Manual de utilizare Immergas Magis Combo-V2
Manual de utilizare Immergas Magis Combo-V2
MAGIS COMBO V2
Hybrid heat pumps
reversible air-water with
with split single-phase inverter
INDEX
MAIN CONTENTS
1 MAGIS COMBO 4 - 6 - 9 V2 (SINGLE-PHASE), INSTANT AND PLUS FEATURES.................................................5
2 AUDAX PRO V2 DIMENSIONS AND CONNECTIONS (CONDENSING UNIT)..................................................6
3 MAGIS COMBO V2 MAIN DIMENSIONS........................................................................................................................7
4 MAGIS COMBO PLUS V2 MAIN DIMENSIONS.............................................................................................................8
5 SINGLE AUDAX PRO V2 MINIMUM INSTALLATION DISTANCES.........................................................................9
6 AUDAX PRO V2 MINIMUM INSTALLATION DISTANCES (SEVERAL APPLIANCES).......................................10
7 DRAIN HOLES AND CONDENSATE DRAIN................................................................................................................11
8 COOLING CIRCUIT FUNCTIONING LIMITS.............................................................................................................12
9 MAGIS COMBO V2 MAIN COMPONENTS (INDOOR UNIT).................................................................................13
10 MAGIS COMBO PLUS V2 MAIN COMPONENTS (INDOOR UNIT)......................................................................14
11 GRAPH OF HEAT GENERATOR PUMP FLOW RATE/HEAD....................................................................................15
12 GRAPH OF HEAT PUMP FLOW RATE/HEAD...............................................................................................................16
13 HYDRAULIC DIAGRAM MAGIS COMBO V2 (INDOOR UNIT)..............................................................................18
14 HYDRAULIC DIAGRAM MAGIS COMBO PLUS V2 (INDOOR UNIT)...................................................................19
15 AUDAX PRO V2 (EXTERNAL CONDENSING UNIT) HYDRAULIC DIAGRAM..................................................20
16 MAGIS COMBO V2 ELECTRONIC MANAGEMENT FUNCTIONS........................................................................21
17 ELECTRIC CONNECTION CABLES FEATURES..........................................................................................................23
18 OUTDOOR UNIT TERMINAL BLOCK ELECTRICAL CONNECTIONS...............................................................24
19 MAGIS COMBO / COMBO PLUS HIGH VOLTAGE ELECTRICAL CONNECTIONS.........................................25
20 MAGIS COMBO V2 / MAGIS COMBO PLUS V2 P.C.B.................................................................................................28
21 INSTALLING THE CHILLER LINES.................................................................................................................................33
22 MAGIS COMBO V2 / MAGIS COMBO PLUS V2 (HEAT PUMP) TECHNICAL DATA.........................................35
23 MAGIS COMBO V2 (HEAT GENERATOR) TECHNICAL DATA...............................................................................36
24 MAGIS COMBO V2 (HEAT GENERATOR) COMBUSTION FEATURES................................................................37
25 PRODUCT FICHE (REGULATION 811/2013)................................................................................................................38
26 “POWER” AND “ABSORPTION” IN CENTRAL HEATING MODE
MAGIS COMBO 4 V2 - MAGIS COMBO 4 PLUS V2.....................................................................................................39
27 PRODUCT FICHE (REGULATION 811/2013)................................................................................................................41
28 “POWER” AND “ABSORPTION” IN CENTRAL HEATING MODE
MAGIS COMBO 6 V2 - MAGIS COMBO 6 PLUS V2.....................................................................................................42
29 PRODUCT FICHE (REGULATION 811/2013)................................................................................................................44
30 “POWER” AND “ABSORPTION” IN CENTRAL HEATING MODE..........................................................................45
MAGIS COMBO 9 V2 - MAGIS COMBO 9 PLUS V2.....................................................................................................45
31 KIT 2 ZONES FOR COUPLING MAGIS COMBO V2 (CODE 3.026301)..................................................................47
32 SYSTEM MANAGER..............................................................................................................................................................53
33 REMOTE PANEL OF ZONE (WITH SYSTEM MANAGER)........................................................................................54
34 REMOTE CONTROL OF ZONE (WITH SYSTEM MANAGER)................................................................................54
35 TEMPERATURE/HUMIDITY SENSOR (WITH SYSTEM MANAGER)....................................................................54
36 EXPANSION BOARD FOR ZONE MANAGEMENT (WITH SYSTEM MANAGER).............................................54
37 DISTRIBUTION KIT TO THE SYSTEM (WITH SYSTEM MANAGER)...................................................................55
38 DEHUMIDIFIER....................................................................................................................................................................59
39 OPTIONAL FOR DIRECT COUPLING TO MAGIS COMBO V2 / COMBO PLUS V2.........................................61
40 OPTIONAL IN THE PRESENCE OF SYSTEM MANAGER.........................................................................................62
41 MAIN INERTIAL STORAGE TANK TECHNICAL FEATURES...................................................................................63
42 MAGIS COMBO V2 OPERATING PRINCIPLES............................................................................................................66
43 MAGIS COMBO PLUS V2 OPERATING PRINCIPLES.................................................................................................71
44 OPERATING PRINCIPLES: ACTIVATION LOGIC........................................................................................................77
45 INTRODUCTION WITH COMMENTARY TO THE DIAGRAMS: MAIN APPLICATIONS...............................79
46 HYDRAULIC DIAGRAM: MAGIS COMBO V2 (INSTANT)
+ KIT 2 ZONES (1 DIRECT AND 1 MIXED) + THERMAL SOLAR SYSTEMS.........................................................80
47 HYDRAULIC DIAGRAM: MAGIS COMBO PLUS V2
+ KIT 2 ZONES (1 DIRECT AND 1 MIXED) + PHOTOVOLTAIC..............................................................................82
48 MAGIS COMBO PLUS V2 RECESSED IN SOLAR CONTAINER COMBO.............................................................84
49 MAGIS COMBO PLUS V2 WITH BASIC MAGIS PRO IN SOLAR CONTAINER COMBO...............................101
50 MAGIS COMBO PLUS V2 WITH SUPER TRIO IN CONTAINER FOR SUPER TRIO........................................105
3
MAGIS COMBO V2
Range of "split" inverter reversible air/water hybrid heat
pumps, composed of an outdoor condensing unit and an in-
door unit (with hydronic exchange unit with chiller unit and
condensation unit); a single "pack" code identifies the complete
system (indoor unit + outdoor condensing unit). There are 3
instant versions (MAGIS COMBO 4 V2, MAGIS COMBO
6 V2 and MAGIS COMBO 9 V2) and 3 PLUS versions
(MAGIS COMBO 4 PLUS V2, MAGIS COMBO 6 PLUS V2
and MAGIS COMBO 9 PLUS V2), all with single-phase supply
voltage. The water circuit is fully protected against freezing be-
cause it can be installed inside the home (in this case there is no
need to add antifreeze); it is, therefore, also particularly suitable
for cold climate areas.
Make the refrigerant connections between the outdoor unit and
the indoor unit.
MAGIS COMBO V2 is ideal for conditioning rooms in central
heating mode (maximum flow temperature 80°C) in cooling
mode, and can produce DHW instantaneously with plate heat
exchanger, or coupled with a separate storage tank unit (PLUS
model).
Thanks to the thrust integration of generators (heat pump and
indoor condensation unit) there are advantages with regard to
both installation and reduction of overall dimensions, compared
to “D.I.Y.” solutions.
The logic of integrated intelligent activation in the system’s elec-
tronics is able to determine the most convenient source of energy
at that time (heat pump / condensation unit) and - therefore - to
chose the source to activate; allows simplifying the electrical
connections (it is not usually necessary to provide the System
Manager, which is still available as optional to manage special
systems, such as systems spread over more than three zones).
The MAGIS COMBO V2 indoor unit is approved for outdoor
use in partially protected environment with IPX4D protection
degree.
MAGIS COMBO V2 also meets the requirements of the ErP
Directive (2009/125/EC) and ELD (2010/30/EC); there are a
number of optional kits available, which allow it to be used in
different plant applications.
Compared to a single condensing boiler, the system allows a
considerable energy saving; also, it occupies little space: it is ideal
for new residential constructions (especially the PLUS version,
which also uses the heat pump for the production of DHW,
facilitating legal compliance), but also for the replacement of
obsolete boilers in systems in which to encourage the use of
renewable energy (in this case, the instant version is particularly
suitable for the purpose).
It is ideal for very high energy classes in new residential con-
structions.
4
MAGIS COMBO V2
1 MAGIS COMBO 4 - 6 - 9 V2 (SINGLE-PHASE), INSTANT AND PLUS FEATURES
"Split" inverter reversible air/water hybrid heat pumps, composed of • The electronics of MAGIS COMBO V2 is designed to directly
an Outdoor condensing unit and a Wall-hung indoor unit; a single manage 3 zones (one direct and two mixed), for the third mixed zone
"pack" code identifies the complete system consisting of the following it is necessary to provide the configurable relay interface kit code
main components: 3.015350) for both central heating and cooling operation; in this
- Outdoor condensing unit (AUDAX PRO V2) which mainly includes case MAGIS COMBO V2 can be connected to zone remote panels
rotary compressor, inverter electronics, throttle valve, 4-way valve for via Bus connections (up to 3 can be provided), or it can be connected
cycle inversion, finned exchange coil with outdoor air (with single with simple on/off contacts (e.g. CHRONO 7) to control the room
fan). The cooling circuit is already preloaded in the condensing unit temperature of the 3 zones. 3 humidistats or 3 Modbus temperature
(refrigerant R32); it is equipped with shut-off valves for the R32 and humidity sensors can be connected to control humidity;
circuit; • Possibility of setting 3 climatic curves for hot and 3 climatic curves
- Wall-hung indoor unit, which includes: for cold (for the 3 zones), on the electronics of the hydronic module,
• The hydraulic circuit components for connection to the system, as no need to provide for the system manager;
well as the relevant management and communication electronics with • Possibility to set on each zone if the zone is only hot, hot/cold, only
the condensing unit; in particular, it is composed of 72-plate R32 / cold (dehumidification included, with dew point calculation);
water exchanger, 10-litre system expansion vessel, flow-meter, 24 Vdc • To manage the dehumidifiers, it is necessary to insert in the indoor
power supply, management electronics; wall-hung unit a 2 relay board kit (optional), to control 2 dehumid-
• Condensing unit with 24 kW nominal useful power (20,640 kcal/h) in ifiers (the third one is controlled by the configurable relay interface
central heating (27.3 kW in DHW) with total premixing combustion kit code 3.015350); the kit allows the dehumidifiers to be activated
system with steel multigas cylindrical burner, complete with ignition through a potential-free contact;
electrode and ionisation control electrode and double shutter pneu- • It includes a 230 V output to control summer/winter diverter valves
matic gas valve, gas/water primary exchanger with composite casing in heating systems with fan coil cold/radiant panels; switching occurs
and stainless steel internal coil; stainless steel combustion chamber with the change of mode (summer/winter) from the control panel;
internally insulated with ceramic panels, fan for flue gas evacuation • The electronic of MAGIS COMBO V2 manages the anti-legionella
at electronically variable speed, circuit for the disposal of condensate function;
including siphon and flexible drain hose; • Input to force activation with photovoltaic system that produces
• 14-plate stainless steel secondary water/water exchanger for the pro- electricity;
duction of domestic hot water, D.H.W. flow switch for detection of • Possible connection to the System Manager (optional) to manage
withdrawal of D.H.W. (MAGIS COMBO V2 instant version); systems with more than 3 zones.
• Hydraulic unit consisting of 3-way electric valve, low consumption 7
m.c.a. circulation pump (associated with the condensation generator Supplied with sample points for combustion analysis, lower protection
operation), low consumption 7 m c.a. circulation pump (associated guard, connection group, cock with filter on system flow, cock on the
with cooling circuit operation), absolute pressure switch for the pri- system flow, gas interception cock and cold water cock.
mary circuit, 3-bar primary circuit safety valve, system drain fitting Category II appliance2H3B/P functions with a natural gas, L.P.G. and
and cock for system filling, in the MAGIS COMBO PLUS V2 there propane air.
is an additional 3-way electric valve to manage the D.H.W. central It is available in the instant models:
heating with the heat pump circuit; • MAGIS COMBO 4 V2 code 3.030609
• Control panel composed of central heating system pressure gauge, • MAGIS COMBO 4 V2 LPG code 3.030609LPG
multifunction display and 7-digit keyboard for setting and adjusting • MAGIS COMBO 6 V2 code 3.030611
the generator operating parameters: central heating/cooling flow • MAGIS COMBO 6 V2 LPG code 3.030611LPG
temperature adjustment buttons, DHW temperature adjustment • MAGIS COMBO 9 V2 code 3.030613
buttons, summer / winter mode button, reset button, menu button; • MAGIS COMBO 9 V2 LPG code 3.030613LPG
• Self-diagnosis system with digital display of the functioning status
and error codes; Or it is available in the PLUS models:
• Ignition delay device in C.H. mode, anti-freeze protection system (to • MAGIS COMBO 4 PLUS V2 code 3.030615
-5°C), pump anti-block device function, three-way valve anti-block • MAGIS COMBO 4 PLUS V2 LPG code 3.030615LPG
device function, chimney sweep function, automatic vent function, • MAGIS COMBO 6 PLUS V2 code 3.030617
screed heater function; • MAGIS COMBO 6 PLUS V2 LPG code 3.030617LPG
• IPX4D Electrical insulation rating; • MAGIS COMBO 9 PLUS V2 code 3.030619
• Possibility of coupling to the system for ducting of existing flues Ø • MAGIS COMBO 9 PLUS V2 LPG code 3.030619LPG
50 mm, Ø 60 mm and Ø 80 mm (for condensation units).
• Selection of C.H. temperature range via the programming menu; • Installation template code 3.016848
• Hydraulically the indoor unit is set-up for connection to 1 heating/
cooling zone and for connection to the DHW storage tank (PLUS
version) or to the D.H.W. circuit (instant); there are also the R32
connections for the condensing unit;
• Compared with block heat pumps, the water circuit is fully protected
against freezing because it can be installed inside the home (important
in cold zones);
5
MAGIS COMBO V2
2 AUDAX PRO V2 DIMENSIONS AND CONNECTIONS (CONDENSING UNIT)
934
660
AUDAX PRO 4 / 6 V2
50 610 12
23
361
358
340
26
364
880 310
310
638
638
GP
LP
211
139
15
880 54.1
229
231
R32
Model LP (Cooling liquid) GP (Gaseous liquid)
AUDAX PRO 9 V2
R32
Model LP (Cooling liquid) GP (Gaseous liquid)
6
MAGIS COMBO V2
3 MAGIS COMBO V2 MAIN DIMENSIONS
A/S = intake/exhaust
A = intake
A A/S A
MAGIS COMBO V2
Flow Return Inlet Hot Outlet R32 R32 Gas Expansion vessel
System system Cold AC LP GP G Litres
M R AF 1/2" 1/4” 5/8"
3/4" 3/4" 1/2" (6.35 mm) (15.88 mm) 3/4" 10 (real 8.3)
7
MAGIS COMBO V2
4 MAGIS COMBO PLUS V2 MAIN DIMENSIONS
A/S = intake/exhaust
A = intake
A A/S A
Flow Return System Filling Storage Storage R32 R32 Gas Expansion vessel
System System RR tank tank LP GP G Litres
M R 1/2" Flow return 1/4” 5/8"
3/4" 3/4" MU RU (6.35 mm) (15.88 mm) 3/4" 10 (real 8.3)
3/4" 3/4"
8
MAGIS COMBO V2
5 SINGLE AUDAX PRO V2 MINIMUM INSTALLATION DISTANCES
With the back side of the With the front side of the With three sides of the unit
unit facing a wall 300 min. unit facing a wall facing a wall
300 min.
1500 min.
300 min. 600 min.
300 min.
1500 min.
300 min.
600 min.
2000 min.
1500 min.
With the top and front sides With the top and back sides With the front and back sides
of the unit facing a wall of the unit facing a wall of the unit facing a wall
(Unit: mm)
Place of installation:
The place of installation is very important and must be estab- - prevent exhaust air from the device from coming into the
lished by the system's designer or by a specifically qualified rooms through doors or windows, thus disturbing people;
person, and must consider the technical requirements, standards • The appliances must:
and laws in force. - be placed on a level surface that is able to withstand its weight;
• The condensing unit must be installed outside the building - be placed on a slab that is hard enough and which does not
only; the indoor unit must be installed inside the building or transfer any vibrations to the underlying or adjacent rooms;
outdoors in a partially protected place; - installed by means of the vibration-dampening supports sup-
• It is recommended to avoid: plied with the machine.
- positioning in basement windows; • If the unit is installed in zones subject to heavy snow, it will
- obstacles or barriers that cause recirculation of exhaust air; be necessary to raise the machine by at least the height of the
- places with aggressive atmospheres; strongest expected snowfall or, alternatively, use wall-support
- limited spaces or anyhow in places where sound levels from brackets (optional).
the appliance can be enhanced through reverberations or
resonance;
- positioning in corners where there is an accumulation of
dust, leaves and anything else that can reduce the appliance's
efficiency due to blocked passageways;
9
MAGIS COMBO V2
6 AUDAX PRO V2 MINIMUM INSTALLATION DISTANCES (SEVERAL APPLIANCES)
The front side of the unit facing a wall With three sides of the units facing a wall
300 min.
1500 min.
300 min. 600 min. 600 min. 600 min.
500 min.
300 min. With the top and back sides
of the units facing a wall
500 min.
(Unit: mm)
1500 min. 600 min. 3000 min. 3000 min. 300 min.
With the units facing each other and with the front and back
sides of the end units facing a wall
In addition: N.B.: The spaces shown must be left free to allow air to
- the unit must be installed in a position protected from snow circulate and to ensure accessibility for repairs or maintenance
falling from above. If this is not possible, you must at least on every side of the units. In fact, it must be possible to
prevent the snow from clogging the air/coolant exchanger disassemble all the unit components under the utmost safety
(even by constructing a small protective roof for the unit, if conditions (both for objects and for people).
necessary);
- the effects of the wind can be minimised by installing the unit
with the intake side facing a wall;
- the unit must not be installed with the intake side against the
wind;
- the effects of the wind can be further minimised by installed
a deflector plate facing the unit air flow side (not supplied).
10
MAGIS COMBO V2
7 DRAIN HOLES AND CONDENSATE DRAIN
Ø20 drainage hole (in 5 positions) Ø20 drainage hole (in 4 positions)
30 mm
11
MAGIS COMBO V2
8 COOLING CIRCUIT FUNCTIONING LIMITS
Central heating
System
KEY:
TM - Flow water temperature (°C)
TE - Outdoor air temperature (°C)
65 KEY:
TB - Storage tank temperature probe (°C)
55 TE - Outdoor air temperature (°C)
A
A = Work area covered by condensation
35
generator
B = Work area covered by Heat pump
B
10
0 TE (°C)
-30 -25 -5 0 35 46 60
Cooling
TM (°C)
35 KEY:
TM - Flow water temperature (°C)
25 TE - Outdoor air temperature (°C)
5
TE (°C)
0 10 46 60
12
MAGIS COMBO V2
9 MAGIS COMBO V2 MAIN COMPONENTS (INDOOR UNIT)
9 10 38
11
12
13
37
7
14
15
6 16 36
17
35
5 18
19 39
4
20
3
21
22
2
23
1
24
34 33 32 31 30 29 28 27 26 25 40
KEY:
1 - Gas valve 19 - One-way valve 37 - Burner
2 - One-way valve 20 - Air vent valve 38 - System expansion vessel
3 - Heat pump circuit circulator 21 - System pressure switch 39 - Heat generator return probe
4 - Heat pump flow probe 22 - Heat generator circuit circulator 40 - DHW probe
5 - Heat generator flow probe 23 - Heat generator three-way valve
6 - Safety thermostat 24 - 3 bar safety valve
7 - Detection electrode 25 - System shut-off cock
8 - System flow-meter 26 - System draining fitting
9 - Flange with sample points 27 - System shut-off cock with filter
10 - Flue gas thermofuse 28 - System filling cock
11 - Heat exchanger safety thermofuse 29 - DHW plate heat exchanger
12 - Condensation module 30 - Domestic hot water inlet cock
13 - Ignition electrode 31 - D.H.W. flow switch
14 - Venturi 32 - Air vent valve
15 - Gas nozzle 33 - Condensate drain trap
16 - Igniter 34 - Gas interception cock
17 - Fan 35 - Liquid phase detection probe
18 - Air intake pipe 36 - Water - gas plate exchanger
13
MAGIS COMBO V2
10 MAGIS COMBO PLUS V2 MAIN COMPONENTS (INDOOR UNIT)
11 12 38
13
14
10
15
9 16 37
8 17
7 18
6
5 19 36
4 20
35 39
3 21
22
34
2
23
1 24
33 32 31 30 29 28 27 26 25
KEY:
1 - Gas valve 19 - Air intake pipe 37 - Burner
2 - Heat pump circuit circulator 20 - One-way valve 38 - System expansion vessel
3 - Condensate drain trap 21 - Air vent valve 39 - Heat generator return probe
4 - Three-way valve 22 - System pressure switch
5 - 3-way valve motor 23 - Heat generator circuit circulator
6 - DHW probe 24 - Heat generator three-way valve
7 - Safety thermostat 25 - System shut-off cock
8 - Gas nozzle 26 - System draining fitting
9 - Detection electrode 27 - System shut-off cock with filter
10 - System flow-meter 28 - 3 bar safety valve
11 - Flue gas thermofuse 29 - System filling cock
12 - Flange with sample points 30 - Domestic hot water inlet cock
13 - Heat exchanger safety thermofuse 31 - Air vent valve
14 - Condensation module 32 - By-pass pipe
15 - Ignition electrode 33 - Gas interception cock
16 - Venturi 34 - Heat pump flow probe
17 - Fan 35 - Liquid phase detection probe
18 - Igniter 36 - Water-gas plate exchanger
14
MAGIS COMBO V2
11 GRAPH OF HEAT GENERATOR PUMP FLOW RATE/HEAD
Max.
Speed
(100
%)
A B
Mi
n Spe
ed(
70%
)
The indoor units are equipped with low power consumption NOTE: for proper system operation, make sure that the
pump with variable speed control associated with the conden- minimum flow rate in operating conditions never drops
sation generator operation (heat generator). below 500 l/h.
The pump speed is set via the following parameters: Treating the feed water allows you to prevent problems and
Fixed ("A 05" = 0): the circulator speed is fixed and corresponds maintain the function and efficiency of the generator over
to the settings made through the “A 19” parameter. time.
∆T constant ("A 05" = 5 ÷ 25 K): the pump speed varies to Legislative Decree 26/06/2015 requires a chemical treatment
maintain the ∆T constant between the system flow and return. of the thermal system water, in compliance with the UNI 8065
Also, you can adjust the pump operating range, by setting the standard, in the cases provided for by the Decree.
maximum speed “A 19” and the minimum speed “A 18”.
15
MAGIS COMBO V2
12 GRAPH OF HEAT PUMP FLOW RATE/HEAD
80 80
70 70
Max
. Spe
ed (100
60 %) 60
40 40
30 30
20 20
10 Min 10
Speed (
45%
)
0 0
0 200 400 600 800 1000 1200 1400 1600 1800 2000
Flow rate (l/h)
KEY: EEI ≤ 0.20 - Part 3
A = Head available to the system
B = Absorbed power by the circulator (dotted area)
The indoor units are equipped with low power consumption NOTE: for proper system operation, make sure that the
pump with variable speed control associated with the heat pump minimum flow rate in operating conditions never drops
operation (chiller circuit). below 500 l/h.
The pump speed is set via the following parameters: Treating the feed water allows you to prevent problems and
Fixed ("A 05" = 0): the circulator speed is fixed and corresponds maintain the function and efficiency of the generator over
to the settings made through the “A 04” parameter. time.
∆T constant ("A 05" = 5 ÷ 25 K): the pump speed varies to Legislative Decree 26/06/2015 requires a chemical treatment
maintain the ∆T (5K) constant between the system flow and of the thermal system water, in compliance with the UNI 8065
return. Also, you can adjust the pump operating range, by set- standard, in the cases provided for by the Decree.
ting the maximum speed through the “A 04” parameter and the
minimum speed through the “A 03” parameter.
16
MAGIS COMBO PLUS V2
12.2 GRAPH OF HEAT PUMP FLOW RATE/HEAD
80 80
70 70
Max
. Spe
60 ed (100 60
%)
40 40
30 30
20 20
10 Min 10
Speed (
45%
)
0 0
0 200 400 600 800 1000 1200 1400 1600 1800
The indoor units are equipped with low power consumption NOTE: for proper system operation, make sure that the
pump with variable speed control associated with the heat pump minimum flow rate in operating conditions never drops
operation (chiller circuit). below 500 l/h.
The pump speed is set via the following parameters: Treating the feed water allows you to prevent problems and
Fixed ("A 05" = 0): the circulator speed is fixed and corresponds maintain the function and efficiency of the generator over
to the settings made through the “A 04” parameter. time.
∆T constant ("A 05" = 5 ÷ 25 K): the pump speed varies to Legislative Decree 26/06/2015 requires a chemical treatment
maintain the ∆T (5K) constant between the system flow and of the thermal system water, in compliance with the UNI 8065
return. Also, you can adjust the pump operating range, by set- standard, in the cases provided for by the Decree.
ting the maximum speed through the “A 04” parameter and the
minimum speed through the “A 03” parameter.
17
MAGIS COMBO V2
13 HYDRAULIC DIAGRAM MAGIS COMBO V2 (INDOOR UNIT)
KEY:
1 - D.H.W. flow switch
2 - Condensate drain trap
3 - Gas valve
4 - Gas valve outlet pressure point (P3)
5 - Liquid phase detection probe
6 - DHW probe
7 - System filling valve
8 - DHW heat exchanger
9 - System expansion vessel
10 - Heat pump flow probe
11 - Water - gas plate exchanger
12 - Air vent valve
13 - Fan
14 - Air/gas Venturi manifold
15 - Gas nozzle
16 - Detection electrode
17 - Burner
18 - Flue safety thermostat
19 - Air intake pipe
20 - Manual air vent valve
21 - Heat exchanger safety thermofuse
22 - Air sample point
23 - Flue sample point
24 - ∆P gas pressure point
25 - Fumes hood
26 - Safety thermostat
27 - Heat generator flow probe
28 - Heat generator return probe
29 - Ignition electrodes
30 - Venturi negative signal (P2)
31 - Venturi positive signal (P1)
32 - One-way valve
33 - System flow-meter
34 - Heat pump return probe
35 - Air vent valve
36 - Heat generator circuit circulator
37 - Heat pump circuit circulator
38 - System pressure switch
39 - Motorised 3-way valve
40 - One-way valve
41 - System draining cock
42 - 3 bar safety valve
43 - System interception cock
44 - System interception cock
with inspectable filter
G - Gas supply
SC - Condensate drain
LP - Chiller line - liquid phase
GP - Chiller line - gaseous phase
AC - Domestic hot water outlet
AF - Domestic hot water inlet
R - System return
M - System flow
18
MAGIS COMBO V2
14 HYDRAULIC DIAGRAM MAGIS COMBO PLUS V2 (INDOOR UNIT)
KEY:
1 - 3 bar safety valve
2 - Condensate drain trap
3 - Gas valve
4 - Gas valve outlet pressure point (P3)
5 - Liquid phase detection probe
6 - System draining cock
7 - System pressure switch
8 - System expansion vessel
9 - Heat generator circuit circulator
10 - Air vent valve
11 - One-way valve
12 - Water - gas plate exchanger
13 - Fan
14 - Air/gas Venturi manifold
15 - Gas nozzle
16 - Detection electrode
17 - Burner
18 - Flue gas thermofuse
19 - Air intake pipe
20 - Manual air vent valve
21 - Heat exchanger safety thermofuse
22 - Air sample point
23 - Flue sample point
24 - ∆P gas pressure point
25 - Fumes hood
26 - Safety thermostat
27 - Heat generator flow probe
28 - Heat generator return probe
29 - Ignition electrodes
30 - Venturi negative signal (P2)
31 - Venturi positive signal (P1)
32 - Air vent valve
33 - One-way valve
34 - System flow-meter
35 - Heat pump return probe
36 - Heat pump 3-way valve
37 - Heat pump flow probe
38 - Heat pump circuit circulator
39 - Heat generator 3-way valve
40 - System filling cock
41 - System filling
42 - System interception cock
43 - System interception cock
with inspectable filter
G - Gas supply
SC - Condensate drain
LP - Chiller line - liquid phase
GP - Chiller line - gaseous phase
RU - Storage tank unit return
MU - Storage tank unit flow
RR - System filling
R - System return
M - System flow
19
MAGIS COMBO V2
15 AUDAX PRO V2 (EXTERNAL CONDENSING UNIT) HYDRAULIC DIAGRAM
KEY:
1 - Compressor
2 - Compressor temperature
3 - Compressor outlet temperature
4 - Silencer
5 - High pressure switch
6 - 4-way valve
7 - Temperature of fluid in finned coil
8 - External probe/installation room temperature
9 - Finned coil + fan
10 - Electronic expansion valve
11 - Dryer filter
12 - Liquid receiver
13 - Liquid separator
20
MAGIS COMBO V2
16 MAGIS COMBO V2 ELECTRONIC MANAGEMENT FUNCTIONS
The electronic of MAGIS COMBO V2 is characterised by an There is an input for system activation in correspondence of
integrated intelligent management system that establishes the electricity production by the photovoltaic system (if installed).
most beneficial operating priority of the generator between Heat This input (when active), if no system requests are in progress,
Pump or condensation unit, on the basis of the external climatic forces the heating of a storage tank for the production of DHW
conditions and central heating system flow temperature set. at maximum storage temperature (if the storage tank is present
MAGIS COMBO V2 works at sliding temperature, using the e.g. MAGIS COMBO PLUS V2).
external probe present on the condensing unit (placed outside); It includes a 230 V output to control summer/winter diverter
it is prepared to directly manage 3 zones (one direct and two valves in heating systems with fan coil cold/radiant panels;
mixed, for the third mixed zone it is necessary to provide the switching occurs with the change of mode (summer/winter)
configurable relay interface kit code 3.015350) for operation in from the control panel or from the remote panel of the zone.
both heating and cooling, with the possibility of setting 3 curves The electronic of MAGIS COMBO PLUS V2 also manages the
in hot and 3 curves in cold (for the 3 zones) without the need to anti-legionella function.
provide the System manager. in this case MAGIS COMBO V2 The electronics of MAGIS COMBO V2, in combination with
can be connected to zone remote panels (code 3.030863) via Bus the configurable relay interface kit (code 3.015350), also manages
connections (up to 3 can be provided), or it can be connected the activation of the recirculation pump.
with simple on/off contacts (e.g. CHRONO 7) to control the In the presence of any "Puffer" which is heated by another
room temperature of the 3 zones. energy source (e.g. thermal chimney), it is possible to connect
3 humidistats (code 3.023302) or 3 Modbus temperature and the hydronic module with a temperature control probe (code
humidity sensors (code 3.030992) can be connected to control 3.019375), exceeded the set temperature MAGIS COMBO V2
humidity. remains off, but the system zones can continue to operate (ob-
When using the ModBus temperature and humidity sensor kit viously in the presence of requests) *.
(code 3.030992), in order to make temperature requests it is Whereas, to control a possible solar system, a solar control unit
necessary to match a room thermostat in the zone as it is not is required (to be purchased separately).
possible to set the room set directly from the control panel. The integrated electronics also manage the screed heating func-
To manage the dehumidifiers, it is necessary to insert in the tion in order to perform the initial central heating cycle on new
indoor wall-hung unit a 2 relay board kit (optional), to control radiant panel systems.
2 dehumidifiers (the third one is controlled by the configurable
relay interface kit code 3.015350); the kit allows the dehumid- * Please note that the relays available within the configurable
ifiers to be activated through a potential-free contact. relay kit code 3.015350 are 3, therefore the functions described
For each zone, from the MAGIS COMBO V2 electronics it is cannot all be used at the same time.
possible to set if the zone is only hot, hot/cold, only cold (dehu-
midification included, with dew point calculation).
21
MAGIS COMBO V2
By setting the parameters in the “Temperature control” menu, operating modes available both with external probe and without
you can adjust how the system operates. in relation to the different zones (direct or mixed).
The following graphs show the default settings in the various
Zone 1 flow temperature in central heating Zone 2 and 3 mixed flow temperature in central
mode, with external probe heating mode, with external probe
R04
U03 R08 (U16)
(R23) U04
R05 R09
(R24)
Zone 1 flow temperature in cooling mode, Zone 2 and 3 mixed flow temperature in cooling
with external probe mode, with external probe
(U17)
U05 U06
R13 (R28)
R17
R16
(R27)
R12
Flow temperature in central heating mode Flow temperature in cooling mode without
without external probe external probe
Z1
1
Z2 (Z3)
U02
(U15)
Z2 (Z3)
U01 Z1
(U14) 2
KEY:
Rxx - "Temperature control" menu parameter external probe on cooling zone 1.
TE - Outside temperature U06 - Offset value compared to the curve set by the
TM - Flow temperature external probe on cooling zone 2.
U01 - Zone 2 flow temperature in "User" menu central U14 - Zone 3 flow temperature in "User" menu
heating mode central heating mode.
U02 - Zone 2 flow temperature in "User" menu cool- U15 - Zone 3 flow temperature in "User" menu
ing mode cooling mode.
U03 - Offset value compared to the curve set by the U16 - Offset value compared to the curve set by the
external probe on central heating zone 1. external probe on central heating zone 3.
U04 - Offset value compared to the curve set by the U17 - Offset value compared to the curve set by the
external probe on central heating zone 2. external probe on cooling zone 3.
U05 - Offset value compared to the curve set by the Zx - Heating system zone
22
MAGIS COMBO V2
17 ELECTRIC CONNECTION CABLES FEATURES
UNIT SUPPLY
OUTDOOR UNIT VOLTAGE
SUPPLY VOLTAGE
1 phase 1 phase
2 conductors
230 Vac PROTECTION UNIT
2 conductors
230 Vac * Example PLUS model
DOMESTIC HOT
*
WATER TANK
OUTDOOR
UNIT
INDOOR
UNIT
COMMUNICATION
CABLE
Features of the indoor unit connection. The outdoor unit or FG 16). Indicatively, the appropriate cable section can be
power cable (not standard supplied) must be suitable for outdoor 2.5 ~ 4 mm2 for AUDAX PROX 4 and 6 V2 and of 4 ~ 6 mm2
installation and must have at least a flexible polychloroprene for AUDAX PRO 9 V2 to be checked depending on the specific
sheath (code IEC:60245 IEC 57 / CENELEC:H05RN-F installation conditions.
Mono-phase,
±10% 0,75 ~ 1.5 mm², 3 wires 0,75 ~ 1.5 mm², 2 wires
220-240V, 50Hz
23
MAGIS COMBO V2
18 OUTDOOR UNIT TERMINAL BLOCK ELECTRICAL CONNECTIONS
KEY:
Depending on the model, the actual appear- ELB - Safety Switch
ance of the unit may differ from the one shown MCCB - Circuit breaker switch
in the figure.
Electrical panel
MCCB
L N
ELB
MCCB
Cable
clamping
clip
Fairlead
terminal
L N L N
L N L N
11.4 10.1 17 17
10,1
10.1 10.1 10.1 13
10.1 13
L N L N
L N
17 15 12 17
10,1 10,1
10.1
10.1 10.1 13 13
24
MAGIS COMBO V2
19 MAGIS COMBO / COMBO PLUS HIGH VOLTAGE ELECTRICAL CONNECTIONS
2 3
6
1
1
Terminal 87
0V Close Winter
230 V Open Summer with cooling
4
5
KEY:
1 - Open / Close
2 - Close
c
3 - Open
4 - Valve with spring return
5 - 2-point valve d
6 - Auxiliaries
M10-1 - Zone 1 circulator pump
M10-2 - Zone 2 circulator pump
c 1
M10-3 - Zone 3 circulator pump a
M31-2 - Zone 2 mixing valve
M52 - Hot/cold 3-way
S39 - Solar inlet
S41 - AUDAX PRO V2 disabling 1
1 2
b
N.B.: To control the dehumidifiers, insert the relay board kit Through the configurable relay interface akit (optional) it is also
(optional) inside the MAGIS COMBO V2 wall-hung indoor a the pump
possible to manage a 3rd zone (mixed) on the system,
unit, for the respective dehumidifiers of the two zones. The relay of zone 3 will need to be connected as shown in the diagram
board kit has only one contact for each zone and, therefore, al- (M10-3). The zone 3 dehumidifier, if any, will be managed by
lows the dehumidifier to work either in neutral air or in cooled means of the configurable relay interface kit, which the zone 3
air. For further information see the chapter on dehumidifiers. mixer will also be connected to. In this way 1 direct zone + 2
mixed zones can be controlled.
25
MAGIS COMBO V2
19.1 ELECTRICAL CONNECTIONS THIRD MIXED OR DIRECT ZONE
It is necessary to insert a
jumper on connector X25
KEY:
A3 - Integrated P.C.B.
A7 - Configurable relay board
A16-3 - Dehumidifier zone 3
B3-3 - Zone 3 flow probe
M10-3 - Zone 3 circulator pump c
M31-3 - Zone 3 mixing valve
K1 - Configurable relay d
K2 - Configurable relay
K3 - Configurable relay
c 1
a
1
1
1 2
26 b a
a
a
19.2
KEY:
B4 - External probe
B9 - Solar inlet probe (instant version)
MAGIS COMBO / COMBO PLUS LOW VOLTAGE ELECTRICAL CONNECTIONS
27
c
2 3
KEY:
1 - P.C.B. adjustment
2 - Vertical terminal block electrical connections (230 Vac)
3 - Horizontal terminal block electrical connections (Very low safety voltage)
A1 - Ignition board
A2 - P.C.B.
A7 - Three-relay board (optional)
A13 - System manager (optional)
A17-1 - Modbus zone 1 temp./humidity probe (optional)
A17-2 - Modbus zone 2 temp./humidity probe (optional)
A17-3 - Modbus zone 3 temp./humidity probe (optional)
A19 - Two-relay board (optional)
A22 - Interface board
A23 - Outdoor unit
A30 - Dominus (optional)
A32-1 - Zone 1 remote panel (optional)
A32-2 - Zone 2 remote panel (optional)
A32-3 - Zone 3 remote panel (optional)
T2 - Ignition transformer
28
MAGIS COMBO V2
Instant version / PLUS version
KEY:
A2 - P.C.B.
A7 - Three-relay board (optional)
G4 - 24 Vdc power supply unit
29
MAGIS COMBO V2
Instant version / PLUS version
A1
KEY:
A2 - P.C.B.
B1-BO - Heat unit flow probe
B1-BO - Heat unit flow probe
B5-BO - Heat unit return probe
B1-HP - HP unit flow probe
B5-HP - HP unit return probe
B25 - System flow-meter
E1 - Ignition electrode
E2 - Detection electrode
E4 - Safety thermostat
E6 - Flue gas thermofuse
E13 - Heat exchanger safety thermofuse
M20 - Fan
M50-BO - Heat unit 3-way valve
S5 - System pressure switch G - Green
T2 - Ignition transformer GY - Grey
Z - Control panel electrical con- OR - Orange
nections compartment terminal P - Purple
board PK - Pink
R - Red
Colour code key: W - White
BK - Black Y - Yellow
BL - Blue Y/G - Yellow/Green
BR - Brown W/BK - White/Black
30
MAGIS COMBO V2
Instant version
KEY:
A2 - P.C.B.
A7 - Three-relay board (optional)
G4 - 24 Vdc power supply unit
M1-BO - Heat generator circulator
M1-HP - HP generator circulator
M20 - Fan
Z1 - Antijamming filter
KEY:
A7 - Three-relay board (optional)
A22 - Condensing unit interface board
B2 - DHW probe
B27 - Liquid phase probe
G4 - 24 Vdc power supply unit
R14 - Configuration resistance
S4 - D.H.W. flow switch
OR - Orange
Colour code key: P - Purple
BK - Black PK - Pink
BL - Blue R - Red
BR - Brown W - White
G - Green Y - Yellow
GY - Grey Y/G - Yellow/Green
W/BK - White/Black
31
MAGIS COMBO V2
PLUS version
KEY:
A2 - P.C.B.
A7 - Three-relay board (optional)
G4 - 24 Vdc power supply unit
M1-BO - Heat generator circulator
M1-HP - HP generator circulator
M20 - Fan
M50-HP - HP three-way valve
Z1 - Antijamming filter
KEY:
A7 - Three-relay board (optional)
A22 - Condensing unit interface board
B27 - Liquid phase probe
G4 - 24 Vdc power supply unit
R14 - Configuration resistance
32
MAGIS COMBO V2
21 INSTALLING THE CHILLER LINES
A
AUDAX PRO 4 and
AUDAX PRO 9 V2
6 V2
A ≤ 30 m ≤ 35 m
H1 ≤ 20 m ≤ 20 m
H2 ≤ 15 m ≤ 15 m
33
MAGIS COMBO V2
Selecting chiller line insulation. NOTE: The insulation cannot be interrupted and for this reason,
- The gas and liquid chiller lines must be insulated with materials its junctions must be sealed with adhesive to prevent moisture
selected based on their respective diameters. from getting in.
- Standard insulation is required at a temperature of 30°C with Should the insulation be exposed to sunlight, it must be protected
85% relative humidity. Should the thermal-hygrometric con- by wrapping it with electrical tape or material suitable for this
ditions of the air be harsher, you must use insulations that can type of application.
be selected from the table below. The insulation must be laid without its thickness being reduced
in the bends and supports of the pipes.
Insulation thickness
EPDM, NBR
Ø 6.35 - 19.05 9 9
Liquid
Ø 12.70 - 19.05 13 13 The pre-selected ma-
Ø 6.35 13 19 terial must be able to
Ø 9.52 withstand temperatures
Gas Ø 12.70 exceeding 120°C
19 25
Ø 15.88
Ø 19.05
Topping up the coolant load. NOTE: If you have already prepared chiller pipes on the 3/8"
Below is the default factory base load: (Ø 9.52 mm) instead of 1/4" (Ø 6.35 mm) liquid line, it should
MAGIS COMBO V2 models with R32 coolant gas: be noted that up to 7 m the machine works correctly without
- AUDAX PRO 4 V2 = 1.2 kg having to add coolant gas, if you exceed this length, you must
- AUDAX PRO 6 V2 = 1.2 kg add 50 g/m linear, but never exceed the total charge of 1.84 kg
- AUDAX PRO 9 V2 = 1.4 kg of R32 coolant (take into account the amount already preloaded
in the machine).
The top-up depends on the total length and diameter of the pipes. N.B.: To avoid breaking the compressor, do not top-up the
All the default factory loads are determined as follows, depending coolant beyond the specified amount.
on the standard length of the pipes (see table below).
If the used pipes are longer than stated below, the load must
be topped-up in the manner and quantities described in the
instruction manual supplied with the product.
Liquid line pipe external Maximum length with- Top-up quantity for
Model
diameter out base load top-up every additional metre
MAGIS COMBO V2
(mm - inch) (liquid line pipe) of the liquid line pipe
34
MAGIS COMBO V2
22 MAGIS COMBO V2 / MAGIS COMBO PLUS V2 (HEAT PUMP) TECHNICAL DATA
4 V2 6 V2 9 V2
Central heating circuit
Power in CH mode with water set at 35 °C (1) kW 4.40 6.00 9.00
Power in CH mode with water set at 45 °C
(2)
kW 4.20 5.40 8.60
Power in CH mode with water set at 55 °C (3) kW 3.90 4.80 8.00
CH mode COP with water set at 35 °C
(1)
5.20 4.92 4.81
CH mode COP with water set at 45 °C (2) 3.85 3.58 3.69
CH mode COP with water set at 55 °C (3) 2.95 2.65 2.93
Flow temperature range °C 20 ÷ 65 20 ÷ 65 20 ÷ 65
Outdoor temp. limits for Heating mode operation °C - 25 ÷ 35 - 25 ÷ 35 - 25 ÷ 35
Cooling circuit
Power in cooling mode with water set at 18 °C (1)
kW 5.00 6.50 8.70
Power in cooling mode with water set at 7 °C
(2)
kW 3.60 4.70 6.50
Cooling mode EER with water set at 18 °C (1) 4.59 4.42 4.12
Cooling mode EER with water set at 7 °C (2) 3.24 3.26 3.33
Flow temperature range °C 5 ÷ 25 5 ÷ 25 5 ÷ 25
Outdoor temp. limits for Cooling mode operation °C 10 ÷ 46 10 ÷ 46 10 ÷ 46
General data
THE REPORTED DATA REFERS TO THE FOLLOWING CONDITIONS (in compliance with EN 14511):
ROOM CENTRAL HEATING PHASE (°C) COOLING PHASE (°C)
(1)
Water TEMP. (F/R) - AIR (db/wb) 35/30 - 7/6 18/23 - 35 (bs)
(2)
Water TEMP. (F/R) - AIR (db/wb) 45/40 - 7/6 7/12 - 35 (bs)
(3)
Water TEMP. (F/R) - AIR (db/wb) 55/47 - 7/6
35
MAGIS COMBO V2
23 MAGIS COMBO V2 (HEAT GENERATOR) TECHNICAL DATA
36
MAGIS COMBO V2
24 MAGIS COMBO V2 (HEAT GENERATOR) COMBUSTION FEATURES
NOTE: The condensation heat generator can also work with propane air.
Gas flow rates refer to the NHV at the temperature of 15° C and pressure of 1013 mbar.
Flue temperature values refer to an air inlet temperature of 15°C and flow/return temperature = 80/60°C.
37
MAGIS COMBO 4 V2
25 PRODUCT FICHE (REGULATION 811/2013)
4
5 5 5
53 5
53
58
38
MAGIS COMBO 4 V2
26 “POWER” AND “ABSORPTION” IN CENTRAL HEATING MODE
MAGIS COMBO 4 V2 - MAGIS COMBO 4 PLUS V2
40
MAGIS COMBO 6 V2
27 PRODUCT FICHE (REGULATION 811/2013)
5
6 6 6
6 6 6
53 53
41
MAGIS COMBO 6 V2
28 “POWER” AND “ABSORPTION” IN CENTRAL HEATING MODE
MAGIS COMBO 6 V2 - MAGIS COMBO 6 PLUS V2
43
MAGIS COMBO 9 V2
29 PRODUCT FICHE (REGULATION 811/2013)
7 8 7
8 9 8
8 9 8
53 53
44
MAGIS COMBO 9 V2
30 “POWER” AND “ABSORPTION” IN CENTRAL HEATING MODE
MAGIS COMBO 9 V2 - MAGIS COMBO 9 PLUS V2
46
MAGIS COMBO V2
31 KIT 2 ZONES FOR COUPLING MAGIS COMBO V2 (CODE 3.026301)
The 2 zone kit for coupling with MAGIS COMBO V2 is
composed of a frame, open hydraulic manifold, low electric
consumption solenoid valves, three-way mixing valve, hydraulic
fitting and pipes and thermometers for temperature reading.
The pumps included in the kit are distinguished for being very
elastic, also thanks to the operating modes that can be pre-set.
All components are already assembled and ready to operate. All
electrical connections are to be taken to the MAGIS COMBO
V2 P.C.B.
This kit is to be used to control differential temperature systems
and/or divided into two distinct zones.
With the acquisition of the outdoor temperature, the MAGIS
COMBO V2 electronics enables you to select independent flow
temperature curves for each of the 2 zones of the system (both
with C.H. and cooling).
Inserting these kits into the system enhances overall comfort
and energy savings.
KEY:
AR - Appliance return (G 3/4”)
AF - Appliance flow (G 3/4”)
V - Electrical connection
X - Holes for wall-hung installation of the kit
47
MAGIS COMBO V2
31.2 MAIN COMPONENTS KIT 2 ZONES FOR COUPLING MAGIS COMBO V2
48
MAGIS COMBO V2
31.3 WIRING DIAGRAM KIT 2 ZONES FOR COUPLING MAGIS COMBO V2
KEY:
B3-2 - Zone 2 flow probe
E7 - Mixed zone 2 safety thermostat
M10-1 - Zone 1 circulator pump
M10-2 - Zone 2 circulator pump
M31-2 - Zone 2 mixing valve
49
MAGIS COMBO V2
31.4 TECHNICAL DATA KIT 2 ZONES FOR COUPLING MAGIS COMBO V2
The kits are supplied with circulating pumps fitted with speed - Constant head (ΔP-C)
regulator. These settings are suitable for most systems. The circulator pump maintains the pressure level (head) constant
For proper use one must select the most suitable type of oper- as the system heat demand decreases (flow rate reduction). With
ation for the system. these settings, the circulator pump is suitable for all floor systems
By rotation, it is possible to select the following pump control where all the circuits must be balanced for the same drop in head.
mode:
Fixed speed I, II, III.
Proportional head I, II, III.
Constant head I, II, III.
- Fixed speed
Adjusts the pump speed in fixed mode.
It is possible to set 3 different speeds:
I: Minimum Speed. 4 3
II: Intermediate speed.
III: Maximum speed (factory set speed).
50
MAGIS COMBO V2
31.6 GRAPHICS PUMPS WITH CONSTANT HEAD PROGRAM
The kit contains an electronic low consumption circulation All pumps in the kit are suitable for operation with heat and
pump, whose flow rate/head features are shown in the graph cold carrying fluid.
below.
A
B
Speed 1
A
Head (kPa)
Speed 1
Spee
d 7
Head (kPa)
A
B
Speed 1
KEY:
A = Head available at speed 1 ÷ 7 EEI ≤ 0.20
B = Power absorbed by the system pump (dotted area)
51
MAGIS COMBO V2
31.7 GRAPHICS PUMPS WITH PROPORTIONAL HEAD PROGRAM
The kit contains an electronic low consumption circulation All pumps in the kit are suitable for operation with heat and
pump, whose flow rate/head features are shown in the graph cold carrying fluid.
below.
Speed 1
B
A
Speed 1
Speed 7
Head (kPa)
Speed 1
KEY:
A = Head available at speed 1 ÷ 7 EEI ≤ 0.20
B = Power absorbed by the system pump (dotted area)
52
MAGIS COMBO V2
32 SYSTEM MANAGER
Using the system manager (integrated with the relative expansion • as far as temperature/humidity control devices are concerned,
kits) it is possible to control: a maximum of 4 Zone Panels/Controls can be associated only
• MAGIS COMBO V2 / MAGIS COMBO PLUS V2; in zones 1-3 and HT (high temperature) zone. The Tempera-
ture/Humidity Sensor Kit can be used instead in all zones 1-8;
• storage tank for D.H.W. production (the D.H.W. temperature
another set-up is for room thermostats and on-off humidistats;
is managed by the NTC probe);
• up to 8 dehumidifiers.
• up to 2 solar circulation units for systems with manifolds
arranged on different slopes; On the other hand, in terms of the main settings that can/must
be carried out, the System Manager allows you to acquire or
• temperature probes (NTC - PT1000);
programme:
• on-off request dry contact;
• external temperature;
• variable flow temperature of the heat pump and the boiler
• system flow temperature;
(using the required models), depending on the external tem-
perature (a climatic curve is pre-selected); • storage tank temperature (even through 2-3 probes, 1 of which
refers to the solar-heated part of the boiler);
• 8 expansion boards for the management of the air condition-
ing system the maximum number of manageable zones is • by means of self-diagnosis, detection and display of error codes
8, to which 2 expansions can be added for special functions in the event of anomalies;
(expansions with address 4 and 5). For each single zone, it is • date and time;
possible to decide whether it is a mixed zone, a direct zone, • differentiated selection and programming for each individual
or a direct zone with water temperature probe (thus allowing zone;
the correction of the outlet temperature from the generator
• programming the time periods for DHW production;
also according to the flow temperature detected on the direct
zones, useful if upstream there is a hydraulic manifold in which • anti-legionella function program;
mixing with the system return takes place); • management of the heat/cooling sources.
• 2 expansion boards for the additional functions, namely:
- hot/cold switch-over on distinct systems (for example systems
with radiant panel heating and fan-coil cooling); • SYSTEM MANAGER code 3.021522
- recirculation pump management for DHW;
- acquisition of a signal from a system that generates electrical
energy (e.g. photovoltaic system);
53
MAGIS COMBO V2
33 ZONE REMOTE PANEL (WITH SYSTEM MANAGER)
It is an electronic device equipped with a back-lit display to
control and adjust the room's temperature and humidity.
Connection to the System manager occurs via two BUS cables.
It programs the relative room heat adjustment.
It can be applied to the wall using the supplied screws and plugs.
The kit is powered at 24 V (directly from the Manager).
54
MAGIS COMBO V2
37 DISTRIBUTION KIT TO THE SYSTEM (WITH SYSTEM MANAGER)
Two pre-packaged systems called: "2 mixed zones kit" and "2
mixed zones and 1 direct zone kit". They are comprised of
2 separate hydraulic manifolds (flow/return) + by-pass, ther-
mometers to read the temperatures, motorised mixing valves,
low energy consumption electro pumps and expansion boards
for electric management.
The pumps included in the kit are distinguished for being very
elastic, also thanks to the operating modes that can be pre-set. All
parts are already assembled and ready for operation exclusively
in combination with the System Manager. With the aid of the
expansions the 2 kits are governed by the System Manager during
the central heating and cooling phases.
Acquisition of the outdoor temperature from system Manager en-
ables you to select independent flow temperature curves for each
of the 2 or 3 zones of the system (both with C.H. and cooling).
Inserting these kits into the technological system enhance overall
comfort and energy savings.
KEY:
RG - Appliance return (G 3/4”)
MG - Appliance flow (G 3/4”)
V - Electrical connection
X - Holes for wall-hung installation of the kit
55
MAGIS COMBO V2
37.2 TECHNICAL DATA
The kits are supplied with circulating pumps fitted with speed - Constant head (ΔP-C)
regulator. These settings are suitable for most systems. The circulator pump maintains the pressure level (head) constant
For proper use one must select the most suitable type of oper- as the system heat demand decreases (flow rate reduction). With
ation for the system. these settings, the circulator pump is suitable for all floor systems
By rotation, it is possible to select the following pump control where all the circuits must be balanced for the same drop in head.
mode:
Fixed speed I, II, III.
Proportional head I, II, III.
Constant head I, II, III.
- Fixed speed
Adjusts the pump speed in fixed mode.
It is possible to set 3 different speeds:
I: Minimum Speed. 4 3
II: Intermediate speed.
III: Maximum speed (factory set speed).
2
- Proportional head (ΔP-V)
This allows the pressure level (head) to be proportionally reduced
as the system heat demand decreases (flow rate reduction).
Thanks to this function, the electric power consumption of the 1 5
circulator pump is reduced further: the energy (power) used by
the pump decreases according to the pressure level and flow rate.
With this setting, the pump guarantees optimal performance in
most heating systems, proving particularly suitable in single-pipe KEY:
and two-pipe installations. Any noise originating from the water 1 - Automatic vent mode operation
flow in the pipes, valves and radiators is eliminated by reducing 2 - Fixed speed operation
the head. Optimal conditions for thermal comfort and acoustic 3 - Constant head operation
well-being. 4 - Proportional head operation
5 - Functioning mode indicator LEDs
56
MAGIS COMBO V2
37.4 GRAPHS OF CIRCULATION PUMP FLOW RATE-ABSORPTION-HEAD
The kit contains an electronic low consumption circulation All pumps in the kit are suitable for operation with heat and
pump, whose flow rate/head features are shown in the graph cold carrying fluid.
below.
70 70
40 40
B
30 30
20 20
10
Speed 2 10
0 0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2300
70 70
Pump absorbed power (W)
60 60
Spee
d 7
50 50
Head (kPa)
40 40
A B
30 30
20 20
10 10
Speed 2
0 0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2300
NOTE: In case of closed by-pass cock, the available head also depends on the upstream circuit of the kit.
Starting from the available head shown in the figure, to determine the available pump head it is necessary to
subtract the head losses of the circuit upstream of the kit.
57
MAGIS COMBO V2
37.5 GRAPHS OF CIRCULATION PUMP FLOW RATE-ABSORPTION-HEAD
The kit contains an electronic low consumption circulation All pumps in the kit are suitable for operation with heat and
pump, whose flow rate/head features are shown in the graph cold carrying fluid.
below.
70 70
40 40
B
30 30
20 20
Speed
10 2 10
0 0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2300
70 70
Pump absorbed power (W)
60 60
Spe
50
e d7 50
Head (kPa)
40 40
A B
30 30
20 20
10 10
Speed 2
0 0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2300
NOTE: In case of closed by-pass cock, the available head also depends on the upstream circuit of the kit.
Starting from the available head shown in the figure, to determine the available pump head it is necessary to
subtract the head losses of the circuit upstream of the kit.
58
MAGIS COMBO V2
38 DEHUMIDIFIER
Designed to be coupled to cooling plants with radiant panels, the
dehumidifier allows to keep the percentage of relative humidity
in the room within the comfort values, preventing the possible
formation of condensate on the walls.
The dehumidifier, which is designed to be installed vertically on
the wall (recessed), has pre- and post-cooling coils.
These components allow excellent control of the air temperature
and humidity.
However, it can function without the aid of pre and post cooling
water coils, thus allowing to dehumidify when the cooling system
is off, typical of mid-season.
In compliance with European Directives, it has EC declaration
of conformity.
Dehumidification can take place:
- with neutral air: without variation of the air temperature,
dehumidifies internal rooms;
- with cooled air:contributes to cooling the rooms, as well as
reducing the internal relative humidity.
This operation can only be obtained with the System manager
and its expansions, to couple the dehumidifier directly to MA-
GIS COMBO V2, see the paragraph "MAGIS COMBO V2
management electronic functions".
1) Deumidificatore
1) Dehumidifier 2) Griglia
2) Grid 3) Frame
Telaio
Modello
Model A (mm) B (mm) C (mm)
164
1 680 545 221
2 750 660 20 140,5
36,6
40
3.1) fondobottom
3.1) Frame Telaio
59
MAGIS COMBO V2
38.2 TECHNICAL DATA
Coolant R134a
Humidity removed in neutral air condition (1) litres/24h 20.1
Cooling capacity (1) W 1250
Nominal water input l/h 150
Head losses kPa 7.8
Water supply temperature operating field °C 15 ÷ 45
work humidity field % 40 ÷ 90
Air flow rate m3/h 250
Fan useful static head (maximum speed) Pa 43
Sound pressure dB(A)
(3)
35
Sound power dB(A) 43
Power absorbed (1) W 340
Power supply V/Ph/Hz 230/1~/50
Maximum power absorbed W (2)
450
Nominal current absorbed (1) A 2.5
Maximum current absorbed (2) A 2.8
Hydraulic F-R connections 1/2"F
Weight kg 38
45
40
35
30
25
Head losses (kPa)
20
15
10
0
100 150 200 250 300 350 400
Flow rate l/h
60
MAGIS COMBO V2
39 OPTIONAL FOR DIRECT COUPLING TO MAGIS COMBO V2 / COMBO PLUS V2
*Device class (REF. Communication of the European Commission 2014/C 207/02 ) with factory settings.
62
MAGIS COMBO V2
41 MAIN INERTIAL STORAGE TANK TECHNICAL FEATURES
TECHNICAL DATA:
Max. operating temperature = 90 °C
Max. operating pressure = 3 bar
Effective capacity = 77 litres
Full weight = 95 kg
Insulating thermal conductivity +20 °C = 0,038
W/(m•K)
No.4 G 1” side connections
63
MAGIS COMBO V2 Indoor Unit
MAGIS COMBO PLUS V2 indoor unit
Local unit
EU DECLARATION OF CONFORMITY
(N.800520/UE)
This declaration of conformity is issued under the exclusive responsibility of the manufacturer.
CONDENSING UNIT
The purpose of the above declaration complies with the relevant Union harmonisation legislation:
Reference to the relevant harmonised standards or references to the other technical specifications in relation
to which conformity is declared:
The control logic of a MAGIS COMBO V2 systems, establishes The diagram below shows the winter heating operation via the
various operating situations described below: Heat Pump (1).
In these conditions, the condensation generator (2) may simul-
CENTRAL HEATING MODE taneously activate to heat the D.H.W.
When operating in winter heating mode the switching logic
between condensation generator and Heat Pump circuit can be
selected between 2 options:
66
MAGIS COMBO V2
If the Heat Pump (1) is unable to bring the system to temperature
within a certain time, the condensation generator (2) activates
(see diagram below) and the Heat Pump is disabled.
67
MAGIS COMBO V2
COOLING MODE
During the summer season only the Heat Pump (1) will operate
the system circuit.
It occurs through the activation of the cooling circuit, according
to the diagram below.
68
MAGIS COMBO V2
D.H.W. MODE
In Instant MAGIS COMBO V2 the D.H.W. is heated by the
condensation generator (2) (obviously because of exchanged
power).
The Instant MAGIS COMBO V2 can be coupled with a separate
storage tank unit, by connection in series: this also takes advan-
tage of the Thermal Solar Systems as Renewable Energy Source
(RES), to supplement the production of D.H.W.
Or you can use a heat pump water heater (e.g. RAPAX), to
supplement the production of D.H.W., again to exploit the RES.
69
MAGIS COMBO V2
D.H.W. MODE + COOLING MODE
Given that in the Instant version it is the condensation generator
(2) to ensure the production of D.H.W., in the summer the
Heat Pump (1) can simultaneously activate to ensure cooling
the rooms.
70
MAGIS COMBO PLUS V2
43 MAGIS COMBO PLUS V2 OPERATING PRINCIPLES
71
MAGIS COMBO PLUS V2
If the Heat Pump (1) is unable to bring the system to temperature
within a certain time, the condensation generator (2) activates
(see diagram below) and the Heat Pump is disabled.
72
MAGIS COMBO PLUS V2
COOLING MODE
During the summer season only the Heat Pump (1) will operate
the system circuit.
It occurs through the activation of the cooling circuit, according
to the diagram below.
73
MAGIS COMBO PLUS V2
D.H.W. MODE
In D.H.W. operation, the condensation generator and Heat The Heat Pump (1) is enabled and starts to work at a flow tem-
Pump work on a single boiler flow/return circuit. perature of +10°C with respect to the DHW set (e.g. DHW set
At operating logic level, you can choose between 2 options on 45°C, the Heat Pump goes to the flow of 55°C), of course if the
parameter I 08 from the INTEGRATION MENU: Heat Pump (1) is not able to bring the domestic hot water to
I 08 = Simultaneous D.H.W. = OFF; temperature within a specific time, or if a domestic hot water
I 08 = Simultaneous D.H.W. = ON. set value greater than 55 °C is set, the condensing generator (2)
is activated (see next figure).
When setting OFF, in case of simultaneous system and D.H.W. The logic for activating the generators (AUTO mode) based
request, the D.H.W. has priority; only one generator works on the outdoor temperatures also applies to operation in the
(based on outdoor temperature and time of integration) - the DHW mode.
following example shows operation with Heat Pump (1).
This setting is suitable, for example, for high inertia ai condi-
tioning systems (e.g. radiant panels); it also favours the energy
performances of the machine, making appropriate use of the
Heat Pump (1) for domestic hot water.
74
MAGIS COMBO PLUS V2
Whereas, by setting parameter I 08 from the INTEGRATION
MENU:
I 08 = Simultaneous D.H.W. = ON, in case of simultaneous
system and D.H.W. request, both requests are run together (both
generators will be active).
In case of simultaneous request, this favours the operation of
the condensation generator (2) for D.H.W. (the water circulates
according to the following diagram).
This mode is useful, for example, with low inertia air condition-
ing systems (e.g. fan coils).
75
MAGIS COMBO PLUS V2
D.H.W. MODE + COOLING MODE
Example of operation by setting parameter I 08 from the IN-
TEGRATION MENU:
I 08 = Simultaneous D.H.W. = ON, in the summer in cooling
mode: The condensation generator (2) ensures the production
of D.H.W.;
The Heat Pump (1) cools the rooms.
76
MAGIS COMBO V2
44 OPERATING PRINCIPLES: ACTIVATION LOGIC
OPERATION IN ROOM CENTRAL HEATING MODE: NOTE: Based on the outdoor temperature, if MAGIS COMBO V2
Following a request during the room heating mode, the elec- requires a flow temperature higher than 65 °C, the condensation
tronics decide, according to the external temperature, whether generator is directly activated.
to activate the heat pump, or (with cold outdoor temperatures) * The heat pump will then restart, thereby creating an alternating
the condensation generator. mechanism between the two generators.
Set Risc
Max
Funzionamento
Exclusive heat generator
55
65 °C esclusivo
operation
del
generatore termico
Funzionamento Funzionamento
pompa di calore pompa di calore
Heat pump operation Heat pump operation
Se dopo il tempo di Se dopo il tempo di
If after activation time the set If attivazione
after activationmoltiplicato
time multiplied
attivazione non si
temperature is not reached the by 2 the set temperature is not
raggiunge la temperatura
heat generator starts * per 2 non si
reached the heat raggiunge
generator
impostata parte la temperaturastarts*impostata
il generatore termico * parte il
generatore termico *
Min Temp
External temp
-15 Te1 Te2 25 esterna
Values Te1 and Te2 are determined by the logic of the P.C.B.
(Setting the manual mode "I 05" = "MA" the "Te1" value matches "I 10" and the
"Te2" value corresponds to "I 10" + 5 °C)
77
MAGIS COMBO V2
Outdoor temperatures that determine the activation logic of the generators (AUTO mode).
16 Central heating
flow set point Test 1 Test 2
heat pump
14
Set < 35 °C 0°C 5 °C
12 from 0 to 10°C from 5 to 15°C
35 < Set < 55 °C
linearly linearly
Test 2
Outside temperature
10
6
Test 1
4
0
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65
The MAGIS COMBO V2 menu contains - among others - the PAR. I 05 - Integration activation mode - (AU - MA settable,
INTEGRATION MENU with the following parameters: default value AU). Establishes when to activate the condensation
generator, in “MA” mode (manual) it is activated an a fixed
INTEGRATION MENU external temperature and is equivalent to the value set with
parameter "I 06", in “AU” mode (automatic) the condensation
Id Parameter Range Default
generator is activated according to the operating conditions.
System integration
I 02 OFF - AL AL
enabling PAR. I 07 - Activation band - (settable from 0°C ÷ 10°C,
Central heating 1 - 255 minutes default value 4°C). It is a hysteresis that is used to establish the
I 04 30
max. wait time (1 minute steps) achievement of the heating set-point, avoiding the activation of
Integration activation the condensation generator.
I 05 AU - MA AU
mode
I 07 Activation band 0 - 10 °C 4 PAR. I 08 - Simultaneous D.H.W. (settable ON - OFF, default
Simultaneous value ON).
I 08 OFF - ON ON
D.H.W. Enables the simultaneous operation in D.H.W. mode and room
System manual acti- air conditioning mode.
I 10 -25 - +35 °C 2 °C For instant MAGIS COMBO V2 the simultaneousness is always
vation temperature
guaranteed regardless of what is set.
PAR. I 02 - System integration enabling - (settable AL - OFF,
default value AL). Using this function, you can enable the con- PAR. I 10 - System manual activation temperature - (settable
densation generator operation (A) to integrate thermal system from -25°C ÷ +35°C, default value +2°C).
central heating. Establishes the outdoor temperature under which the central
N.B.: With OFF Mode, always and only the Heat Pump will run, heating condensation generator is enabled.
even in case of Heat Pump block, the condensation generator
does NEVER activates for system integration. It is possible to also use MAGIS COMBO V2 only as heat gener-
ator (if AUDAX PRO V2 is installed at a later time), setting the
PAR. I 04 - Central heating max. wait time - (settable from “A11” parameter at OFF. The management logic now becomes
1 - 255 minutes, default value 30 minutes). Establishes the totally similar to that of a “normal” condensation generator.
reference time of the activation and deactivation timing of the
central heating integration.
78
MAGIS COMBO V2
45 INTRODUCTION WITH COMMENTARY TO THE DIAGRAMS: MAIN APPLICATIONS
46-46.1 Diagram with MAGIS COMBO V2 (instant) and 2 zone kit (1 direct and 1 mixed) + Thermal Solar System
Description of winter functioning:
- CH phase active:
One or more room sensors activate the consent during the winter phase.
When operating in winter heating mode the switching logic between condensation generator and heat pump circuit can be selected
between 2 options:
1) With variable external switching temperature according to the flow temperature (“AUTO” mode);
2) With fixed external switching temperature (“MANUAL” mode).
If the heat pump is unable to bring the system to temperature within a certain time, the condensation generator activates.
The logic of intelligent activation of the generators (heat pump and condensation generator) is integrated in the MAGIS COMBO V2
electronics.
- DHW phase:
In Instant MAGIS COMBO V2 the D.H.W. is heated by the boiler (obviously because of exchanged power).
The diagram shows the coupling of a separate storage tank unit, by connection in series: this also takes advantage of the Solar as
RES, to supplement the production of D.H.W.
47-47.1 Diagram with MAGIS COMBO PLUS V2 and 2 zone kit (1 direct and 1 mixed) + Photovoltaic
Description of winter functioning:
- Central heating mode active:
One or more room sensors activate the consent during the winter phase.
When operating in winter heating mode the switching logic between condensation generator and heat pump circuit can be selected
between 2 options:
1) With variable external switching temperature according to the flow temperature (“AUTO” mode);
2) With fixed external switching temperature (“MANUAL” mode).
If the heat pump is unable to bring the system to temperature within a certain time, the condensation generator activates.
The logic of intelligent activation of the generators (heat pump and condensation generator) is integrated in the
MAGIS COMBO PLUS V2 electronics.
- DHW phase:
In D.H.W. operation, condensation generator and heat pump work on a single boiler flow/return circuit.
At operating logic level, you can choose between 2 options:
1) SIMULTANEOUS D.H.W. = OFF (standard);
2) SIMULTANEOUS D.H.W. = ON.
Leaving OFF, in case of simultaneous system and D.H.W. request, the D.H.W. has priority; only one generator works (based on
outdoor temperature and time of integration).
This setting is suitable for high inertia air conditioning system (e.g. radiant floor panels).
- Photovoltaic contact:
If the photovoltaic contact (contact “S 39”) is closed, the minimum convenience outdoor temperature (automatically) is temporarily
set to -25°C and the condensation generator is forced off; only the maximum operating time remains active.
If no system requests are in progress, the system forces the heating of a storage tank for the production of DHW at maximum
storage temperature (if the storage tank is present e.g. MAGIS COMBO PLUS V2), then resumes any system requests occurred
in the meantime.
79
80
46
KEY: A - MAGIS COMBO V2 condensing unit supply voltage
1 - MAGIS COMBO V2 (inclusive of external probe) B - MAGIS COMBO V2 indoor unit supply voltage
2 - Separate storage tank unit UB INOX SOLAR 200 V2 C - UB INOX SOLAR 200 V2 supply voltage
inclusive of:
solar circulation unit
solar expansion vessel
thermostatic mixing valve
solar adjustment control unit
3 - NTC probe for Storage Tank Unit bottom part
(standard with UB INOX SOLAR 200 V2)
4 - Solar inlet probe (to be placed inside the MAGIS COMBO V2)
5 - Flat solar collectors
6 - Solar collector probe PT1000
(standard with UB INOX SOLAR 200 V2)
7 - Thermal flywheel (to be sized)
8 - Kit 2 zones (for coupling to MAGIS COMBO V2)
9 - Zone remote panel
10 - ModBus temperature/humidity sensor
11 - CRONO 7
Water-DHW mains
HYDRAULIC DIAGRAM: MAGIS COMBO V2 (INSTANT)
+ KIT 2 ZONES (1 DIRECT AND 1 MIXED) + THERMAL SOLAR SYSTEMS
NOTE: this diagram is an example. It is also required to convey the condensate drain of the heat pump and condensation generator.
In order to guarantee proper Heat Pump operation, each system must consider inserting a bypass to guarantee a minimum flow rate of 500 l/h.
MAGIS COMBO V2
MAGIS COMBO V2
46.1 WIRING DIAGRAM: MAGIS COMBO V2 (INSTANT)
+ KIT 2 ZONES (1 DIRECT AND 1 MIXED) + THERMAL SOLAR SYSTEMS
NOTE: please note that, in a setting without room ther- BUS communication
mostats, in order to meet the requirements coming from connection Indoor unit
OUTDOOR UNIT with Outdoor unit.
Zone remote panel, it is necessary to keep the jumper
AWG 20/22 type shielded
[X40-1] on terminals 40-1 and 41-1. cable
A32-1 A17-2
S 20-2
Zone 1 Zone 2
MAGIS
MAGIS COMBO
COMBO V2
Brown
Blue Yellow Power supply
Blue
Brown 230 Vac
Yellow
50Hz
Blue Green
White
Green
Orange
Purple
Blue
Brown Red
MAGIS COMBO V2 TERMINAL BOARD KEY:
Blue Red
Brown
A16-1 - Dehumidifier zone 1
A16-2 - Dehumidifier zone 2
A17-2 - Zone 2 ModBus humidity sensor
A32-1 - Zone 2 remote panel
A19 - 2-relay board
B9 - Solar inlet probe
SOLAR CONTROL UNIT KEY: B3-2 - Zone 2 mixed flow probe
A12 - Solar management control unit M10-1 - Zone 1 circulator pump
B2 - NTC DHW probe (not used) M10-2 - Zone 2 circulator pump
B11 - Solar collector probe PT1000 M31-2 - Zone 2 mixing valve
B12 - Solar storage tank probe NTC S20-1 - CRONO 7
B19 - Domestic inhibition probe NTC F1/F2 (ODU) - AUDAX PRO V2 communication Bus
(not used)
M6 - Solar circuit pump
R8 - Storage tank resistance NOTE: To control the 2 dehumidifiers provide the 2-relay
(not used) board kit (A19) (optional) code 3.026302.
When using the ModBus temperature and humidity sen-
sor kit (code 3.030992), in order to make temperature
requests it is necessary to match a room thermostat in
the zone as it is not possible to set the room set directly
from the control panel.
81
82
47
KEY:
1 - MAGIS COMBO PLUS V2 (inclusive of external probe)
2 - Photovoltaic inverter (with production outlet contact)
3 - Photovoltaic Panels
4 - Thermostatic mixing valve
5 - INOXSTOR V2 storage tank unit
6 - NTC probe for storage tank unit
7 - DHW inlet safety unit (not supplied)
8 - Thermal flywheel (to be sized)
9 - Kit 2 zones (for coupling to MAGIS COMBO PLUS V2)
10 - CRONO 7
11 - Zone remote panel
Water-DHW
+ KIT 2 ZONES (1 DIRECT AND 1 MIXED) + PHOTOVOLTAIC
mains
NOTE: this diagram is an example. It is also required to convey the condensate drain of the heat pump and condensation generator.
In order to guarantee proper Heat Pump operation, each system must consider inserting a bypass to guarantee a minimum flow rate of 500 l/h.
MAGIS COMBO PLUS V2
MAGIS COMBO PLUS V2
47.1 WIRING DIAGRAM: MAGIS COMBO PLUS V2
+ KIT 2 ZONES (1 DIRECT AND 1 MIXED) + PHOTOVOLTAIC
OUTDOOR UNIT
NOTE: please note that, in a setting without room ther-
mostats, in order to meet the requirements coming from BUS communication
the Zone Remote panel, it is required to bridge [X40-2] connection Indoor unit
on terminals 40-2 and 41-2. with Outdoor unit.
AWG 20/22 type shielded
cable
A32-2 S 39
S 20-1
Zone 2
MAGIS
MAGIS COMBO V2
PLUS V2
KEY:
A16-2 - Dehumidifier zone 2 NOTE: To control the 2 dehumidifiers provide the 2-relay
A32-2 - Zone 2 remote panel board kit (A19) (optional) code 3.026302.
A19 - 2-relay board When using the ModBus temperature and humidity sen-
B2 - Storage tank temperature probe
sor kit (code 3.030992), in order to make temperature
B3-2 - Zone 2 mixed flow probe
M10-1 - Zone 1 circulator pump
requests it is necessary to match a room thermostat in
M10-2 - Zone 2 circulator pump the zone as it is not possible to set the room set directly
M31-2 - Zone 2 mixing valve from the control panel.
S20-1 - CRONO 7
S39 - Photovoltaic inlet contact
F2/F1 (ODU) - AUDAX PRO V2 communication Bus
83
MAGIS COMBO PLUS V2 RECESSED
APPENDIX B): MAGIS COMBO PLUS V2 RECESSED
Recessed solution ideal for new buildings achieving high energy • Hydronic kit for MAGIS COMBO PLUS V2 recessed;
classes, it allows to recover living space thanks to the retractable • Additional 2nd mixed zone kit for MAGIS COMBO PLUS V2
installation. recessed (optional);
The complete system consists of separate units that can be pur- • Zone hydraulic connections kit for vertical, horizontal or rear
chased separately and installed at different times: outlet (optional);
• SOLAR CONTAINER COMBO (Recess frame); • Air intake and flue exhaust kit (optional);
• MAGIS COMBO PLUS V2 in its various power; • Solar system coupling kit (optional).
INSTALLABLE MODELS:
1) MAGIS COMBO 4 PLUS V2 code 3.030615
2) MAGIS COMBO 4 PLUS V2 LPG
code 3.030615LPG
3) MAGIS COMBO 6 PLUS V2 code 3.030617
4) MAGIS COMBO 6 PLUS V2 LPG
code 3.030617LPG
5) MAGIS COMBO 9 PLUS V2 code 3.030619
6) MAGIS COMBO 9 PLUS V2 LPG
code 3.030619LPG
84
MAGIS COMBO PLUS V2 RECESSED
48.1 SOLAR CONTAINER COMBO RECESSED FRAME DIMENSIONS CODE 3.028187
A B
C C B B C C
THERMAL SOLAR
Right SYSTEMS CIRCUIT
CONNECTING BRACKET
Left
side side
OUTDOOR UNIT
box box
CONNECTION
INERTIAL STORAGE
TANK
CONNECTION
85
MAGIS COMBO PLUS V2 RECESSED
48.2 50-LITRE RECESSED INERTIAL STORAGE TANK KIT INSTALLATION
CODE 3.027709 ON THE TOP OF THE COMBO SOLAR CONTAINER
NOTE: With the installation of the inertial storage tank in the upper part of the recessed frame, it is NOT possible to exit with
the flue from the upper part of the frame, the pre-section on the LEFT side can only be used for flue exhaust with separator
Ø 80/80, suction can take place on the right/rear or front side. The connection of the solar thermal pipes must also be done
only on the right or left and NOT on the upper part.
N.B.: Remove
the pre-sections
to allow pipe
passage
86
MAGIS COMBO PLUS V2 RECESSED
48.3 50-LITRE RECESSED INERTIAL STORAGE TANK KIT INSTALLATION
CODE 3.027709 ON THE SIDE OF THE COMBO SOLAR CONTAINER
N.B.: Remove
the pre-sections
to allow pipe
passage
87
MAGIS COMBO PLUS V2 RECESSED
48.4 SOLAR CONTAINER COMBO RECESSED FRAME CONNECTIONS
REAR CONNECTION
NOTE: For the hydronic kit code 3.027867 use the
Rear connection unit kit - code 3.020630
connections highlighted with the red arrow.
Flow Ist zone Return Ist zone Hot Outlet Cold Input
3.027867
MZ1 RZ1 AC AF
3/4" 3/4" 1/2" 1/2"
88
MAGIS COMBO PLUS V2 RECESSED
48.5 HYDRONIC KIT FOR MAGIS COMBO PLUS RECESSED CODE 3.027867
The above kits are the main ones; additional accessories are avail-
able to complete the installation (see section on optional kits).
89
MAGIS COMBO PLUS V2 RECESSED
48.6 ADDITIONAL 2ND MIXED ZONE KIT FOR MAGIS COMBO PLUS CODE 3.027865
90
MAGIS COMBO PLUS V2 RECESSED
48.7 MAGIS COMBO PLUS AND HYDRONIC KIT ELECTRICAL WIRING
10 8
11
9
14
91
MAGIS COMBO PLUS V2 RECESSED
48.8 MAIN COMPONENTS MAGIS COMBO PLUS WITH 2nd ADDITIONAL ZONE KIT
KEY:
1 - Storage tank draining cock / tap
2 - Sacrificial anodes
3 - Solar probe (optional)
4 - 8 bar safety valve
5 - DHW (Domestic hot water)
vessel interception cock
6 - Storage tank flange
7 - Antifreeze thermostat
8 - Antifreeze kit connection box
9 - 8 l domestic hot water expansion
vessel
10 - One-way valve
11 - Heat pump probe
12 - Storage tank
13 - MAGIS COMBO PLUS V2
indoor unit
14 - DHW circuit mixing valve
15 - Manifold draining valves
16 - Hydraulic manifold
17 - 3-way Mixing valve (*)
18 - Direct zone pump
19 - Safety thermostat (*)
20 - Zone 2 flow probe (low temper-
ature) (*)
21 - Mixed zone pump (*)
22 - Zone 2 flow temperature ther-
mometer (low temperature) (*)
23 - Zone 1 flow temperature ther-
mometer (high temperature)
(*) the following components are only present when including the additional second mixed zone kit (optional).
92
MAGIS COMBO PLUS V2 RECESSED
48.9 HYDRAULIC DIAGRAM MAGIS COMBO PLUS WITH 2nd ADDITIONAL ZONE KIT
KEY:
1 - Storage tank
2 - Condensing unit
3 - Hydraulic manifold
4 - Manifold draining valves 13 - Antifreeze thermostat
5 - 8 L DHW expansion vessel 14 - Storage tank draining cock / tap
6 - MAGIS COMBO PLUS V2 indoor unit 15 - DHW (Domestic hot water) vessel interception cock
7 - Mixing valve filter 16 - 3-way Mixing valve
8 - DHW circuit mixing valve 17 - Safety thermostat
9 - Heat pump probe 18 - Mixed zone pump / circulator
10 - Direct zone pump 19 - Low temperature system flow probe
11 - One-way valve 20 - Inertial storage tank (optional kit)
12 - 8 bar safety valve 21 - Flexible connection pipes (optional kit)
93
MAGIS COMBO PLUS V2 RECESSED
48.10 CHART OF THE HEAD FLOW RATE AVAILABLE TO THE DIRECT ZONE
Downstream of the hydraulic compensator, part of the hydron- in the graphs below.
ic kit of the MAGIS COMBO PLUS recessed system code The flow circulator to the direct zone is suitable for both central
3.027867 inserted in SOLAR CONTAINER COMBO, there heating and cooling operation.
is a low consumption electronic booster pump to the system for The use of these pumps prevents the insertion/presence of any
the direct zone, whose flow rate/head characteristics are shown by-pass.
Spe
Speed MIN
.
Sp
e
Pump absorbed power (W)
ed
M
AX
.
Head (kPa)
A B
Speed MIN
.
94
MAGIS COMBO PLUS V2 RECESSED
48.11 CHART OF THE HEAD FLOW RATE AVAILABLE TO THE MIXED ZONE (OPTIONAL)
The additional 2nd mixed zone kit code 3.027865, contains a The flow circulator to the mixed zone is suitable for both central
low consumption electronic booster pump to the system for the heating and cooling operation.
mixed zone, whose flow rate/head characteristics are shown in The use of these pumps prevents the insertion/presence of any
the graphs below. by-pass.
Spe
Speed MIN.
Spe
Pump absorbed power (W)
e dM
AX
.
Head (kPa)
A B
Speed MIN.
95
MAGIS COMBO PLUS V2 RECESSED
48.12 SYSTEM FLOW CIRCULATOR PUMP SETTINGS AND CONFIGURATIONS
The circulator pumps control the room heating or cooling - Proportional head (ΔP-V)
requests downstream of the hydraulic manifold. In fact, the This allows the pressure level (head) to be proportionally reduced
circulator pumps are equipped with electronic control that as the system heat demand decreases (flow rate reduction).
allows to set advanced functions. These settings are suitable for Thanks to this function, the electric power consumption of the
most systems. circulator pump is reduced further: the energy (power) used by
For proper use one must select the most suitable type of oper- the pump decreases according to the pressure level and flow rate.
ation for the system. With this setting, the pump guarantees optimal performance in
By rotation, it is possible to select the following pump control most heating systems, proving particularly suitable in single-pipe
mode: and two-pipe installations. Any noise originating from the water
Fixed speed I, II, III. flow in the pipes, valves and radiators is eliminated by reducing
Proportional head I, II, III. the head. Optimal conditions for thermal comfort and acoustic
Constant head I, II, III. well-being.
KEY:
4 3 1 - Automatic vent mode operation
2 - Fixed speed operation
3 - Constant head operation
4 - Proportional head operation
2 5 - Functioning mode indicator LEDs
1 5
NOTE:
Treating the feed water allows you to prevent problems and maintain the function and efficiency of the generator over time. It.Leg-
islative Decree 26/06/2015 requires a chemical treatment of the thermal system water, in compliance with the UNI 8065 standard,
in the cases provided for by the Decree.
96
MAGIS COMBO PLUS V2 RECESSED
48.13 PRODUCT FICHE (REGULATION 811/2013)
Unità
"!! Bollitore TRIO V2
A+
A
B
C C
D
E
F
67 W
151 L
2017 812/2013
6.2. Contribution to temperature controls of seasonal space heating energy efficiency of packages of space heaters, temperature
control and solar devices or of packages of combination heaters, temperature control and solar devices
97
MAGIS COMBO PLUS V2 RECESSED
48.14 TECHNICAL DATA MAGIS COMBO PLUS RECESSED
OPTIONAL components but required to make the MAGIS COMBO PLUS recessed system Code
SOLAR CONTAINER COMBO (Recessed frame) 3.028187
MAGIS COMBO 4 PLUS V2 3.030615
MAGIS COMBO 4 PLUS V2 LPG 3.030615 LPG
MAGIS COMBO 6 PLUS V2 3.030617
MAGIS COMBO 6 PLUS V2 LPG 3.030617 LPG
MAGIS COMBO 9 PLUS V2 3.030619
MAGIS COMBO 9 PLUS V2 LPG 3.030619 LPG
Hydronic kit for MAGIS COMBO PLUS IN SOLAR CONTAINER COMBO 3.027867
Additional 2nd mixed zone kit for MAGIS COMBO PLUS (additional for two-zone system solutions) 3.027865
TEMPERATURE CONTROL OPTIONALS available Code
Zone remote panel - (device class V* or VI) 3.030863
CRONO 7 (Digital weekly chrono-thermostat) - (device class IV* or VII) 3.021622
CRONO 7 WIRELESS (device class IV* or VII) 3.021624
External probe - if the condensing unit is installed under unfavourable conditions (device class II* or VI or VII) 3.015266
Room hygrostat kit - (operates on the Dehumidifier according to the humidity detected in the room and
3.023302
according to what is set on the device)
Temperature and humidity sensor kit ModBus - (device class V or VI*) - to make temperature requests, it is
3.030992
necessary to couple a chrono-thermostat code 3.021622 or 3.021624
OTHER OPTIONALS available Code
Vertical connection unit kit for lower connection 3.020575
Horizontal connection unit kit for side connection 3.020574
Rear connection unit kit for rear connection 3.020630
Three-way deviator valve kit used as hot/cold system deviator 3.020632
Configurable relay board kit 3.015350
Two relay board kit (for dehumidifier management) 3.026302
Dehumidifier kit - for recessed installation only 3.021529
Dehumidifier frame kit 3.022146
Dehumidifier grid kit 3.022147
Condensate antifreeze heating cable kit (for outdoor unit 4 - 6 V2) 3.027385
Antifreeze resistance kit up to -15 °C (for heat generator) 3.017324
Wall installation brackets kit for outdoor condensing unit 3.022154
Solar thermal system coupling kit** 3.024719
Inertial 50-litre recessed storage tank kit 3.027709
DHW recirculation kit (1) (including circulator pump) 3.026169
Polyphosphate dispenser kit (1) 3.020628
Safety thermostat kit 3.013794
Propane air kit 3.027664
HYDRO 3 range Wall-hung hydronic split, HYDRO FS range floor standing hydronic fan coil, HYDRO Codes
IN range recessed hydronic fan coil various
*Device class (REF. Communication of the European Commission 2014/C 207/02 ) with factory settings.
** In case of application with solar heating, as well as Kit code 3.024719, the solar heating components on the list are available.
We recommend using flat solar manifolds.
(1) The DHW recirculation Kit and the polyphosphate dispenser kit CANNOT coexist together within the SOLAR CONTAINER
COMBO.
99
MAGIS COMBO PLUS V2 RECESSED
48.16 MAGIS COMBO PLUS RECESSED SYSTEM DIAGRAM SYSTEM WITH ONE
RADIANT PANEL HEATING ZONE + ONE COOLING AND HEATING
ZONE WITH HYDRONIC SPLITS
KEY:
1 - MAGIS COMBO PLUS hydronic kit 6 - Solar thermal system coupling kit
2 - MAGIS COMBO PLUS V2 indoor unit 7 - Solar collector
3 - AUDAX PRO V2 Condensing unit 8 - Recess inertial storage tank
4 - Zone Remote panel 9 - HYDRO wall-hung hydronic split
5 - DHW probe (standard with Hydronic kit)
100
MAGIS COMBO PLUS V2 WITH BASIC MAGIS PRO
APPENDIX C): MAGIS COMBO PLUS V2 WITH BASIC MAGIS PRO
49 MAGIS COMBO PLUS V2 WITH BASIC MAGIS PRO IN SOLAR CONTAINER COMBO
Recessed solution, ideal for high energy class and small apart- • BASIC MAGIS PRO package with 160 litre DHW tank in
ments, it allows the recovery of living space thanks to the Stainless steel;
retractable installation. • MAGIS COMBO PLUS application kit with BASIC MAGIS
The complete system consists of separate units that can be pur- PRO;
chased separately and installed at different times: • Hydraulic connections kit for vertical, horizontal or rear outlet
• SOLAR CONTAINER COMBO (Recess frame); (optional);
• MAGIS COMBO PLUS V2 in its various power; • Solar system coupling kit (optional).
INSTALLABLE MODELS:
1) MAGIS COMBO 4 PLUS V2 code 3.030615
2) MAGIS COMBO 4 PLUS V2 LPG
code 3.030615LPG
3) MAGIS COMBO 6 PLUS V2 code 3.030617
4) MAGIS COMBO 6 PLUS V2 LPG
code 3.030617LPG
5) MAGIS COMBO 9 PLUS V2 code 3.030619
6) MAGIS COMBO 9 PLUS V2 LPG
code 3.030619LPG
101
MAGIS COMBO PLUS V2 WITH BASIC MAGIS PRO
49.1 MAIN COMPONENTS MAGIS COMBO PLUS V2 WITH BASIC MAGIS PRO
KEY:
1 - Storage tank draining cock / tap
2 - Sacrificial anodes
3 - Solar probe (optional)
4 - 8 bar safety valve
5 - DHW (Domestic hot water)
vessel interception cock
6 - Storage tank flange
7 - Antifreeze thermostat
8 - Antifreeze kit connection box
9 - 8 l domestic hot water expan-
sion vessel
10 - DHW probe
11 - Storage tank
12 - MAGIS COMBO PLUS V2
indoor unit
13 - Circuit mixing valve
domestic hot water
14 - By-pass
15 - Zone 1 flow temperature ther-
mometer (direct zone)
16 - Gas cock
17 - One-way valve
102
MAGIS COMBO PLUS V2 WITH BASIC MAGIS PRO
49.2 RECESS MAGIS COMBO PLUS V2 WITH BASIC MAGIS PRO SYSTEM DIAGRAM:
SYSTEM WITH HEATING AND COOLING WITH HYDRONIC SPLITS
NOTE: this diagram is an example. It is also required to convey the outdoor condensing unit condensate drain.
KEY:
1 - BASIC MAGIS PRO system composed of: 4 - AUDAX PRO thermal condensing unit
• Double coil 160 litre storage tank 5 - 15-Litre inertial storage kit 3.029928
• Hydronic unit and connection unit 6 - DHW probe
2 - MAGIS COMBO PLUS V2 indoor unit 7 - SOLAR CONTAINER COMBO
3 - Zone remote panel 8 - HYDRO wall-hung hydronic split
103
MAGIS COMBO PLUS V2 WITH BASIC MAGIS PRO
49.3 OPTIONAL MAGIS COMBO PLUS V2 WITH BASIC MAGIS PRO
OPTIONAL components but necessary to make the BASIC MAGIS PRO system Code
SOLAR CONTAINER COMBO (Recessed frame) 3.028187
BASIC MAGIS PRO Pack 3.029721
MAGIS COMBO PLUS application kit with BASIC MAGIS PRO 3.029947
MAGIS COMBO 4 PLUS V2 3.030615
MAGIS COMBO 4 PLUS V2 LPG 3.030615 LPG
MAGIS COMBO 6 PLUS V2 3.030617
MAGIS COMBO 6 PLUS V2 LPG 3.030617 LPG
MAGIS COMBO 9 PLUS V2 3.030619
MAGIS COMBO 9 PLUS V2 LPG 3.030619 LPG
TEMPERATURE CONTROL OPTIONALS available for the BASIC MAGIS PRO system Code
Zone remote panel - (device class V* or VI) 3.030863
Temperature and humidity sensor kit ModBus - (device class V or VI*) - to make temperature requests, it is
3.030992
necessary to couple a chrono-thermostat code 3.021622 or 3.021624
CRONO 7 (Digital weekly chrono-thermostat) - (device class IV* or VII) 3.021622
CRONO 7 WIRELESS (device class IV* or VII) 3.021624
External probe - if the condensing unit is installed under unfavourable conditions (device class II* or VI or VII) 3.015266
Room hygrostat kit - (operates on the Dehumidifier according to the humidity detected in the room and
3.023302
according to what is set on the device)
OTHER OPTIONALS available for the BASIC MAGIS PRO system Code
Antifreeze resistance kit up to -15 °C for hydronic module 3.017324
Vertical connection unit kit for lower connection 3.020575
Horizontal connection unit kit for side connection 3.020574
Rear connection unit kit for rear connection 3.020630
Three-way deviator valve kit used as hot/cold system deviator 3.020632
Configurable relay board kit 3.015350
Two relay board kit (for dehumidifier management) 3.026302
Dehumidifier kit - for recessed installation only 3.021529
Dehumidifier frame kit 3.022146
Dehumidifier grid kit 3.022147
Condensate antifreeze heating cable kit (for outdoor unit 4 - 6 V2) 3.027385
Wall installation brackets kit for outdoor condensing unit 3.022154
Solar thermal system coupling kit** 3.024719
15-litre inertial storage kit for BASIC MAGIS PRO (it ONLY can be inserted in SOLAR CONTAINER) 3.029928
Inertial 50-litre recessed storage tank kit 3.027709
DHW recirculation kit(1) (including circulator pump) 3.026169
Polyphosphate dispenser kit(1) 3.020628
Safety thermostat kit 3.019229
DOMINUS Interface board kit 3.026273
HYDRO 3 range Wall-hung hydronic split, HYDRO FS range floor standing hydronic fan coil, HYDRO Codes
IN range recessed hydronic fan coil various
*Device class (REF. Communication of the European Commission 2014/C 207/02 ) with factory settings.
** In case of application with solar heating, as well as Kit code 3.024719, the solar heating components on the list are available.
We recommend using flat solar manifolds.
(1) The DHW recirculation Kit and the polyphosphate dispenser kit CANNOT coexist together within the SOLAR CONTAINER
COMBO.
104
MAGIS COMBO PLUS V2 WITH SUPER TRIO
APPENDIX D): MAGIS COMBO PLUS V2 WITH SUPER TRIO
50 MAGIS COMBO PLUS V2 WITH SUPER TRIO IN CONTAINER FOR SUPER TRIO
SUPER TRIO is the solution for new buildings, designed to build and saves living space thanks to the specific recessed CONTAINER.
hybrid systems or with heat pump only in large apartments and vil- The complete system consists of separate units that can be purchased
las, to easily meet the obligations on the use of renewable energy in separately and installed at different times:
new systems and major renovations; ideal in those situations where • SOLAR CONTAINER for SUPER TRIO (Recessed frame);
you have to cope with the need for a lot of hot water (e.g. whirlpool • DOMUS CONTAINER for SUPER TRIO (Technical cabinet);
baths) or where you expect more simultaneous withdrawals, thanks • SUPER TRIO pack;
to a DHW storage of 250 litres. • MAGIS COMBO PLUS V2 in its various power;
The system can be built with extreme flexibility and with great ease • MAGIS COMBO PLUS connection kit with SUPER TRIO;
of installation in recessed or technical cabinet, the SUPER TRIO • 2nd additional mixed zone kit (optional);
hydronic unit in fact integrates into the structures of the building • Solar system coupling kit (optional).
INSTALLABLE MODELS:
1) MAGIS COMBO 4 PLUS V2 code 3.030615
2) MAGIS COMBO 4 PLUS V2 LPG
code 3.030615LPG
3) MAGIS COMBO 6 PLUS V2 code 3.030617
4) MAGIS COMBO 6 PLUS V2 LPG
code 3.030617LPG
5) MAGIS COMBO 9 PLUS V2 code 3.030619
6) MAGIS COMBO 9 PLUS V2 LPG
code 3.030619LPG
105
MAGIS COMBO PLUS V2 WITH SUPER TRIO
50.1 MAIN COMPONENTS MAGIS COMBO PLUS V2 WITH SUPER TRIO
12
13
11
14
10
9
15
8
16
7
17
6
5
4 18
3
2
1 19
106
MAGIS COMBO PLUS V2 WITH SUPER TRIO
50.2 SYSTEM DIAGRAM MAGIS COMBO PLUS V2 WITH SUPER TRIO:
SYSTEMS WITH A HEATING AND COOLING ZONE
WITH FAN COILS + A RADIANT PANEL ZONE
KEY:
1 - SUPER TRIO system consisting of: 3 - AUDAX PRO 9 V2 Condensing unit
• 250-Litre single coil storage tank 4 - CRONO 7
• Hydronic unit with direct pump 5 - DHW probe
• DHW vessel 6 - CONTAINER for SUPER TRIO
• 30-Litre inertial storage tank 7 - Second mixed zone kit
2 - MAGIS COMBO PLUS V2 indoor unit 8 - HYDRO FS fan coil
107
MAGIS COMBO PLUS V2 WITH SUPER TRIO
50.3 OPTIONAL SYSTEM MAGIS COMBO PLUS V2 WITH SUPER TRIO
OPTIONAL components but necessary to complete the SUPER TRIO SYSTEM Code
SUPER TRIO 3.030395
CONTAINER for SUPER TRIO 3.030394
DOMUS CONTAINER for SUPER TRIO 3.030393
Top guard kit for DOMUS CONTAINER for SUPER TRIO 3.030484
Exclusive SUPER TRIO SYSTEM optional components with MAGIS COMBO PLUS Code
MAGIS COMBO 4 PLUS V2 3.030615
MAGIS COMBO 4 PLUS V2 LPG 3.030615 LPG
MAGIS COMBO 6 PLUS V2 3.030617
MAGIS COMBO 6 PLUS V2 LPG 3.030617 LPG
MAGIS COMBO 9 PLUS V2 3.030619
MAGIS COMBO 9 PLUS V2 LPG 3.030619 LPG
MAGIS COMBO PLUS connection kit with SUPER TRIO 3.030599
OPTIONAL components available for all SUPER TRIO systems Code
Zone remote panel - (device class V* or VI) 3.030863
Temperature and humidity sensor kit ModBus - (device class V or VI*) - to make temperature requests, it is
3.030992
necessary to couple a chrono-thermostat code 3.021622 or 3.021624
CRONO 7 (Digital weekly chrono-thermostat) - (device class IV* or VII) 3.021622
CRONO 7 WIRELESS (device class IV* or VII) 3.021624
External probe - if the condensing unit is installed under unfavourable conditions (device class II* or VI or VII) 3.015266
Room hygrostat kit - (operates on the Dehumidifier according to the humidity detected in the room) 3.023302
Additional 2nd mixed zone kit 3.027865
Antifreeze resistance kit up to -15 °C for hydronic module 3.017324
Vertical connection unit kit for lower connection 3.020575
Horizontal connection unit kit for side connection 3.020574
Rear connection unit kit for rear connection 3.020630
Three-way deviator valve kit used as hot/cold system deviator 3.020632
Configurable relay board kit 3.015350
Two relay board kit (for dehumidifier management) 3.026302
Dehumidifier kit - for recessed installation only 3.021529
Dehumidifier frame kit 3.022146
Dehumidifier grid kit 3.022147
Condensate antifreeze heating cable kit (for outdoor unit 4 - 6 V2) 3.027385
Wall installation brackets kit for outdoor condensing unit 3.022154
DHW recirculation kit (1) (including circulator pump) 3.030483
Polyphosphate dispenser kit (1) 3.020628
Safety marker thermostat kit 3.019229
DOMINUS Interface board kit 3.026273
Solar thermal system coupling kit:**
consisting of a single solar circulation unit, solar control unit, 16-plate heat exchanger, connection tubes, 3.030482
18-litre solar expansion vessel and temperature sensors (for storage tank and solar collector)
*Device class (REF. Communication of the European Commission 2014/C 207/02 ) with factory settings.
** In case of application with solar heating, as well as Kit code 3.030482, the solar heating components on the list are available.
We recommend using 2 flat solar manifolds at most.
(1) The DHW recirculation Kit and the polyphosphate dispenser kit CANNOT coexist together within the CONTAINER and/
or DOMUS CONTAINER for SUPER TRIO.
108
During the useful life of the products, performance is affected by external factors, e.g. the hardness of the DHW, atmospheric
agents, deposits in the system and so on.
The declared data refer to new products that are correctly installed and used in observance of the Standards in force.
N.B.: correct periodic maintenance is highly recommended.
NOTE: Depending on the specific design and installation conditions, the diagrams and drawings provided in this documentation
can require further integration or modifications, according to what is set forth by the Standards and technical regulations in force
and applicable (as an example, the R stamp - edition 2009 is mentioned). It is the professional's responsibility to identify the
applicable provisions, to evaluate compliance with these in each case and the necessity of any changes to diagrams and drawings.
Immergas reserves the right to make any modifications to its models, which are believed useful for the development of the product, without forewarning - Code S.0247 - rev.000 (ver. 409) - 12/21
ImmergasTOOLBOX
Immergas TOOLBOX
TheApp
The App designed
designed by
by Immergas
Immergasfor
forprofessionals
professionals
Disponibile
Available onsu Disponibile
Available onsu Disponibile
Available onsu
To request
To request further
furtherspecific
specific details,
details,sector
sectorProfessionals
Professionals
cancan
alsoalso
use
usefollowing
the the following
e-maile-mail
address:address:
[email protected]
[email protected]
UNI EN ISODI9001:2015
SISTEMA QUALITÀ
CERTIFIED
CERTIFICATO
QUALITY
UNI EN ISO SYSTEM
9001:2008
Design, manufacture
Progettazione, fabbricazione anded assistenza
after-sales MIXED
assistance
post-venditaof di
gascaldaie
boilers,a gas
gas,water heaters
scaldabagni
Paper from sources
managed responsibly
and relative
a gas accessories
e relativi accessori