ASTM F-13(2024)
ASTM F-13(2024)
for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
INTRODUCTION
Passive fire protection materials have been required and used on commercial ships for decades. The
passive systems include the non-combustible insulation material and its means of attachment to steel
or aluminum divisions. The passive system has been evaluated in a standard fire test using a standard
steel or aluminum structural core. No impact loading has been required prior to testing for fire
resistance.
The United States Navy requires shock testing of passive fire protection prior to fire resistance
testing; this test is defined in MIL-STD-3020, Fire Resistance of U.S. Naval Surface Ships, 7
November, 2007. The technology to economically shock test the passive fire protection systems was
developed 50 years ago, and equipment in commercial laboratories is available.
After the terrorist attack on September 11, 2001, it is our responsibility that we add a level of shock
protection to our passive fire protection systems on commercial ships where appropriate.2 Many of the
passive fire protection systems used today are mechanically fastened and will perform the intended
function after a shock event.
Passive fire protection insulation may have thermal or acoustic treatments added to the insulated
division. These treatments add mass to the fire protection system and their effect on shock is not
included in this specification.
TABLE OF CONTENTS
Introduction
Section 1 Scope
Section 2 Referenced Documents
Section 3 Terminology
Section 4 Significance and Use
Section 5 Shock Test Prior to Fire Resistance Test
Section 6 Criteria to Evaluate Shock Test Specimens
Section 7 Post Shock Fire Resistance Test
Section 8 Criteria to Evaluate the Fire Resistance of the Shock Tested Specimen
Section 9 Test Report
Section 10 Precision and Bias
Section 11 Keywords
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
FIG. 2 Aluminum Test Specimen Construction Details for A-Class FIG. 4 Aluminum Test Specimen Construction Details for A-Class
Bulkhead Deck
9. Test Report
9.1 A test report shall be written by the shock test laboratory
FIG. 8 Deck Orientations
for the shock test, irrespective of the outcome of the test.
9.1.1 The shock test report shall be written by the shock test
laboratory personnel and shall include:
9.1.1.1 Description of the insulation to include weights of
6.1.3 The insulation develops a noticeable crack or void
each piece of material installed on the test specimen.
which exposes the test specimen to direct heat transfer path
from the fire exposure.
6.2 If adhesives are used to attach the insulation to the
standard structural core, any of the following observations
would deem the insulation system has failed the shock test.
6.2.1 The insulation cracks exposing the test specimen.
6.2.2 The insulation comes adrift forming a direct heat
transfer path to the test specimen.
6.2.3 The insulation becomes loose and forms a noticeable
void within the insulation itself or between the insulation and
the test specimen.
9.2 Electronic copies of the test report shall be sent to the 11. Keywords
client and or their designee. A copy of the videos and 11.1 A-Class division; shock test; structural insulation;
photographs shall be sent to the client on a CD. structural fire protection
APPENDIX
(Nonmandatory Information)
X1. DISCUSSION OF RESTRICTED AND UNRESTRICTED INSULATION ON A-CLASS STEEL AND ALUMINUM DIVISIONS
X1.1 Introduction on the bare steel side. This type of system is tested with the
X1.1.1 The International Code for Application of Fire Test stiffened side of the steel division as the unexposed side, see
Procedures, FTP Code, became mandatory under the SOLAS Fig. X1.3.
Convention and entered in the force 1 July, 1998. Structural X1.3.3 In the second unrestricted steel bulkhead
insulations are approved for steel and aluminum division in configuration, the same insulation is installed on each side of
accordance with Part 3 Test for “A,” “B,” and “F” class the bulkhead, see Fig. X1.4. All unrestricted aluminum bulk-
divisions, 2010 FTP Code, 2012 Edition. The 2012 Edition of head divisions shall be insulated on both sides. When fire
the FTP Code entered into force on 1 July, 2012; all approvals testing the stiffened side of the division is the unexposed side.
for structural fire protection shall be tested and approved by the
2012 Edition of the FTP Code after 1 July, 2013.
X1.1.2 The purpose of this commentary is to explain
restricted and unrestricted A-Class structural insulation sys-
tems for steel and aluminum divisions. Steel division for A-0
class bulkheads and decks are exempt from testing when they
are constructed in accordance with Annex 2, 3 “A,” “B,” and
“F” class divisions, of 2012 FTP Code. All structural insulation
for aluminum divisions must be tested.
X1.2 Restricted Structural Insulation Systems
X1.2.1 A restricted structural insulation system will provide
protection from a fire even when the insulation and the fire
exposure are on the same side. A restricted bulkhead is
insulated on the exposed stiffened side, see Fig. X1.1. A deck
is insulated from below on the exposed stiffened side, see Fig.
X1.2. If the deck insulated system is successfully tested, that
system is also acceptable for a restricted bulkhead.
X1.3 Unrestricted Structural Insulation System for Bulk-
heads
X1.3.1 An unrestricted structural insulation system will
provide protection from a fire event when the fire exposure is FIG. X1.1 A-Class Restricted Bulkhead, Steel or Aluminum
from either side of the bulkhead.
X1.3.2 Steel bulkhead divisions can have two configuration
of unrestricted insulation. In one case the insulation is installed
on the unexposed side of the bulkhead and the fire exposure is
This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years and
if not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standards
and should be addressed to ASTM International Headquarters. Your comments will receive careful consideration at a meeting of the
responsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you should
make your views known to the ASTM Committee on Standards, at the address shown below.
This standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,
United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the above
address or at 610-832-9585 (phone), or through the ASTM website (www.astm.org/contact). Permission rights to photocopy the
standard may also be secured from the Copyright Clearance Center, 222 Rosewood Drive, Danvers, MA 01923, Tel: (978) 646-2600;
http://www.copyright.com/