flat slabs
flat slabs
1.1 Introduction
a) Flat Plate: they are flat slabs with flat soffit. Such slabs have uniform
thickness supported on columns. They are used for relatively light loads, as
experienced in apartments or similar buildings. Flat plats are most
economical for spans from 4.5m to 6m (see Fig. 4.1a).
b) Flat slab: they are slab systems with the load transfer to the column is
accomplished by thickening the slab near the column, using drop panels
and/or by flaring the top of the column to form a column capital. They
may be used for heavy industrial loads and for spans of 6m to 9m (see Fig.
1.1c)
c) Waffle slabs: they are two-way joist systems with reduced self weights.
They are used for spans from 7.5m to 12m. (Note: for large spans, the
thickness required to transmit the vertical loads to the columns exceeds
that required for bending. As a result the concrete at the middle of the
panel is not efficiently used. To lighten the slab, reduce the slab moments,
and save material, the slab at mid span can be replaced by intersecting
ribs. Near the columns the full depth is retained to transmit loads from the
slab to the columns (see Fig. 4.1b)
In this chapter, consideration will be given to flat slabs with or with out drop
panels or column capitals.
A similar situation is obtained in the flat plate floor (see Fig. 1.3b) where broad
strips of the slab centered on the column lines in each direction serve the same
function as the beams. Therefore; for column supported construction, 100
percent of the applied load must be carried in each direction, jointly by the slab
and its supporting beams.
(a)
From the above static moment in each direction, the moment in the long
direction is larger than those in the short direction unlike to the situation for the
slab with stiff edge beams.
Lateral Distributions of moments
The moments across the width of critical sections such as AB or EF are not
constant as shown qualitatively (see Fig.1.4 c). For design purpose, moments
may be considered constant within the bounds of a middle strip or column strip,
unless beams are present in column lines.
Where L1 is the panel length parallel to span, measured from centers of columns.
L2 is the panel width, measured from centers of columns
hc is the effective diameter of a column or column head (see below)
When the above condition is not satisfied, the negative design moments shall be
increased.
For a flared head, the actual dimension L ho is that measured to the center of
the reinforcing steel (see Fig. 4.5)
1. Design is based on the single load case of all spans loaded with the
maximum design ultimate load.
2. There are at least three rows of panels of approximately equal span in the
direction being considered.
3. Successive span length in each direction shall not differ by more than one-
third of the longer span
4. Maximum offsets of columns from either axis between center lines of
successive columns shall not exceed 10% of the span (in the direction of
the offset)
Longitudinal Distribution
The distribution of design span and support moments depends on the relative
stiffness of the different sections which in turn depends on the restraint provided
for the slab by the supports. Accordingly, the distribution factors are given in the
following table.
Table 4.1 Bending Moment and Shear Force Coefficients for Flat slabs of Three or
More Equal Spans.
Column L
moments
NOTE:
1. F is the total design ultimate load on the strip of slab between adjacent
columns considered.
2. L is the effective span = L1-2hc/3
3. The limitations of Section A.4.3.1(2) of EBCS 2, need not be
checked
4. The moments shall not be redistributed
Lateral Distribution
The design moment obtained from the above (or equivalent frame analysis) shall
be divided b/n the column and middle strips according to the following table.
Table 4.2 Distribution of Design Moments in Panels of Flat Slabs
Apportionment been column and middle strip
expressed as percentages of the total negative or
positive design moment
Column strip (%) Middle. strip (%)
Negative 75 25
Positive 55 45
NOTE: For the case where the width of the column strip is taken as equal to that
of the drop and the middle strip is thereby increased in width, the design
moments to be resisted by the middle strip shall be increased in proportion to its
increased width. The design moments to be resisted by the column strip may be
decreased by an amount such that the total positive and the total negative
design moments resisted by the column strip and middle strip together are
unchanged.
According to the ACI Code specification, the Equivalent Frame method was
developed with the assumption that the analysis would be done using the
moment distribution method.
a) Basis of Analysis
The equivalent Frame method was developed with the assumption that the
analysis would be done using the moment distribution method. For vertical
loading, each floor with its columns may be analyzed separately by assuming the
columns to be fixed at the floors above and below.
b) Moment of Inertia of Slab Beam
The slab beam includes the portion of then slab bounded by panel centerlines on
each side of the columns, together with column line beams or drop panels (if
used).
The moment of inertia used for analysis may be based n the concrete cross-
section, neglecting reinforcement, but variations in cross section along the
member axis should be accounted for (see below).
The above effects can be considered by replacing the actual beam and columns
with an equivalent column having the following stiffness:
Fig. 1.10
Torsional
members
The final design moments shall not be less than for the case of full factored dead
and live load on all panels.
The shear force to be resisted can be calculated as the total design load on the
area bounded by the panel centerlines around the column less the load applied
with in the area defined by the critical shear perimeter.
The punching shear resistance with out shear reinforcement is:
Table 1.4a
Table 1.4b
Table 1.4c
Table 1.5
Minimum Bend Point Locations and Extensions for reinforcement in Flat Slabs