BSD- LOADS (2)
BSD- LOADS (2)
Slab Loads:
Kpa/mm
Superimposed Dead Load:
Slab weight 2.950 kpa h= 125 mm
Ceiling 0.008 0.102 kpa h= 12.7 mm
Floor finish 0.023 0.575 kpa h= 25 mm
Partition 1.00 kpa
Windows, Glass, Frames & Sash 0.38 kpa
Live Load:
Office 2.4 kpa
Store 4.8 kpa
L S L/S
7.5 4 1.875 <2.0, Two-way
LOAD DISTRIBUTION:
SLAB 1: DEAD LOAD:
Long Side: 7.5 m L/S 1.875
Short Side: 4 m Design as: Two Way
Stair Loading:
Kpa/mm
Superimposed Dead Load:
Slab weight (landing) 2.950 kpa
Floor finish 0.023 0.575 kpa t=
Weight of waist 5.01 kpa R=
Weight of Steps 2.36 kpa T=
Live Load:
Stair 1.9 kpa
SLAB 5: DEAD LOAD:
Long Side: 2.89 m L/S 2.627
ONE-WAY B15
Short Side: 1.1 m Design as: SLAB B8
Landing Dimension:
L 1 m
W 1 m
SECOND FLOOR (KN/M)
Wall Load:
2.622 kN/m (Lightweight: Full Grout)( t = 100 mm) for B5
8.046 kN/m (Lightweight: Full Grout)( t = 100 mm)
10.989 kN/m (Lightweight: Full Grout)( t = 200 mm) with firewall
Beam Weight for Long Span:
4.956 kN/m
Beam Weight for Short Span:
2.36 kN/m
150 mm
200 mm
200 mm
LIVE LOAD: DEAD LOAD (UDL):
5.990 kN/m 1.045 kN/m 4.956 kN/m
5.990 kN/m 1.045 kN/m - kN/m
LOAD (UDL):
kN/m
Unit weight of Conc
23.6 kn/m^3
BEAM LOADS:
Beam(landing):
L S L/S
7.5 4 1.875 <2.0, Two-way
LOAD DISTRIBUTION:
SLAB 1: DEAD LOAD:
Long Side: 7.5 m L/S 1.875
Short Side: 4 m Design as: Two Way
L=7500-350 7150
L/10 715 700
L/12 595.833333 600
b 350
b/d > 0.3 0.58333333
BEAM LOADS:
Member DL LL UDL TOTAL DL(KN/M)
B1 5.8672 1.2 6.446 12.3132
B2 11.7344 2.4 4.956 16.6904
B3 11.7344 2.4 4.956 16.6904
B4 11.7344 2.4 4.956 16.6904
B5 5.8672 1.2 6.446 12.3132
B6 5.8672 1.2 3.85 9.7172
B7 5.8672 1.2 5.885 11.7522
B8 5.8672 1.2 3.85 9.7172
B9 5.8672 1.2 5.885 11.7522
B10 5.8672 1.2 3.85 9.7172
B11 5.8672 1.2 5.885 11.7522
B12 5.8672 1.2 3.85 9.7172
B13 5.8672 1.2 5.885 11.7522
Beam Dimension for ShortSpan:
H 400 0.4
W 250 0.25
BEAM WEIGHT: 2.36
L=4000-350 3650
L/10 365 400
L/12 304.1667
b 250
b/d > 0.3 0.625
SECOND FLOOR
DEAD LOAD: 5.007 kpa
Tributary: 2.000 m
SLAB
Slab 1: 150.198 KN
Slab 2: 150.198 KN
Slab 3: 150.198 KN
Slab 4: 150.198 KN
BEAM
B1 37.170 KN
B2 37.170 KN
B3 37.170 KN
B4 37.170 KN
B5 37.170 KN
B6 9.440 KN
B7 9.440 KN
B8 9.440 KN
B9 9.440 KN
B10 9.440 KN
B11 9.440 KN
B12 9.440 KN
B13 9.440 KN
Walls
W1 60.345 KN
W2 60.345 KN
W3 60.345 KN
W4 60.345 KN
W5 7.695 KN
W6 32.184 KN
W7 43.956 KN
W8 32.184 KN
W9 43.956 KN
W10 4.104 KN
W11 43.956 KN
W12 32.184 KN
W13 43.956 KN
Total weight of Wall: 525.555 KN
Beam(landing):
Member DL LL UDLTOTAL DL(Kn/m)
WDL(KN)
B15 5.990 1.045 4.956 10.946 31.635
TOTAL WEIGHT :
ROOF SLAB AND BEAM WEIGHT
DEAD LOAD: 2.934 kpa
Tributary: 2.000 m
SLAB
Slab 1: 88.008 KN
Slab 2: 88.008 KN
Slab 3: 88.008 KN
Slab 4: 88.008 KN
BEAM
B1 37.170 KN
B2 37.170 KN
B3 37.170 KN
B4 37.170 KN
B5 37.170 KN
B6 9.440 KN
B7 9.440 KN
B8 9.440 KN
B9 9.440 KN
B10 9.440 KN
B11 9.440 KN
B12 9.440 KN
B13 9.440 KN
Parapet Wall
W1 11.175 KN
W5 11.175 KN
W6 5.960 KN
W7 14.100 KN
W8 5.960 KN
W9 14.100 KN
W10 5.960 KN
W11 14.100 KN
W12 5.960 KN
W13 14.100 KN
Total weight of Wall: 102.590 KN
2135.344 KN
EIGHT
MAIN WIND FORCE RESISTING SYSTEM
DIMENSIONS
Roof Type Flat Roof
Parapet Height (m) 7.26
Angle 1°
Length, B 16
Width, L 7.5
WALLS
RISK CATEGORY II
BASIC WIND SPEED,V (m/s) 72.22222222
WIND LOAD PARAMETERS:
0.85
Wind Directionality Factor, Kd B
Exposure Category 1
Topographic Factor, Kzt 0.85
Gust Effect Factor, G
Enclosure Classification Enclosed
Internal Pressure Coefficient, GCpi 0.18
VELOCITY PRESSURE EXPOSURE COEFFICIENT, Kz
z (0-4.5) 0.57
z (6) 0.62
z (6.5) 0.63
VELOCITY PRESSURE, qz or qh
qz (0-4.5) 1549.158843
qz (6) 1685.049969
qh (6.5) 1712.228194
EXTERNAL PRESSURE COEFFICIENT, CP
0.8
Windward Wall
Leeward Wall -0.5
Side Wall -0.7
WIND PRESSURE, p (kPa), 0-4.5 Case 1
0.7745794213
Windward Wall
Leeward Wall
Side wall
Windward Wall
Leeward Wall -1.035898058
Side wall -1.326976851
WIND PRESSURE, p (kPa), 6 Case 1
0.8425249846
Windward Wall
Leeward Wall -1.035898058
Side wall -1.326976851
WIND PRESSURE, p (kPa), 6.5 Case 1
0.8561140972
Windward Wall
Leeward Wall -1.035898058
Side wall -1.326976851
Windward Wall
Leeward Wall
L/B
0.46875
PARAPET
II VELOCITY PRESSURE EXPOSURE COEFFICIENT, Kp 0.65
72.22222222 VELOCITY PRESSURE, qp 1766.5846
COMBINED NET PRESSURE COEFFICIENT, GCpn
0.85 Windward 1.5
B Leeward -1.0
1 WIND PRESSURE, P kPa
0.85 Windward ###
Enclosed Leeward ###
-0.18
0.57
0.62
0.63
1549.158843
1685.049969
1712.228194
0.8
-0.5
-0.7
Case 2
1.332276605
-0.4194959076
-0.7105747007
Case 2
1.449142973
-0.4194959076
-0.7105747007
Case 2
1.472516247
-0.4194959076
-0.7105747007
Case 1 Case 2
82.839 142.483
107.733 43.628
211.772 171.978
LOAD ANALYSIS PROCEDURE
1. Occupancy Category OCCUPANCY CATEGORY
2. Importance Factor (I) IMPORTANCE FACTOR, I
3. Soil Profile Type SOIL PROFILE TYPE
4. Seismic Zone SEISMIC ZONE
5. Seismic Zone Factor (Z) SEISMIC ZONE FACTOR, Z
6. Basic Seismic Force Resisting System
BASIC SEISMIC FORCE RESISTING SYSTEM
7. Seismic Source Type
8. Distance from the nearest Active Fault SEISMIC SOURCE TYPE
9. Near Source Factor (Na)
DISTANCE FROM THE NEAREST ACTIVE FAULT
10. Near Source Factor (Nv)
11. Seismic Coefficient (Ca) NEAR SOURCE FACTOR, Na
12. Seismic Coefficient (Cv) NEAR SOURCE FACTOR, Nv
13. R & Ω0 SEISMIC COEFFICIENT, Ca
14. Ct and hn SEISMIC COEFFICIENT, Cv
15. Period (T) Ct
16. Total Weight (W) hn
17. Design Base Shear (V) PERIOD, T
18. Additional Lateral force at the roof top (F i) TOTAL WEIGHT, W
DESIGN BASE SHEAR, V (kN
elevation (m)
Roof 6.5
2nd floor 3.5
V
ADDITIONAL LATERAL FORCE AT THE ROOF TOP, F t (k
170.78917 kN
DISTRIBUTE DESIGN BA
m
3
0
.
LEVEL, X WEIGHT, W
ROOF 715.992
174.62401 kN
2ND FLOOR 1419.352
m
3
5
.
345.41318 kN
Span
2
Span
2
5 4 3 2 1
A
Span 1
B
Span length (m)
1 7.5
2 16
II
1.25
SD
Zone 4
0.4
R Ω0
RCE RESISTING SYSTEM
8.5 2.8
SOURCE TYPE C
E NEAREST ACTIVE FAULT 2.0
CE FACTOR, Na 1.0
CE FACTOR, Nv 1.0
OEFFICIENT, Ca 0.44
OEFFICIENT, Cv 0.64
Ct 0.0731
hn 6.5
RIOD, T 0.2976
WEIGHT, W
DESIGN BASE SHEAR, V (kN) SEISMIC COEFFICIENT, Ca
SEISMIC COEFFICIENT, Cv
675.3664696
DESIGN BASE SHEAR, V
345.41318
129.18829
100.48927
V 345.41318
RCE AT THE ROOF TOP, F t (kN) 7.1951
Roof
Along 'X'-axis FRoof 163.59
k
FRAME k Fy (kN) FJ'y (kN)
∑k
1 6 0.2 163.59 32.72
2 6 0.2 163.59 32.72
3 6 0.2 163.59 32.72
4 6 0.2 163.59 32.72
5 6 0.2 163.59 32.72
30
2nd Floor
Along 'Y'-axis F2nd Floor 174.62
k
FRAME k FX (kN) FJ'x (kN)
∑k
A 3 0.5 174.62 87.31
B 3 0.5 174.62 87.31
6
2nd Floor
Along 'X'-axis F2nd Floor 174.62
k
FRAME k Fy (kN) FJ'y (kN)
∑k
1 6 0.2 174.62 34.92
2 6 0.2 174.62 34.92
3 6 0.2 174.62 34.92
4 6 0.2 174.62 34.92
5 6 0.2 174.62 34.92
30
0.44Na
0.64Nv
E SHEAR, V
0.31628
0.16176
0.06050
0.04706
ROOF
32.72 32.72 32.72 32.72
5 4 3 2 1
81.80
A
81.80 B
87.31
87.31
ROOF L
Basic Load Combinations:(page 66)
1.4(D + F)
1.2(D + F + T)+ 1.6(L+H)+0.5(Lr or R)
1.2D + 1.6(Lr or R) + (f1L or 0.5W)
1.2D + 1.0W +f1L +0.5(Lr or R)
1.2D + 1.0E + F1l
0.9D + 1.0W + 1.6H
0.9D + 1.0E + 1.6H
where:
f1 = 1.0 for floors in places of public assembly,
for live loads in excess of 4.8 kPa,
and for garage live load, or
= 0.5 for other live loads
D -
E -
Em 0 Basic Load Combinat
F 0 1.4D
H 0 1.2D+ 1.6L
L - 1.2D + f1L
Lr 0 1.2D + 1.0E + f1L
P 0 0.9D + 1.0E
R 0
T 0
W 0
f1 0.5
LOADS (kN/m)
Member DL LL UDL TOTAL DL SL(KN) 1.4UDL
ROOF LOAD COMBINATION B1 5.8672 1.2 6.446 12.3132 32.72 9.024
B2 11.7344 2.4 4.956 16.6904 32.72 6.938
B3 11.7344 2.4 4.956 16.6904 32.72 6.938
B4 11.7344 2.4 4.956 16.6904 32.72 6.938
B5 5.8672 1.2 6.446 12.3132 32.72 9.024
B6 5.8672 1.2 3.85 9.7172 81.80 5.390
B7 5.8672 1.2 5.885 11.7522 81.80 8.239
B8 5.8672 1.2 3.85 9.7172 81.80 5.390
B9 5.8672 1.2 5.885 11.7522 81.80 8.239
B10 5.8672 1.2 3.85 9.7172 81.80 5.390
B11 5.8672 1.2 5.885 11.7522 81.80 8.239
B12 5.8672 1.2 3.85 9.7172 81.80 5.390
B13 5.8672 1.2 5.885 11.7522 81.80 8.239
where:
f1 = 1.0 for floors in places of public assembly,
for live loads in excess of 4.8 kPa,
and for garage live load, or
= 0.5 for other live loads
D -
E -
Em 0.000
F 0.000
H 0.000
L -
Lr 0.000
P 0.000
R 0.000
T 0.000
W 0.000
f1 0.500
Summary of Loads:
Summary of Shear:
COND FLOOR LOAD COMBINATION
Member
FRAME 1 B1
FRAME 2 B2
FRAME 3 B3
FRAME 4 B4
FRAME 5 B5
FRAME B B6
FRAME A B7
FRAME B B8
FRAME A B9
FRAME B B10
FRAME A B11
FRAME B B12
FRAME A B13
B15
B8 (2.89m)
B16
MAX(7.5M)
MAX(4M)
SECOND FLOOR
Member (+)Mu (-)Mu
B1 166.973 185.548
B2 225.619 217.382
B3 231.051 201.038
B4 200.899 195.186
B5 112.690 163.903
B6 51.058 100.271
B7 37.617 100.290
B8 40.755 99.034
B9 27.219 89.930
B10 31.092 73.470
B11 26.655 89.608
B12 33.812 90.365
B13 28.007 93.025
5.990 1.045
ROOF BEAM
Member (+)Mu (-)Mu
B1 59.888 72.161
B2 81.116 80.445
B3 79.893 80.850
B4 79.893 79.868
B5 62.981 68.528
B6 13.775 29.455
B7 13.077 34.588
B8 10.259 31.672
B9 9.390 33.442
B10 11.300 30.097
B11 9.737 33.166
B12 10.019 90.365
B13 10.291 33.978
SECOND FLOOR
Within 2h Beyond 2h
123.330 105.334
168.745 149.049
165.714 146.025
144.866 127.586
95.730 85.139
78.032 68.671
82.810 71.687
90.527 80.914
72.924 61.862
51.681 46.132
73.483 62.355
68.415 59.309
72.689 62.141
168.745 149.049
90.527 80.914
2nd floor roof
1.2UDL 0.9UDL SL(KN) 1.4UDL 1.2UDL
15.602 11.702 32.719 9.024 7.735
5.947 4.460 32.719 6.938 5.947
5.947 4.460 32.719 6.938 5.947
5.947 4.460 32.719 6.938 5.947
9.924 7.443 32.719 9.024 7.735
15.602 11.702 81.797 5.390 4.620
19.134 14.351 81.797 8.239 7.062
15.602 11.702 81.797 5.390 4.620
19.134 14.351 81.797 8.239 7.062
7.178 5.384 81.797 5.390 4.620
19.134 14.351 81.797 8.239 7.062
15.602 11.702 81.797 5.390 4.620
19.134 14.351 81.797 8.239 7.062
5.947 4.460 0.000
r (kN/m)
Beam 8 Beam 9 Beam 10 Beam 11 Beam 12 Beam 13
32.221 36.341 22.393 36.341 32.221 36.341
42.978 46.510 34.554 46.510 35.298 38.830
32.418 35.950 23.994 35.950 30.018 33.550
32.418 35.950 23.994 35.950 30.018 33.550
20.714 23.362 14.396 23.362 20.714 23.362
N/m)
Beam 8 Beam 9 Beam 10 Beam 11 Beam 12 Beam 13
13.604 16.453 13.604 16.453 13.604 16.453
13.581 16.023 13.581 16.023 13.581 16.696
12.261 14.703 12.261 14.703 12.261 14.703
12.261 14.703 12.261 14.703 12.261 14.703
8.745 10.577 8.745 10.577 8.745 10.577
Second Floor
Beam 6 Beam 7 Beam 8 Beam 9
Shear (kN) Moment (kN-m) Shear (kN) Moment (kN-m) Shear (kN) Moment (kN-m)
55.610 -45.319, +25.885 62.496 -50.612,+33.405 76.109 -42.558, +21.585
84.037 -53.093, +31.219 70.303 -63.278, +38.254 84.037 -49.608, +25.978
52.986 -43.300, +25.010 58.799 -52.316, +31.640 71.111 -40.582, +20.839
83.890 -100.290, +37.617 89.704 -99.034, +40.755 73.928 -89.930, +27.219
66.669 -86.124, +35.094 71.081 -83.714, +32.103 74.693 -77.134, +22.842
ROOF
Beam 6 Beam 7 Beam 8 Beam 9
Shear (kN) Moment (kN-m) Shear (kN) Moment (kN-m) Shear (kN) Moment (kN-m)
17.697 -17.328, +10.140 24.260 -14.879, +6.120 18.187 -16.336, +9.008
17.594 -16.242, +9.458 22.522 -14.499, 6.231 17.594 -16.163, +8.824
15.851 -15.288, +8.935 21.335 -13.299, +5.554 16.216 -15.070, +8.063
25.768 -34.588, +13.077 31.459 -31.672, 7.088 25.438 -33.442, +9.390
21.461 -30.439, +11.630 25.720 -27.944, +10.259 20.912 -29.290, +9.356
Beam 6 Beam 7 Beam 8 Beam 9
Vud (342 mm) Reaction(kN) Vud (342 mm) Reaction(kN) Vud (342 mm) Reactions(kN)
48.996, 15.582 77.312, 169.032 54.489, 21.253 164.328, 143.968 69.653, 16.132 169.032, 163.585
58.570, 14.970 82.367, 180.616 62.910, 19.880 180.618, 161.965 78.084, 15.794 180.616, 175.039
47.123, 14.085 71.297, 156.051 51.771, 18.737 153.280, 135.4533 65.453, 14.448 156.051,151.115
78.046, 23.992 30.269, 162.745 82.718, 28.850 159.974, 135.477 90.581, 23.664 162.745,151.140
62.408, 20.140 8.673, 115.359 65.916, 23.787 112.537, 93.260 70.535, 19.600 115.359,105.188
ROOF
Beam 6 Beam 7 Beam 8 Beam 9
Vu2h Vud(242mm) Vu2h Vud(242mm) Vu2h Vud(242mm)
13.844 22.178 18.687 16.771 14.342 21.445
13.867 20.682 17.611 16.354 14.120 20.354
12.494 19.573 16.502 14.999 12.854 19.015
22.416 29.659 26.653 24.230 22.068 28.255
18.984 24.363 22.157 20.013 18.433 23.025
22.416 29.659 26.653 24.230 22.068 28.255
SECOND FLOOR
Beam 6 Beam 7 Beam 8 Beam 9
Vu2h Vud(342mm) Vu2h Vud(342mm) Vu2h Vud(342mm)
38.816 54.011 42.449 69.470 59.317 50.986
47.895 63.055 50.468 77.802 67.213 57.929
37.849 51.846 40.901 65.258 55.892 48.440
68.671 82.810 71.687 90.527 80.914 72.924
55.852 65.921 58.175 70.406 63.750 57.452
68.671 82.810 71.687 90.527 80.914 72.924
0.9UDL
5.801 FRAME 5
4.460 FRAME 4
4.460 FRAME 3
4.460 FRAME 2
5.801 FRAME 1
3.465 FRAME B
5.297 FRAME A
3.465 FRAME B
5.297 FRAME A
3.465 FRAME B
5.297 FRAME A
3.465 FRAME B
5.297 FRAME A
Beam 12 Beam 13
Shear (kN) Moment (kN-m) Shear (kN)
52.568 -45.319, +25.859 62.496
53.790 -47.347, +26.153 62.328
47.787 -41.498, +23.432 56.309
74.109 -93.025, +28.007 79.715
61.693 -85.306, +25.063 65.905
Beam 12 Beam 13
Vu2h Vud(242mm) Vu2h
14.884 22.140 18.694
14.411 21.451 18.277
13.173 19.588 16.511
21.796 28.435 25.388
18.483 23.446 21.161
21.796 28.435 25.388
Beam 12 Beam 13
Vu2h Vud(342mm) Vu2h
35.724 54.469 42.409
38.147 55.164 43.882
33.000 49.435 38.767
59.309 72.689 62.141
50.874 60.730 52.995
59.309 72.689 62.141
FRAME B
UDL(B14)
2.478
2.124
2.124
2.124
1.593
Beam 2 (cantilever beam)
Shear (kN)
29.776
27.939
26.278
26.278
19.142
29.776
Vud Vu2h
26.013 22.144
24.711 21.397
23.054 19.736
23.054 19.736
16.721 14.236
26.013 22.144
Basic Load Combinations BEAM 1
1.4D 2.50511
1.2D+ 1.6L 2.24384
1.2D + f1L 2.17728
1.2D + 1.0E + f1L 2.19237
0.9D + 1.0E 1.6312
CANTILEVER BEAM
Basic Load Combinations BEAM 2
1.4D 0.78099
1.2D+ 1.6L 1.95913
1.2D + f1L 1.09308
1.2D + 1.0E + f1L 0.43995
0.9D + 1.0E 0.30649
SUMMARY
ROOF BEAM (7.5M) 3.37451 mm
ROOF BEAM (4M) 0.70117 mm
SECOND FLOOR BEAM (7.5M) 8.79208 mm
SECOND FLOOR BEAM (4M) 1.95913 mm
CANTILEVER BEAM 1.9943 mm
ROOF BEAMS
BEAM 2 BEAM 3 BEAM 4 BEAM 5 BEAM 6 BEAM 7
3.37451 3.28435 3.28435 2.61922 0.58848 0.65999
3.10462 3.00836 3.1309 2.4645 0.58892 0.63832
2.75152 2.66051 2.69872 2.3136 0.53078 0.58841
2.76719 2.67315 2.17735 2.32723 0.5904 0.65616
2.19053 2.12553 2.12609 1.70296 0.45753 0.5079
LOOR BEAMS
BEAM 8 BEAM 9 BEAM 10 BEAM 11 BEAM 12 BEAM 13
1.62749 1.03989 0.37535 1.03989 1.15807 1.24455
1.80168 1.19358 0.64693 1.23373 1.16057 1.23197
1.52212 0.98593 0.42332 0.99782 1.0451 1.11863
1.61858 1.14894 0.74089 1.22729 1.02309 1.07298
1.9943 0.89086 0.62009 0.95389 0.79936 0.83332
base=
SBC = 150 KPa assumed, t=
Fy = 275 MPa assumed height from NGL=
f'c = 21 MPa column width=
main bar, ⌀=
concrete cover=
DESIGN LOADS :
ROOF LOADS :
COLUMN: @AC25
DEAD LOADS :
Footing Self-Weight
Column Weight
Beam Weight
Slab weight
Ceiling 0.008
Floor finish 0.023
Partition
Windows, Glass, Frames & Sash
TOTAL =
Live Load (type of occupancy)
1 Office
2 Store
71.7912 kn
36.08145 kn
2.360 kn/m
2.950 kpa
0.102 kpa
0.575 kpa
1.00 kpa
0.38 kpa
kpa
kpa
kpa
kpa
kpa
LOADS NEEDED
# STOREY Mux, UNFACTORED MOMENT Muy, UNFACTORED MOMENT
2 15.622 4.969
2 18.453 0.376
2 20.316 0
2 17.919 0.376
2 10.555 4.969
2 69.907 3.972
2 171.949 2.598
2 152.214 3.778
2 119.873 1.252
2 62.395 4.139
PROGRAMMED :
P= 393.881
qe = 122.58
L= 2.55919307470322
Vu qu= 68.59618343
Mu qu= 158.7412676
PUNCHING STRESS AT CRITICAL
Vu= 428.6421161
Vp=Vu/(Φb₀d)
Vp= 0.5474880942
Vall= 1.512249979
Vp < Vall
SAFE
As= 4831.272727
N= 15.37841872
S= 162.5
UNFACTORED LOADS
P Mx
393.881 35.792
qe =
Equation=
L=
FA
FB
FC
FD
qave=
qu=
Spacing o
Mu=
Rn=
ρ=
ρmin=
Use ρ=
As=
N=
S=
LOADS NEEDED FOR CALCULATION
uy, UNFACTORED MOMENT P, UNFACTORED POINT LOAD (KN) Factor
4.969 209.0242 1.2DL + 1.6LL
0.376 318.989 1.2DL + 1.6LL
0 317.1021 1.2DL + 1.6LL
0.376 308.591 1.2DL + 1.6LL
4.969 176.589 1.2DL + 1.6LL
3.972 143.7042 1.2DL + 1.6LL
2.598 204.294 1.2DL + 1.6LL
3.778 178.7191 1.2DL + 1.6LL
1.252 151.7684 1.2DL + 1.6LL
4.139 112.7592 1.2DL + 1.6LL
Mx= 35.792
My= 108.972 Pu=
Equation= 868.5839131
Result= 868.584
Vp > Vall
kN-m
Mpa
mm²
bars ≈
mm ≈
122.58
122.58(L³)- (P+footing weight) Result= 868.584
2.55919307470322
68.5961834319527 kPa
158.741267637688 kPa
4831.27272727273 mm²
15.3784187194103 ≈ 16 bars
162.5 ≈ 150 mm
Pu, POINT LOAD (KN) MuXx, FACTORED MOMENT Muy, FACTORED MOMENT
266.6917 20.608 6.308
415.394 25.81 0.619
413.2635 28.102 0.009
390.2905 24.267 0.416
217.4583 13.54 5.473
254.1437 20.608 5.435
450.228 27.097 2.122
400.1895 28.102 3.784
346.0465 24.267 1.35
206.1723 13.54 5.07
Mux= 159.974
391.919 Muy= 104.091
≈ 2.6 2600
d= 0.365
16
150
LOADS
Muy
104.091
VALUES CALCU
EFFECTIVE SOIL PRESSURE LENGTH OR WIDTH (m)
122.58 1.6
122.58 1.9
122.58 1.9
122.58 1.8
122.58 1.5
122.58 1.9
122.58 2.4
122.58 2.3
122.58 2.1
122.58 1.8
2.6
mm
m
VALUES CALCULATED
Mu(KN-m), ULTIMATE MOMENT
47.4575562
83.5615738
84.0643726
72.9055843
34.3955029
57.8818128
127.9238155
108.9221516
83.0638464
43.0673813
68.59618343 261.1789919
16 150
ESSURES SIDES
KPa
KPa
KPa
KPa
# STOREY Mux, UNFACTORED MOMENT Muy, UNFACTORED MOMENT
2 30.722 74.018
2 38.766 71.187
2 37.789 69.324
2 37.726 71.694
2 39.931 79.058
2 31.72 105.095
2 35.792 108.972
2 41.567 109.789
2 36.749 107.366
2 39.1 100.002
P, UNFACTORED MuXx,
Pu, POINT LOAD Muy, FACTORED
uy, UNFACTORED MOMENT POINT LOAD Factor FACTORED
(KN) MOMENT
74.018 (KN)
157.55 1.2DL + 1.0E +f1L 149.055 MOMENT
81.702 71.705
71.187 287.5 1.2DL + 1.0E +f1L 296.246 93.735 71.327
69.324 282.811 1.2DL + 1.0E +f1L 287.856 91.839 69.19
71.694 271.513 1.2DL + 1.0E +f1L 276.763 92.232 70.388
79.058 159.373 1.2DL + 1.0E +f1L 200.821 89.885 76.137
105.095 215.141 1.2DL + 1.0E +f1L 202.401 82.534 102.512
108.972 393.881 1.2DL + 1.0E +f1L 391.919 159.974 104.091
109.789 344.95 1.2DL + 1.0E +f1L 337.93 135.477 202.453
107.366 298.423 1.2DL + 1.0E +f1L 299.335 90.515 103.83
100.002 214.529 1.2DL + 1.0E +f1L 255.909 89.453 98.081
VALUES CALCULATED
Mu(KN-m),
EFFECTIVE SOIL LENGTH OR N, NUMBER OF S(mm), SPACING
ULTIMATE
PRESSURE WIDTH (m) BARS OF BARS
122.58 2.1 MOMENT
115.6084479 13 150
122.58 2.1 148.5104531 13 150
122.58 2.3 157.9094455 14 150
122.58 2.3 157.0138184 14 150
122.58 2.2 137.0962245 14 150
122.58 2.3 153.1972477 14 150
122.58 2.6 261.1789919 16 150
122.58 2.6 289.5262397 16 150
122.58 2.5 192.3278952 15 150
122.58 2.3 165.5963807 14 150
WALL THICKNESS (interior) = 100 mm
WALL THICKNESS (exterior) = 150 mm
FULL GROUT = 2.82 KPa a.) Effective Soil Pressure: CHECK FOR ADEQUACY:
HEIGHT = 3.2 m qe = qa - pressure due to wt. of soil and concrete Check for Wide Beam ( ONE-WAY SHEAR)
COMP. STRENGTH OF CONCRETE= 20.7 Kn/m^3 qe = 147.6 qu = 74.66666667 d= 0.069
YIELDING STRENGTH = 275 Kn/m^3 ΦVc= 40.02620803
CONCRETE COVER = 75 mm b.) Length of Wall Footing Vu= 0.448 OKAY, PROCCEED TO THE NEXT STEP
DIAMETER (MAIN) = 12 mm L = (Total unfactored Load)/(qe*1 meter strip)
DIAMETER (TEMP.) = 10 mm L= 0.1756097561 ≈ 0.3
SUMMARY
LOAD CALCULATION USE 4 PCS 12 mm MAIN BARS c.) Spacing of Bars at Critical Section:
UNIFORM DISTRIBUTED LOAD = 25.92 kn/m USE 2 PCS 10 mm TEMP. BARS qu = 74.66666667
IDEAL SBC = 150 KPa Mu = 0.21
FACTORED LOAD = 22.4 kn/m Rn = 0.04900931177
wt. of soil = 16 kn/m ρ= 0.0001784645749
wt. of concrete = 23.6 kn/m ρmin= 0.005090909091
assumed height from NGL = 0.3 m use, ρ= 0.005090909091 ≈ 0.005091
considering, length = 1 m strip As= 351.279
Thickness = 150 mm N= 3.105988292 ≈ 4 BARS
S= 250 ≈ 250 mm
LOAD CALCULATION
UNIFORM DISTRIBUTED LOAD = 25.504 kn/m
IDEAL SBC = 150 KPa
FACTORED LOAD = 35.7056 kn/m
wt. of soil = 16 kn/m a.) Effective Soil Pressure: CHECK FOR ADEQUACY:
wt. of concrete = 23.6 kn/m qe = qa - pressure due to wt. of soil and concrete Check for Wide Beam ( ONE-WAY SHEAR)
assumed height from NGL = 1.5 m qe = 147.6 qu = 119.0186667 d= 0.069
considering, length = 1 m strip ΦVc= 40.02620803
b.) Length of Wall Footing Vu= 3.689578667 OKAY, PROCCEED TO THE NEXT STEP
L = (Total unfactored Load)/(qe*1 meter strip)
L= 0.1727913279 ≈ 0.3
SUMMARY
USE 4 PCS 12 mm MAIN BARS
USE 2 PCS 10 mm TEMP. BARS
STAIRS FOUNDATION
t = 300 mm
D = 0.9 m
diameter, ⌀ = 16 mm PROGRAMMED:
LOADS NEEDED FOR CALCUL
P, UNFACTORED POINT LOAD (KN)
16.053525
PROGRAMMED:
P= 16.053525
qe = 133.32
w= 0.24537056684 Equation= 16.05351851
Result= 16.053525
qu (max) = 27.791328
@LONG
Mu= 1.196872622 d=
Rn= 0.0263332 Mpa
ρ= 9.58287793E-05
ρmin= 0.005090909091
Use ρ= 0.005090909091
Pu= 21.711975
≈ 0.625
L= 1.25
0.217
0.201
As1= 690.4545455
As2= 588.6363636
bars
bars
P, FACTORED POINT LOAD (KN)
21.711975
21.711975
625 mm
600 mm
VALUES CALC
EFFECTIVE SOIL PRESSURE LENGTH OR WIDTH (m)
qu(KPa), ULTIMATE UPWARD SOIL PRESSURE
133.32 0.6, 0.3 27.791328
SU
USE 7 PCS
USE 3 PCS
ALUES CALCULATED
Mu(KN-m), ULTIMATE MOMENT (LONGER SIDE) N, NUMBER OF BARS
2.8714087 7
SUMMARY
16 mm
16 mm
(SHORTER SIDE) N, NUMBER OF BARS
3
X-DIRECTION
Y-DIRECTION
STAIRS FOUNDATION
t = 300 mm
D = 0.9 m
diameter, ⌀ = 16 mm PROGRAMMED:
LOADS NEEDED FOR CALCULATION
P, UNFACTORED POINT LOAD (KN)
16.053525
PROGRAMMED:
P= 16.053525 Pu=
qe = 133.32
w= 0.24537056684494 Equation= 16.05351851
Result= 16.053525
qu (max) = 27.791328
@LONG
Mu= 1.196872622 d= 0.201
Rn= 0.0263332 Mpa
ρ= 0.00009582877925
ρmin= 0.005090909091
Use ρ= 0.005090909091
As1=
As= 1279.090909 mm² As2=
N= 6.361676276 bars ≈ 7 bars
N2= 2.927637092 bars ≈ 3 bars
UNFACTORED LOADS
P
16.053525
L = 2W
qe = 133.32
Equation= 122.58(L²)
W= 0.625 m
qu= 27.791328
As= 690.454545454545
N= 2.19778507778717
S= 208.333
DESIGN MOMENT ALONG L
Mu= 1.196872621875
d= 201
Rn= 0.0263332
ρ= 9.58287792507666E-05
ρmin= 0.00509090909090909
Use ρ= 0.00509090909090909
As= 1279.09090909091
As1= 690.454545454545
As2= 588.636363636364
N= 6.36167627642888
N2= 2.92763709238643
S= 178.571428
CULATION
P, FACTORED POINT LOAD (KN)
21.711975
21.711975
≈ 0.625 625 mm
L= 1.25 600 mm
690.4545455
588.6363636
FACTORED LOADS
Pu
21.711975
L = 2W
kPa
Result= 16.053525
L= 1.25 m
27.791328 kPa
mm² mm²
bars 3 bars
≈ 200 mm
GN MOMENT ALONG LONG
1.196872621875 kN-m
201 mm
0.0263332 MPa
9.58287792507666E-05
0.00509090909090909
0.00509090909090909
mm²
mm²
mm²
bars 7 bars
≈ 3 bars
≈ 175 mm
VALUES CALC
EFFECTIVE SOIL PRESSURE LENGTH OR WIDTH (m)
qu(KPa), ULTIMATE UPWARD SOIL PRESSURE
133.32 0.6, 0.3 27.791328
SU
USE 7 PCS
USE 3 PCS
ALUES CALCULATED
Mu(KN-m), ULTIMATE MOMENT (LONGER SIDE) N, NUMBER OF BARS
2.8714087 7
SUMMARY
16 mm
16 mm
(SHORTER SIDE) N, NUMBER OF BARS
3
X-DIRECTION
Y-DIRECTION