7-TestingNumericalTransformerDiffRelays PPT 9-8-09
7-TestingNumericalTransformerDiffRelays PPT 9-8-09
INTRODUCTION
Commissioning versus Maintenance Testing
INTRODUCTION
Topics:
Transformer Differential Boundary Test
(Commissioning)
Ground Differential Sensitivity Test
(Commissioning/Maintenance)
Harmonic Restraint for Transformer Inrush
(Maintenance)
Testing Numerical Transformer Differential Relays
Commissioning
Common Practice:
Test all numerical relay settings –
verify settings properly entered
Easily facilitated using computer –
automate test set & store results
Hundreds of tests are possible –
numerical relays have many settings
Testing Numerical Transformer Differential Relays
Commissioning
Final Goal
Ensure the transformer is properly protected
for the particular application
Testing Numerical Transformer Differential Relays
46 RG
E
+
46 RG
ZT
I2
3RG
ZT
Testing Numerical Transformer Differential Relays
Y Y
Y Y
87
* Simulate Through Current
Differential Characteristic
Operating Equations
Differential Characteristic
Id
% = Y *100%
X
(%)
e nt
Perc pe
Slo Y
X
Minimum
Pickup
(per unit) Ir
Testing Numerical Transformer Differential Relays
Differential Characteristic
Id
e rc ent
P
e
Slop
e gion
R
Trip gion
Minimum kR e
Bloc
Pickup
Ir
Testing Numerical Transformer Differential Relays
x1 = a/m1 y1 = a
Id
y2 = m2*x2 + b
(y)
Matrix
[]
Id
Ir
= [ ][]
1 -1 *
½ ½
I1
I2
Testing Numerical Transformer Differential Relays
Inverted Matrix
[]
I1
I2
= [ ][]
½ 1
-½ 1
* Id
Ir
Testing Numerical Transformer Differential Relays
Differential Characteristic
Test Current Equations
Differential Characteristic
Test Points
Minimum Pickup = 0.2 per unit
Id
Slope = 28.6%
e rc ent
P
e
4 Slop
3
1 2
Minimum
Pickup
Ir
Testing Numerical Transformer Differential Relays
Differential Characteristic
Test Points (Per Unit)
Id Ir I1 I2
TABLE 1
Testing Numerical Transformer Differential Relays
DAB
I1 I2
Y
Y Y
87
* Simulate Through Current
MVA#
TAP# =
kV#LL*CTR#*SQRT(3)
Testing Numerical Transformer Differential Relays
From TABLE 1:
Id Ir I1 I2
2 0.2 0.7 0.8 0.6
IA1test = 0.8*TAP1
IA2test = 0.6*TAP2*SQRT(3)
Testing Numerical Transformer Differential Relays
Internal External
I0 IG
-90o
Operate When:
180
160
140
Fault Resistance
120
100
80
60
40
20
0
0 20 40 60 80 100 120
Source Impedance
IG
Directional Element
INTERNAL EXTERNAL
IG2
IOP
CTCF*3I0(2)
New Pickup = 1.0 Amps
Testing Numerical Transformer Differential Relays
Waveform Sources:
•Events from Numerical Relays
•Events from Digital Fault Recorders
•Simulate using Transient Software
Testing Numerical Transformer Differential Relays
W3
delta
345 kV 230 kV
wye wye
W1 W2
Z HM + Z HL − Z ML
ZH = 2 = 0.0140 per unit
Z HM + Z ML − Z HL
ZM =
2
= -0.0029 per unit
Z HL + Z ML − Z HM
ZL = 2 = 0.0340 per unit
600 MVA
TAP2 = = 3.77
230 kV * 400 * SQRT(3)
Slope = 25%
2 2 1/2
Ieven = (I2 + I4 )
Testing Numerical Transformer Differential Relays
CONCLUSIONS
Testing Numerical Transformer Differential Relays
CONCLUSIONS
Transformer Differential Boundary Test
(Commissioning)
Ground Differential Sensitivity Test
(Commissioning/Maintenance)
Harmonic Restraint for Transformer Inrush
(Maintenance)
Testing Numerical Transformer Differential Relays
QUESTIONS