IECEx Certificate

of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification System for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com

Certificate No.: IECEx DEK 11.0083X Page 1 of 4 Certificate history:


Issue 6 (2021-07-13)
Status: Current Issue No: 7 Issue 5 (2020-09-14)
Issue 4 (2018-10-04)
Date of Issue: 2023-06-01 Issue 3 (2017-09-08)
Issue 2 (2017-06-26)
Applicant: Yokogawa Electric Corporation Issue 1 (2016-04-05)
2-9-32 Nakacho Issue 0 (2012-02-02)
Musashino-shi
Tokyo, 180-8750
Japan

Equipment: Process Gas Chromatograph, Model GC8000

Optional accessory:

Type of Protection: flameproof enclosures "d", pressurized enclosure "p", increased safety "e", intrinsic safety "i" and type of
protection "n"

Marking: For GC8000-E:


Type GC8000-*…A: Ex db pxb IIB + H2 T1 Gb
Type GC8000-*…B: Ex db pxb IIB + H2 T2 Gb
Type GC8000-*…C: Ex db pxb IIB + H2 T3 Gb
Type GC8000-*…D: Ex db pxb IIB + H2 T4 Gb

For GC8000-M400:
Type GC8000-M400C: Ex db ec ic nC pxb pyb IIB + H2 T3 Gb
Type GC8000-M400D: Ex db ec ic nC pxb pyb IIB + H2 T4 Gb

Approved for issue on behalf of the IECEx R. Schuller


Certification Body:

Position: Certification Manager

Signature:
(for printed version)

Date:
(for printed version) 2023-06-01

1. This certificate and schedule may only be reproduced in full.


2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting www.iecex.com or use of this QR Code.

Certificate issued by:

DEKRA Certification B.V.


Meander 1051
6825 MJ Arnhem
Netherlands
IECEx Certificate
of Conformity
Certificate No.: IECEx DEK 11.0083X Page 2 of 4

Date of issue: 2023-06-01 Issue No: 7

Manufacturer: Yokogawa Electric Corporation


2-9-32 Nakacho
Musashino-shi
Tokyo, 180-8750
Japan

Manufacturing Yokogawa Manufacturing


locations: Corporation
2 Kominedai, Akiruno-shi,
Tokyo, 190-0153
Japan

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the
IEC Standard list below and that the manufacturer's quality system, relating to the Ex products covered by this certificate, was assessed and
found to comply with the IECEx Quality system requirements.This certificate is granted subject to the conditions as set out in IECEx Scheme
Rules, IECEx 02 and Operational Documents as amended

STANDARDS :
The equipment and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found
to comply with the following standards

IEC 60079-0:2017 Explosive atmospheres - Part 0: Equipment - General requirements


Edition:7.0

IEC 60079-1:2014-06 Explosive atmospheres - Part 1: Equipment protection by flameproof enclosures "d"
Edition:7.0

IEC 60079-11:2011 Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"
Edition:6.0

IEC 60079-15:2010 Explosive atmospheres - Part 15: Equipment protection by type of protection "n"
Edition:4

IEC 60079-2:2014-07 Explosive atmospheres - Part 2: Equipment protection by pressurized enclosure "p"
Edition:6

IEC 60079-7:2017 Explosive atmospheres - Part 7: Equipment protection by increased safety "e"
Edition:5.1

This Certificate does not indicate compliance with safety and performance requirements
other than those expressly included in the Standards listed above.

TEST & ASSESSMENT REPORTS:


A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in:

Test Report:
NL/DEK/ExTR11.0096/07

Quality Assessment Reports:


NL/DEK/QAR11.0022/10 NL/DEK/QAR11.0029/08
IECEx Certificate
of Conformity
Certificate No.: IECEx DEK 11.0083X Page 3 of 4

Date of issue: 2023-06-01 Issue No: 7

EQUIPMENT:
Equipment and systems covered by this Certificate are as follows:

Process Gas Chromatograph, Model GC8000-E is used for the analysis of flammable gases. The process gas chromatograph with a
containment system and a touch screen (touch panel) is protected by pressurized enclosure “p” with a continuous flow of the protective gas
(air). The Ex pxb safety device (protection system) is mounted in an enclosure in type of protection flameproof enclosures “d”.
The flameproof enclosure includes integral bushings (wire entries), blanking elements and adapters.
A flame proof pressure switch is mounted on the Ex p enclosure.

Process Gas Chromatograph, Model GC8000-M400 is used for the analysis of flammable gases.
The equipment has an electronic section and an isothermal oven 3. The electronic section is protected by pressurized enclosure “pyb” with
internal equipment providing EPL “Gc”. The isothermal oven 3 is protected by pressurized enclosure “pxb” with a containment system. A flame
proof pressure switch is mounted on the Ex p enclosure.

For more information see Annex 1.

SPECIFIC CONDITIONS OF USE: YES as shown below:


• The analyzers shall be installed and used in such a way that the risk from electrostatic discharges is avoided.
• Modification of the flameproof joints is not allowed.
• All externally powered input signals into the pressurized enclosure shall be isolated by external relays controlled by the Ex px safety
device (protection system).
• For GC8000-M400, it shall only be used in an area of at least pollution degree 2, as defined in IEC 60664-1 (EN IEC 60664-1).
• For GC8000-M400, transient protection shall be provided that is set at a level not exceeding 119 V peak at the Input/Output terminals of
the equipment.
IECEx Certificate
of Conformity
Certificate No.: IECEx DEK 11.0083X Page 4 of 4

Date of issue: 2023-06-01 Issue No: 7

DETAILS OF CERTIFICATE CHANGES (for issues 1 and above)


Addition of Model GC8000-M400.
Minor construction changes.

Annex:

510069900-ExTR11.0096.07-Annex 1.pdf
Annex 1 to: Report No. NL/DEK/ExTR11.0096/07
IECEx DEK 11.0083X

Description

The relation between the model designation, maximum temperature of the internal ovens/heaters, temperature
class and maximum ambient temperature is shown in the table below.

For all types except GC8000-B400* and GC8000-M400*

Model designation Maximum temperature setting of Temperature Ambient temperature


internal ovens/heaters class
GC8000-****A 320 °C T1 -10 °C to +40 °C
GC8000-****B 225 °C T2 -10 °C to +40 °C
GC8000-****C 145 °C T3 -10 °C to +45 °C
GC8000-****D 95 °C T4 -10 °C to +50 °C

For types GC8000-B400* and GC8000-M400*

Model designation Maximum temperature setting of Temperature Ambient temperature


internal ovens/heaters class
GC8000-B400C
145 °C T3 -10 °C to +50 °C
GC8000-M400C
GC8000-B400D
95 °C T4 -10 °C to +50 °C
GC8000-M400D

Type Designation
Model code Suffix Code
GC8000- abcde*g-h*j-****-*****-*-***/*

a = Area classification
- A:ATEX for Ex db and pxb type
- B : ATEX for Ex db, pxb and pyb type
- E:IECEx for Ex db and pxb type
- M : IECEx for Ex db, pxb and pyb type

b = Oven 11)
- 1:Large isothermal oven
- 2 : Standard isothermal oven
- 4 : Large isothermal oven for type GC8000-B400* and GC8000-M400* (Isothermal over 3)

c = Oven 21)
- 0 : None
- 1:Large isothermal oven
- 2 : Standard isothermal oven
- 3 : Programmed temperature oven

d = Oven 31)
- 0 : None
- 2 : Standard isothermal oven
e = Temperature rating

Page 1 of 3
2954:2
Annex 1 to: Report No. NL/DEK/ExTR11.0096/07
IECEx DEK 11.0083X

- A:Setting temperature T1 (320 °C or less)


- B:Setting temperature T2 (225 °C or less)
- C:Setting temperature T3 (145 °C or less)
- D:Setting temperature T4 (95 °C or less)

g = Display
- N : None
- 1 : Provided

h = Power supply
- A : 100 Vac B : 110 Vac C : 115 Vac D : 120 Vac
- E : 200 Vac F : 220 Vac G : 230 Vac H : 240 Vac

j = Wiring connection
- Q : Cable packing (3/4NPT)
- R : Cable packing (M25 X 1.5)

1) Sequential codes to be selected are 100, 110, 120, 222, 230 and 400
*: Number or letter not relevant for the explosion safety properties

Electrical data

Power supply: 100 to 240 Vac, maximum 3560 W

Pressurization data

For all types except GC8000-B400* and GC8000-M400*

Free internal volume: maximum 142.0 l


Supply pressure: 350 - 900 kPa
Minimum purge flow: 35 l/min
Purge time: 18 min (the electronics section)
8 min (the oven section)
Continuous flow: minimum 40 l/min
Minimum overpressure: 392 Pa
Maximum overpressure: 2000 Pa (programmed temperature oven of Model GC8000-*230)
3000 Pa (all other compartments/models)
Maximum leakage rate: 100 l/min

For types GC8000-B400* and GC8000-M400*

Free internal volume: 36.5 l (the electronic section)


47.5 l (the isothermal oven 3)
Supply pressure: 350 - 900 kPa
Minimum purge flow: 5.5 l/min (the electronic section)
35 l/min (the isothermal oven 3)
Purge time: 40 min (electronics section)
8 min (the isothermal oven 3)
Continuous flow: minimum 8 l/min (the electronic section)
minimum 40 l/min (the isothermal oven 3)
Minimum overpressure: 392 Pa
Maximum overpressure: 3000 Pa
Maximum leakage rate: 100 l/min

Page 2 of 3
2954:2
Annex 1 to: Report No. NL/DEK/ExTR11.0096/07
IECEx DEK 11.0083X

Process data

Maximum flow of flammable gas (hydrogen) to oven: 0.3 l/min


Maximum pressure to oven: 451 kPa

* Note) A point, “.” is used as decimal separator.