Cooling & Heating Load Calculation (Sample)
Cooling & Heating Load Calculation (Sample)
Email : [email protected]
25.05.2022
COOLING & HEATING LOAD CALCULATION
78 AIRPORT BOULEVARD #B2-227/228 JEWEL CHANGI AIRPORT SINGAPORE 819666
ROOM DIMENSION FOR REFRESHMENT AREA
Note: Occupancy for refreshment area calcuated based on seating table/chair arrangement layout plan.
Ceiling Recessed
2 Adjustable LED 14 179 0.8 2005 -
Downlight
5 Emergency Light 3 12 1 36 -
6 Exit Light 1 6 1 6 -
ASHRAE
1 People 75 95 207 0.85 29912
HANDBOOK
Table D: Ventilation Heat Gain is excluded due to return air grille provided.
Table E: Transmission Heat Gain is not require to include due to surrounding area under air-conditioning.
Table F: Solar Heat Gain is not require to include due to located at basement level 2.
1 Btu/h = 0.29308 W
Email : [email protected]
25.05.2022
COOLING & HEATING LOAD CALCULATION
78 AIRPORT BOULEVARD #B2-227/228 JEWEL CHANGI AIRPORT SINGAPORE 819666
ROOM DIMENSION FOR KITCHEN AREA
OCCUPANCY (Pax) 13
Note: Occupancy for kitchen area calcuated based on TABLE 1.4B : occupant load factors (10 m2/ person) from fire code 2018.
2 Emergency Light 3 8 1 24 -
3 Exit Light 1 7 1 7 -
ASHRAE
1 People 95 95 13 0.85 2100
HANDBOOK
Table D: Ventilation Heat Gain is excluded due to return air grille provided.
Table E: Transmission Heat Gain is not require to include due to surrounding area under air-conditioning.
Table F: Solar Heat Gain is not require to include due to located at basement level 2.
1 Btu/h = 0.29308 W