Tubular Gel Battery

7 OPzV490 (2V490AH)
Specification
Nominal Voltage 2V
Capacity 490.0Ah@10hr to 1.80V/cell
Length 166 2mm (6.54 inches)
Tubu
Width 206 3mm (8.11 inches) GEL lar
Batt
Dimension ery
Container Height 471 3mm (18.5 inches) 7OPzV
490
(2V,4
Maint
ence
-free 90AH
)
Total Height (with Terminal) 506 3mm (19.9 inches) SE LE
DIS PO

LE OC
D LE
SE D

H BA
AD BA
OF PR
Seale
TT ER
d Lead
Y MU
-acid
OP ER ST BE RE
LY
GEL
CY CL
Batte
ry
MA DE TT ER ED OR
IN CH Y CO
INA .,LT D.

Approx Weight Approx 39.0 kg (86.0lbs)


Container Material ABS
490 AH/49.0A (10hr,1.80V/cell,200C/680F)
426.5 A H/85.3A (5hr,1.75V/cell,200C/680F)
Rated Capacity
378 AH/126A (3hr,1.75V/cell,200C/680F)
279 AH/279A (1hr,1.60V/cell,200C/680F)
Max. Discharge Current 4800A (5s) Applications
Internal Resistance Approx 0.73mÙ
Solar energy, wind energy
Discharge : -20 550C (-4 1310F)
Electric power, nuclear power
Operating Temp.Range Charge : 0 400C (32 1040F )
Communication
Storage : -20 500C (-4 1220F)
Ship, maritime affairs
Initial Charging Current less than 98.0 A.Voltage UPS, medical facilities and emergency
Cycle Use
2.40V~2.50V at 200 C(680 F)Temp. Coefficient -5mV/0C lighting
No limit on Initial Charging Current Voltage Situation with high environmental protection
Standby Use and energy-saving
2.25V~2.30V at 200 C(680 F)Temp. Coefficient -3mV/0C
Better safety performance and reliability
Self-discharge <2% pre month @ 20 0 C(68 0 F) Designed service life of 20 years

Main Technical Advantages


Plate: positive plate adopts tubular plate which can prevent active material falling, and adopts multi-component alloy frame.
have fine corrosion-resisting performance and long service life. Negative plate adopts special radiated structure.
Separator: adopt special micro-pore PVC-SiO 2 separator from Europe AMER-SIL Company, separator have big porosity and low resistance.
Electrolyte: adopts Germany gas silicon dioxide,electrolyte in gel state in the battery without flowing,leakage and lamination can be avoided.
Safety valve: adopt Germany technology,constant opening and closing,accumulator case expansion,damage and electrolyte dry up can be avoided.

0 0
Constant Current Discharge (Amperes) at 20 C (68 F )
F.V/Time 10min 15min 30min 1h 2h 3h 5h 8h 10h
1.85V/cell 384 354 289 219 147 113 77.6 54.2 45.9
1.80V/cell 472 429 337 247 162 123 83.7 58.0 49.0
1.75V/cell 559 480 359 257 166 126 85.3 59.0 49.8
1.70V/cell 627 523 380 267 170 129 86.7 59.8 50.3
1.65V/cell 673 553 395 274 174 131 88.0 60.5 50.9
1.60V/cell 704 572 405 279 176 133 88.9 61.0 51.2

Constant Power Discharge (Watts) at 20 0C (68 0F )


F.V/Time 10min 15min 30min 1h 2h 3h 5h 8h 10h
1.85V/cell 714 665 552 424 286 221 153 107 91.3
1.80V/cell 863 794 637 474 313 240 164 115 97.3
1.75V/cell 1003 876 672 491 320 244 167 116 98.7
1.70V/cell 1106 942 704 506 326 248 169 118 99.7
1.65V/cell 1166 980 725 517 332 252 171 119 101
1.60V/cell 1197 1000 736 523 334 253 172 120 102

1
Dimensions

T11 Terminal

Discharge Characteristics Charging Characteristics


2.50 25
A
2.45 0.1C 10
Charge voltage (V/cell)

Charging time in hours


Equaling charge voltage 20
2.40
for max. 16 hours
2.35
A
2.30 0.2C 10 B
10
2.25
Float voltage +/- 1%
2.20

2.15

2.10
0
-10 10 20 30 40 50 0 50 100
-20 0
Temperature ( C) 0 Depth of discharge in % of C10
For continuous charging we recommend a voltage of 2.25 V. Charge voltage:
The charging voltage must be compensated to the curve for A 2.25 V/cell B 2.40 V/cell
acontinuously different battery ambient temperature. State of charge 100 % State of charge 90 %

Temperature Effects in Relation to Battery Capacity Effect of Temperature on Long Term Float Life

110
105 22
100
20
Available capacity( % )

Life expectancy (year)

95
90 18
Charging voltage
85 16
80 2.25V/cell
14
75
70 12
65
C 10 10
60 C5
55 C3 5
50
45
C1
40
35
0
30 20 30 40 50 O
C
-20 -15 -10 -5 0 5 10 15 20 25 30 68 86 104 122 F
Ambient temperature( ) Battery temperature

Cycle Life in Relation to Depth of Discharge General Relation of Capacity VS. Storage Time
0 0
Acc.to IEC 896-2 (20 C / 68 F)
Residual average capacity in % of C10
100 120
90
Available capacity / %
Extracted capacity in %

100
80

70 80
10
60
60
50
40 30
20
40 40
30
20
20

10 0 5 10 15 20 25
1500 2000 2500 3000 3500 4000 4500 5000 5500 6000 6500
Number of Cycles Storage time (months)

Sales Office
Sales Office
China sales office: North America sales office: Europe sales office:
Add:5th Floor,Xinbaohui Bldg.,Nanhai Blvd., Add: 19751 Descartes, Unit A, Add: 9B Wheatstone Park, Waterwells
Nanshan,Shenzhen, China. 518052 Foothill Ranch, CA 92610, USA Business Park, Gloucester, GL2 2AQ. UK.
Tel:+ 86-755-86036060 (100 lines) Tel: 949-588-5853 Tel: +44(0) 1452 729428
Fax: +86-755-26067269 Fax: 949-588-5966 Fax: +44 (0)1452-690125
E-mail:[email protected] E-mail: [email protected] E-mail: [email protected]