REX-C900.C700.C400.C100.

C10 Table A

Instruction Manual Display


Thermocouple(TC) Resistance Temperature DetectorRTD) Voltage and Current
Thank you for using our company's products. This series of products Input Type
is an intelligent temperature controller with PID on the most K J R S B E N T Pt100 Cu50 oM mV mA V
advanced modern control theory and controlled by microcomputer
microcontroller. Please read this manual carefully before use. 3.2 Parameter Setting Mode
1. Model Description
This parameter is used to set alarm, PID and other parameters. In the
REX F - * normal state, after pressing "SET" for three seconds, the parameter
Alm2:Please refer to the Alm1 setting will be displayed in PV, and the corresponding value will be
Alm1:N: No alarm
displayed in SV. and the following parameter symbols will be displayed
A: Deviation upper limit alarm
by pressing "SET" in turn:
F : Deviation lower limit alarm
H: Absolute upper limit alarm Note: This Instrument has a display auto-reply. When the User
L : Absolute lower limit alarm forgets to return to the main display mode for operations such as
Ou t : M: Relay setting modification, the Instrument will automatically return to the
V : SSR main display mode after 30 seconds.
8 : DC4~20mA
Read the following in detail before using the instrument or when
Range: 02 : 0-400℃
05 :0-999℃ making parameter changes. The following process will not display this
06 :0-1200℃ content if the instrument does not have this function.
07 :0-1372℃
08 :0-1600℃
Symbol Explain Setting Range Factory
09 :0-1820℃ Name
Default
Input: K:K- type TC PV/SV Process value / settings value Full scale
J : J - type TC Alarm1 setting
AL1 Full scale
S : S- type TC
AL2 Alarm2 setting Full scale
D: Pt100 RTD
ATU Auto-tuning 0: off auto-tuning 0
U: Universal types(K...D) 1 :On auto-tuning

PID Auto-Tuning P Proportional band (check*1) 0 - full scale 15

Check Table 1 I Integration time (sec) 0 - 3600 seconds 240


REX:
Model
D Derivative time (seconds) 0 - 3600 seconds 60

Table 1 Unit: mm AR Reference values (check*2) Automatic setting after AT 25

Model Surface frame (WxH) Shape (W x H x D) Hole size (W x H) T working cycle Time proportional cycle 1-100 (seconds) (check*3)

REX-C100 48x48 44 x 44x100 (44+1) x (44+1)


OH Return Difference Value Size 1-100 unit (PV) 2
REX-C400 48x96 44 x 92x100 (44+1) x (92+1)
SC Correction of PV -200-200 unit (PV) 0
REX-C700 72x72 68 x 68 x 100 (68+1) x (68+1)
LCK Data lock (check*4) 0000-0111 0000
REX-C900 96x96 92x92x100 (92+1) x (92+1)

Example:C900FK06-V*EN
1: When≠0, instrument is PID control, means need to set values of
This instrument is: panel size is 96*96; with PID ; with K-type thermocouple; temperature "I”/”D” ,will open the "AT"(auto-tuning) at first time , Make the control of best
range is 0-1200℃; with solid state relay (SSR) output; the alarm1 is deviation upper when P=0,means ON/OFF control, and then should be set"OH" .
limit alarm; no alarm2 2: This is means PID internal reference value . Usually do not need to set, After “AT”,This value
will be set automatically
3:Means Relay output:20s,means Voltage pulse output, flip-flop output for gate control tube
2. Panel Names And Individual Functions
drive, gate control tube output 2s
4: Set data lock (LCK):Means set data lock function is used to prevent misuse of certain
No. Panel Description Content Description
1 PV Measurement Value / Mode Display Value parameters that are not set. There are 3 levels of locking status, means parameters can be
PV 2 SV Settings / Mode Content Displayed Value locked by each level of status, means parameters can not be set or changed after locking but can
3 OUT1 Output 1 Indicator be monitored
SV 4 OUT2 Output 2 Indicator
5 AT PID Automatic Calculation Indicator
OUT1 OUT2 AT ALM1 ALM2
6 ALM1 Alarm 1 Indicator
ALM 2 Alar m2 Indicator
When LCK=0000 Can Modify all data When LCK=0011 Except for SV are not modifiable
7
SET
8 Increase the Key
C900 When LCK=0001 Except for SV.AL1.AL2 are not modifiable When LCK=0111 Can‘t Modify all data
9 Reduce the Key
10 Shift Key
11 SET Set / Mode Key
4. Error Display
When the instrument does not work, the instrument will checks
3. Operation Process
itselfand displays a code.
3.1 Turn-on process

Turn on the power Code Note Exclusion method Code Note Exclusion method
PV
Input Type Input Type Code Please send Input disconnection, Please check
Auto Change SV Instrument failure for repair Reverse polarity connection or the input
Out of input range。
Input Range PV Input disconnection,
Auto Change Display input range Reverse polarity connection Please check
SV or Out of input range。 the input
Sv/pv display mode
5. Engineer Mode Settings tuning is successful; otherwise, the power is cut off in the middle or the “AT” is artificially
turned off, means the A uto- tuning is invalid. usually, two or three times of Auto-tuning is
5.1 Follow the parameter setting mode to enter and find "LCK" set it to
make the effect better.
"1000", then press "SET" to confirm, and press "SET" and 6.3 On/off and hysteresis setting
"<" at the same time. Press and hold "SET" and "<" at the same time, In the normal state, press "set" for three seconds, the parameter setting state will be
displayed on the“pv”, and the corresponding value will be displayed on the “sv”,press the "set"
after three seconds, "PV" will displayed"Cod". When "Cod"=0000, press
to find the " ".then set the “sv” to "0", so it becomes on/off control. At this time, there is an
"SET" to get the following parameters extra " " in the program parameter, is used to set the r eturn difference value
Table 3 Example: to control 80-100 ℃, you need to set the main control temperature at 90, and their
Display intermediate value and hysteresis difference are 20, so set " " in the program to 20.
Settings Specification Scale Range
Character 6.4 Alarm setting
0 0 0 0 K 0-1372℃ This product has upper limit alarm, upper limit deviation alarm, lower limit alarm and lower
0 0 0 1 J 0-1200℃ limit deviation alarm.
Example of setting the upper limit alarm: the temperature is 100℃, the upper
0 0 1 0 R 0-1769℃
limit alarm temperature is 110℃, and hold "set" for three seconds in the normal state, the
0 0 1 1 S 0-1769℃ parameter setting state will be displayed in the "pv", and the parameter setting state will be
0 1 0 0 B 0-1820℃ displayed in the "sv".. press the "set" to find the " ". Set the "sv" to 110℃, then hold the
"set" for seconds to exit, and the setting is completed. If you need the upper limit deviation
0 1 0 1 E 0-800℃
alarm, just set the character " " to 10.
0 1 1 0 N 0-1300℃
6.5 Alarm type of change:
0 1 1 1 T -200-400℃-199.9-400.0℃
Both the alarm1 and alarm2 can be set as to upper limit or lower limit alarm
1 0 0 0 Pt100 -200-650℃-199.9-650.0℃ After pressing the "set" for three seconds, the parameter setting state will be displayed on
1 0 0 1 Cu50 -50-150℃-50.0-150.0℃ the"pv", and the corresponding value will be displayed on the "sv". press the "set" to find the
" ",set it to "1000", and press the "set", then press and hold the "set" and "<" at the same
1 0 1 0 0-400Ω -1999,℃-9999℃
time. after 3 seconds, "cod" will be displayed in the "pv". when "cod"= 0000, press the "set"to
1 0 1 1 0-50mV -1999℃-9999℃
" to set the alarm mode you need. press the "set" again to confirm (please
find the "
1 1 0 0 0-20mA -1999℃-9999℃ refer to the parameter mode table of the instrument engineer), and then press and hold the
0-5V(0-10V) -1999℃-9999℃ "set" and the "<" at the same time, and it will return to the normal state after 3 seconds.
1 1 0 1
alarm 1 (sl4) is the same as alarm 2 (sl5).
0 0 0 0 6.6 Input type setting
0 0 0 0 In the normal state, hold the "set" for three seconds, the parameter setting state will
0 0 0 The Alm1 is not set be displayed on the "pv", and the corresponding value will be displayed on the "sv". press the
0 0 1 Alm1 type select
"set" to find the " ", set the"sv" to "1000", and then press the "set" to confirm. then
Upper limit deviation alarm
hold the "set" and "<" at the same time, after 3 seconds, the "pv" will display "cod". when
0 1 0 Upper/lower limit deviation alarm
"cod" = "0000", press the "set" to find the " " to set the input type you need. And then
0 1 1 Process value upper limit alarm Alm1 type select
press the "set" again to confirm (please refer to the parameter mode table of the
1 0 1 Lower limit deviation alarm instrument engineer), then hold the "set"and the "<"at the same time, it will return to the
1 1 0 With alarm (in-range alarm)
normal state after 3 seconds.

1 1 1 Process value lower limit alarm. 7. Instrument Technical Specifications


0 No standby alarm function ALM1 standby function selection
1.Measurement error:1%+1℃、0.5%±1℃、0.2%±1℃。Three grades
1 With standby alarm function.
Additional cold end compensation error: ≤±2℃ in the range of 0~50℃, temperature
0 0 0 0 ALM2 Settings Same as Alm1 setting coefficient ≤0.05%/℃.

0 Positive motion control (cooling). Master control positive and negative selection 2.Measurement temperature range:-1999~9999℃、-199~9999℃,Two type

1 Reverse motion control (heating) 3.Alarm range:Full range setting


4.Relay output contact capacity:3A/220V,Resistive Or Specified capacitance
0 Time proportional output Output Type Select
5. Solid state relay(SSR) output signal
1 Main control continuous output(4-20mA)
Incentive Alarm Incentive Alarm /Non-incentive alarm 6.Power Supply:220V~±10% ,50Hz ,4W
0
ALM1 Side
7.Working Environment:0~50℃,Relative Humidity 35%~85%RH,Non-corrosive and no
1 Non-incentive alarm
Incentive Alarm /Non-incentive alarm strong electromagnetic field radiation occasions.。
0 Incentive Alarm

1 Non-incentive alarm ALM2 Side 8. Application Notes


0 0 0 0 1.Check whether the Instruments output model and power supply voltage are the same as the
0 0 0 0 Instrument.。
0 0 0 0 2.Normal wiring according to the wiring diagram
0 0 0 0 3.For thermocouple input signal, please use compensation wire of the same material as the
thermocouple wire.
5.2 When”Cod”=0001. Press "SET" in sequence to get the following 4.For RTD input signal, please use the same specification of low resistance wire, and try to
parameters have the same length of three wires.
*5.Pay special attention to the power input line and the sensor signal input line must not be
Symbols Default value Notes Setting Range
confused with the wrong connection, otherwise the whole instrument will be burned. The
Factory Settings Temperature Set Value Upper limit range check Table 3 output terminals must not be short-circuited by strong currents.
6.The instrument power and signal lines need to be separated from the high current output
Factory Settings Temperature Set Value Lower limit range check Table 3
lines to reduce the electromagnetic influence on the instrument, and when this is
0 Number of decimal places 0-3 unavoidable the instrument connection lines should be shielded as far as possible.
7.Please specify when ordering:
2or2.0 Return Difference Value 0-100or 0.0-100.0
① Instrument type
2or2.0 ALM1 output no operate bandwidth 0-100or 0.0-100.0 ② Sensor type
③ Instrument output type
2or2.0 ALM2 output no operate bandwidth 0-100or 0.0-100.0
④ Temperature range
1 Digital filtering constants 0-100 ⑤ Other special functional requirements

9. Simple Problem Repairs


6. Mode Setting And Operation Method After connecting the corresponding power cable,sensor and output
control cableaccording to the instrument specification,"PV" displays the
6.1 Temperature setting
measured value and "sv"displays the set value after power on, and enters
In the normal state, press the "set" to make the "sv" in the flashing state, by pressing the
"<" to find the number of digits of the desired set temperature, and then press the "↑" or "↓" the automatic temperature control state.
to set, after setting the required temperature value, press the "set" again to turn the 1. lf the instrument does not indicate correctly, check the sensor and wiring
instrument to the normal state of sv/pv. 2. lf the instrument panel displays various functions and output indications
6.2 Auto-tuning settings normally,but the instrument is faulty, please check whether the output line is
In the normal state, press and hold the "set" for three seconds, the parameter setting
connectedcorrectly,whether the load is short-circuited, broken, etc. causing
state will be displayed on the “pv”, and the corresponding value will be displayed on the “sv”.
press the "set" to find the " " ”, then set the “sv” to “0001”, Hold the “set” for three seconds damage to theinternal components of the instrument, if necessar y, you can
to turn the instrument to the“sv”/”pv” normal state. At this time, the “AT” on the panel is turn off the power andopen the instrument, check whether the output
flashing, means the Auto-tuning starts ,until the flashing state disappears , then the Auto- terminal copper foil, outputprotection resistor is burnt, etc.