Unit-3-1
Unit-3-1
Differential Relay:
➢ A differential relay is defined as the relay that operates when the phase difference of two or more
identical electrical quantities exceeds a predetermined / threshold value.
➢ The differential relay works on the principle of comparison between the phase angle and
magnitude of two or more similar electrical quantities.
ID Operating
Coil
Transformer Protection:
Types of Faults in Transformer:
1. Fault in the auxiliary equipment (Transformer Oil, Gas Cushion, Oil Pumps and Forced Air
Fans, Core and Winding Insulation)
2. Fault in the transformer windings and connections (Phase-Phase Faults, Phase-Earth Faults)
3. Overloads and external short circuits
Types of Relays used in Three-phase Transformer Protection:
Sl. No. High-Voltage Side Low-Voltage Side Common Relay on Both Side
1. Over-Current Relay Over-Current Relay Percentage Differential Relay
2. Over-Voltage Relay Over-Voltage Relay Buchholz Relay
3. Earth Fault Relay Earth Fault Relay
4. Over-Flux Relay Over-Flux Relay
Percentage Differential Protection for a Transformer Winding:
➢ The fault occurs on the transformer is mainly divided into two type external faults and internal
fault. External fault is cleared by the relay system outside the transformer within the shortest
possible time in order to avoid any danger to the transformer due to these faults.
➢ The protection for internal fault in such type of transformer is to be provided by using differential
protection system. Differential protection schemes are mainly used for protection against phase-
to-phase fault and phase to earth faults. The differential protection used for power transformers is
based on Merz-Prize circulating current principle.
➢ In case of power transformer of star-delta / delta-star configuration. Their exist 30-degree phase
difference between primary and secondary currents which causes unequal currents flow in the pilot
wire. Hence, the percentage differential relay will also produce trip signal without any fault in the
power transformer. To compensate effect, CT on the corresponding side of the power transformer
is connected in the opposite configuration of power transformer.
For Example: The power transformer is star connected on one side and delta connected on the
other side. The CTs on the star connected side are delta-connected and those on delta-connected
side are star-connected. The neutral of the current transformer star connection and power
transformer star connections are grounded.
Generator Protection:
Types of Faults in Generator and Types of Relays Used:
Sl. No. Types of Faults Name of Relay
Phase-Phase Faults Percentage Differential Relay
1. Stator Fault Inter-Phase Faults Split-Phase Relay
Earth Faults Restricted Earth Fault Relay
2. Rotor Fault Earth Faults Sensitive Earth Fault Relay
Failure of Prime Mover Reverse Power Relay
Loss of Excitation / Field
OFFSET Mho Relay
Failure
External Faults /
3. Abnormal Running Over-speeding Flyball Governor
Conditions Over-loading Over-current Relay
Over-voltage Over-voltage Relay
Unbalanced Loading Negative Sequence Current Relay
Percentage Differential Protection for a Generator Winding:
➢ The percentage differential relay gives protection against short circuit fault (phase-phase faults
and phase-earth faults) in the stator winding of a generator.
➢ When the neutral point of the windings is available then the CTs may be connected in star on both
the phase outgoing side and the neutral earth side as shown in the above figure.
➢ If the neutral point is not available, then the phase side CTs are connected in a residual connection.
(So that it can be made suitable for comparing the current with the generator ground point CT
secondary current.)
➢ The restraining coils are energized from the secondary connection of CTs in each phase through
pilot wires. The operating coils are energized by the tappings from restraining coils and the CT
neutral earthing connection.
➢ In single-turn generator, there is no inter-turn faults. But in multi-turn generator, the inter-turn fault
protection is necessary for each phase winding such as hydroelectric generators.
➢ These generators have double winding armatures. This means, each phase winding is divided into
two halves, due to the very heavy currents which they have to carry.
➢ This splitting of single-phase winding into two is advantageous in providing inter-turn fault
protection to such hydroelectric generators.
Restricted Earth Fault Protection for a Generator Winding:
➢ This type of protection is provided to detect earth-faults within the protected zone of the generator
/ alternator. The typical arrangement of restricted earth fault protection of a generator is shown
below.
➢ For Example: Let F1 be the external fault occurs in the network. This fault induces the I1 and
I2 current which flows in the secondary of the CTs. The resultant current of the I1 and I2 becomes
zero in the relay. When the fault occurs inside the protective zone say F2, then only current I2 exist,
and I1 is neglected. The current I2 passes through the earth fault relay. The earth fault relay operates
only for the internal fault of the protective zone.
Restricted Earth
Fault Relay
➢ A small DC power supply is connected to the field circuit. A fault detecting sensitive relay and the
resistance are also connected in series with the circuit. This high resistance limits the current
through the circuit.
➢ A fault at any point on the field circuit will pass a current of sufficient magnitude through the relay
to cause its operation. The DC supply is preferred and simple to use and it has no problem of the
leakage currents.
Prime-Mover Failure Protection:
➢ A synchronous Generator / Alternator is expected to supply active power to the system in normal
operating condition.
➢ If the turbine i.e., prime mover fails the Generator / Alternator connected to the system will
continue to operate as synchronous Motor drawing active power from the system.
➢ This reversal of power flow due to loss of prime mover can be detected by reverse power relay.
Normal P
Q
P
Failure Q
P = Active Power
Q = Reactive Power
OFFSE Fiel
T Mho Relay Normal
P
d
P = Active Power Q
Fail
ure
Q = Reactive Power P
Field Failure Q
OFFSET
Mho Relay
Field Failure
Busbar Protection:
Busbar:
➢ An electrical busbar is defined as a conductor or a group of conductors used for collecting electric
power from the incoming feeders and distributes them to the outgoing feeders.
➢ In other words, it is a type of electrical junction in which all the incoming and outgoing electrical
current meets. Thus, the electrical busbar collects the electric power at one location.
➢ The busbar system consists the isolator and circuit breaker. On the occurrence of a fault, the circuit
breaker is tripped off and the faulty section of the busbar is easily disconnected from the circuit.
8. Mesh Arrangement:
➢ In such type of arrangement, the circuit breakers are installed in the mesh formed by the buses.
The circuit is tapped from the node point of the mesh. Such type of bus arrangement is controlled
by four circuit breakers.
➢ When a fault occurs on any section, two circuit breakers have to open, resulting in the opening of
the mesh. Such type of arrangement provides security against busbar fault. It is preferred for
substations having a large number of circuits.
Busbar Protection / Busbar Differential Protection:
➢ Busbar Differential Protection or Circulating Current Protection is working under the principle of
differential protection.
➢ The current transformers are arranged as shown in the figure. Under normal condition, Incoming
current into the busbar is equal to the outgoing current from the busbar, therefore the net circulating
current is equal to zero. Since the relay become inoperative.
➢ Under abnormal condition, the fault in the protected zone, the current become unequal. Therefore,
there is circulating will be present in the relay circuit. If the circulating current is higher than the
pickup current the relay trips all circuit breaker.