Smart Energy & Power Quality Solutions

Power Quality Analyser

UMG 604-PRO
Data sheet
12/2023
Dok.-Nr. 2.033.158.1.a
DEVICE VIEWS
UMG 604-PRO

Front view

Side view

All dimensions in mm

2 – Data sheet UMG 604-PRO • 12/2023


TECHNICAL DATA

UMG 604-PRO
General
Net weight 350 g (0.771 lb)
Device dimensions Approx. l=107.5 mm (4.23 in), w=90 mm (3.54 in), h=82 mm (3.23 in)
(per DIN 43871:1992)
Horizontal pitch 6 HP
Housing flammability rating UL 94V-0
Installation position any
Fastening/assembly 35 mm DIN rail
(per IEC/EN60999-1, DIN EN 50022)
Battery Type Lithium CR2032, 3 V (approval i.a.w. UL 1642)
Service life of the backlight (optional) 40000 h (50% of the initial brightness)
Impact resistance IK08 according to IEC 62262

Transport and storage


The following information applies to devices which are transported or stored in the original packaging.
Free fall 1 m (39.37 in)
Temperature -20 °C (-4° F) to +70 °C (158° F)

Ambient conditions during operation


The device is intended for weather-protected, stationary use.
Protection class II in accordance with IEC 60536 (VDE 0106, part 1), i.e. a ground wire connection is not required!
The device meets the operational conditions in accordance with DIN IEC 60721-3-3.
Working temperature range -10 °C (14° F) to +55 °C (131° F)
Relative humidity 5 to 95% RH (at 25°C / 77° F without condensation)
Operating altitude 0 to 2000 m (1.24 mi) above sea level
Pollution degree 2
Installation position any
Ventilation forced ventilation is not required.
Protection against ingress of solid foreign IP20 in accordance with EN60529 September 2014,
bodies and water IEC60529:2013

Supply voltage
The supply voltage must be connected through 6A, char. B (approved to UL/IEC)
a fuse to the device.

230 V option:
Nominal range 95 V to 240 V (50/60 Hz) / DC 135 V to 340 V
Operating range +-10% of nominal range
Power consumption max. 3.2 W / 9 VA
Overvoltage category 300 V CATII

90 V option (without UL approval):


Nominal range 50 V to 110 V (50/60 Hz) / DC 50 V to 155 V
Operating range +-10% of nominal range
Power consumption max. 3.2 W / 9 VA
Overvoltage category 300 V CATII

24V option:
Nominal range
Operating range 20 V to 50 V (50/60Hz) / DC 20 V to 70 V
Power consumption +-10% of nominal range
Overvoltage category max. 5 W / 8 VA
150 V CATII

12/2023 • Data sheet UMG 604-PRO – 3


UMG 604-PRO

Terminal connection capacity (supply voltage)


Conductors to be connected. Only one conductor can be connected per terminal!
Single core, multi-core, fine-stranded 0.08 - 2.5 mm2, AWG 28 - 12
Cable end sleeve (not insulated) 0.20 - 1.5 mm2, AWG 24 - 16
Cable end sleeve (insulated) 0.25 - 1.5 mm2, AWG 24-16
Stripping length 5-6 mm (0.2 - 0.24 in)

Digital inputs
Maximum counter frequency 20 Hz
(Pulse input S0)
Switching input
Input signal present 18 V to 28 V DC (typical 4 mA)
Input signal not present 0 to 5 V DC, current less than 0.5 mA
Response time (Jasic program) 200 ms
Cable length up to 30 m (32.81 yd) unshielded,
from 30 m (32.81 yd) shielded

Digital outputs
2 digital outputs; semiconductor relays, not short-circuit proof
Switching voltage max. 60 V DC, 30 V AC
Switching current max. 50 mAeff AC/DC
Response time (Jasic program) 200 ms
Output of voltage dips 20 ms
Output of voltage exceedance events 20 ms
Switching frequency max. 20 Hz
Cable length up to 30 m (32.81 yd) unshielded,
from 30 m (32.81 yd) shielded

Temperature measurement input


3-wire measurement
Update time Approx. 200 ms
Connectable sensors PT100, PT1000, KTY83, KTY84
Total burden (sensor + cable) max. 4 kOhm
Cable length up to 30 m (32.81 yd) unshielded,
from 30 m (32.81 yd) shielded

Sensor type Temperature range Resistor range Measurement


uncertainty
KTY83 -55 °C (-67 °F) to +175 °C (347 °F) 500 Ohm to 2.6 kOhm ± 1.5% rng1)
KTY84 -40 °C (-40 °F) to +300 °C (572 °F) 350 Ohm to 2.6 kOhm ± 1.5% rng1)
PT100 -99 °C (-146 °F) to +500 °C (932 °F) 60 Ohm to 180 Ohm ± 1.5% rng1)
PT1000 -99 °C (-146 °F) to +500 °C (932 °F) 600 Ohm to 1.8 kOhm ± 1.5% rng1)
1)
rng = metering range

Terminal connection capacity: Digital inputs and outputs, temperature measurement input
Single core, multi-core, fine-stranded 0.2 - 1.5 mm2, AWG 24-16
Cable end sleeve (not insulated) 0.2 - 1.5 mm2
Cable end sleeve (insulated) 0.2 - 1.5 mm2
Tightening torque 0.25 Nm (2.21 lbf in)
Stripping length 7 mm (0.2756 in)

4 – Data sheet UMG 604-PRO • 12/2023


UMG 604-PRO
Voltage measurement
Three-phase 4-conductor systems (L-N/L-L) max. 277 V / 480 V
Three-phase 3-conductor systems (L-L) max. 480 V
Resolution 0.01 V
Metering range L-N 01) to 600 Vrms
Metering range L-L 01) to 1000 Vrms
Crest factor 2 (related to 480 Vrms)
Overvoltage category 300 V CAT III
Measurement surge voltage 4 kV
Protection of voltage measurement 1 - 10 A
Impedance 4 MOhm / phase
Power consumption approx. 0.1 VA
Sampling rate 20 kHz / phase
Transients > 50 μs
Frequency of the fundamental oscillation 45 Hz to 65 Hz
- Resolution 0.001 Hz

1)
The UMG device can only determine measured values if at least one voltage measurement input
has an L-N voltage of greater than 10 Veff or an L-L voltage of greater than 18 Veff.

Terminal connection capacity (voltage measurement)


Conductors to be connected. Only one conductor can be connected per terminal!
Single core, multi-core, fine-stranded 0.08 - 4.0 mm2, AWG 28-12
Cable end sleeve (not insulated) 0.25 - 2.5 mm2
Cable end sleeve (insulated) 0.25 - 2.5 mm2
Stripping length 8-9 mm (0.31 - 0.35 in)

Current measurement
Rated current 5A
Rated current 6A
Protection when measuring directly 6 A, char. B (approved i.a.w. UL/IEC)
(without a current transformer)
Resolution on the display 10 mA
Metering range 0.005 to 7 Amps
Crest factor 2 (related to 6 Amps)
Overvoltage category 300 V CAT III
Measurement surge voltage 4 kV
Power consumption approx. 0.2 VA (Ri = 5 mOhm)
Overload for 1 sec. 100 A (sinusoidal)
Sampling rate 20 kHz

Measurement precision phase angle 0,15°

Terminal connection capacity (current measurement)


Conductors to be connected. Only one conductor can be connected per terminal!
Single core, multi-core, fine-stranded 0.08 - 4.0 mm2, AWG 28-12
Cable end sleeve (not insulated) 0.25 - 2.5 mm2
Cable end sleeve (insulated) 0.25 - 2.5 mm2
Stripping length 8-9 mm (0.31 - 0.35 in)

12/2023 • Data sheet UMG 604-PRO – 5


UMG 604-PRO

RS232 interface
Connection 5-pin screw-type terminals
Protocol Modbus RTU/slave
Transmission rate 9.6 kbps, 19.2 kbps, 38.4 kbps, 57.6 kbps, 115.2 kbps

RS485 interface
Connection 2-pin screw-type terminals
Protocol Modbus RTU/slave, Modbus RTU/master
Transmission rate 9.6 kbps, 19.2 kbps, 38.4 kbps, 57.6 kbps, 115.2 kbps, 921.6 kbps

Terminal connection capacity (RS 232 / RS 485)


Single core, multi-core, fine-stranded 0.20 - 1.5 mm2, AWG 24-16
Cable end sleeve (not insulated) 0.20 - 1.5 mm2, AWG 24-16
Cable end sleeve (insulated) 0.20 - 1.0 mm2, AWG 24-18
Tightening torque 0.20 - 0.25 Nm (1.77 - 2.21 lbf in)
Stripping length 7 mm (0.2756 in)

Ethernet interface
Connection RJ45
Function Modbus gateway, embedded web server (HTTP)
Protocols TCP/IP, EMAIL (SMTP), DHCP client (BootP),Modbus/TCP(port 502),
ICMP (ping), NTP, TFTP, Modbus RTU over Ethernet (port 8000), FTP SNMP

6 – Data sheet UMG 604-PRO • 12/2023


UMG 604-PRO
Measurement uncertainty
Measurement uncertainty on the device applies when using the following metering ranges. The measured value
must be within the specified limits. The measurement uncertainty is not specified outside of these limits.
Measured value Measurement uncertainties
Voltage ± 0.2% per DIN EN 61557-12:2008
Current L ± 0.25% in accordance with DIN EN 61557-12:2008
Current N ± 1% per DIN EN 61557-12:2008
Power ± 0.4% per DIN EN 61557-12:2008
Harmonics U, I Class 1, DIN EN 61000-4-7
Active energy
Current transformer ../5 A Class 0,5 (IEC61557-12)
Class 0,5S (IEC62053-22)
Class 0,5 (ANSI C12.20)
Current transformer ../1 A Class 1 (IEC61557-12)
Reactive energy
Current transformer ../5 A Class 2 (IEC62053-23)
Current transformer ../1 A Class 2 (IEC62053-23)
Frequency ± 0.01 Hz
Internal clock ±1 minute/month (18 °C (-64,4 °F) to 28 °C (158 °F)
• Specification: information at the user manual
• annual re-calibration,
• a warm-up time of 10 minutes,

12/2023 • Data sheet UMG 604-PRO – 7


Smart Energy & Power Quality Solutions

Janitza electronics GmbH


Vor dem Polstück 6 | 35633 Lahnau
Germany

Tel. +49 6441 9642-0


[email protected] | www.janitza.com