E-8 Alternator Technical Description & Main Curves List
E-8 Alternator Technical Description & Main Curves List
Main data C 1
Generator type: LSA 56 XXXX 1
Power: 3 750 kVA 3 000 kWe 3 104 kWm 1
Voltage: 6 600 V Star serial 1
Rated voltage range: +5/-5% 1f
Power factor - Lagging: 0,8 1
Frequency: 50 Hz 1
Speed: 1 500 rpm 1
Nominal current: 328 A 1
Winding type: p5/6 1
Classes (Insulation / Temperature Rise): H/F 1
Ambient temperature: 40 °C 1
Altitude: 1 000 m 1
-
Installation IEC Quantity 1 1
Prime mover: Steam turbine 1
Manufacturer: - 1
Type: - 1
Duty: Base Rating 1
Industry: Utility Power 1
-
Quality 1
Factory Acceptance Test: Included - With client and/or third party 1
Mechanical construction IM1101 1
Type of construction: Two bearing 1
Mounting arrangement: Horizontal Axis 1
Direction of rotation: Counter clockwise (seen when facing the drive end - DE) 1
Bearing type: Sleeve 1
Bearing Lubrication: By oil circulation, with external Oil lubrication unit 1
Bearing insulation: 1 bearing insulated (NDE) 1
Shaft end type: Cylindrical with keyway 1
Balancing - Class (ISO 1940/1): Half key - G1 1
Flange: None / without 1
Shaft height: 600 mm 1
Width: 1 540 mm 1
Main data: C
Power: 3 750 kVA 3 000 kW e 3 104 kWm 1
Voltage: 6600 V Frequency: 50 Hz 1
Rated voltage range: +5% / -5% Speed: 1500 rpm 1
Power factor - Lagging: 0,8 1
Nominal current: 328 A Phases 3
Insulation / Temperature rise: H/F Connexion Star serial 1
Cooling: IC81W Winding type: p5/6 1
Water : 32 °C Winding: - 6 Wires 1
Ambient temperature: 40 °C 1
Altitude: 1000 m Overspeed (rpm) 1800 1
Duty: Base Rating Total Harmonic Distortion (THD) < 1,5% 1
Resistances (%)
Ra 0,7 Armature resistance R0 3,6 Zero sequence resistance 1
X/R 16,3 X/R ratio (without unit) R2 3,9 Negative sequence resistance
Rating is provided for the specified temperature rise, by resistance measurement according to IEC60034-1
According to: I.E.C. 60034.1 - 60034.2 - NEMA MG 1-32
Products and materials shown in this catalogue may, at any time, be modified in order to follow the latest technological developments,
Umax + 5% 6 930 V
Capability Curve Un 6 600 V
Umin - 5% 6 270 V
0,8
PF -0,6 PF 0,6
0,6
PF -0,5 PF 0,5
PF -0,4 0,4
PF 0,4
PF -0,3 PF 0,3
PF -0,1 PF 0,1
0
-1,0 -0,8 -0,6 -0,4 -0,2 0,0 0,2 0,4 0,6 0,8 1,0
kVAr // rated
kVAr ratedkVA
kVA
PF 1 PF 0,8
98,0
97,39 97,45
97,06
97,0
Efficiency - Rendement en %
96,19
96,65 96,66
96,0 96,47
95,74
95,0
94,0
93,20
93,0
92,89
92,0
25 50 75 100 125
Load (% of rated kWe) - Charge (% kWe nominaux)
Isc ( Short circuit current per rated current - Courant de court circuit / In )
Symmetrical Phase to neutral short circuit
12 Symmetrical two phase short circuit
Symmetrical three phase short circuit
Thermal limit curve
10
court circuit aux bornes de l'alternateur
short circuit at generator terminals -
0
0,001 0,01 0,1 1 10 100
Time - Temps (second.)
Isc ( Short circuit current per rated current - Courant de court circuit / In )
Symmetrical three phase short circuit (rms)
16
Asymmetrical three phase short circuit (peak)
12
court circuit aux bornes
10
0
0,001 0,01 0,1 1 10 100
Time - Temps (second.)
5%
10%
15%
20%
25%
30%
35%
40%
35%
30%
25%
20%
15%
10%
5%
0%
0 1 000 2 000 3 000 4 000 5 000 6 000 7 000 8 000 9 000 10 000
PF = 0,8 100%
Stator current
(per rated current)
6
5,5
4,5
3,5
2,5
1,5
1
1 10 100 1000 10000
Maximum duration - durée maximum (second.)
2 50 C
B
1 25
A
0 0
1 10 100 1000 10000 0 1 2 3 4 5 6 7 8 9 10 11 12
Maximum duration of fault - Maximum duration of fault -
Durée max. du defaut (second.) Durée max. du defaut (second.)