (Category 2a)
or two levels of intensity (Category 2b) and whether the direction indicator
may also be used in an assembly of two lamps of the same category.
12.5.2 See para 12.4.3
12.5.3 For a direction indicator of category 2b, an arrangement diagram and a
specification of the characteristics of the system ensuring the two level of
intensity. Also two samples of the parts constituting the system which
ensure the two levels of intensity.
12.6 Reversing lamp
12.6.1 See para 12.4.3
12.7 Parking lamp
12.7.1 See para 12.4.3
12.8 Side-marker lamp
12.8.1 See para 12.4.3
12.9 Rear fog lamp
12.9.1 See para 12.4.3
12.10 Rear registration plate ( mark) illuminating lamp :
12.10.1 Whether the device intended to illuminate a wide plate or tall plate
12.10.1 Drawings showing geometrically the position in which the illuminating
device is to be fitted in relation to the space to be occupied by the
registration plate, and the outlines of the area adequately illuminated.
11/205
AIS-012
ANNEX : A1
(See para 5.1)
REQUIREMENTS FOR MAIN-BEAM HEADLAMP AND
DIPPED-BEAM HEADLAMP
12/205
AIS-012
A1.1.5 The filament lamp holder shall conform to the characteristics given
in AIS 034. The holder data sheet relevant to the category of
filament lamp used applies.
A1.1.8 If the lens of the headlamp is of plastic material, tests shall be done
according to the requirements of Annex : A5.
13/205
AIS-012
ANNEX : A2
(See para 5.1 and A1.1.1.)
PHOTOMETRIC TEST PROCEDURE AND
ILLUMINATION REQUIREMENTS FOR MAIN-BEAM
HEADLAMP AND DIPPED-BEAM HEADLAMP
14/205
AIS-012
(1)
A2.2.2.3 The "elbow" of the "cut-off" is on line vv
A2.2.3 When so aimed, the headlamp need, if its approval is sought solely
for provision of a dipped-beam(2), comply only with the
requirements set out in paragraphs A2.2.5 to A2.2.7 below; if it is
intended to provide both a dipped-beam and a main-beam, it shall
comply with the requirements set out in paragraphs from A2.2.5 to
A2.2.7 and A 2.3.
A2.2.4 Where a headlamp so aimed does not meet the requirements set out
in paragraphs A2.2.5 to A2.2.7 and A 2.3, its alignment may be
changed, provided that the axis of the beam is not displaced
laterally by more than 10 (= 44 cm) to the right or left (3). To
facilitate alignment by means of the "cut-off", the headlamp may
be partially occulted in order to sharpen the "cut-off".
15/205
AIS-012
A2.2.7 The illumination values (1) in zones "A" and "B" as shown in
Figure A2 shall be checked by the measurement of the photometric
values of points 1 to 8 on this Figure; these values shall lie within
the following limits: (1)
1+2+3 0.3 lux, and
4+5+6 0.6 lux, and
0.7 lux 7 0.1 lux and
0.7 lux 8 0.2 lux
A2.3.2.1.2 The reference mark (I’M) indicating this maximum intensity shall
be obtained by means of the formula:
I’M = IM / 3 = 0.208 EM
(1) Illumination values in any point of Zones A & B, which also lies with Zone
III, shall not exceed 0.7 lux
16/205
AIS-012
A2.3.2.2. Starting from point HV, horizontally to the right and left the
illumination shall be not less than 16 lux for Class A headlamp and
24 lux for Class B headlamp up to a distance of 1.125 m and not
less than 4 lux for Class A headlamp and 6 lux for Class B
headlamp up to a distance of 2.25 m.
A2.4.2. With the reflector initially fixed according to paragraph A2.4.1, the
headlamp must meet the relevant photometric requirements of
paragraphs A2.2 and A2.3;
A2.4.3 Additional tests are made after the reflector has been moved
vertically ± 2 degrees or at least into the maximum position, if less
than 2 degrees, from its initial position by means of the headlamps
adjusting device. Having re-aimed the headlamp as a whole (by
means of the goniometer for example) in the corresponding
opposite direction, the light output in the following directions shall
be controlled and lie within the required limits:
A2.4.4 If the applicant has indicated more than one mounting position, the
procedure of paragraphs A2.4.1 to A2.4.3 shall be repeated for all
the other positions;
A2.4.5 If the applicant has not asked for special mounting positions, the
headlamp shall be aimed for measurements of paragraphs A2.2 and
A2.3 with the headlamps adjusting device in its mean position. The
additional tests of paragraph A2.4.3 shall be made with the
reflector moved into its extreme positions (instead of ± 2°) by
means of the headlamps adjusting device.
17/205
AIS-012
A2.6.3 Provides with a standard filament lamp, at the various point and in
the various zones referred to in paragraph A2.2.5., illumination
equal to:
A2.6.3.2 Not less than 120% of the minimum limits prescribed in the table
in paragraph A2.2.5.
18/205
AIS-012
ANNEX : A3
(See para 5.1 and A1.1.1.)
19/205
AIS-012
ANNEX : A4
(See para A1.1.7)
20/205
AIS-012
(c) in the case of a headlamp with a front fog lamp and one or
more main-beams:
22/205
AIS-012
Dipped-beam: 50 L - B 50 R - HV.
Main-beam: Point of Emax
23/205
AIS-012
This test consists of verifying that the vertical drift of the cut-off
line under the influence of heat does not exceed a specified value
for an operating passing lamp. The headlamp tested in accordance
with paragraph A4.1, shall be subjected to the test described in
paragraph A4.2.1., without being removed from or readjusted in
relation to its test fixture.
A4.2.1. Test
The test shall be carried out in a dry and still atmosphere at an
ambient temperature of 23° C ± 5° C.
(1) See foot note (1) on page no 23
(2) The tolerance on quantity is due to the necessity of obtaining a dirt that
correctly spreads out on all the plastic lens.
(3) Point 50 V is situated 375 mm below HV on the vertical line v-v on the
screen at 25 m distance.
24/205
AIS-012
Using a mass production filament lamp, which has been aged for at
least one hour the headlamp shall be operated on dipped-beam
without being dismounted from or readjusted in relation to its test
fixture. (For the purpose of this test, the voltage shall be adjusted as
specified in paragraph A4.1.1.1.2.). The position of the cut-off line
in its horizontal part (between vv and the vertical line passing
through point B 50 R ) shall be verified 3 minutes (r3) and 60
minutes (r60) respectively after operation.
A4.2.2.2 However, if this value is more than 1.0 mrad but not more than
1.5 mrad (1.0 mrad < delta rI < 1.5 mrad) a second headlamp shall
be tested as described in paragraph A4.2.1 after being subjected
three consecutive times to the cycle as described below, in order to
stabilize the position of mechanical parts of the headlamp on a base
representative of the correct installation on the vehicle:
25/205
AIS-012
ANNEX : A5
(See para A1.1.8)
A5.1.4. However, if the lamp manufacturer can prove that the product has
already passed the tests prescribed in paragraphs A5.2.1.to A5.2.5.
below, or the equivalent tests pursuant to another standard those
tests need not be repeated; only the tests prescribed in Appendix 1,
Table B, shall be mandatory.
A5.2. TESTS
A5.2.1.1 Tests
26/205
AIS-012
Before this test, the samples shall be kept at 23°C ± 5°C and
60-75 % RH for at least four hours.
Note:
The periods of one hour at 23°C ± 5°C shall include the periods of
transition from one temperature to another, which are needed in
order to avoid thermal shock effects.
A5.2.1.2.1. Method
A5.2.1.2.2. Results
27/205
AIS-012
Soak a piece of cotton cloth (as per ISO 105) until saturation with
the mixture defined in paragraph A5.2.2.2.1 above and, within
10 seconds, apply it for 10 minutes to the outer face of the sample
at a pressure of 50 N/cm2, corresponding to an effort of 100 N
applied on a test surface of 14 x 14 mm.
During this 10-minute period, the cloth pad shall be soaked again
with the mixture so that the composition of the liquid applied is
continuously identical with that of the test mixture prescribed.
A5.2.2.2.3. Cleaning
At the end of the application of the test mixture, the samples shall
be dried in the open air and then washed with the solution
described in paragraph A5.2.3. (Resistance to detergents) at
23°C ± 5°C.
28/205
AIS-012
A5.2.2.3. Results
A5.2.2.3.1 After the test of resistance to atmospheric agents, the outer face of
the samples shall be free from cracks, scratches, chipping and
deformation, and the mean variation in transmission
A5.2.2.3.2 After the test of resistance to chemical agents, the samples shall not
bear any traces of chemical staining likely to cause a variation of
flux diffusion, whose mean variation
The outer face of these three samples shall then be lightly rubbed
for one minute with a cotton cloth soaked in a mixture composed of
70% n-heptane and 30%toluene (volume %), and shall then be
dried in the open air.
29/205
AIS-012
A5.2.3.3. Results
After the above two tests have been performed successively, the
mean value of the variation in transmission
The outer face of the three new samples (lenses) shall be subjected
to the uniform mechanical deterioration test by the method
described in Appendix 3 to this Annex.
A5.2.4.2. Results
and in diffusion:
30/205
AIS-012
A5.2.5.2. Description of the Test
Then the end of the adhesive tape shall be loaded in such a way
that the force of adhesion to the surface considered is balanced by a
force perpendicular to that surface. At this stage, the tape shall be
torn off at a constant speed of 1.5 m/s ± 0.2 m/s.
A5.2.5.3. Results
A5.2.6.1.1. Tests
A5.2.6.1.2. Results
A5.3.1. With regard to the materials used for the manufacture of lenses, the
lamps of a series shall be recognized as complying with this
Standard if:
31/205
AIS-012
A5.3.1.1. After the test for resistance to chemical agents and the test for
resistance to detergents and hydrocarbons, the outer face of the
samples exhibits no cracks, chipping or deformation visible to the
naked eye (see para. A5.2.2.2, A5.2.3.1. and A5.2.3.2.);
A5.3.2. If the test results fail to satisfy the requirements, the tests shall be
repeated on another sample of headlamps selected at random.
32/205
AIS-012
ANNEX:A5 – APPENDIX:1
(See para A5.1.3)
33/205
AIS-012
34/205
AIS-012
ANNEX:A5 – APPENDIX:2
(See para A5.2.2.3.1)
35/205
AIS-012
FIGURE
36/205
AIS-012
ANNEX:A5 – APPENDIX:3
(See para A5.2.4.1.)
A5:App3.2. TEST
T5 - T4
d = __________ = 0.0250 ± 0.0025
T2
Several reference samples may be used to check that the whole
surface to be tested has deteriorated homogeneously.
37/205
AIS-012
ANNEX: A5 – APPENDIX:4
(See para A5.2.5.2)
A5:App4.1. PURPOSE
A5:App4.2. PRINCIPLE
Five test pieces each 400 mm long shall be tested from each
roll. These test pieces shall be taken from the roll after the first
three turns were discarded.
A5:App4.5. PROCEDURE
Take the five test pieces while unrolling the tape radially at a
speed of approximately 300 mm/s, then apply them within
15 seconds in the following manner:
38/205
AIS-012
Fix the plate and fold back the free end of the tape at 90 0.
Apply force in such a manner that the separation line between
the tape and the plate is perpendicular to this force and
perpendicular to the plate.
A5:App4.6. RESULTS
39/205
AIS-012
ANNEX: A6
(See para 8.0)
A6.1. GENERAL
A6.1.2.2.1. For the dipped-beam, the values prescribed in this standard are met
at HV (with a tolerance of + 0.2 lx) and related to that aiming at
least one point of each area delimited on the measuring screen
(at 25 m) by a circle 15 cm in radius around points B 50 R (with a
tolerance of + 0.1 lx), 75 L, 50 V, 25 R, 25 L, and in the entire
area of zone IV which is not more than 22.5 cm above line 25 R
and 25 L;
A6.1.2.2.2. And if, for the main-beam, HV being situated within the isolux
0.75 Emax, a tolerance of + 20 per cent for maximum values and-
20 per cent for minimum values is observed for the photometric
values at any measuring point specified in paragraph A2.3.2. of this
standard.
40/205
AIS-012
A6.1.2.3. If the results of the test described above do not meet the
requirements, the alignment of the headlamp may be changed,
provided that the axis of the beam is not displaced laterally by
more than 1 0 to the right or left.(1)
A6.1.2.4. If the results of the tests described above do not meet the
requirements, tests shall be repeated using another standard
(étalon) filament lamp.
If this value exceeds 1.5 mrad but is not more than 2.0 mrad, a
second sample shall be subjected to the test after which the mean of
the absolute values recorded on both samples shall not exceed
1.5 mrad.
For each type of headlamp the holder of the approval mark shall
carry out at least the following tests, at appropriate intervals. The
tests shall be carried out in accordance with the provision of this
standard.
(1) The limit of realignment of 10 towards the right or left is not incompatible
with upward or down ward vertical realignment. The latter is limited only
by the requirements of paragraph A2.3 However, the horizontal part of the
“cut-off” should not extend beyond the line hh (the provisions of paragraph
A2.3 are not applicable to headlamps intended to meet the requirements of
relevant Annexes only for provision of a dipped-beam).
41/205
AIS-012
A6.2.2. Methods used in tests
A6.2.2.1. Tests shall generally be carried out in accordance with the methods
set out in this standard
A6.2.2.4. In all cases the reference methods shall be those of this Standard,
particular for the purpose of administrative verification and
sampling.
42/205
AIS-012
A6.2.5. Criteria Governing Acceptability
43/205
AIS-012
ANNEX: A7
(See para 8.0 and para A6.2.5)
A7.1. GENERAL
B 50 R : 0.2 lx equivalent 20 %
0.3 lx equivalent 30 %
Zone III : 0.3 lx equivalent 20 %
0.45 lx equivalent 30 %
A7.1.2.2. or if
A7.1.2.2.1. for the dipped-beam, the values prescribed in this standard are met
at HV (with a tolerance of 0.2 lx) and related to that aiming at least
one point of each area delimited on the measuring screen (at 25 m)
by a circle 15 cm in radius around points B 50 R (with a tolerance
of 0.1 lx), 75 L, 50 V, 25 R, 25 L, and in the entire area of zone IV
which is not more than 22.5 cm above line 25 R and 25 L;
A7.1.2.2.2. and if, for the main-beam, HV being situated within the isolux
0.75 Emax, a tolerance of + 20 per cent for maximum values and
- 20 per cent for minimum values is observed for the photometric
values at any measuring point specified in paragraph A 2.3.2 of
Annex: A2. The reference mark is disregarded.
44/205
AIS-012
A7.1.2.3. If the results of the test described above do not meet the
requirements, the alignment of the headlamp may be changed,
provided that the axis of the beam is not displaced laterally by
more than 1 0 to the right or left(1).
A7.1.2.4. If the results of the tests described above do not meet the
requirements, tests shall be repeated using another standard
filament lamp.
A7.2.1.1.1. Sample A
A7.2.1.1.2. Sample B
(1) The limit of realignment of 10 towards the right or left is not incompatible
with upward or down ward vertical realignment. The latter is limited only
by the requirements of paragraph A2.3 However, the horizontal part of the
“cut-off” should not extend beyond the line hh (the provisions of paragraph
A2.3 are not applicable to headlamps intended to meet the requirements of
relevant Annexes only for provision of a dipped-beam).
45/205
AIS-012
A7.2.2. The Conformity is Contested
A7.2.2.1.1. Sample A
A3: one headlamp not more than 20%
one headlamp more than 20%
but not more than 30%
A7.2.2.1.2. Sample B
A7.2.3.1. Sample A
A4: one headlamp not more than 20%
one headlamp more than 30%
A5: Both headlamps more than 20%
A7.2.3.2. Sample B
B4: in the case of A2
one headlamp more than 0%
but not more 20%
than
one headlamp more than 20%
B5: in the case of A2
both headlamps more than 20%
B6: in the case of A2
one headlamp 0%
one headlamp more than 30%
46/205
AIS-012
A7.3.1.1.1. Sample C
A7.3.1.1.2. Sample D
A7.3.2.1.1. Sample D
47/205
AIS-012
A7.3.3.1. Sample C
C3: one headlamp not more 20%
than
one headlamp more than 20%
C4: both headlamps more than 20%
A7.3.3.2. Sample D
D3: in the case of C2
one headlamp 0 or more than 0%
one headlamp more than 20%
If this value exceeds 1.5 mrad but is not more than 2.0 mrad, the
second headlamp of sample A shall be subjected to the test after
which the mean of the absolute values recorded on both samples
shall not exceed 1.5 mrad.
All following grouped headlamps and front fog lamps together with the added class B marking
symbols are given as examples and are not exhaustive.
P, D or F
1. P or D or F (HC or HR or B)
0 6 12 h
D
P
2. P+D (HCR) or P+D1+D2 (HCR HR)
0 6 12 h
D
P
3. P+D (HC/R) or P+D1+D2 (HC/R HR)
0 6 12 h
F
P
4. P+F (HC B)
0 6 12 h
F
P
5. P+F (HC B/) or HC/B
0 6 12 h
D
F
6. D+F (HR B) or D1+D2+F (HR HR B)
0 6 12 h
49/205
AIS-012
D
F
7. D+F (HR B/) or D1+D2+F (HR HR B/)
0 6 12 h
D+F
P
8. P+D+F (HCR B) or P+D1+D2+F (HCR HR B)
0 6 12 h
F
D
P
9. P+D+F (HC/R B) or P+D1+D2+F (HC/R HR B)
0 6 12 h
F
D
P
10. P+D+F (HCR B/) or P+D1+D2+F (HCR HR B/)
0 6 12 h
F
D
P
11. P+D+F (HC/R B/) or P+D1+D2+F (HC/R HR B/)
0 4 8 12 h
50/205
AIS-012
ANNEX : B1
(See para 5.2)
REQUIREMENTS FOR HEADLAMP EQUIPED WITH
GAS-DISCHARGE LIGHT SOURCES
B1.1.1. Each sample shall conform to the specifications set forth in Annex
B1,B2, B3 and Annex L
51/205
AIS-012
B1.1.8. The headlamp and ballast system shall not generate radiated or
power line disturbances to cause a malfunction of other electric /
electronic system of the vehicle (1)
52/205
AIS-012
ANNEX : B2
(See para 5.2 and B1.1.1)
PHOTOMETRIC TEST PROCEDURE AND
ILLUMINATION REQUIREMENTS FOR HEADLAMP
EQUIPED WITH GAS-DISCHARGE LIGHT SOURCES
B2.1.4 The dimensions determining the position of the arc inside the
standard gas-discharge light source are shown in the relevant data
sheet of standard AIS 034.
B2.1.6 Four seconds after ignition of a headlamp which has not been
operated for 30 minutes or more, 60 lux at least must be reached at
point HV of a main-beam and 10 lux at point 50V of a dipped-
beam for headlamps incorporating main-beam and dipped-beam
functions, or 10 lux at point 50V for headlamps having only a
dipped-beam function. The power supply shall be sufficient to
secure the quick rise of the high current pulse.
53/205
AIS-012
B2.2. PROVISIONS CONCERNING DIPPED-BEAM
B2.2.4 Where a headlamp so aimed does not meet the requirements set out
in paragraphs B2.2.6 and B2.3., its alignment may be changed,
provided that the axis of the beam is not displaced laterally by
more than 0.5° (=22 cm) (2) to the right or left and vertically not
more than 0.2° (=8.7 cm) up or down. To facilitate alignment by
means of the "cut-off", the headlamp may be partially occulted in
order to sharpen the "cut-off".
B2.2.5 Only one gas-discharge light source is permitted for each dipped-
beam headlamp.
54/205
AIS-012
Vertical
Points of Illuminances Horizontal
Designation Distances
Segments Lux Distances (cm)
(cm)
On & above line H/H2, or
1 Max
On & above line H/H3/H4
1 HV 1 max 0 0
2 B 50R 0.5 max R 150 U 25
3 75 L 20 min L 50 D 25
4 50 R 20 max R 150 D 37.5
5 25 R1 30 max R 150 D 75
6 50 V 12 min 0 D 37.5
7 50 L 20 min L 75 D 37.5
8 25 R2 4 min R 396 D 75
9 25 L1 4 min L 396 D 75
10 25 R3 2min R 670 D 75
11 25 L2 2min L 670 D 75
12 15 R 1min R 910 D 125
13 15 L 1 min L 910 D 125
(*)
14 R 350 U 175
(*)
15 0 U 175
(*)
16 L 350 U 175
(*)
17 R 175 U 87.5
(*)
18 0 U 87.5
(*)
19 L 175 U 87.5
20 0.1 min R 350 0
21 0.2 min R 175 0
R 225 to
A to B Segment I 6 min D 37.5
L 225
L 140 to
C to D Segment II 6 max U 45
L 396
Segment III & R 417 to
E to F 20 max D 187.5
under R 375
E max L 70 max Left of VV Line Above D 75
E max R 50 max Right of VV line
(*) The illumination values at points 14 through 19 shall be such that:
55/205
AIS-012
B2.3 PROVISIONS CONCERNING MAIN-BEAM
B2.3.2 It is possible to use several light sources for the main-beam, these
light sources being listed in AIS 034. The following provisions
shall be met:
B2.3.2.3 Starting from point HV, horizontally to the right and left, the
illuminance shall be not less than 40 lux up to a distance of 1.125m
and not less than 10 lux up to a distance of 2.25 m.
B2.5.1 With the lamp fixed according to all the positions described in
relevant paragraph of Table:2 of this standard, the headlamp must
meet the photometric requirements of paragraph B2.2 or B2.3, or
both.
B2.5.2 Additional tests are made after the reflector has been tilted
vertically upwards by the angle quoted in relevant paragraph of
Table:2 of this standard or 2° ; whichever is smaller, by means of
the headlamp aiming devices. The headlamp is then re-aimed
downwards (by means of the goniometer), and the photometric
specifications must be met at the following points:
56/205
AIS-012
Dipped-beam: HV and 75 L respectively
Main-beam: E max, HV as % of Emax
57/205
AIS-012
ANNEX : B3
(See para 5.2 and B1.1.1)
COLORIMETRIC REQUIREMENTS FOR HEADLAMP EQUIPED WITH
GAS-DISCHARGE LIGHT SOURCES
The trichromatic coordinates of the light of the beams emitted by headlamps using
gas discharge light sources must be in the following boundaries:
58/205
AIS-012
ANNEX : B4
(See para B1.1.6)
TEST FOR STABILITY OF PHOTOMETRIC
PERFORMANCE OF HEADLAMPS IN OPERATION.
B4.1.1.1.1
(a) In the case where only one lighting function (driving or dipped-
beam) is to be approved, the corresponding light source is lit
for the prescribed time, (1)
59/205
AIS-012
If the applicant declares that the headlamp is to be used with a
single filament lit, (1) the test shall be carried out in accordance
with this condition, activating (2) each specified function
successively for half the time specified in paragraph B4.1.1.
In all other cases, (1), (2) the headlamp shall be subjected to the
following cycle until the time specified is reached:
The voltage for the ballast is 13.5 ± 0.1 volts for 12V network
system, or other wise specified in the application for approval. If
there are reciprocally incorporated filament lamps, the voltage
producing the reference flux shall be used.
(1) Should two or more light sources be simultaneously lit when headlamp
flashing is used, this shall not be considered as being normal use of the
filaments simultaneously.
(2) See foot note ( 1) on page 59
60/205
AIS-012
61/205
AIS-012
B4.1.2.1.2. Application of the test mixture to the headlamp
This test consists of verifying that the vertical drift of the cut-off
line under the influence of heat does not exceed a specified value
for an operating passing lamp.
(1) 50V is situated 375 mm below HV on the vertical line v-v on the screen at
25 m distance
62/205
AIS-012
B4.2.2.2 However, if this value is more than 1.0mrad but not more than 1.5
mrad (1.0 mrad < r1 1.5mrad), a second headlamp shall be
tested as described in paragraph B4.2.1. after being subjected three
consecutive times to the cycle as described below, in order to
stabilize the position of mechanical parts of the headlamp on a base
representative of the correct installation on the vehicle:
Operation of the passing lamp for one hour (the voltage shall be
adjusted as specified in paragraph B4.1.1.1.2.).
63/205
AIS-012
ANNEX : B 5
(See para B1.1.7)
REQUIREMENTS FOR LAMPS INCORPORATING
LENSES OF PLASTIC MATERIAL – TESTING OF LENS
OR MATERIAL SAMPLES AND OF COMPLETE LAMPS
B5.1.4. However, if the lamp manufacturer can prove that the product has
already passed the tests prescribed in paragraphs B5.2.1.to B5.2.5.
below, or the equivalent tests pursuant to another Regulation, those
tests need not be repeated; only the tests prescribed in Appendix 1,
Table B, shall be mandatory.
B5.2. TESTS
B5.2.1.1 Tests
B5.2.1.2.1. Method
B5.2.1.2.2. Results
The variation between the photometric values measured on each
sample before and after the test shall not exceed 10 % including the
tolerances of the photometric procedure.
64/205
AIS-012
B5.2.2.3. Results
Refer paragraph Annex : A5.2.2.3.
B5.2.3.3. Results
Refer Annex A5.2.3.3.
B5.2.4.2. Results
Refer paragraph A5.2.4.2.
65/205
AIS-012
ANNEX:B 5 – APPENDIX:1
(See para B5.1.3)
CHRONOLOGICAL ORDER OF APPROVAL TESTS
66/205
AIS-012
67/205
AIS-012
ANNEX:B 5 – APPENDIX:2
ANNEX:B 5 – APPENDIX:3
ANNEX: B 5 – APPENDIX:4
68/205
AIS-012
ANNEX: B 6
( See para 8.0)
MINIMUM REQUIREMENTS FOR CONFORMITY OF
PRODUCTION CONTROL PROCEDURES
B6.1. GENERAL
either
or
69/205
AIS-012
B6.1.2.2. or if
B6.1.2.2.1. For the dipped-beam, the values prescribed in this standard are met
at HV (with a tolerance of + 0.2 lx) and related to that aiming at
one point of each area delimited on the measuring screen (at 25 m)
by a circle 15 cm in radius around points B 50 R (with a tolerance
of + 0.1 lx), 75 L , 50 V, 25 R1, 25 L2, and on segment I;
B6.1.2.2.2. and if, for the main-beam, HV being situated within the isolux
0.75 Emax, a tolerance of + 20 % for maximum values and -20 %
for minimum values is observed for the photometric values at any
measuring point specified in paragraph B2.3 of Annex B2. of this
standard.
B6.1.2.3. If the results of the test described above do not meet the
requirements, the alignment of the headlamp may be changed,
provided that the axis of the beam is not displaced laterally by
more than 0.50 to the right or left and not by more than 0.20 up or
down.
B6.1.2.4. If the results of the tests described above do not meet the
requirements, tests on the headlamp shall be repeated using another
standard gas-discharge light source or gas-discharge light source
and ballast, whatever is applicable according to paragraph B6.1.2.
above.
If this value exceeds 1.5 mrad but is not more than 2.0 mrad, a
second sample shall be subjected to the test after which the mean of
the absolute values recorded on both samples shall not exceed
1.5 mrad.
70/205
AIS-012
For each type of headlamp the holder of the approval mark shall
carry out at least the following tests, at appropriate intervals. The
tests shall be carried out in accordance with the provision of this
standard.
B6.2.2.1. Tests shall generally be carried out in accordance with the methods
set out in this standard
B6.2.2.2. In any test of conformity carried out by the manufacturer,
equivalent methods may be used with the consent of the test
agency responsible for approval tests. The manufacturer is
responsible for proving that the applied methods are equivalent to
those laid down in this standard.
B6.2.2.4. In all cases the reference methods shall be those of this standard,
particular for the purpose of administrative verification and
sampling.
71/205
AIS-012
72/205
AIS-012
ANNEX: B 7
( See para 8.0)
B7.1. GENERAL
either
or
B 50 R : 0.20 lx equivalent 20 %
0.30 lx equivalent 30 %
On line
H/H3/H4)
and above : 0.30 lx equivalent 20 %
0.45 lx equivalent 30 %
73/205
AIS-012
B7.1.2.2. or if
B7.1.2.2.1. for the dipped-beam, the values prescribed in this standard are met
at HV (with a tolerance of + 0.2 lx) and related to that aiming at
one point of each area delimited on the measuring screen (at 25 m)
by a circle 15 cm in radius around points B 50 R (1) (with a
tolerance of 0.1 lx), 75 L , 50 V, 25 R1, 25 L2, and on Segment I;
B7.1.2.2.2. and if, for the main-beam, HV being situated within the isolux
0.75 Emax, a tolerance of + 20 per cent for maximum values and
- 20 per cent for minimum values is observed for the photometric
values at any measuring point specified in paragraph B2.3 of
Annex B2 . The reference mark is disregarded.
B7.1.2.3. If the results of the test described above do not meet the
requirements, the alignment of the headlamp may be changed,
provided that the axis of the beam is not displaced laterally by
more than 0.50 to the right or left and not by more than 0.2° up or
down.
B7.1.2.4. If the results of the tests described above do not meet the
requirements, tests on the headlamp shall be repeated using another
standard gas-discharge light source or gas-discharge light source
and ballast, whatever is applicable according to paragraph B7.1.2
above.
If this value exceeds 1.5 mrad but is not more than 2.0 mrad, a
second sample shall be subjected to the test after which the mean of
the absolute values recorded on both samples shall not exceed
1.5 mrad.
74/205
AIS-012
B7.2.1.1.1. Sample A
B7.2.1.1.2. Sample B
B7.2.2.1.1. Sample A
75/205
AIS-012
B7.2.2.1.2. Sample B
one headlamp 0%
one headlamp more than 20%
but not more than 30%
B7.2.3.1. Sample A
B7.2.3.2. Sample B
one headlamp 0%
one headlamp more than 30%
76/205
AIS-012
B7.3.1.1.1. Sample C
B7.3.1.1.2. Sample D
B7.3.2.1.1. Sample D
D2: in the case of C2
one headlamp more than 0%
but not more than 20%
one headlamp not more than 20%
77/205
AIS-012
B7.3.3. Approval Withdrawn
B7.3.3.1. Sample C
B7.3.3.2. Sample D
If this value exceeds 1.5 mrad but is not more than 2.0 mrad, the
second headlamp of sample A shall be subjected to the test after
which the mean of the absolute values recorded on both samples
shall not exceed 1.5 mrad.
78/205
AIS-012
ANNEX: B 8
(See para 12.6)
CENTRE OF REFERENCE
This optional mark of the center of reference shall be positioned on the lens at its
intersection with the reference axis of the dipped-beam, and also on the lenses of
the main-beams when they are neither grouped nor combined nor reciprocally
incorporated with a dipped-beam.
The above drawing represents the mark of the center of reference as projected on a
plane substantially tangent to the lens about the center of the circle. The lines
constituting this mark may either be solid or dotted.
79/205
AIS-012
ANNEX: B 9
( See para. B2.2.5.1 )
VOLTAGE MARKINGS
This marking must be placed on the main body of each headlamp containing only
gas discharge light sources and ballast, and on each external part of the ballast.
The ballast(s) is(are) designed for a ** Volts network system.
This marking must be placed on the main body of each headlamp containing at
least one gas discharge light source and ballast.
The ballast(s) is (are) designed for a ** Volts network system.
None of the filament lamps which the headlamp contains is designed for a 24
Volts network system.
80/205
AIS-012
ANNEX : C1
( See para 5.3)
C1.1.2 The front fog lamps shall be so designed and constructed that in
normal use, despite the vibrations to which they may then be
subjected, their satisfactory operation continues to be ensured and
they retain the characteristics prescribed by this standard. The
correct position of the lens shall be clearly marked and the lens and
reflector shall be so secured as to prevent any rotation during use.
Conformity with the requirements of this paragraph shall be
verified by visual inspection and, where necessary, by a trial
fitting.
C1.1.2.1 Front fog lamps shall be fitted with a device enabling them to be so
adjusted on the vehicles as to comply with the rules applicable to
them. Such a device need not be fitted on units in which the
reflector and the diffusing lens cannot be separated, provided the
use of such units is confined to vehicles on which the front fog
lamp setting can be adjusted by other means. Where a front fog
lamp and another front lamp, each equipped with its own filament
lamp, are assembled to form a composite unit, the adjusting device
shall enable each optical system individually to be duly adjusted.
C1.1.2.2 However, these provisions shall not apply to front lamp assemblies
whose reflectors are indivisible. For this type of assembly the
requirements of paragraph C2.2.6 of Annex :C2 shall apply.
C1.1.4 If the lens of the front fog lamp is of plastic material, tests shall be
done according to the requirements of Annex : C5.
81/205
AIS-012
ANNEX : C2
(See para 5.3 and C1.1.1)
PHOTOMETRIC TEST PROCEDURE AND
ILLUMINATION REQUIREMENTS FOR
FRONT FOG LAMP
C2.1 ILLUMINATION
Approximate
Filament Lamp Light flux in
supply voltage (V)
Category Lumens
for measurement
H1 12 1,150
H2 12 1,300
H3 12 1,100
H4 12 750 ( *)
H7 12 1,100
H8 12 600
HB3 12 1,300
HB4 12 825
H27W / 1 12 350
H27W / 2 12 350
H10 12 600
H11 12 1,000
H12 12 775
(*) 55 W filament
82/205
AIS-012
C2.1.4. The beam shall produce on the screen, over a width of not less than
2.25 m on both sides of the line VV, a symmetrical cut-off
approximating sufficiently closely to the horizontal to enable
adjustment to be performed with its aid.
C2.1.5. The front fog lamp shall be so directed that the cut-off on the
screen is 50 cm below the line hh.
C2.1.6 When so adjusted, the front fog lamp shall meet the requirement set
out in paragraph C2.1.7.below.
C2.1.7 The illumination produced on the screen (see Figure C1) shall meet
the following requirements:
83/205
AIS-012
ANNEX : C3
(See para 5.3 and C.1.1.1)
C3.1 COLOUR
Limit Towards
Red y ≥ 0.138 + 0.580x
Green y ≤ 1.290 x– 0.100
White y ≥ – x + 0.940 and y ≥ 0.440
84/205
AIS-012
ANNEX : C 4
(See para C1.1.3)
TEST FOR STABILITY OF PHOTOMETRIC
PERFORMANCE OF FRONT FOG LAMP IN OPERATION
C4.1.1.1.1. (a) In the case where only a front fog lamp is to be approved, the
corresponding filament lamp(s) is (are) lit for the prescribed time;
Once the front fog lamp has been stabilized to the ambient
temperature, the front fog lamp lens and the external lens, if any,
shall be cleaned with a clean, damp cotton cloth. It shall then be
inspected visually; no distortion, deformation, cracking or change
in color of either the front fog lamp lens or the external lens, if any,
shall be noticeable.
C4.1.2.1.1.1. For front fog lamp with the outside lens in glass:
The mixture of water and a polluting agent to be applied to the
front fog lamp shall be composed of:
9 parts by weight of silica sand with a particle size of 0-100
micrometres,
1 part by weight of vegetal carbon dust (beechwood) with a particle
size of 0-100 micrometres,
0.2 part by weight of NaCMC (1) .
and an appropriate quantity of distilled water, with a conductivity
of < 1 mS/m.
The mixture must not be more than 14 days old.
C4.1.2.1.1.2. For front fog lamp with outside lens in plastic material:
The mixture of water and polluting agent to be applied to the front
fog lamp shall be composed of:
9 parts by weight of silica sand with a particle size of 0-100
micrometres,
1 part by weight of vegetal carbon dust (beechwood) with a particle
size of 0-100 micrometres,
0.2 part by weight of NaCMC (1),
13 parts by weight of distilled water with a conductivity of < 1
mS/m, and
2 +/- 1 parts by weight of surface-actant.(2)
The mixture must not be more than 14 days old.
(1) NaCMC represents the sodium salt of carboxymethylcellulose, customarily
referred to as CMC. The NaCMC used in the dirt mixture shall have a degree of
substitution (DS) of 0.6-0.7 and a viscosity of 200-300 cP for a 2 % solution at
20 degrees C.
(2) The tolerance on quantity is due to the necessity of obtaining a dirt that correctly
spreads out on all the plastic lens.
87/205
AIS-012
C4.1.2.1.2. Application of the test mixture to the front fog lamp
This test consists of verifying that the vertical drift of the cut-off
line under the influence of heat does not exceed the specified value
for an operating front fog lamp. The front fog lamp tested in
accordance with paragraph C4.1, shall be subjected to the test
described in C4.2.1., without being removed from or readjusted in
relation to its test fixture.
C4.2.1. Test
88/205
AIS-012
C4.2.2.2. However, if this value is more than 2 mrad but not more than 3
mrad (2 mrad < delta rI < 3 mrad) a second front fog lamp shall be
tested as described in paragraph 2.1 after being subjected three
consecutive times to the cycle as described below, in order to
stabilize the position of mechanical parts of the front fog lamp on a
base representative of the correct installation on the vehicle:
operation of the front fog lamp for one hour (the voltage shall be
adjusted as specified in paragraph C4.1.1.1.2.).
The front fog lamp type shall be considered acceptable if the mean
value of the absolute values delta rI measured on the first sample
and delta rII measured on the second sample is not more than 2
mrad.
89/205
AIS-012
ANNEX : C 5
(See para C1.1.4)
REQUIREMENTS FOR LAMPS INCORPORATING
LENSES OF PLASTIC MATERIAL – TESTING OF LENS
OR MATERIAL SAMPLES AND OF COMPLETE LAMPS
C5.2. TESTS
C5.2.1.1 Tests
Refer paragraph Annex: A5.2.1.1
C5.2.1.2.1. Method
C5.2.1.2.2. Results
90/205
AIS-012
C5.2.3.2. Resistance to Hydrocarbons
C5.2.4.2. Results
C5.2.6.1.1. Tests
C5.2.6.1.2. Results
C5.3.2. If the test results fail to satisfy the requirements, the tests shall be
repeated on another sample of front fog lamps selected at random
91/205
AIS-012
ANNEX:C 5 – APPENDIX:1
(See para C5.1)
92/205
AIS-012
93/205
AIS-012
ANNEX:C5 – APPENDIX:2
ANNEX:C 5 – APPENDIX:3
ANNEX: C5 – APPENDIX:4
94/205
AIS-012
ANNEX: C 6
( See para 8.0)
MINIMUM REQUIREMENTS FOR CONFORMITY OF
PRODUCTION CONTROL PROCEDURES
C6.1. GENERAL
One of the sampled front fog lamp shall be tested according to the
procedure described in paragraph C4.2.1. of Annex:C4 after being
subjected three consecutive times to the cycle described in
paragraph C4.2.2.2. of Annex : C4
If this value exceeds 3.0 mrad but is not more than 4.0 mrad, a
second front fog lamp shall be subjected to the test after which the
mean of the absolute values recorded on both samples shall not
exceed 3.0 mrad.
95/205
AIS-012
The photometric performance of a front fog lamp emitting an
enlarged selective yellow light when equipped with colourless
filament lamp shall be the values contained in this standard
multiplied by 0.84.
For each type of front fog lamp the holder of the approval mark
shall carry out at least the following tests, at appropriate intervals.
The tests shall be carried out in accordance with the provision of
this standard.
A6.2.2.1. Tests shall generally be carried out in accordance with the methods
set out in this standard
C6.2.2.4. In all cases the reference methods shall be those of this standard,
particularly for the purpose of administrative verification and
sampling.
96/205
AIS-012
The assessment shall, in general, cover series production from
individual factories. However, a manufacturer may group together
records concerning the same type from several factories provided
these operate under the same quality system and quality
management.
97/205
AIS-012
ANNEX: C7
(See para 8.0)
MINIMUM REQUIREMENTS FOR SAMPLING BY
AN INSPECTOR
C7.1. GENERAL
C7.1.2.1. If the results of the tests described above do not meet the
requirements, tests shall be repeated using another standard
filament lamp.
In the first sampling four front fog lamps are selected at random.
The first sample of two is marked A, the second sample of two is
marked B.
98/205
AIS-012
C7.2.1.1.1. Sample A
C7.2.1.1.2. Sample B
C7.2.2.1.1. Sample A
C7.2.2.1.2. Sample B
99/205
AIS-012
C7.2.3.1. Sample A
C7.2.3.2. Sample B
C7.3.1.1.1. Sample C
C1: one front fog lamp 0%
one front fog lamp not more than 20%
C2: both front fog lamps more than 0%
but not more than 20%
go to sample D
C7.3.1.1.2. Sample D
100/205
AIS-012
C7.3.2. The Conformity is Contested
C7.3.2.1.1. Sample D
C7.3.3.1. Sample C
C7.3.3.2. Sample D
101/205
AIS-012
If this value exceeds 3.0 mrad but is not more than 4.0 mrad, the
second front fog lamp of sample A shall be subjected to the test
after which the mean of the absolute values recorded on both
samples shall not exceed 3.0 mrad.
102/205
AIS-012
ANNEX : D1
(See para 5.4)
REQUIREMENTS FOR FRONT AND REAR POSITION
(SIDE) LAMPS, STOP LAMPS AND
END-OUTLINE MARKER LAMPS
D1.1.1 Each device supplied shall conform to the specifications set forth in
Annex : D1,D2, D3 and Annex :L
D1.1.3 Lamps having been approved as front or rear position (side) lamps,
are deemed being also approved end-outline marker lamps.
D1.1.4 Front and rear position (side) lamps which are grouped or
combined or reciprocally incorporated may also be used as end-
outline marker lamps.
103/205
AIS-012
ANNEX : D2
(See para 5.4 and D1.1.1.)
PHOTOMETRIC TEST PROCEDURE AND
INTENSITY REQUIREMENTS FOR FRONT AND
REAR POSITION (SIDE) LAMPS,
STOP LAMPS AND END-OUTLINE MARKER LAMPS
D2.1.1. In the reference axis, the light emitted by each of the two devices
supplied must be of not less than the minimum intensity and of not
more than the maximum intensity specified below:
104/205
AIS-012
D2.1.2. Outside the reference axis and within the angular fields defined in
the diagrams Annex : D2 – Appendix 1, the intensity of the light
emitted by each of the two devices supplied shall:
D2.1.2.4. Moreover,
(1) The installation of the devices referred to above in power-driven vehicles and their trailers is
provided for in the standard concerning the installation of lighting and light-signalling devices
(AIS-008).
(2) The total value of maximum intensity for an assembly of two or more lamps is given by
multiplying by 1.4 the value prescribed for a single lamp. When an assembly of two or more
lamps having the same function is deemed to be, for the purpose of installation on a vehicle, a
''single lamp'' (following the definition of AIS-008 and its amendments in force at the time of
application for type approval), this assembly shall comply with the minimum intensity
required when one lamp has failed, and all the lamps together shall not exceed the admissible
maximum intensity (last column of the table).
In the case of a single lamp containing more than one light source:
(i) all light sources which are connected in series are considered to be one light source;
(ii) the lamp shall comply with the minimum intensity required when any one light source
has failed. However, for lamps designed for only two light sources, 50 per cent of the
minimum intensity in the axis of reference of the lamp shall be considered sufficient,
provided that a note in the technical information to be submitted by manufacturer
shall states that the lamp is only for use on a vehicle fitted with an operating tell-tale
which indicates when any one of these two light sources has failed.
(iii) when all light sources are illuminated the maximum intensity specified for a single lamp
may be exceeded provided that the single lamp is not marked ''D'' and the maximum
intensity specified for an assembly of two or more lamps (last column of the table) is not
exceeded.
(3) Devices which may be used as part of an assembly of two lamps
105/205
AIS-012
D2.1.2.4.2. If a rear position (side) lamp is reciprocally incorporated with a
stop-lamp, the ratio between the luminous intensities actually
measured of the two lamps when turned on simultaneously at the
intensity of the rear position (side) lamp when turned on alone
should be at least 5 : 1 in the field delimited by the straight
horizontal lines passing through + 50 V and the straight vertical
lines passing through + 100 H of the light distribution table. If the
stop-lamp has two levels of intensity, this requirement must be
satisfied when the night condition is switched on; If the rear
position (side) lamp or the stop lamp or both contain more than one
light source and are considered as a single lamp as defined in
note (2) of the table in paragraph D2.1.1 above, the values to be
considered are those obtained with all sources in operation;
D2.2.1.1 In the case of a system with more than one intensity, the reference
luminous flux prescribed for the specific category of filament lamp
shall be applied to the greatest intensity.
106/205
AIS-012
D2.2.1.3. In the case of light sources supplied by a special power supply, the
above test voltages shall be applied to the input terminals of that
power supply. The test laboratory may require from the
manufacturer the special power supply needed to supply the light
sources.
D2.2.3.2. Where the additional system is not part of the device, then the tests
shall be performed at the rated secondary design voltage applied to
the light source. The test laboratory may require from the
manufacturer the additional system needed to regulate the light
source.
(1) The functioning and installation conditions of these additional systems will
be defined by special provisions.
107/205
AIS-012
ANNEX : D 2 – APPENDIX 1
( See para D2.1.2)
FRONT AND REAR POSITION (SIDE) LAMPS, END-OUTLINE
MARKER LAMPS AND STOP LAMPS
Stop lamp S3
(1) The angles shown in these diagrams are correct for devices to be mounted on the right
side of the vehicle . The arrows point to the front of the vehicles
108/205
AIS-012
ANNEX : D2 – APPENDIX 2
( See para. D2.1.2.1)
PHOTOMETRIC MEASUREMENTS
D2.App.2.1.2.1 The distance of measurement shall be such that the law of the
inverse of the square of the distance is applicable;
D2.App.2.1.2.2. The measuring equipment shall be such that the angular aperture
of the receiver viewed from the reference centre of the lamp is
comprised between 10 angular minutes and one degree;
D2.App.2.1.3. In the case where the device may be installed on the vehicle in
more than one or in a field of different positions the photometric
measurements shall be repeated for each position or for the
extreme positions of the field of the reference axis specified by
the manufacturer.
109/205
AIS-012
Table : D1
( See para. D2.1.2.1)
Table : D2
( See para. D2.1.2.1)
110/205
AIS-012
TABLE : D3
( See para D2.1.2.1)
INTENSITY VALUES IN CANDELAS
FOR POSITION (SIDE) LAMP, END-OUTLINE MARKER LAMP
15 U V 0.05 60 0.05 12
10 U 5L 0.8 60 0.8 12
10 U 5R 0.8 60 0.8 12
5U 20 L 0.4 60 0.4 12
5U 10 L 0.8 60 0.8 12
5U V 2.8 60 2.8 12
5U 10 R 0.8 60 0.8 12
5U 20 R 0.4 60 0.4 12
H 80 L 0.05 60 0.05 12
H 45 L 0.05 60 0.05 12
H 10 L 1.4 60 1.4 12
H 5L 3.6 60 3.6 12
H V 4.0 60 1 4.0 12
H 5R 3.6 60 3.6 12
H 10 R 1.4 60 1.4 12
H 45 R 0.05 60 0.05 12
H 80 R 0.05 60 0.05 12
5D 20 L 0.4 60 0.4 12
5D 10 L 0.8 60 0.8 12
5D V 2.8 60 2.8 12
5D 10 R 0.8 60 0.8 12
5D 20 R 0.4 60 0.4 12
10 D 5 L 0.8 60 0.8 12
10 D 5 R 0.8 60 0.8 12
15 D V 0.05 60 0.05 12
Note to table :
(1) For front position lamp when incorporated in head lamp
max. 100 cd.
111/205
AIS-012
TABLE : D4
( See para. D2.1.2.1)
INTENSITY VALUES IN CANDELAS FOR STOP LAMP
10 U 10 L - 185 - 520 - 80 8 80
10 U 5L 12.0 185 26 520 6 80 - 80
10 U V - 185 - 520 - 80 16 80
10 U 5R 12.0 185 26 520 6 80 - 80
10 U 10 R - 185 - 520 - 80 8 80
H 80 L - 185 - 520 - 80 - -
H 45 L 0.3 185 0.3 520 0.07 80 - -
H 10 L 21.0 185 45.5 520 10.5 80 16 80
H 5L 54.0 185 117 520 27 80 25 80
H V 60.0 185 130 520 30 80 25 80
H 5R 54.0 185 117 520 27 80 25 80
H 10 R 21.0 185 45.5 520 10.5 80 16 80
H 45 R 0.3 185 0.3 520 0.07 80 - -
H 80 R - 185 - 520 - 80 - -
112/205
AIS-012
D2.App.2.3.3. For any signaling lamp except those equipped with filament
lamp(s), the luminous intensities, measured after one minute and
after 30 minutes of operation, shall comply with the minimum and
maximum requirements. The luminous intensity distribution after
one minute of operation can be calculated from the luminous
intensity distribution after 30 minutes of operation by applying at
each test point the ratio of luminous intensities measured at HV
after one minute and after 30 minutes of operation.
113/205
AIS-012
ANNEX : D3
(See para 5.4 and D1.1.1)
D3.1 The colour of the light emitted inside the field of the light distribution grid
defined in paragraph D2.App2.2 of Annex : D2 – Appendix 2 shall be
within the limits of the coordinates prescribed in para D3.2 of this
Annex : D3 given below. Outside this field, no sharp variation of colour
shall be observed.
114/205
AIS-012
ANNEX: D4
(See Para 8.0)
MINIMUM REQUIREMENTS FOR
CONFORMITY OF PRODUCTION
CONTROL PROCEDURES
D4.1. GENERAL
D4.1.2.2. If, in the case of a lamp equipped with a replaceable light source
and if results of the test described above do not meet the
requirements, tests on lamps shall be repeated using another
standard filament lamp.
115/205
AIS-012
D4.2.2. Methods used in Tests
116/205
AIS-012
ANNEX: D5
( See para 8.0 and D4.2.5 of Annex : D4)
MINIMUM REQUIREMENTS FOR SAMPLING BY
AN INSPECTOR
D5.1. GENERAL
D5.1.2.2. If, in the case of a lamp equipped with a replaceable light source
and if results of the test described above do not meet the
requirements, test on lamps shall be repeated using another
standard filament lamp.
D5.1.3. The chromaticity coordinates shall be complied with then the lamp
is equipped with a standard filament lamp, or for lamps equipped
with non-replaceable light sources (filament lamps or other), when
the colorimetric characteristics are verified with the light source
present in the lamp.
117/205
AIS-012
D5.2.1.1.2. Sample B
D5.2.2.1.2. Sample B
D5.2.3.1. Sample A
D5.2.3.2. Sample B
118/205
AIS-012
D5.3.1. The Conformity is Not Contested
D5.3.1.1.1. Sample C
Refer paragraph A7.3.1.1.1. of Annex : A7 with replacing word
“lamp” for “headlamp” wherever it appears.
D5.3.1.1.2. Sample D
D5.3.2.1.1. Sample D
D5.3.3.1. Sample C
Refer paragraph A7.3.3.1. of Annex : A7 with replacing word
“lamp” for “headlamp” wherever it appears.
D5.3.3.2. Sample D
Refer paragraph A7.3.3.2. of Annex : A7 with replacing word
“lamp” for “headlamp” wherever it appears.
119/205
AIS-012
ANNEX: E1
(See para 5.5)
REQUIREMENTS FOR DIRECTION INDICATORS
E1.1.1. Each device supplied shall conform to the specifications set forth in
Annexes : E1,E2,E3 and Annex :L.
120/205
AIS-012
ANNEX: E2
( See para E1.1.1)
PHOTOMETRIC TEST PROCEDURE AND INTENSITY
REQUIREMENTS FOR DIRECTION INDICATORS
E2.1.2 Outside the reference axis, within the angular fields specified in the
arrangement diagrams in Appendix : 1 to this Annex : E2, the
intensity of the light emitted by each of the two devices supplied
must:
E2.1.2.2. In no direction within the area from which the indicator lamp is
visible, exceed the maximum specified in paragraph E2.1.1. above;
E2.1.2.3. Moreover,
E2.1.2.3.2. For devices of categories 1 and 2b by night and, to the front, for
devices of categories 3 and 4, the intensity of the light emitted
outside the zone defined by the measuring points + 100 H and +
100V (100-field) must not exceed the following values:
122/205
AIS-012
E2.1.2.3.3. For devices of category 1a and 1b, the intensity of the light emitted
outside the zone defined by the measuring points + 150 H and + 150
V (150 field) shall not exceed the following values:
Between the boundaries of the 150 - field (+ 150 H and +150 V) and
the 50 - field (+ 50 H and + 5 0 V), the maximum values are
increased linearly up to the values as defined in paragraph E2.1.1.
E2.1.3. In general the intensities shall be measured with the light source(s)
continuously alight.
E2.1.4. In the case of devices of category 2b the time that elapses between
electrical supply being switched on and the light output measured
on the reference axis to reach 90 % of the value measured in
accordance with paragraph E2.1.3. above shall be measured for
both the day and the night conditions of use. The time measured for
the night condition of use shall not exceed that measured for the
day condition of use.
123/205
AIS-012
(1) The functioning and installation conditions of this additional device will be
defined by special provisions measuring the day-time intensity.
124/205
AIS-012
ANNEX : E2 - APPENDIX: 1
( See para E2..1.1)
In all cases, the minimum vertical angles of light distribution in space of direction
indicator lamps are 15 0 above and 15 0 below the horizontal except:
(i) direction indicator lamps with a mounting height of equal to or less
than 750 mm above the ground, for which they are 15 0 above and 5 0
below the horizontal;
(ii) direction indicator lamps of Category 6, for which they are 30 0 above
and 5 0 below the horizontal.
Minimum Horizontal Angles Of Light Distribution In Space:
Categories 1, 1a and 1b: direction indicators for the front of the vehicle
Category 1 : for use at a distance not less than 40 mm from the headlamp
Category 1a: for use at a distance greater than 20 mm but less than 40 mm from
the headlamp
Category 1b: for use at a distance less than 20 mm from the headlamp
Categories 2a and 2b: direction indicators for the rear of the vehicle
Category 2a: Direction indicators with one level of intensity
Category 2b: Direction indicators with two levels of intensity
(1) The angles shown in these arrangements are correct for devices to be mounted on the right
side of the vehicle. The arrows in these diagrams point towards the front of the vehicle.
125/205
AIS-012
Categories 3 and 4: front-side direction indicators
Category 3: Front-side direction indicators for use on a vehicle equipped with this
category of direction indicator only
126/205
AIS-012
127/205
AIS-012
ANNEX: E2 – APPENDIX: 2
( See para E2.1.2.1)
PHOTOMETRIC MEASUREMENTS
E2.App.2.1.2.1. The distance of measurement shall be such that the law of the
inverse of the square of the distance is applicable;
E2.App.2.1.3. In the case where the device may be installed on the vehicle in
more than one or in a field of different positions the photometric
measurements shall be repeated for each position or for the extreme
positions of the field of the reference axis specified by the
manufacturer.
128/205
AIS-012
Table : E1
( See para E2.1.2.1)
Table : E2
( See para E2.1.2.1)
129/205
AIS-012
TABLE : E3
( See para E 2.1.2.1)
INTENSITY VALUES IN CANDELAS FOR DIRECTION INDICATOR
15 U V 0.3 400 0.3 800 0.7 860 0.3 350 0.3 700 0.07 100
H 80 L 0.3 400 0.3 250 0.7 400 0.3 350 0.3 700 0.07 100
H 45 L 0.3 400 03 250 0.7 400 0.3 350 0.3 700 0.07 100
H 10 L 61.25 700 87.5 800 140 860 17.5 350 61.25 700 14 120
H 5L 157.5 700 225 800 360 860 45 350 157.5 700 36 120
H V 175 700 250 800 400 860 50 350 175 700 40 120
H 5R 157.5 700 225 800 360 860 45 350 157.5 700 36 120
H 10 R 61.25 700 87.5 800 140 860 17.5 350 61.25 700 14 120
H 45 R 0.3 400 0.3 250 0.7 400 0.3 350 0.3 700 0.07 100
H 80 R 0.3 400 0.3 250 0.7 400 0.3 350 0.3 700 0.07 100
15 U V 0.3 400 0.3 800 0.7 860 0.3 350 0.3 700 0.07 100
130/205
AIS-012
Table: E4
( See para E2.1.2.1)
INTENSITY VALUES IN CANDELAS FOR
DIRECTOR INDICATOR OF CATEGORY 3,4
(1) The point (H, 60L), (H,60R) is same as (H, 55L), (H, 55R) in case of Category 4
direction indicator.
(2) For maximum values refer paragraph E2.1, E2.1.1. and in case of single lamp.
131/205
AIS-012
Table : E5
( See para E2.1.2.1)
132/205
AIS-012
E2.App.2.3.3. For any direction indicator lamp except those equipped with
filament lamp(s), the luminous intensities measured after one
minute and after 30 minutes of operation in flashing mode
(f = 1.5 Hz, duty factor 50 %), shall comply with the minimum and
maximum requirements. The luminous intensity distribution after
one minute of operation can be calculated by applying at each test
point the ratio of luminous intensity measured in HV after one
minute and after 30 minutes of operation as above described.
133/205
AIS-012
ANNEX: E3
( See para 5.5 and E1.1.1)
COLOUR OF LIGHT EMITTED
The colour of the light emitted inside the field of the light
distribution grid defined in paragraph E2.App.2.2 of Appendix E2
of of Annex : E2 of this standard shall be within the limits of the
coordinates prescribed below in para E3.2.
TRICHROMATIC CO-ORDINATES
134/205
AIS-012
ANNEX: E 4
(See para 8.0)
MINIMUM REQUIREMENTS FOR CONFORMITY OF
PRODUCTION CONTROL PROCEDURES
E4.1. GENERAL
135/205
AIS-012
ANNEX: E 5
( See para 8.0 and E 4.2.5 of Annex: E4)
MINIMUM REQUIREMENTS FOR
SAMPLING BY AN INSPECTOR
E5.1. GENERAL
E5.2.1.1.2 Sample B
B1: Both direction indicator 0%
136/205
AIS-012
E5.2.2.1.2 Sample B
E5.2.3.1 Sample A
E5.2.3.2. Sample B
E5.3.1.1.1. Sample C
Refer paragraph A7.3.1.1.1. of Annex : A7 with replacing word
“direction indicator” for “headlamp” wherever it appears.
E5.3.1.1.2. Sample D
137/205
AIS-012
E5.3.2.1.1. Sample D
E5.3.3.1. Sample C
E5.3.3.2. Sample D
138/205
AIS-012
ANNEX: F1
( See para 5.6)
REQUIREMENTS FOR REVERSING LAMPS
F1.1.1. Each sample shall conform to the specifications set forth in the
Annexs: F1,F2, F3 and Annex : L.
139/205
AIS-012
ANNEX: F2
( See para. F1.1.1)
PHOTOMETRIC TEST PROCEDURE AND INTENSITY
REQUIREMENTS FOR REVERSING LAMPS
F2.1.1. The intensity of the light emitted by each of the two samples shall
be not less than the minima and not greater than the maxima
specified below and shall be measured in relation to the axis of
reference in the directions shown below (expressed in degrees of
angle with the axis of reference).
F2.1.2. The intensity along the axis of reference shall be not less than
80 candelas.
F2.1.3. The intensity of the light emitted in all directions in which the light
can be observed shall not exceed:
F2.1.5. In the case of a single lamp containing more than one light source,
the lamp shall comply with the minimum intensity required when
any one light source has failed and when all light sources are
illuminated the maximum intensities shall not be exceeded.
140/205
AIS-012
F2.2 TEST PROCEDURE
141/205
AIS-012
ANNEX : F2 – APPENDIX :1
( See para F2.1.4)
PHOTOMETRIC MEASUREMENTS
F2.App.1.1.2.1. the distance of measurement shall be such that the law of the
inverse of the square of the distance is applicable;
F2.App.1.1.2.2 the measuring equipment shall be such that the angle subtended
by the receiver from the reference center of the light is between
10' and 1 0
F2.App.1.1.3 In the case where the device may be installed on the vehicle in
more than one or in a field of different positions the photometric
measurements shall be repeated for each position or for the extreme
positions in the field of reference axis specified by the
manufacturer.
142/205
AIS-012
143/205
AIS-012
ANNEX: F3
( See para F1.1.1)
(Trichromatic coordinates)
Limit towards blue : x > 0.310
Limit towards yellow : x < 0.500
Limit towards green : y < 0.150 + 0.640x
Limit towards green : y < 0.440
Limit towards purple : y > 0.050 + 0.750x
Limit towards red : y > 0.382
144/205
AIS-012
ANNEX: F 4
( See para 8.0)
MINIMUM REQUIREMENTS FOR CONFORMITY OF
PRODUCTION CONTROL PROCEDURES
F4.1. GENERAL
145/205
AIS-012
Annex: F 5
( See para 8.0 and para F4.2.5 of Annex :F4)
MINIMUM REQUIREMENTS FOR
SAMPLING BY AN INSPECTOR
F5.1. GENERAL
F5.2.1.1.2 Sample B
146/205
AIS-012
F5.2.2.1.2 Sample B
F5.2.3.1 Sample A
F5.2.3.2. Sample B
F5.3.1.1.1. Sample C
Refer paragraph A7.3.1.1.1. of Annex:A7 with replacing word
“reversing lamp” for “headlamp” wherever it appears.
F5.3.1.1.2. Sample D
147/205
AIS-012
F5.3.2.1.1. Sample D
F5.3.3.1. Sample C
Refer paragraph A7.3.3.1. of Annex : A7 with replacing word
“reversing lamp” for “headlamp” wherever it appears.
F5.3.3.2. Sample D
Refer paragraph A7.3.3.2. of Annex : A7with replacing word
“reversing lamp” for “headlamp” wherever it appears.
148/205
AIS-012
ANNEX: G1
( See para 5.7)
REQUIREMENTS FOR PARKING LAMPS
149/205
AIS-012
ANNEX: G2
( See para G1.1.1)
G2.1.1. In the reference axis, the light emitted by each of the two samples
shall be of not less than the minimum intensity and of not more
than the maximum intensity specified below:
G2.1.1.3 In the case of a single lamp containing more than one light source,
the lamp shall comply with the minimum intensity required when
any one light source has failed and when all light sources are
illuminated the maximum intensities shall not be exceeded.
G2.1.2. Outside the reference axis and within the angular fields defined in
the diagrams in Annex:G2 – Appendix:1 to this Annex, the
intensity of the light emitted by each of the two samples shall:
G2.1.2.2. in any direction within the space from which the light in question is
visible, not exceed the maximum specified in paragraph G2.1.1.
G2.1.2.4 Moreover,
G2.1.2.4.1. throughout the fields defined in Annex:G2–Appendix:1 the
intensity of the light emitted shall be not less than 0.05 cd,
150/205
AIS-012
151/205
AIS-012
ANNEX: G2 – APPENDIX: 1
( See Para G2.1.2 of Annex G2)
MINIMUM ANGLES REQUIRED FOR THE
LIGHT DISTRIBUTION IN SPACE (1)
(1) The angles shown in these diagrams are correct for devices to be mounted on the
right side of the vehicle. The arrows point to the front of the vehicles.
152/205
AIS-012
ANNEX: G2 – APPENDIX: 2
( See para G2.1.2.1 of Annex:G2)
PHOTOMETRIC MEASUREMENTS
G2.App.2.1.2.1. the distance of measurements shall be such that the law of the
inverse of the square of the distance is applicable;
Table : G1
( See para G2.1.2.1)
153/205
AIS-012
TABLE : G 2
( See para G2.1.2.1)
LUMINOUS INTENSITY VALUES IN CANDELAS
FOR PARKING LAMP
15 U V 0.05 60 0.05 30
10 U 5L 0.4 60 0.4 30
10 U 5R 0.4 60 0.4 30
5U 20 L 0.2 60 0.2 30
5U 10 L 0.4 60 0.4 30
5U V 1.4 60 1.4 30
5U 10 R 0.4 60 0.4 30
5U 20 R 0.2 60 0.2 30
H 80 L - 60 - 30
H 45 L 0.05 60 0.05 30
H 10 L 0.7 60 0.7 30
H 5L 1.8 60 1.8 30
H V 2.0 60 2.0 30
H 5R 1.8 60 1.8 30
H 10 R 0.7 60 0.7 30
H 45 R 0.05 60 0.05 30
H 80 R - 60 - 30
5D 20 L 0.2 60 0.2 30
5D 10 L 0.4 60 0.4 30
5D V 1.4 60 1.4 30
5D 10 R 0.4 60 0.4 30
5D 20 R 0.2 60 0.2 30
10 D 5 L 0.4 60 0.4 30
10 D 5 R 0.4 60 0.4 30
15 D V 0.05 60 0.05 30
154/205
AIS-012
G2.App.2.2.1. The direction H = 0 degrees and V = 0 degrees corresponds to the
reference axis. (On the vehicle it is horizontal, parallel to the
median longitudinal plane of the vehicle and oriented in the
required direction of visibility). It passes through the centre of
reference. The values shown in the table give, for the various
directions of measurements, the minimum intensities as a
percentage of the minimum required in the axis for each lamp (in
the direction H = 0 degrees and V = 0 degrees).
G2.App.2.3.1. For non-replaceable light sources (filament lamps and other): with
the light sources present in the lamp, in accordance with
paragraph G2.2.1. of Annex:G2.
G2.App.2.3.3. For any signaling lamp except those equipped with filament
lamp(s), the luminous intensities, measured after one minute and
after 30 minutes of operation, shall comply with the minimum and
maximum requirements. The luminous intensity distribution after
one minute of operation can be calculated from the luminous
intensity distribution after 30 minutes of operation by applying at
each test point the ratio of luminous intensities measured at HV
after one minute and after 30 minutes of operation.
155/205
AIS-012
ANNEX: G3
( See para G1.1.1)
The colour of the light emitted inside the field of the light
distribution grid defined in G2.App.2.2.2. of Annex : G2 –
Appendix G2, measured by using a source of light with a colour
temperature of 2,856 K, corresponding to illuminant A of the
International Commission on Illumination (CIE), shall be within
the limits of the co-ordinates prescribed for the colour in question
given below. Outside this field no sharp variation of colour shall be
observed.
156/205
AIS-012
ANNEX: G 4
( See para 8.0)
MINIMUM REQUIREMENTS FOR CONFORMITY OF
PRODUCTION CONTROL PROCEDURES
G4.1. GENERAL
G5.1. GENERAL
G5.2.1.1.2 Sample B
158/205
AIS-012
G5.2.2.1.1 Refer paragraph A7.2.2.1.1. of Annex : A7 with replacing word
“parking lamp” for “headlamp” wherever it appears.
G5.2.2.1.2 Sample B
G5.2.3.1 Sample A
G5.2.3.2. Sample B
G5.3.1.1.1. Sample C
Refer paragraph A7.3.1.1.1. of Annex : A7 with replacing word
“parking lamp” for “headlamp” wherever it appears.
G5.3.1.1.2. Sample D
159/205
AIS-012
G5.3.2.1.1. Sample D
G5.3.3.1. Sample C
G5.3.3.2. Sample D
160/205
AIS-012
ANNEX: H1
( See para 5.8)
REQUIREMENTS FOR SIDE-MARKER LAMPS
H1.1.1. Each side-marker lamp submitted for approval shall conform to the
specifications set out in Annexes : H1,H2,H3 and Annex : L
ANNEX: H2
(See para H1.1.1 )
PHOTOMETRIC TEST PROCEDURE AND INTENSITY
REQUIREMENTS FOR SIDE-MARKER LAMP
H2.1.1. The intensity of the light emitted by each of the two samples
submitted shall be:
H2.1.1.4. In the case of a lamp containing more than one light source:
The lamp shall comply with the minimum intensity required when
any one light source has failed;
H2.1.2. Outside the reference axis and within the angular fields defined in
the diagrams in Annex : H2 – Appendix :1 , the intensity of the
light emitted by each of the two side-marker lamps supplied must:
161/205
AIS-012
H2.1.2.2. In no direction within the space from which the side-marker lamp
is visible, exceed the maximum specified in paragraph H2.1.1.
above;
162/205
AIS-012
ANNEX: H2 – APPENDIX: 1
(See para H2. 1.2)
The angle of 10° below the horizontal may be reduced to 5° in case of lamps
with a mounting height of equal to or less than 750 mm above the ground.
163/205
AIS-012
ANNEX: H2 – APPENDIX: 2
(See para H2.1.2.1)
PHOTOMETRIC MEASUREMENTS
H2.App.2.1.2.1. The distance of measurement shall be such that the law of the
inverse of the square of the distance is applicable;
H2.App.2.1.3. In the case where the device may be installed on the vehicle in
more than one or in a field of different positions the photometric
measurements shall be repeated for each position or for the extreme
positions of the field of the reference axis specified by the
manufacturer.
164/205
AIS-012
H2.APP.2.2. TABLES OF LIGHT DISTRIBUTION
Table : H2
(See para H2.1.2.1)
165/205
AIS-012
H2.App.2.2.4. Within the field of light distribution shown above as a grid the light
pattern should be substantially uniform, i.e. the light intensity in
every direction within a part of the field formed by the grid lines
shall meet at least the lowest minimum value applicable to the
respective grid lines.
H2.App.2.3.3. For any signalling lamp except those equipped with filament
lamp(s), the luminous intensities, measured after one minute and
after 30 minutes of operation, shall comply with the minimum and
maximum requirements. The luminous intensity distribution after
one minute of operation can be calculated from the luminous
intensity distribution after 30 minutes of operation by applying at
each test point the ratio of luminous intensities measured at HV
after one minute and after 30 minutes of operation.
166/205
AIS-012
ANNEX: H3
(See para H1.1.1)
COLOUR OF LIGHT EMITTED
H3.1.1. The side-marker lamp must emit amber light; however it can emit
red, if the rearmost side-marker lamp is grouped or combined or
reciprocally incorporated with the rear position lamp, the rear end-
outline marker lamp, the rear fog lamp, the stop lamp, or is
grouped with or has part of the light emitting surface in common
with the rear retro-reflector.
H3.1.2. The colour of the light emitted inside the field of the light
distribution grid defined in H2.App.2.2.2. of Annex : H2 –
Appendix :H2 must be within the limits of the trichromatic
coordinates prescribed for the colour in question given below.
Outside this field no sharp variation of colour shall be observed.
167/205
AIS-012
ANNEX: H 4
( See para 8.0)
MINIMUM REQUIREMENTS FOR CONFORMITY OF
PRODUCTION CONTROL PROCEDURES
H4.1. GENERAL
168/205
AIS-012
ANNEX: H 5
( See para 8.0 and H4.2.5 of Annex: H4)
MINIMUM REQUIREMENTS FOR
SAMPLING BY AN INSPECTOR
H5.1. GENERAL
H5.2.1.1.2 Sample B
B1: Both“side-marker 0%
lamps”
169/205
AIS-012
H5.2.2.1.2 Sample B
170/205
AIS-012
H5.2.3. Approval Withdrawn
H5.2.3.1 Sample A
H5.2.3.2. Sample B
H5.3.1.1.1. Sample C
Refer paragraph A7.3.1.1.1. of Annex : A7 with replacing word
“side-marker lamp” for “headlamp” wherever it appears.
H5.3.1.1.2. Sample D
D1: in the case of C2
Both “side- 0%
marker lamps”
H5.3.2.1.1. Sample D
Refer paragraph A7.3.2.1.1. of Annex : A7 with replacing word
“side-marker lamp” for “headlamp” wherever it appears.
171/205
AIS-012
H5.3.3.1. Sample C
Refer paragraph A7.3.3.1. of Annex : A7 with replacing word
“side-marker lamp” for “headlamp” wherever it appears.
H5.3.3.2. Sample D
Refer paragraph A7.3.3.2. of Annex : A7with replacing word
“side-marker lamp” for “headlamp” wherever it appears.
172/205
AIS-012
ANNEX: J1
( See para 5.9)
REQUIREMENTS FOR REAR FOG LAMPS
J1.1.1 Each sample shall conform to the specifications set forth in the
Annexes:J1, J2, J3 and Annex : L
J1.1.2. Rear fog lamps shall be so designed and constructed that in normal
use, despite the vibration to which they may then be subjected, they
continue to function satisfactorily and retain the characteristics
prescribed by this standard.
173/205
AIS-012
ANNEX: J2
( See para J1.1.1)
PHOTOMETRIC TEST PROCEDURE AND INTENSITY
REQUIREMENTS FOR REAR FOG LAMPS
J2.1.1. The intensity of the light emitted by each of the two samples shall
be not less than the minima and not greater than the maxima
specified below and shall be measured in relation to the axis of
references in the directions shown below (expressed in degrees of
angle with the axis of reference).
J2.1.2. The intensity along the H and V axes, between 100 to the left and
100 to the right and between 50 up and 50 down, shall not be less
than 150 cd.
J2.1.3 The intensity of the light emitted in all directions in which the
light(s) can be observed shall not exceed 300 cd per light.
J2.1.4 In the case of a single lamp containing more than one light source,
the lamp shall comply with the minimum intensity required when
any one light source has failed and when all light sources are
illuminated the maximum intensities shall not be exceeded.
J2.1.5 The apparent surface in the direction of the reference axis shall not
exceed 140 cm2.
174/205
AIS-012
J2.3. HEAT RESISTANCE TEST
J2.3.2. Where only the maximum power is specified, the test shall be
carried out by regulating the voltage to obtain a power equal to
90% of the specified power. The specified average or maximum
power referred to above shall in all cases be chosen from the
voltage range of 6, 12 or 24 V at which it reaches the highest value.
J2.3.3. After the lamp has been stabilized at the ambient temperature, no
distortion, deformation, cracking or color modification shall be
perceptible.
175/205
AIS-012
ANNEX: J2 – APPENDIX: 1
(See para J2.1.6)
PHOTOMETRIC MEASUREMENTS
J2.App.1.2.1. The distance of measurement shall be such that the law of the
inverse of the square of the distance is applicable;
J2.App.1.2.2. The measuring equipment shall be such that the angle subtended by
the receiver from the reference centre of the light is between 10'
and 1 degree;
J2.App.1.3. In the case where the device may be installed on the vehicle in
more than one or in a field of different positions the photometric
measurements shall be repeated for each position or for the extreme
positions of the field of the reference axis specified by the
manufacturer.
176/205
AIS-012
177/205
AIS-012
ANNEX: J3
(See para J1.1.1)
COLOUR OF LIGHT EMITTED
The color of the light emitted inside the field of the light
distribution grid defined at paragraph J2.App.1.4 Annex : J2 –
Appendix :1, which shall be measured by using a source of light at
a color temperature of 2854 K, (1) must lie within the limits of the
following trichromatic coordinates:
O
utside this field no sharp variation of colour shall be observed.
178/205
AIS-012
ANNEX: J 4
( See para 8.0)
MINIMUM REQUIREMENTS FOR CONFORMITY OF
PRODUCTION CONTROL PROCEDURES
J4.1. GENERAL
179/205
AIS-012
Annex: J 5
( See para 8.0 and J 4.2.5 of Annex: J4)
MINIMUM REQUIREMENTS FOR
SAMPLING BY AN INSPECTOR
J5.1. GENERAL
J5.1.2.2 If, in the case of a “rear fog lamp” equipped with a replaceable
light source and if results of the test described above do not meet
the requirements, test on “rear fog lamp” shall be repeated using
another standard filament lamp.
J5.2.1.1.2 Sample B
180/205
AIS-012
J5.2.2.1.2 Sample B
J5.2.3.1 Sample A
J5.2.3.2. Sample B
J5.3.1.1.1. Sample C
Refer paragraph A7.3.1.1.1. of Annex : A7 with replacing word
“rear fog lamp” for “headlamp” wherever it appears.
181/205
AIS-012
J5.3.1.1.2. Sample D
J5.3.2.1.1. Sample D
J5.3.3.1. Sample C
Refer paragraph A7.3.3.1. of Annex : A7 with replacing word
“rear fog lamp” for “headlamp” wherever it appears.
J5.3.3.2. Sample D
Refer paragraph A7.3.3.2. of Annex : A7with replacing word “rear
fog lamp” for “headlamp” wherever it appears.
182/205
AIS-012
ANNEX: K1
(See Para 5.10)
REQUIREMENTS FOR REAR REGISTRATION PLATE
( MARK) ILLUMINATING LAMP
K1.1. Each sample shall conform to the lighting specifications set forth in
a paragraph K4 below. (1)
K1.3. For any rear registration plate( mark ) illuminating device, except
those equipped with filament lamp(s), the luminance values
measured after one minute and after 30 minutes of operation shall
comply with the minimum requirements.
183/205
AIS-012
K3. MEASURING PROCEDURE
184/205
AIS-012
K6.1.1 For non - replaceable light sources (filament lamps & other) :
With the light sources present in the lamp, in accordance with
paragraph K1.2.1. of Annex : K1
185/205
AIS-012
ANNEX : K2
(See para K1.1)
MINIMUM FIELD OF VISIBILITY OF THE SURFACE
TO BE ILLUMINATED
K2.2 The field of visibility of the registration plate when mounted on the
vehicle remains subject to the relevant national regulations.
K2.3 The angles shown take account of the partial occultation caused by
the illuminating device. They must be adhered to in the directions
in which there is most occultation. The illuminating devices must
be such as to reduce the areas partly occulted to the minimum
strictly necessary.
186/205
AIS-012
ANNEX : K3
(See para K3)
MEASUREMENT POINTS FOR TEST PURPOSES
Note : In the case of devices for illuminating two or all of the plates the measurement points
used are obtained by combining the two drawings above in accordance with the
outline indicated by the make or manufacturer; however if two measurement points are
less than 30 mm apart, only one shall be used.
187/205
AIS-012
ANNEX: K4
( See para 8.0 )
MINIMUM REQUIREMENTS FOR CONFORMITY OF
PRODUCTION CONTROL PROCEDURES
K4.1. GENERAL
188/205
AIS-012
K4.2.3. Nature of Sampling
189/205
AIS-012
ANNEX: K 5
( See para 8.0 and K4.2.5 of Annex: K4)
MINIMUM REQUIREMENTS FOR
SAMPLING BY AN INSPECTOR
K5.1. GENERAL
190/205
AIS-012
K5.2.1.1.2 Sample B
K5.2.2.1.2 Sample B
K5.2.3.1 Sample A
K5.2.3.2. Sample B
191/205
AIS-012
K5.3.1 . The Conformity is Not Contested
K12.3.1.1.1. Sample C
K5.3.1.1.2. Sample D
K5.3.2.1.1. Sample D
K5.3.3.1. Sample C
Refer paragraph A7.3.3.1. of Annex : A7 with replacing word
“rear registration plate ( mark) illuminating lamp”for “headlamp”
wherever it appears.
K5.3.3.2. Sample D
Refer paragraph A7.3.3.2. of Annex : A7with replacing word “rear
registration plate ( mark) illuminating lamp”for “headlamp”
wherever it appears.
192/205
AIS-012
ANNEX : L
( See para 6.2)
ENVIRONMENTAL TESTS
L1 The following are the procedures and requirements for environmental tests.
The applicability of the tests are as given in the Table - 1.
L2.0 Vibration Test
L2.1 The test specimen mounted on a suitable support shall be rigidly fixed on a
suitable vibrating machine constructed to produce simple harmonic function (a
total amplitude of 1.5 mm) and shall be subjected to vibration through a
frequency range of 10-55-10 Hz in a period of 1 minute with continuously
varying frequencies. The vibration shall be applied for not less than 1 hour in
the directions of each of the 3 major axes of the light.
L2.3 At the end of the vibration test, the test specimen shall not show evidence of
material defects, lens or reflector rotation, displacement or rupture of parts
except filaments lamp failures.
L3.0 Corrosion Resistance Test
L3.1 Apparatus : Salt Spray Chamber
L3.1.1 The chamber for this test shall be so constructed that the salt spray is produced
in the lower part of the chamber, in the upper part of which the parts to be
exposed are suspended.
L3.1.2 The construction of the ceiling walls and other parts of the chamber shall be
such that no condensate can drip on the test specimen. The spray shall be
produced by an atomizer employing compressed air free from all impurities.
L3.1.3 In general, a salt spray chamber shown in Figure L1, with a spraying
arrangement as shown in Figure L2 and complying with the following
requirements would be suitable.
L3.1.4 The cabinet shall approximately be of the dimensions shown, and the cabinet
and its internal fittings shall be made of monel metal or other suitable material.
A shelf capable of being fitted in the upper or lower part of the cabinet shall be
provided.
L3.1.5 The air used for atomizing the salt solution shall be clean. It shall be possible to
adjust the pressure by a relief valve or by the pressure outlet of the blower.
L3.1.6 It shall be possible to control the amount of spray by adjusting the position of
the lower nozzle C by unscrewing the bottom lock-nut B. The diameter of
nozzle shall be 1.5 mm. A tap and second branch in the air-line shall be
available for agitating the salt solution as required.
L3.1.7 The spraying apparatus shall be capable of atomizing not less than 1450 ml
salt solution per hour. The quantity of solution sprayed per cubic meter
capacity of the chamber shall be approximately 175 ml per minute.
L3.1.8 A container filled with cotton wool shall be provided as shown in fig. L1. It acts
as breather and provides an outlet for the air which is constantly being pumped
into the chamber, the cotton wool acting as a filter and preventing salt mist
from being discharged into the atmosphere.
193/205
AIS-012
Figure L1. Salt Spray Chamber (See L3.1.3)
194/205
AIS-012
L3.2 Procedure
The nozzle for atomizing the salt solution shall be adjusted for maximum
amount of spray. The pressure of the solution shall be maintained between 29
and 33 kPa. The test piece shall be sprayed in the chamber with 5% solution
of sodium chloride in water at the standard temperature of 27 ± 2o C for 50
hours consisting of two periods, each period being of 24 hours of
spraying and one hour of draining. The pH of the salt solution shall be such
that the collected solution will be in the pH range of 6.5 to 7.2.
L3.3 The unit under test shall not show a corrosion which shows a change of more
than 10% variation in the unfavorable direction, in the photometry requirements
as specified in the relevant Annexes.
L4.0 Dust Test for Seals & Gaskets
L4.1 A sample unit with any drain hole closed shall be mounted in its normal
operating position 150 mm from the wall in a box measuring 900 mm in all
directions, containing 5 kg of fine powdered cement.
At intervals of 15 minutes this dust shall be agitated by compressed air or fan
blower by projecting blasts of air for a two second period in downward
direction into the dust in such a way that the dust shall be completely and
uniformly diffused throughout the entire cube. The dust is then allowed to
settle.
In the meantime, the lamp is operated at the rated voltage continuously with an
operating cycle of 30 minutes (15 min. ON and 15 min. OFF).
This test shall be continued for 5 hrs.
L4.2 After this test, the exterior surface of the unit shall be cleaned and the
photometric test repeated and if the maximum intensity is within 10% of the
maximum value found in the photometric test, it shall be considered adequately
dust tight.
L5.0 Moisture Test for Adequate Drainage
L5.1 A sample unit shall be mounted in its normal operating position with all drain
holes open and subjected to a precipitation of 2.5 mm of water per minute
delivered at an angle of 45 degrees from a nozzle with a solid cone spray. The
rate of water spray shall be measured by the rise of water in small straight sided
pan placed horizontally and completely within the area covered by the water
spray. During the moisture test, the unit shall revolve about its vertical axis at a
rate of 4 rev/min. This test shall be continued for 12 hours. The water be then
be turned off and the unit permitted to drain for 1 hour.
L5.2 After the test, unit under test shall not accumulate moisture in excess of 2 ml.
L6.0 Thermal Shock Resistance Test
L6.1 A sample unit shall be connected for not less than 15 minutes with the filament
at 7, 14 and 28 V for rated voltages of 6, 12 and 24 V respectively in its normal
operating position in an ambient temperature of approximately 27 oC.
It shall then be disconnected and immediately plunged into water at 5oC below
the ambient such that the lens comes in contact with water.
L6.2 After the test, no cracking or fracture of the lens shall occur.
195/205
AIS-012
L7.0 Warpage Test for Devices with Plastic Lenses
L7.1 The sample unit shall be mounted in its normal position and operated as
indicated in Table L1 at design working voltage in an oven controlled at
50° ±10°C for a duration of 1 hour
Table : L1
Direction Indicator
L7.2 There shall be no evidence of excessive warpage of lenses, which would affect
the proper functioning of the unit.
L8.0 Resistance to Oil -Test for Light-Signalling Devices with Plastic Lenses
L8.1 The outer surface of the lens of the sample unit shall be gently wiped with a
cotton cloth soaked in detergent lubricating oil. After 5 minutes the surface
shall be cleaned by washing in detergent solution. The surface shall be
inspected. The application of various oils shall be done on the same sample
one after another.
L8.2 The unit under test shall not show any deterioration of the unit.
L9.0 Resistance to Fuel - Test for Light-Signalling Devices with Plastic Lenses
L9.1 The outer surface of the lens of the sample unit shall be gently wiped with a
cotton cloth soaked in a mixture of petrol and benzol (90 : 10).
L9.2 After 5 minutes, the surface shall not show any visible change.
Note: Tests prescribed in L8.0 and L9.0 shall be conducted on the same sample, not
necessarily in the same sequence.
L10.0 High Voltage (flash) Test
L10.1 The test piece shall be isolated from the condensers, if any, and internally
ground, and shall be subjected to flash test, with an alternating current of 500 V
rms. at any convenient frequency between 40 and 60 Hz between the end of the
terminals and the ground. During this test the lamps shall be removed.
L10.2 The test specimen shall satisfactorily withstand this test without arcing or
puncture
196/205
AIS-012
ANNEX : M
( See para 5.12)
SPECIAL REQUIREMENTS FOR NON-REPLACEABLE LIGHT
SOURCES AND LIGHT SOURCE MODULES
1 Definitions:
1.1 Non-replaceable light source means a light source which can only be replaced
by replacement of the device to which this light source is fixed.
1.2 Light source module means an optical part of a device which is specific to that
device, is containing one or more non-replaceable light sources, and is only
removable from its device with the use of tool(s)
1.3 Light-emitting diode (LED) means a light source where the element for visible
radiation is one or more solid state junctions producing injection-luminescence /
fluorescence.
2.0 Marking
2.1 In the case of devices with non-replaceable light sources bear the marking of the
rated voltage and rated wattage
2.2 in the case of devices with light source module(s), the light source module(s)
shall bear
2.2.1 the trade name or mark of the applicant; this marking shall be clearly legible and
indelible;
2.2.2 the specific identification code of the module; this marking must be clearly
legible and indelible.
2.2.3 the marking of the rated voltage and rated wattage
the specific identification code of the module; this marking must be clearly
legible and indelible.
This specific identification code shall comprise the starting letters "MD" for
"MODULE". This specific identification code shall be shown in the drawings
submitted.
3.0 Requirements:
3.1 The design of the light source module(s) shall be such that even in darkness the
light source module(s) can be fitted in no position, but the correct one.
4.0 Life testing:
4.1 The procedure for testing of life for light source modules shall be same as those
prescribed AIS 034 as applicable, taking the following into account.
4.2 The number of samples to be subjected to life test (LTQ) shall be 5.
4.3 The life requirement shall be Lsp shall be 2000hours and LTQ shall be 1700
hours.
4.4 The life test shall be carried out on the light source module independently
without the lighting/light-signalling device.
4.5 Lumen maintenance shall be established by measuring the illumination of the
light/light-signalling device by installing the test piece of the light source
module.
In the case of light source modules using filament light sources with halogen,
the lumen maintenance shall be checked at 75 + 5% of LSP and for all other
cases at 50 + 5% of LSP.
4.6 Test voltage shall be same that specified by the manufacturer and used for
checking the illumination of the light/light-signalling device.
197/205
AIS-012
FIGURE: A1
( See para A2.1.2)
STANDARD EUROPEAN BEAM
198/205
FIGURE : A2
( See para A2.2.7)
8 7
199/205
AIS-012
FIGURE: A3
( See para A7.2.1.1 )
200/205
AIS-012
FIGURE : B1
( See para B2.1.2)
Dipped-Beam- Measuring Screen 1
Do not scale
Dimensions are in cm on a flat vertical screen at 25 m.The HH and VV lines
are the intersections with this screen of the horizontal and vertical planes
passing through the axis of reference of the dipped beam as declared by the
applicant
201/205
AIS-012
FIGURE : B2
( See para B2.1.2)
Dipped-Beam- Measuring Screen 2
Do not scale
Dimensions are in cm on a flat vertical screen at 25 m. The HH and VV lines
are the intersections with this screen of the horizontal and vertical planes
passing through the axis of reference of the dipped beam as declared by the
applicant
202/205
FIGURE: B3
( See para B2.2.6)
21 20
203/205
AIS-012
FIGURE: C1
( See para C2.1.2)
204/205
AIS-012
Annex : N
(See Introduction)
COMMITTEE COMPOSITION
Automotive Industry Standards Committee
Chairman
Shri B. Bhanot Director
The Automotive Research Association of India, Pune
Members Representing
Shri Alok Rawat Ministry of Road Transport & Highways, New Delhi
Member Secretary
Mrs. Rashmi Urdhwareshe
Sr. Assistant Director
The Automotive Research Association of India, Pune
205/205