Improving_Transient_Stability_of_Grid-Forming_DFIG_Based_on_Enhanced_Hybrid_Synchronization_Control
Improving_Transient_Stability_of_Grid-Forming_DFIG_Based_on_Enhanced_Hybrid_Synchronization_Control
Abstract—Grid-forming (GFM) technique is attractive for Ws,d, Ws,q dq-axis components of the stator flux.
doubly fed induction generator (DFIG)-based wind turbines Ig,d, Ig,q dq-axis components of the current output by grid-side
(WTs) to realize its stable operation and grid-support ability converter (GSC).
under weak ac grid. Meanwhile, GFM-DFIG suffers from Vdc, C DC-link voltage and DC-link capacitance.
instability under grid voltage sag due to its poor ability to LF, CF Filter inductance and filter capacitance.
resist disturbed grid voltage. In this article, focusing on its
transient stability under symmetrical grid voltage fault, the Subscripts
large-signal model of GFM-DFIG with voltage-orientation ref Reference value.
control (VOC) considered is established, based on which its
transient behavior is studied. It is found that two types of I. INTRODUCTION
transient instability exist during a symmetrical grid voltage
fault. The first is induced by the inexistence of the postfault
equilibrium point (EP). The second is induced by the exces-
sive dynamic deviation between synchronous angle and
W IND power generation is one kind of essential sources in
power system in view of its contribution to low-carbon
economy. With the sustained capacity growth of wind power
point of common coupling (PCC) voltage angle. Given that
the postfault EP and transient damping are vital for tran-
generation, the renewable energy generation (REG)-dominated
sient stability, an enhanced hybrid-synchronization control power system has formed in some local area located far away
(EHSC) strategy based on adaptive Integrator is proposed, from load center, causing low short-circuit ratio (SCR) and great
through which both the postfault EP and the transient necessity of grid-supporting wind power generation [1].
damping can be improved. Finally, theoretical findings and Among various types of wind power generation, doubly fed
effectiveness of proposed strategy are verified with a 5 kW
DFIG-based experimental platform.
induction generator (DFIG)-based wind turbines (WTs) are used
widely for its lower costs of construction and maintenance. The
Index Terms—Doubly fed induction generator (DFIG), grid-supporting ability of DFIG-based WTs can be realized
grid-forming (GFM), transient stability. through grid-following (GFL) control or grid-forming (GFM)
control. The GFL-DFIG synchronizes with grid through phase-
NOMENCLATURE locked loop (PLL), the output of which does not respond to the
variation of grid frequency and voltage [2], so virtual inertia
hpcc, href PCC voltage angle and synchronous angle. (VI) and automatic voltage regulator (AVR) are needed to real-
Vpcc, Vref Amplitudes of PCC voltage and command.
hsl, hr Slip angle and electrical angle of rotor. ized its grid-supporting ability [3], [4]. As a contrast, the GFM-
kslip, kSCR Slip rate of DFIG and short-circuit ratio (SCR). DFIG synchronizes with grid via its power controller (PC), and
hpll Output angle of phase-locked loop (PLL). it can support grid frequency and voltage without additional
Ls, Lr, Lm Stator, rotor and mutual inductances of DFIG. control loops [5], [6]. In 2023, the Australian energy market
Lg, Xg Grid inductance and grid reactance. operator (AEMO) established an expert group on the specifica-
Vpcc,d,Vpcc,q dq-axis components of the PCC voltage.
Ipcc,d, Ipcc,q dq-axis components of the PCC current. tion for GFM devices, and it pointed out that a GFM device
Vs,d, Vs,q dq-axis components of the stator voltage. should behave like a voltage source while in normal operation,
Is,d, Is,q dq-axis components of the stator current. thereby allowing immediate response to a change in the external
grid [7].
Regarding as the choice between GFL and GFM control, it is
Manuscript received 26 October 2023; revised 22 January 2024 and found that GFL control is more suitable in stiff grid (i.e., SCR > 3)
12 March 2024; accepted 12 April 2024. Date of publication 23 May and GFM control is more suitable in weak grid (i.e., SCR < 3),
2024; date of current version 11 October 2024. This work was due to their small-signal stability relevant to grid impedance [8], [9].
supported by the National Natural Science Foundation of China under
Grant 52377177. (Corresponding author: Zhen Xie.) Therefore, it is suggested for DFIG-based WTs to operate with
The authors are with the School of Electrical Engineering and GFM control under weak grid condition. However, this choice is
Automation, Hefei University of Technology, Hefei 230009, China hard to trust when a grid voltage fault occurs. Limited by the
(e-mail: [email protected]; [email protected]; poor ability to provide short-circuit current, GFM-REGs tend to be
[email protected]; [email protected]).
unstable if it tries to maintain its GFM ability under a grid voltage
Color versions of one or more figures in this article are available at
https://doi.org/10.1109/TIE.2024.3393134. fault [10], which aggravates the imbalance of active power control
Digital Object Identifier 10.1109/TIE.2024.3393134 and the uncontrollability of grid voltage. To avoid this problem,
0278-0046 © 2024 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.
Authorized licensed use limited to: State Grid Corporation of China (SGCC). Downloaded on November 27,2024 at 08:50:38 UTC from IEEE Xplore. Restrictions apply.
15882 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 71, NO. 12, DECEMBER 2024
switching the control algorithm from GFM to GFL is considered its transient stability, but GFM-DFIG should switch its reactive
under lager-signal disturbances [11], [12], which seems to be a fea- power loop to avoid the fault current caused by the excessive
sible scheme. In fact, GFL-DFIG is also vulnerable to small-signal reactive power [27]. Therefore, the reliability of those transient
instability during a weak grid fault [13], [14], [15]. In [13], the stability analysis and methods for GFM-VSC are uncertain for a
small-signal behavior of a GFL-DFIG attached to weak grid is GFM-DFIG. Given that less researches focus on the transient
investigated, and it is found that the negative damping due to the stability of GFM-DFIG, additional research on its transient
interaction between PLL and rotor current control will be increased behavior and transient stability is necessary.
under deeper voltage sag. Similar conclusions are also obtained in In this article, focusing the transient behavior of GFM-DFIG
[14], [15], where the stability of GFL-DFIG during grid fault is in electromechanical time scale, both the dynamic of inner volt-
investigated based on the impedance method and the singular per- age control and the switched reactive power control is consid-
turbation theory, respectively. Thus, new schemes should be pro- ered during the transient modeling process. The impacts of
vided to ensure the transient stability of GFM-DFIG during the control parameter in APC and inner voltage loop on transient
weak grid fault. stability is studied with the state trajectory, and an enhanced
There are many researches on the transient stability of GFM hybrid-synchronization control (EHSC) strategy is proposed to
control under a symmetrical grid voltage fault, most of which improving the transient stability boundary of GFM-DFIG under
are relevant to a voltage-source converter (VSC) system [16], a symmetrical grid voltage sag. The contributions of this article
[17], [18], [19], [20]. The transient stability of GFM-VSC is can be concluded as follows.
studied in [16], where noninertia GFM control and inertia GFM 1) Two types of transient instability for GFM-DFIG during
control are investigated comprehensively with the phase por- a symmetrical grid voltage fault is revealed based on the
trait. In [17], the damping in GFM control is quantitatively large-signal model and state trajectory analysis. The first
assessed via the damping energy visualization and geometry is induced by the inexistence of the postfault EP. The
approximation, which has critical impact on its transient stability second is induced by the excessive dynamic deviation
boundary and critical clearing angle (CCA). In [18], the large- between synchronous angle and point of common cou-
signal stability of GFM control and GFL control is compara- pling (PCC) voltage angle.
tively studied based on the energy function model, and it is 2) It is found that the postfault EP of GFM-DFIG tends to
shown that GFL-VSC will lose stability by exhibiting a varying be nonexistent with lower grid voltage, SCR and higher
damping coefficient. In [19], both the CCA and critical clearing postfault active power command, which is similar to that
time (CCT) is analyzed to quantitatively describe the transient of a GFM-VSC.
stability boundary of virtual synchronous generator (VSG). In 3) Voltage-orientation control (VOC) plays considerable
[20], the transient stability of hybrid power systems dominated roles on the resynchronization of GFM-DFIG, which
by different GFM devices is investigated, which contributes the regulates the active rotor current based on dynamic devi-
further appliance of GFM control in modern power system. In ation between synchronous angle and PCC voltage
those researches, the active and reactive power control loops are angle, so the second types of transient instability can be
focused, so many methods on enhancing transient stability of improved with smaller P-f droop gain and larger propor-
GFM control are proposed on this basis [21], [22], [23], [24], tional and integral gain of VOC.
[25]. The poor damping of VSG during a grid voltage fault is 4) The EHSC strategy is proposed to address the transient
usually treated as a main factor causing instability, so a transient instability of GFM-DFIG. The transient damping can be
damping method (TDM) is introduced in [21] to enhance the improved by the conventional HSC strategy. Specially,
transient stability of GFM-VSC. An enhanced VSG controller is synchronous angle when postfault EP does not exist can
proposed in [22], which also focuses the optimization of VSG be limited by an adaptive integrator, which generates an
control. A mode- adaptive power-angel control method is pro- adaptive compensation based on the cumulative error
posed in [23] to restrain the divergent power angle when there is between synchronous angle and PCC voltage angle.
no postfault equilibrium point (EP). In addition, the impacts of The rest of this article is organized as follows. The structure
current limitation on the transient stability of GFM-VSC have of GFM-DFIG is introduced in Section II. The large-signal
been paid more attention [24], [25], since steady-state overcur- modeling and transient stability analysis are given in Section III.
rent during a grid voltage fault will be inevitable for the In Section IV, the concept of HSC is introduced first, then
unchanged power control loops. EHSC strategy is proposed to improve the transient stability of
Although those researches are valuable for solving transient GFM-DFIG, and its effectiveness is validated by comparing the
instability of a GFM-DFIG, there still exist differences between stable area of EHSC and HSC. Experimental validation is given
a GFM-VSC and a GFM-DFIG. First, the dynamic of inner volt- in Section V. Finally, Section VI concludes the article.
age control is neglected in most transient stability analysis of
GFM-VSC, since the bandwidth of inner voltage control can be II. GFM CONTROL OF DFIG-BASED WTS
designed high to realize a faster power response. However, lim-
A. Basic Principle of GFM-DFIG
ited by the large electromagnetic time constant, dynamic of
inner voltage control is usually slower and cannot be neglected Usually, a GFM-DFIG is the DFIG-based WT realizing its
[26]. Second, the reactive power control loop of a GFM-VSC GFM capacities by rotor-side control [28], and its structure is
remain unchanged during the grid voltage fault when analyzing given in Fig. 1. It can be seen that the GFM algorithm is used in
Authorized licensed use limited to: State Grid Corporation of China (SGCC). Downloaded on November 27,2024 at 08:50:38 UTC from IEEE Xplore. Restrictions apply.
LI et al.: TRANSIENT STABILITY OF GRID-FORMING DFIG 15883
where KP is P-f droop gain; x0 equals to 100p (rad/s). Fig. 1. Basic structure of GFM-DFIG.
The synchronous angle in (1) serves as the oriented angle of
synchronous rotating frame (SRF) in rotor-side control, then
VOC can ensure the alignment of PCC voltage vector with the
d-axis of SRF, that is,
(
ðK p;q þKi,q =sÞð0 Vpcc,q Þ ¼ Ir,d
ref
: (2)
Vpcc,q ¼ xs Lm Ir,d þ Rs Is,q þ xs Ls Is,d
Authorized licensed use limited to: State Grid Corporation of China (SGCC). Downloaded on November 27,2024 at 08:50:38 UTC from IEEE Xplore. Restrictions apply.
15884 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 71, NO. 12, DECEMBER 2024
the power angle when the voltage phase of infinite grid bus is The voltage equation at PCC is expressed as
taken as a reference. Therefore, power angle stability is used to
describe the transient characteristics of GFM-VSC during its Vpcc ejhpcc ¼ Vpcc ejðhpcc href Þ ejhref ¼ Vg þ jXg Is ejðhpcc þuÞ (11)
grid synchronization. In Fig. 3(a), active power feedback is cal- where u denotes the power factor angle at PCC.
culated based on Equation (11) can be repressed in another SRF, the d-axis of
Pout ¼ 1:5Eref Vg sin href =Xg : (7) which is aligned with href
However, the synchronous loop of GFM-DFIG as shown in Vpcc ejðhpcc href Þ ¼ Vg ejhref þ jXg Is ejðhpcc href þuÞ : (12)
Fig. 2 is different with that of a droop-controlled GFM-VSC,
and it is given in Fig. 3(b) for illustration. It can be seen that That is
VOC is a mediate link between the forward loop of APC and (
G
Vpcc,d ¼ Vg coshref Xg Ipcc,q
G
¼ Vpcc cosðhpcc href Þ
the feedback loop of active power. In Fig. 3(b), (18) denotes the (13)
calculation of active power feedback, which will be given in the Vpcc,q ¼ Vg sinhref þ Xg Ipcc,d ¼ Vpcc sinðhpcc href Þ
G G
next section. Given that VOC regulates the active rotor current
based on the error between PCC voltage angle and the synchro- where superscript “G” denotes the SRF oriented based on GFM
nous angle, it is nonnegligible when analyzing the transient control.
characteristics of GFM-DFIG during its grid synchronization. Assuming the rotor current can always track to its reference
During a symmetrical grid voltage sag, the resynchronization in GFM-based SFR, there are
of GFM-DFIG is closely related to its transient stability. Based G
Ir,d ¼ Ir,d
ref
¼ ðKp,q þ Ki,q =sÞð0 Vpcc,q
G
Þ (14)
on the aforementioned information, a high-order large-signal
model should be considered when analyzing the transient stabil- G
Ir,q ¼ Ir,q
ref
¼ Ir,q0 þ DIr,q
lvrt
(15)
ity of GFM-DFIG, which will be mainly introduced in the
Section III of our article. where Kp,q and Ki,q are proportional and integral coefficients
of VOC; Ir,q0 is initial rotor current before grid voltage dips,
and DIr,q
lvrt
is dynamic reactive rotor current to support grid
III. LARGE-SIGNAL MODEL AND TRANSIENT STABILITY OF G G
voltage.Vpcc,d , Vpcc,q can be calculated based on (10) and
GFM-DFIG UNDER SYMMETRICAL GRID VOLTAGE DIP
(13), there is
A. Large-Signal Reduced-Order Model (
G
Vpcc,d ¼ k0 ðVg coshref Ir,q
G
Lm Xg =Ls Þ
The purpose of deducing the large-signal model is to analyze (16)
the transient behavior of nonlinear system, so that quantitative Vpcc,q ¼ k0 ðIr,d Lm Xg =Ls Vg sinhref Þ
G G
Authorized licensed use limited to: State Grid Corporation of China (SGCC). Downloaded on November 27,2024 at 08:50:38 UTC from IEEE Xplore. Restrictions apply.
LI et al.: TRANSIENT STABILITY OF GRID-FORMING DFIG 15885
Authorized licensed use limited to: State Grid Corporation of China (SGCC). Downloaded on November 27,2024 at 08:50:38 UTC from IEEE Xplore. Restrictions apply.
15886 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 71, NO. 12, DECEMBER 2024
Authorized licensed use limited to: State Grid Corporation of China (SGCC). Downloaded on November 27,2024 at 08:50:38 UTC from IEEE Xplore. Restrictions apply.
LI et al.: TRANSIENT STABILITY OF GRID-FORMING DFIG 15887
TABLE I
IMPACTS OF DIFFERENT FACTORS ON TRANSIENT STABILITY
Authorized licensed use limited to: State Grid Corporation of China (SGCC). Downloaded on November 27,2024 at 08:50:38 UTC from IEEE Xplore. Restrictions apply.
15888 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 71, NO. 12, DECEMBER 2024
Fig. 9. Vector diagram: (a) steady state 1; (b) transient process; and
(c) steady state 2.
Fig. 10. Basic topology of EHSC.
angle href and PCC voltage angle hpcc does not exist for GFM- (33)
DFIG with PI-based VOC, it can be found from Fig. 9(b) that a Usually, the active power command is calculated based on
dynamic angle error exists due to the hysteresis characteristic of the real-time torque command determined by maximum power
VOC. Therefore, the enhanced HSC method can be proposed as point tracking (MPPT) control, and the maximum active power
shown in Fig. 10, which utilizes the dynamic error between syn- transmission capability of DFIG is limited by its rated current,
chronous angle href and PCC voltage angle hpcc to enhance the SCR and grid voltage [32]. Thus, the active power unbalance
transient stability of GFM-DFIG. would exist between its command and feedback when grid volt-
As shown in Fig. 10, there are two modifications comparing age sags, which generates a positive angular velocity x1 acceler-
with the original HSC method in Fig. 7. The first modification is ating the divergence of href and inducing synchronous
a low-pass filter (LPF) after coordinate transformation, and its instability, and this process can be understood with the time-
function is to eliminate the impact of voltage jump caused by domain curves in Fig. 11(a). Now, this positive angular velocity
the electromagnetic process in DFIG. The second modification x1 can be offset by the negative integral term x2 provided by
is the adaptive integral gain of VBS, and it is given as DPeq,2. As shown in (33), Dx can equal to 0 by compensating
KI,VBS ¼ KI,0 ½1 þ Kt ð1 Vpcc =VN Þ (31) x2 when the active power unbalance exists, and this process can
be demonstrated by the time-domain curves in Fig. 11(b).
where KI,0 is the fiducial value of integration coefficient and Kt Besides, x2 is calculated automatically based on the dynamic
is a variable gain related to active power instruction and SCR. variation of q-axis PCC voltage, and the adaptive integral gain
The principles of proposed EHSC method can be explained KI,VBS is regulated with the change of grid voltage. It also pro-
as follows. First, the synchronization equation of droop-based vides additional degrees of freedom for regulating x2 (i.e., Kt).
APC with EHSC method is given as Given that the active power unbalance will be aggravated at
Dx high wind speed and low SCR grid, Kt can be further designed
¼ Pfault
ref ðKP,VBS Vpcc =KP Þsinðhref hpcc Þ as (34) to enhance its transient stability under different scenarios
KP |fflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflffl{zfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflffl}
DPeq,1
Kt ¼ Kt0 ½1 þ kSCR 1 ePref =PN
fault
ð (34)
½ðKI,VBS Vpcc =KP Þsinðhref hpcc Þ Pfault out (32) where Kt0 is the fiducial value of Kt.
|fflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflffl{zfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflfflffl}
DPeq,2 C. Parameter Design of Adaptive Integral Gain
According to (32), there are two terms (i.e., DPeq,1 and It should be noted that the task of providing frequency com-
DPeq,2) after the postfault active power command. DPeq,1 is pensation is time-starved because synchronous angle href will
related to the real-time deviation between synchronous angle exceed its stable margin if a positive Dx exists for a long time,
href and PCC voltage angle hpcc, which equals to zero in steady which means frequency compensation x2 should be provided
state. DPeq,2 is related to the cumulative deviation between correctly in a short time. Usually, area “href > p/2” denotes a
them, so it is a nonzero term helping to adjust the equivalent dangerous signal of transient instability, so a permissive accel-
active power command. eration time Tþ exists when neglecting the compensation term
Authorized licensed use limited to: State Grid Corporation of China (SGCC). Downloaded on November 27,2024 at 08:50:38 UTC from IEEE Xplore. Restrictions apply.
LI et al.: TRANSIENT STABILITY OF GRID-FORMING DFIG 15889
Fig. 12. Transient trajectories under grid voltage sag: (a) increasing
KP,VBS; and (b) effect of EHSC on transient stability.
Authorized licensed use limited to: State Grid Corporation of China (SGCC). Downloaded on November 27,2024 at 08:50:38 UTC from IEEE Xplore. Restrictions apply.
15890 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 71, NO. 12, DECEMBER 2024
Fig. 13. Transient stability boundary: (a) Pout ¼ 0.3 p.u.; and (b) Pout ¼
0.9 p.u. Fig. 14. Experimental platform.
Authorized licensed use limited to: State Grid Corporation of China (SGCC). Downloaded on November 27,2024 at 08:50:38 UTC from IEEE Xplore. Restrictions apply.
LI et al.: TRANSIENT STABILITY OF GRID-FORMING DFIG 15891
Fig. 16. Reactive-current-controlled mode under grid voltage sag. Fig. 19. Transient stability when Pref decreases from 0.7 to 0.35 p.u.
Fig. 17. Transient instability when Vg drops from 1 to 0.2 p.u. Fig. 20. Dynamic error between href and hpcc: (a) increasing Kp,q; and
(b) increasing Ki,q.
B. Transient Stability Problem of GFM-DFIG However, this dynamic angle error can never be eliminated even
Figure 17 shows the transient instability of GFM-DFIG due to pushing the VOC parameter to its limitation. In fact, the PCC
the increasing depth of grid voltage sag. Comparing with Fig. 16, voltage angle is changed by the flowing current on the line
the only change is that the postfault grid voltage drops from 0.5 impedance, and it is easier to be changed in low SCR grid. Con-
to 0.2 p.u. This instability is also shown in Fig. 18, comparing sidering the rate of change of PCC voltage angle is limited, it
with Fig. 16, the line inductance increases from 4 to 24 mL. Both cannot track to its command href as fast as it is desired. Besides,
the transient instability of Figs. 17 and 18 are manifested in the the flowing current on the line impedance is controlled by the
enlarged active power imbalance and the uncontrolled synchro- regulation of this dynamic angle error realized in VOC, so the
nous angle href, which suggests that a lower SCR and a severer inner voltage loop cannot be neglected in the large-signal model
voltage fault will induce the transient instability. of GFM-DFIG. This dynamic angle error will also be influenced
As a contrast to Fig. 18, the result of Fig. 19 is stable and the by the P-f droop gain. In Fig. 21, the dynamic angle error is
active power reference reduces to half the original, suggesting enlarged when increasing KP from 0.7 to 1.5 p.u. Specially, the
that GFM-DFIG is tend to be stable under a lower active power system will be unstable due to the overlarge dynamic angle error
reference when grid voltage dips. when KP is 1.5 p.u.
The impacts of VOC parameters and P-f droop gain are given
as Figs. 20 and 21, where the dynamic error between href and C. Comparison of HSC and EHSC Methods
hpcc is observed during the active power synchronization (Pref ¼ The result of Fig. 18 is used here to illustrate the function of HSC
0.7 p.u., Lg ¼ 24 mL). As shown in Fig. 20(a) and 20(b), the method and EHSC method, where Pref ¼ 0.7 p.u., Lg ¼ 24 mL,
dynamic angle error will decrease with larger Kpq or Kiq. and the grid voltage drops from 1 to 0.5 p.u.
Authorized licensed use limited to: State Grid Corporation of China (SGCC). Downloaded on November 27,2024 at 08:50:38 UTC from IEEE Xplore. Restrictions apply.
15892 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 71, NO. 12, DECEMBER 2024
Fig. 22. Effect of HSC method: Vg ¼ 0.5 p.u., Pref ¼ 0.7 p.u., Lg ¼ 24 mL.
Fig. 25. Effect of EHSC method (Vg ¼ 0.2 p.u., Pref ¼ 0.7 p.u., Lg ¼
24 mL): (a) results of active power and synchronous angle. (b) result of
PCC voltage.
Fig. 24. Effect of EHSC method (Vg ¼ 0.2 p.u., Pref ¼ 0.7 p.u., Lg ¼ VI. CONCLUSION
4 mL): (a) results of active power and synchronous angle and (b) result of
PCC voltage. To investigate the transient behavior of the DFIG-based WT
with GFM control under a symmetrical grid voltage fault, the
In Figs. 22 and 23, the uncontrolled synchronous angle reduced-order large-signal model is established in this article,
depicted by red line and the imbalanced active power depicted through which two types of transient instability for GFM-DFIG
by purple line are the unstable results. The results of angle refer- is revealed. The first is induced by the inexistence of postfault
ence and active power with HSC/EHSC method applied are EP. The second is induced by the excessive dynamic deviation
denoted by blue and green line, respectively. between synchronous angle and PCC voltage angle. An EHSC
In Fig. 22, the synchronous angle and active power are still method based on adaptive integrator is proposed to improve its
divergent when HSC method is applied, but the divergence transient stability during a symmetrical grid voltage fault. The
speed is slowed down. In the previous analysis, when HSC main conclusions can be summarized as follows.
method is applied on a GFM-DFIG with VOC, it cannot provide 1) The transient behavior of GFM-DFIG conforms to the
a new postfault EP if the original postfault EP does not exist, general rules of GFM control. During a symmetrical grid
while its only contribution on enhancing transient stability is voltage sag, the active power imbalance will be enlarged
improving the transient damping. This conclusion can be well with lower SCR and grid voltage, or higher active power
validated by the result of Fig. 22. instruction, causing the absence of postfault EP.
Authorized licensed use limited to: State Grid Corporation of China (SGCC). Downloaded on November 27,2024 at 08:50:38 UTC from IEEE Xplore. Restrictions apply.
LI et al.: TRANSIENT STABILITY OF GRID-FORMING DFIG 15893
2) Differing with GFM-VSC, whose inner voltage dynamic [16] D. Pan, X. Wang, F. Liu, and R. Shi, “Transient stability of voltage-
can be neglected during transient. A GFM-DFIG using source converters with grid-forming control: A design-oriented study,”
IEEE J. Emerg. Sel. Topics Power Electron., vol. 8, no. 2,
P-f droop controller exhibits underdamped feature due to pp. 1019–1033, Jun. 2020.
the lag characteristic introduced by VOC, which is not [17] J. Lei, X. Xiang, B. Liu, W. Li, and X. He, “Transient stability analysis
consistent with the overdamped P-f droop control. of grid forming converters based on damping energy visualization and
geometry approximation,” IEEE Trans. Ind. Electron., vol. 71, no. 3,
3) The HSC method can enhance the transient stability of pp. 2510–2521, Mar. 2024.
GFM control by improving the transient damping and [18] X. Fu et al., “Large-signal stability of grid-forming and grid-following
the postfault EP. However, it is unsuitable for a GFM- controls in voltage source converter: A comparative study,” IEEE
Trans. Power Electron., vol. 36, no. 7, pp. 7832–7840, Jul. 2021.
DFIG, whose VOC forces PCC voltage angle tracking [19] P. Ge, C. Tu, F. Xiao, Q. Guo, and J. Gao, “Design-oriented analysis and
its angle command. The proposed EHSC method can transient stability enhancement control for a virtual synchronous generator,”
resolve this problem by introducing a compensation fre- IEEE Trans. Ind. Electron., vol. 70, no. 3, pp. 2675–2684, Mar. 2023.
[20] X. He, S. Pan, and H. Geng, “Transient stability of hybrid power
quency to its synchronous angle, which is adaptive to systems dominated by different types of grid-forming devices,” IEEE
grid voltage, SCR and postfault active power instruction. Trans. Energy Convers., vol. 37, no. 2, pp. 868–879, Jun. 2022.
[21] X. Xiong, C. Wu, P. Cheng, and F. Blaabjerg, “An optimal damping
design of virtual synchronous generators for transient stability
REFERENCES enhancement,” IEEE Trans. Power Electron., vol. 36, no. 10,
pp. 11026–11030, Oct. 2021.
[1] Q. Peng, Q. Jiang, Y. Yang, T. Liu, H. Wang, and F. Blaabjerg, “On
[22] M. Chen, D. Zhou, and F. Blaabjerg, “Enhanced transient angle stability
the stability of power electronics-dominated systems: Challenges
control of grid-forming converter based on virtual synchronous generator,”
and potential solutions,” IEEE Trans. Ind. Appl., vol. 55, no. 6,
IEEE Trans. Ind. Electron., vol. 69, no. 9, pp. 9133–9144, Sep. 2022.
pp. 7657–7670, Nov. 2019.
[23] H. Wu and X. Wang, “A mode-adaptive power-angle control method
[2] J. Ma, Y. Shen, and A. G. Phadke, “DFIG active damping control
for transient stability enhancement of virtual synchronous generators,”
strategy based on remodeling of multiple energy branches,” IEEE
IEEE J. Emerg. Sel. Topics Power Electron., vol. 8, no. 2,
Trans. Power Electron., vol. 36, no. 4, pp. 4169–4186, Apr. 2021.
pp. 1034–1049, Jun. 2020.
[3] Y. Zhou, D. Zhu, X. Zou, C. He, J. Hu, and Y. Kang, “Adaptive
[24] E. Rokrok, T. Qoria, A. Bruyere, B. Francois, and X. Guillaud, “Transient
temporary frequency support for DFIG-based wind turbines,” IEEE
stability assessment and enhancement of grid-forming converters
Trans. Energy Convers., vol. 38, no. 3, pp. 1937–1949, Sep. 2023.
embedding current reference saturation as current limiting strategy,” IEEE
[4] Z. Dong, Z. Li, L. Du, Y. Liu, and Z. Ding, “Coordination strategy of
Trans. Power Syst., vol. 37, no. 2, pp. 1519–1531, Mar. 2022.
large-scale DFIG-based wind farm for voltage support with high
[25] S. P. Me et al., “Transient stability analysis of virtual synchronous
converter capacity utilization,” IEEE Trans. Sustain. Energy, vol. 12,
generator equipped with quadrature-prioritized current limiter,” IEEE
no. 2, pp. 1416–1425, Apr. 2021.
Trans. Power Electron., vol. 38, no. 9, pp. 10547–10553, Sep. 2023.
[5] L. Huang, H. Xin, L. Zhang, Z. Wang, K. Wu, and H. Wang,
[26] Z. Li, Z. Xie, and X. Zhang, “An improved strategy of grid-forming
“Synchronization and frequency regulation of DFIG-based wind turbine
DFIG based on disturbance rejection stator flux control,” IEEE Trans.
generators with synchronized control,” IEEE Trans. Energy Convers.,
Ind. Electron., vol. 71, no. 3, pp. 2498–2509, Mar. 2024.
vol. 32, no. 3, pp. 1251–1262, Sep. 2017.
[27] S. Wang and L. Shang, “Fault ride through strategy of virtual-
[6] H. Nian and Y. Jiao, “Improved virtual synchronous generator control
synchronous-controlled DFIG-based wind turbines under symmetrical
of DFIG to ride-through symmetrical voltage fault,” IEEE Trans.
grid faults,” IEEE Trans. Energy Convers., vol. 35, no. 3,
Energy Convers., vol. 35, no. 2, pp. 672–683, Jun. 2020.
pp. 1360–1371, Sep. 2020.
[7] “Voluntary specification for grid-forming inverters,” AEMO Tech.
[28] I. Oraa, J. Samanes, J. Lopez, and E. Gubia, “Single-loop droop control
Rep., 2023. [Online]. Available: https://aemo.com.au/-/media/files/
strategy for a grid-connected DFIG wind turbine,” IEEE Trans. Ind.
initiatives/primary-frequency-response/2023/gfm-voluntary-spec.pdf
Electron., vol. 71, no. 8, pp. 8819–8830, Aug. 2024.
[8] W. Wu et al., “Sequence impedance modeling and stability comparative
[29] R. Rosso, X. Wang, M. Liserre, X. Lu, and S. Engelken, “Grid-forming
analysis of voltage-controlled VSGs and current-controlled VSGs,”
converters: Control approaches, grid-synchronization, and future
IEEE Trans. Ind. Electron., vol. 66, no. 8, pp. 6460–6472, Aug. 2019.
trends—A review,” IEEE Open J. Ind. Appl., vol. 2, pp. 93–109, 2021.
[9] X. Zhang, D. Xia, Z. Fu, G. Wang, and D. Xu, “An improved
[30] L. Harnefors, J. Kukkola, M. Routimo, M. Hinkkanen, and X. Wang,
feedforward control method considering PLL dynamics to improve
“A universal controller for grid-connected voltage-source converters,”
weak grid stability of grid-connected inverters,” IEEE Trans. Ind. Appl.,
IEEE J. Emerg. Sel. Topics Power Electron., vol. 9, no. 5,
vol. 54, no. 5, pp. 5143–5151, Sep. 2018.
pp. 5761–5770, Oct. 2021.
[10] M. G. Taul, X. Wang, P. Davari, and F. Blaabjerg, “Current limiting
[31] T. Liu and X. Wang, “Physical insight into hybrid-synchronization-
control with enhanced dynamics of grid-forming converters during fault
controlled grid-forming inverters under large disturbances,” IEEE Trans.
conditions,” IEEE J. Emerg. Sel. Topics Power Electron., vol. 8, no. 2,
Power Electron., vol. 37, no. 10, pp. 11475–11480, Oct. 2022.
pp. 1062–1073, Jun. 2020.
[32] X. Guo et al., “Analysis and enhancement of active power transfer
[11] K. Shi, W. Song, P. Xu, R. Liu, Z. Fang, and Y. Ji, “Low-voltage ride-
capability for DFIG-based WTs in very weak grid,” IEEE J. Emerg. Sel.
through control strategy for a virtual synchronous generator based on
Topics Power Electron., vol. 10, no. 4, pp. 3895–3906, Aug. 2022.
smooth switching,” IEEE Access, vol. 6, pp. 2703–2711, 2018.
[12] Z. Shuai, W. Huang, C. Shen, J. Ge, and Z. J. Shen, “Characteristics
and restraining method of fast transient inrush fault currents in
synchronverters,” IEEE Trans. Ind. Electron., vol. 64, no. 9,
pp. 7487–7497, Sep. 2017.
[13] J. Hu, B. Wang, W. Wang, H. Tang, Y. Chi, and Q. Hu, “Small signal
dynamics of DFIG-based wind turbines during riding through
symmetrical faults in weak AC grid,” IEEE Trans. Energy Convers., Zhe Li received the B.S degree in electrical
vol. 32, no. 2, pp. 720–730, Jun. 2017. engineering and automation in 2019 from Hefei
[14] Y. Ma, D. Zhu, Z. Zhang, X. Zou, J. Hu, and Y. Kang, “Modeling and University of Technology, Hefei, China, where
transient stability analysis for type-3 wind turbines using singular he is currently working toward the Ph.D. degree
perturbation and lyapunov methods,” IEEE Trans. Ind. Electron., in electrical engineering.
vol. 70, no. 8, pp. 8075–8086, Aug. 2023. His research interests include modeling and
[15] P. Sun, J. Yao, R. Liu, J. Pei, H. Zhang, and Y. Liu, “Virtual control of wind turbine generation system,
capacitance control for improving dynamic stability of the DFIG-based renewable energy generation, and the power
wind turbines during a symmetrical fault in a weak ac grid,” IEEE electronics application in power systems.
Trans. Ind. Electron., vol. 68, no. 1, pp. 333–346, Jan. 2021.
Authorized licensed use limited to: State Grid Corporation of China (SGCC). Downloaded on November 27,2024 at 08:50:38 UTC from IEEE Xplore. Restrictions apply.
15894 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 71, NO. 12, DECEMBER 2024
Zhen Xie (Member, IEEE) was born in Anhui, Xing Zhang (Senior Member, IEEE) was born
China, in 1976. He received the Ph.D. degree in in Shanghai, China, in 1963. He received the
electrical engineering from Hefei University of B.S., M.S., and Ph.D. degrees in electrical engi-
Technology, Hefei, China, in 2005. neering and automation from Hefei University of
From 2005 to 2008, he has been a Lecturer Technology, Hefei, China, in 1984, 1990, and
with the School of Electrical Engineering and 2003, respectively.
Automation, Hefei University of Technology, Since 1984, he has been a Faculty Member
where he is currently a Professor. His current with the School of Electric Engineering and
research interests include the control of doubly Automation, Hefei University of Technology,
fed induction generators for wind power genera- where he is currently a Professor. He is also
tion and renewable energy conversion systems. with the Photovoltaic Engineering Research
Center of the Ministry of Education. His research interests include photo-
voltaic generation technologies, wind power generation technologies,
and distributed generation systems.
Shang Xu received the B.S degree in electrical
engineering and automation in 2020 from Hefei
University of Technology, Hefei, China, where
he is currently working toward the Ph.D. degree
in electrical engineering.
His research interests include control and
modeling of wind power generation systems,
system stability analysis, renewable energy gen-
eration, and motor control with power electronics
devices.
Authorized licensed use limited to: State Grid Corporation of China (SGCC). Downloaded on November 27,2024 at 08:50:38 UTC from IEEE Xplore. Restrictions apply.