SECON

Slab Loads:
Kpa/mm
Superimposed Dead Load:
Slab weight 2.950 kpa h= 125 mm
Ceiling 0.008 0.102 kpa h= 12.7 mm
Floor finish 0.023 0.575 kpa h= 25 mm
Partition 1.00 kpa
Windows, Glass, Frames & Sash 0.38 kpa

Total Dead load: 5.007

Live Load:
Office 2.4 kpa
Store 4.8 kpa

L S L/S
7.5 4 1.875 <2.0, Two-way

DL= 5.01 kpa


LL= kpa

LOAD DISTRIBUTION:
SLAB 1: DEAD LOAD:
Long Side: 7.5 m L/S 1.875
Short Side: 4 m Design as: Two Way

SLAB 2: DEAD LOAD:


Long Side: 7.5 m L/S 1.875
Short Side: 4 m Design as: Two Way

SLAB 3: DEAD LOAD:


Long Side: 7.5 m L/S 1.875
Short Side: 4 m Design as: Two Way

SLAB 4: DEAD LOAD:


Long Side: 7.5 m L/S 1.875
Short Side: 4 m Design as: Two Way

Stair Loading:

Kpa/mm
Superimposed Dead Load:
Slab weight (landing) 2.950 kpa
Floor finish 0.023 0.575 kpa t=
Weight of waist 5.01 kpa R=
Weight of Steps 2.36 kpa T=

Total Dead load: 10.891 kpa

Live Load:
Stair 1.9 kpa
SLAB 5: DEAD LOAD:
Long Side: 2.89 m L/S 2.627
ONE-WAY B15
Short Side: 1.1 m Design as: SLAB B8

For Lintel Beam:


DEAD LOAD: LIVE LOAD: DEAD LOAD (UDL):
B16 5.446 kN/m 0.95 kN/m 1.18

Landing Dimension:
L 1 m
W 1 m
SECOND FLOOR (KN/M)
Wall Load:
2.622 kN/m (Lightweight: Full Grout)( t = 100 mm) for B5
8.046 kN/m (Lightweight: Full Grout)( t = 100 mm)
10.989 kN/m (Lightweight: Full Grout)( t = 200 mm) with firewall
Beam Weight for Long Span:
4.956 kN/m
Beam Weight for Short Span:
2.36 kN/m

DEAD LOAD: LIVE LOAD: DEAD LOAD (UDL):


B1 10.0132 kN/m 9.6 kN/m 13.002 kN/m
B2 10.0132 kN/m 9.6 kN/m 4.956 kN/m
B6 10.0132 kN/m 9.6 kN/m 13.002 kN/m
B7 10.0132 kN/m 9.6 kN/m 15.945 kN/m

DEAD LOAD: LIVE LOAD: DEAD LOAD (UDL):


B2 10.0132 kN/m 9.6 kN/m 4.956 kN/m
B3 10.0132 kN/m 9.6 kN/m 4.956 kN/m
B8 10.0132 kN/m 9.6 kN/m 13.002 kN/m
B9 10.0132 kN/m 9.6 kN/m 15.945 kN/m

DEAD LOAD: LIVE LOAD: DEAD LOAD (UDL):


B3 10.0132 kN/m 9.6 kN/m 4.956 kN/m
B4 10.0132 kN/m 9.6 kN/m 4.956 kN/m
B10 10.0132 kN/m 9.6 kN/m 5.982 kN/m
B11 10.0132 kN/m 9.6 kN/m 15.945 kN/m

DEAD LOAD: LIVE LOAD: DEAD LOAD (UDL):


B4 10.0132 kN/m 4.8 kN/m 13.002 kN/m
B5 10.0132 kN/m 4.8 kN/m 8.270 kN/m
B12 10.0132 kN/m 4.8 kN/m 13.002 kN/m
B13 10.0132 kN/m 4.8 kN/m 15.945 kN/m

150 mm
200 mm
200 mm
LIVE LOAD: DEAD LOAD (UDL):
5.990 kN/m 1.045 kN/m 4.956 kN/m
5.990 kN/m 1.045 kN/m - kN/m

LOAD (UDL):
kN/m
Unit weight of Conc
23.6 kn/m^3

Beam Dimension: (m) Beam Dimension:


H 600 mm 0.6 H
W 350 mm 0.35 W
BEAM WEIGHT: 4.956 BEAM WEIGHT:
Wall height:
2.7
3.2

Column Dimension: (m)


H 350 mm 0.35
W 350 mm 0.35

BEAM LOADS:

Member DL LL UDL TOTAL DL(Kn/m)


B1 10.0132 9.6 13.002 23.0152
B2 20.0264 19.2 4.956 24.9824
B3 20.0264 19.2 4.956 24.9824
B4 20.0264 14.4 4.956 24.9824
B5 10.0132 4.8 8.270 18.2832
B6 10.0132 9.6 13.002 23.0152
B7 10.0132 9.6 15.945 25.9582
B8 10.0132 9.6 13.002 23.0152
B9 10.0132 9.6 15.945 25.9582
B10 10.0132 9.6 5.982 15.9952
B11 10.0132 9.6 15.945 25.9582
B12 10.0132 4.8 13.002 23.0152
B13 10.0132 4.8 15.945 25.9582

Beam(landing):

Member DL LL UDL TOTAL DL(Kn/m)


B15 5.990 1.045 4.956 10.946
m Dimension: (m)
400 mm 0.4
250 mm 0.25
AM WEIGHT: 2.36
Roof Beam
Superimposed Dead Load:
Slab weight 23.6 2.832 kpa h= 120 mm
Ceiling 0.008 0.102 kpa h= 12.7 mm

Total Dead load: 2.934

Live Load: 0.6 kpa

L S L/S
7.5 4 1.875 <2.0, Two-way

DL= 2.93 kpa


LL= 0.6 kpa

LOAD DISTRIBUTION:
SLAB 1: DEAD LOAD:
Long Side: 7.5 m L/S 1.875
Short Side: 4 m Design as: Two Way

SLAB 2: DEAD LOAD:


Long Side: 7.5 m L/S 1.875
Short Side: 4 m Design as: Two Way

SLAB 3: DEAD LOAD:


Long Side: 7.5 m L/S 1.875
Short Side: 4 m Design as: Two Way
SLAB 4: DEAD LOAD:
Long Side: 7.5 m L/S 1.875
Short Side: 4 m Design as: Two Way
Roof Beam (KN/M)
Wall Load:
1.49 kn/m (Lightweight: Full Grout)( t = 100 mm) Unit weight of Concrete:
2.035 kn/m (Lightweight: Full Grout)( t = 200 mm) with firewall 23.6
Beam Weight for Long Span:
4.956 kn/m
Beam Weight for Short Span:
2.36 kN/m

DEAD LOAD: LIVE LOAD: DEAD LOAD (UDL):


B1 5.8672 kN/m 1.2 kN/m 6.446 kN/m
B2 5.8672 kN/m 1.2 kN/m 4.956 kN/m
B6 5.8672 kN/m 1.2 kN/m 3.85 kN/m
B7 5.8672 kN/m 1.2 kN/m 5.885 kN/m

DEAD LOAD: LIVE LOAD: DEAD LOAD (UDL):


B2 5.8672 kN/m 1.2 kN/m 4.956 kN/m
B3 5.8672 kN/m 1.2 kN/m 4.956 kN/m
B8 5.8672 kN/m 1.2 kN/m 3.85 kN/m
B9 5.8672 kN/m 1.2 kN/m 5.885 kN/m

DEAD LOAD: LIVE LOAD: DEAD LOAD (UDL):


B3 5.8672 kN/m 1.2 kN/m 4.956 kN/m
B4 5.8672 kN/m 1.2 kN/m 4.956 kN/m
B10 5.8672 kN/m 1.2 kN/m 3.85 kN/m
B11 5.8672 kN/m 1.2 kN/m 5.885 kN/m

DEAD LOAD: LIVE LOAD: DEAD LOAD (UDL):


B4 5.8672 kN/m 1.2 kN/m 4.956 kN/m
B5 5.8672 kN/m 1.2 kN/m 6.446 kN/m
B12 5.8672 kN/m 1.2 kN/m 3.85 kN/m
B13 5.8672 kN/m 1.2 kN/m 5.885 kN/m
Unit weight of Concrete: Beam Dimension for Long Span:
kn/m^3 H 600 0.6
W 350 0.35
BEAM WEIGHT: 4.956
dimension
2.7
3.2

L=7500-350 7150
L/10 715 700
L/12 595.833333 600

b 350
b/d > 0.3 0.58333333

BEAM LOADS:
Member DL LL UDL TOTAL DL(KN/M)
B1 5.8672 1.2 6.446 12.3132
B2 11.7344 2.4 4.956 16.6904
B3 11.7344 2.4 4.956 16.6904
B4 11.7344 2.4 4.956 16.6904
B5 5.8672 1.2 6.446 12.3132
B6 5.8672 1.2 3.85 9.7172
B7 5.8672 1.2 5.885 11.7522
B8 5.8672 1.2 3.85 9.7172
B9 5.8672 1.2 5.885 11.7522
B10 5.8672 1.2 3.85 9.7172
B11 5.8672 1.2 5.885 11.7522
B12 5.8672 1.2 3.85 9.7172
B13 5.8672 1.2 5.885 11.7522
Beam Dimension for ShortSpan:
H 400 0.4
W 250 0.25
BEAM WEIGHT: 2.36

L=4000-350 3650
L/10 365 400
L/12 304.1667

b 250
b/d > 0.3 0.625
SECOND FLOOR
DEAD LOAD: 5.007 kpa
Tributary: 2.000 m

SLAB
Slab 1: 150.198 KN
Slab 2: 150.198 KN
Slab 3: 150.198 KN
Slab 4: 150.198 KN

TotaL weight of slab: 600.792 kn

BEAM
B1 37.170 KN
B2 37.170 KN
B3 37.170 KN
B4 37.170 KN
B5 37.170 KN
B6 9.440 KN
B7 9.440 KN
B8 9.440 KN
B9 9.440 KN
B10 9.440 KN
B11 9.440 KN
B12 9.440 KN
B13 9.440 KN

Total weight of Beam: 261.370 KN

Walls
W1 60.345 KN
W2 60.345 KN
W3 60.345 KN
W4 60.345 KN
W5 7.695 KN
W6 32.184 KN
W7 43.956 KN
W8 32.184 KN
W9 43.956 KN
W10 4.104 KN
W11 43.956 KN
W12 32.184 KN
W13 43.956 KN
Total weight of Wall: 525.555 KN

Beam(landing):
Member DL LL UDLTOTAL DL(Kn/m)
WDL(KN)
B15 5.990 1.045 4.956 10.946 31.635

Total weight in Second Floor: 1419.352 KN

TOTAL WEIGHT :
ROOF SLAB AND BEAM WEIGHT
DEAD LOAD: 2.934 kpa
Tributary: 2.000 m

SLAB
Slab 1: 88.008 KN
Slab 2: 88.008 KN
Slab 3: 88.008 KN
Slab 4: 88.008 KN

TotaL weight of slab: 352.032 KN

BEAM
B1 37.170 KN
B2 37.170 KN
B3 37.170 KN
B4 37.170 KN
B5 37.170 KN
B6 9.440 KN
B7 9.440 KN
B8 9.440 KN
B9 9.440 KN
B10 9.440 KN
B11 9.440 KN
B12 9.440 KN
B13 9.440 KN

Total weight of Roof Beam: 261.370 KN

Parapet Wall
W1 11.175 KN
W5 11.175 KN
W6 5.960 KN
W7 14.100 KN
W8 5.960 KN
W9 14.100 KN
W10 5.960 KN
W11 14.100 KN
W12 5.960 KN
W13 14.100 KN
Total weight of Wall: 102.590 KN

Total weight in Roof: 715.992 KN

2135.344 KN
EIGHT
MAIN WIND FORCE RESISTING SYSTEM

DIMENSIONS
Roof Type Flat Roof
Parapet Height (m) 7.26
Angle 1°
Length, B 16
Width, L 7.5

WALLS
RISK CATEGORY II
BASIC WIND SPEED,V (m/s) 72.22222222
WIND LOAD PARAMETERS:
0.85
Wind Directionality Factor, Kd B
Exposure Category 1
Topographic Factor, Kzt 0.85
Gust Effect Factor, G
Enclosure Classification Enclosed
Internal Pressure Coefficient, GCpi 0.18
VELOCITY PRESSURE EXPOSURE COEFFICIENT, Kz
z (0-4.5) 0.57
z (6) 0.62
z (6.5) 0.63
VELOCITY PRESSURE, qz or qh
qz (0-4.5) 1549.158843
qz (6) 1685.049969
qh (6.5) 1712.228194
EXTERNAL PRESSURE COEFFICIENT, CP
0.8
Windward Wall
Leeward Wall -0.5
Side Wall -0.7
WIND PRESSURE, p (kPa), 0-4.5 Case 1
0.7745794213
Windward Wall
Leeward Wall
Side wall
Windward Wall
Leeward Wall -1.035898058
Side wall -1.326976851
WIND PRESSURE, p (kPa), 6 Case 1
0.8425249846
Windward Wall
Leeward Wall -1.035898058
Side wall -1.326976851
WIND PRESSURE, p (kPa), 6.5 Case 1
0.8561140972
Windward Wall
Leeward Wall -1.035898058
Side wall -1.326976851

WIND LOAD, P (KN), 0-4.5


Windward Wall
Leeward Wall
Side wall
WIND LOAD, P (KN), 6
Windward Wall
Leeward Wall
Side wall
WIND LOAD, P (KN), 6.5
Windward Wall
Leeward Wall
Side wall

Windward Wall
Leeward Wall

Base Shear (KN)


Basic Windspeed (Kph)
260

L/B
0.46875

PARAPET
II VELOCITY PRESSURE EXPOSURE COEFFICIENT, Kp 0.65
72.22222222 VELOCITY PRESSURE, qp 1766.5846
COMBINED NET PRESSURE COEFFICIENT, GCpn
0.85 Windward 1.5
B Leeward -1.0
1 WIND PRESSURE, P kPa
0.85 Windward ###
Enclosed Leeward ###
-0.18

0.57
0.62
0.63

1549.158843
1685.049969
1712.228194

0.8
-0.5
-0.7
Case 2
1.332276605
-0.4194959076
-0.7105747007
Case 2
1.449142973
-0.4194959076
-0.7105747007
Case 2
1.472516247
-0.4194959076
-0.7105747007

Wind Base Shear


Pointload(KN)
Case 1 Case 2 Parapet Wall:
55.770 95.924 WIND FORCE, P (KN) PL(KN)
-74.585 -30.204 Windward 21.199
-95.542 -51.161 Leeward -14.133
Case 1 Case 2
20.221 34.779
-24.862 -10.068
-31.847 -17.054
Case 1 Case 2
6.849 11.780
-8.287 -3.356
-10.616 -5.685

Case 1 Case 2
82.839 142.483
107.733 43.628

211.772 171.978
LOAD ANALYSIS PROCEDURE
1. Occupancy Category OCCUPANCY CATEGORY
2. Importance Factor (I) IMPORTANCE FACTOR, I
3. Soil Profile Type SOIL PROFILE TYPE
4. Seismic Zone SEISMIC ZONE
5. Seismic Zone Factor (Z) SEISMIC ZONE FACTOR, Z
6. Basic Seismic Force Resisting System
BASIC SEISMIC FORCE RESISTING SYSTEM
7. Seismic Source Type
8. Distance from the nearest Active Fault SEISMIC SOURCE TYPE
9. Near Source Factor (Na)
DISTANCE FROM THE NEAREST ACTIVE FAULT
10. Near Source Factor (Nv)
11. Seismic Coefficient (Ca) NEAR SOURCE FACTOR, Na
12. Seismic Coefficient (Cv) NEAR SOURCE FACTOR, Nv
13. R & Ω0 SEISMIC COEFFICIENT, Ca
14. Ct and hn SEISMIC COEFFICIENT, Cv
15. Period (T) Ct
16. Total Weight (W) hn
17. Design Base Shear (V) PERIOD, T
18. Additional Lateral force at the roof top (F i) TOTAL WEIGHT, W
DESIGN BASE SHEAR, V (kN
elevation (m)
Roof 6.5
2nd floor 3.5

V
ADDITIONAL LATERAL FORCE AT THE ROOF TOP, F t (k
170.78917 kN
DISTRIBUTE DESIGN BA
m
3

0
.

LEVEL, X WEIGHT, W
ROOF 715.992
174.62401 kN
2ND FLOOR 1419.352
m
3

5
.

345.41318 kN

Span
2
Span
2

5 4 3 2 1
A
Span 1

B
Span length (m)
1 7.5
2 16
II
1.25
SD
Zone 4
0.4
R Ω0
RCE RESISTING SYSTEM
8.5 2.8
SOURCE TYPE C
E NEAREST ACTIVE FAULT 2.0
CE FACTOR, Na 1.0
CE FACTOR, Nv 1.0
OEFFICIENT, Ca 0.44
OEFFICIENT, Cv 0.64
Ct 0.0731
hn 6.5
RIOD, T 0.2976
WEIGHT, W
DESIGN BASE SHEAR, V (kN) SEISMIC COEFFICIENT, Ca
SEISMIC COEFFICIENT, Cv
675.3664696
DESIGN BASE SHEAR, V
345.41318

129.18829

100.48927

V 345.41318
RCE AT THE ROOF TOP, F t (kN) 7.1951

DISTRIBUTE DESIGN BASE SHEAR


HEIGHT, h Wxh FX (kN)
6.5 4653.948 163.59
3.5 4967.7306 174.62
TOTAL 9621.6786 338.21804

TOTAL WEIGHT, W 2135.344 kN


Roof
Along 'Y'-axis FRoof 163.59
k
FRAME k FX (kN) FJ'x (kN)
∑k
A 3 0.5 163.59 81.80
B 3 0.5 163.59 81.80
6

Roof
Along 'X'-axis FRoof 163.59
k
FRAME k Fy (kN) FJ'y (kN)
∑k
1 6 0.2 163.59 32.72
2 6 0.2 163.59 32.72
3 6 0.2 163.59 32.72
4 6 0.2 163.59 32.72
5 6 0.2 163.59 32.72
30

2nd Floor
Along 'Y'-axis F2nd Floor 174.62
k
FRAME k FX (kN) FJ'x (kN)
∑k
A 3 0.5 174.62 87.31
B 3 0.5 174.62 87.31
6

2nd Floor
Along 'X'-axis F2nd Floor 174.62
k
FRAME k Fy (kN) FJ'y (kN)
∑k
1 6 0.2 174.62 34.92
2 6 0.2 174.62 34.92
3 6 0.2 174.62 34.92
4 6 0.2 174.62 34.92
5 6 0.2 174.62 34.92
30
0.44Na
0.64Nv

E SHEAR, V

0.31628

0.16176

0.06050

0.04706

ROOF
32.72 32.72 32.72 32.72

5 4 3 2 1
81.80
A

81.80 B

34.92 34.92 34.92 34.92 34.92


32.72

87.31

87.31
ROOF L
Basic Load Combinations:(page 66)
1.4(D + F)
1.2(D + F + T)+ 1.6(L+H)+0.5(Lr or R)
1.2D + 1.6(Lr or R) + (f1L or 0.5W)
1.2D + 1.0W +f1L +0.5(Lr or R)
1.2D + 1.0E + F1l
0.9D + 1.0W + 1.6H
0.9D + 1.0E + 1.6H

where:
f1 = 1.0 for floors in places of public assembly,
for live loads in excess of 4.8 kPa,
and for garage live load, or
= 0.5 for other live loads

D -
E -
Em 0 Basic Load Combinat
F 0 1.4D
H 0 1.2D+ 1.6L
L - 1.2D + f1L
Lr 0 1.2D + 1.0E + f1L
P 0 0.9D + 1.0E
R 0
T 0
W 0
f1 0.5
LOADS (kN/m)
Member DL LL UDL TOTAL DL SL(KN) 1.4UDL
ROOF LOAD COMBINATION B1 5.8672 1.2 6.446 12.3132 32.72 9.024
B2 11.7344 2.4 4.956 16.6904 32.72 6.938
B3 11.7344 2.4 4.956 16.6904 32.72 6.938
B4 11.7344 2.4 4.956 16.6904 32.72 6.938
B5 5.8672 1.2 6.446 12.3132 32.72 9.024
B6 5.8672 1.2 3.85 9.7172 81.80 5.390
B7 5.8672 1.2 5.885 11.7522 81.80 8.239
B8 5.8672 1.2 3.85 9.7172 81.80 5.390
B9 5.8672 1.2 5.885 11.7522 81.80 8.239
B10 5.8672 1.2 3.85 9.7172 81.80 5.390
B11 5.8672 1.2 5.885 11.7522 81.80 8.239
B12 5.8672 1.2 3.85 9.7172 81.80 5.390
B13 5.8672 1.2 5.885 11.7522 81.80 8.239

MAX(7.5M) 2.4 16.6904 19.0904


MAX(4M) 1.2 11.7522 12.9522

Roof Floor (kN/m)


Basic Load Combinations Beam 1 Beam 2 Beam 3 Beam 4 Beam 5 Beam 6 Beam 7 Beam 8 Beam 9 Beam 10
1.4D 17.238 23.367 23.367 23.367 17.238 13.604 16.453 13.604 16.453 13.604
1.2D+ 1.6L 16.696 23.868 23.868 23.868 16.696 13.581 16.023 13.581 16.023 13.581
1.2D + f1L 15.376 20.028 20.028 20.028 15.376 12.261 14.703 12.261 14.703 12.261
1.2D + 1.0E + f1L 15.376 20.028 20.028 20.028 15.376 12.261 14.703 12.261 14.703 12.261
0.9D + 1.0E 11.082 15.021 15.021 15.021 11.082 8.745 10.577 8.745 10.577 8.745
1.2UDL 0.9UDL
7.735 5.8014 FRAME 1
5.947 4.4604 FRAME 2
5.947 4.4604 FRAME 3
5.947 4.4604 FRAME 4
7.735 5.8014 FRAME 5
4.620 3.465 FRAEM B
7.062 5.2965 FRAME A
4.620 3.465 FRAME B
7.062 5.2965 FRAME A
4.620 3.465 FRAME B
7.062 5.2965 FRAME A
4.620 3.465 FRAME B
7.062 5.2965 FRAME A

Beam 11 Beam 12 Beam 13


16.453 13.604 16.453
16.023 13.581 16.696
14.703 12.261 14.703
14.703 12.261 14.703
10.577 8.745 10.577
SECOND FLOOR LOAD COMBINATION

Basic Load Combinations:(page 66)


1.4(D + F)
1.2(D + F + T)+ 1.6(L+H)+0.5(Lr or R)
1.2D + 1.6(Lr or R) + (f1L or 0.5W)
1.2D + 1.0W +f1L +0.5(Lr or R)
1.2D + 1.0E + f1L
0.9D + 1.0W + 1.6H
0.9D + 1.0E + 1.6H

where:
f1 = 1.0 for floors in places of public assembly,
for live loads in excess of 4.8 kPa,
and for garage live load, or
= 0.5 for other live loads

D -
E -
Em 0.000
F 0.000
H 0.000
L -
Lr 0.000
P 0.000
R 0.000
T 0.000
W 0.000
f1 0.500

Basic Load Combinations


1.4D
1.2D+ 1.6L
1.2D + f1L
1.2D + 1.0E + f1L
0.9D + 1.0E

Basic Load Combinations


1.4D
1.2D+ 1.6L
1.2D + f1L
1.2D + 1.0E + f1L
0.9D + 1.0E
Basic Load Combinations
1.4D
1.2D+ 1.6L
1.2D + f1L
1.2D + 1.0E + f1L
0.9D + 1.0E

Summary of Loads:

Basic Load Combinations


1.4D
1.2D+ 1.6L
1.2D + f1L
1.2D + 1.0E + f1L
0.9D + 1.0E

Basic Load Combinations


1.4D
1.2D+ 1.6L
1.2D + f1L
1.2D + 1.0E + f1L
0.9D + 1.0E

Summary of Shear:
COND FLOOR LOAD COMBINATION
Member
FRAME 1 B1
FRAME 2 B2
FRAME 3 B3
FRAME 4 B4
FRAME 5 B5
FRAME B B6
FRAME A B7
FRAME B B8
FRAME A B9
FRAME B B10
FRAME A B11
FRAME B B12
FRAME A B13
B15

B8 (2.89m)

B16
MAX(7.5M)
MAX(4M)

Basic Load Combinations Beam 1


1.4D 32.221
1.2D+ 1.6L 42.978
1.2D + f1L 32.418
1.2D + 1.0E + f1L 32.418
0.9D + 1.0E 20.714
39.579

Basic Load Combinations Beam 1


1.4D 17.238
1.2D+ 1.6L 16.696
1.2D + f1L 15.376
1.2D + 1.0E + f1L 15.376
0.9D + 1.0E 11.082
20.028

Beam 1 Beam 2 Beam 3


Moment (kN-m) Shear (kN) Moment (kN-m) Shear (kN) Moment (kN-m)
-91.845, +125.364 106.811 -114.945, +125.065 106.485 -96.546, +130.681
-116.965, +166.973 133.792 -176.762, +225.619 176.071 -159.237, +231.051
-90.674, +126.054 104.752 -122.509, +144.671 117.776 -106.164, +149.704
-185.548,+135.960 130.059 -217.382, 154.699 143.083 -201.038, +157.823
-153.918, +96.08 93.973 -168.795,+97.089 93.764 -156.939, +98.279

Beam 1 Beam 2 Beam 3


Moment (kN-m) Shear (kN) Moment (kN-m) Shear (kN) Moment (kN-m)
-47.433, +59.888 52.796 -56.052, + 81.116 64.762 -56.631, +79.893
-50.651, +53.557 50.533 -68.096, +74.281 65.600 -68.530, +72.928
-43.78, +52.028 46.903 -52.064, +65.811 55.023 -52.469, +64.550
-72.161, +54.011 54.465 -80.445, +67.493 62.585 -80.850, +66.135
-58.873, +41.268 41.501 -64.492, +54.488 48.823 -64.786, +53.479
Beam 1 Beam 2 Beam 3
Reaction(kN) Vud (542 mm) Reaction(kN) Vud (542 mm) Reactions(kN)
159.607 95.943, 47.412 200.36(FB), 162.516(FA) 100.546, 59.217 167.047
184.325 123.330, 45.760 269.610(FB), 234.778(FA) 168.745, 61.173 238.225
151.655 95.111, 42.288 199.076(FB), 166.370(FA) 111.981, 50.835 169.585
184.524(FB), 118.786(FA) 120.364, 49.70 231.945(FB), 133.501(FA) 137.292, 58.405 202.453(FB), 136.716(FA)
135.473(FB), 69.736(FA) 87.015, 37.992 161.729(FB), 72.186(FA) 89.914, 45.792 140.255(FB), 74.518(FA)

SECOND FLOOR
Member (+)Mu (-)Mu
B1 166.973 185.548
B2 225.619 217.382
B3 231.051 201.038
B4 200.899 195.186
B5 112.690 163.903
B6 51.058 100.271
B7 37.617 100.290
B8 40.755 99.034
B9 27.219 89.930
B10 31.092 73.470
B11 26.655 89.608
B12 33.812 90.365
B13 28.007 93.025

Beam 1 Beam 2 Beam 3


Vud(342mm) Vu2h Vud(342mm) Vu2h Vud(342mm)
49.496 44.524 61.173 56.393 61.204
47.701 43.112 62.997 58.326 62.852
44.124 39.625 52.514 48.424 52.448
51.563 47.270 60.127 55.961 59.939
39.333 36.124 46.925 43.849 46.891
51.563 47.270 62.997 58.326 62.852

Beam 1 Beam 2 Beam 3


Vud(542mm) Vu2h Vud(542mm) Vu2h Vud(542mm)
95.943 79.798 100.546 87.987 97.390
123.330 105.334 168.745 149.049 165.714
95.111 79.950 111.981 98.573 109.142
120.364 105.183 137.292 123.913 134.391
87.015 76.677 89.914 81.901 87.911
123.330 105.334 168.745 149.049 165.714

ROOF SECOND FLOOR


Member Within 2h Beyond 2h Member
B1 51.563 47.270 B1
B2 62.997 58.326 B2
B3 62.852 59.036 B3
B4 62.877 58.069 B4
B5 51.661 47.183 B5
B6 24.553 22.416 B6
B7 29.659 26.653 B7
B8 24.230 22.068 B8
B9 28.255 25.229 B9
B10 24.184 22.024 B10
B11 27.992 24.977 B11
B12 23.958 21.796 B12
B13 28.435 25.388 B13

7.5m 62.997 59.036 7.5m


4m 29.659 26.653 4m
LOADS (KN/M)
DL LL UDL TOTAL DL SL(KN) 1.4UDL
10.013 9.600 13.002 23.015 34.925 18.203
20.026 19.200 4.956 24.982 34.925 6.938
20.026 19.200 4.956 24.982 34.925 6.938
20.026 14.400 4.956 24.982 34.925 6.938
10.013 4.800 8.270 18.283 34.925 11.578
10.013 9.600 13.002 23.015 87.312 18.203
10.013 9.600 15.945 25.958 87.312 22.323
10.013 9.600 13.002 23.015 87.312 18.203
10.013 9.600 15.945 25.958 87.312 22.323
10.013 9.600 5.982 15.995 87.312 8.375
10.013 9.600 15.945 25.958 87.312 22.323
10.013 4.800 13.002 23.015 87.312 18.203
10.013 4.800 15.945 25.958 87.312 22.323
5.990 1.045 4.956 10.946 - 6.938

5.990 1.045

5.446 0.950 1.180 6.626 -


19.200 24.982 44.182
9.600 25.958 35.558

(Wu)-Second Floor (kN/m)


Beam 2 Beam 3 Beam 4 Beam 5 Beam 6 Beam 7
34.975 34.975 34.975 25.596 32.221 36.341
60.699 60.699 53.019 29.620 42.978 46.510
39.579 39.579 37.179 24.340 32.418 35.950
39.579 39.579 37.179 24.340 32.418 35.950
22.484 22.484 22.484 16.455 20.714 23.362
35.950
(Wu)-Roof (kN/m)
Beam 2 Beam 3 Beam 4 Beam 5 Beam 6 Beam 7
23.367 23.367 23.367 17.238 13.604 16.453
23.868 23.868 23.868 16.696 13.581 16.023
20.028 20.028 20.028 15.376 12.261 14.703
20.028 20.028 20.028 15.376 12.261 14.703
15.021 15.021 15.021 11.082 8.745 10.577
14.703

Beam 3 Beam 4 Beam 5 Beam 6


Shear (kN) Moment (kN-m) Shear (kN) Moment (kN-m) Shear (kN) Moment (kN-m)
103.119 -96.546, +130.681 103.119 -73.419, +97.208 81.967 -44.976,+20.492
172.869 -140.510, +200.899 151.749 -82.445, +112.690 91.379 -53.688,+26.241
114.789 -100.312, +140.282 108.189 -69.030, +92.500 76.859 -43.281, +20.276
140.096 -195.186, +148.922 133.496 -163.903, +105.684 102.166 -100.271, +43.211
91.598 -156.939, +98.279 91.598 -142.072, +81.981 78.001 -85.954, +51.058

Beam 3 Beam 4 Beam 5 Beam 6


Shear (kN) Moment (kN-m) Shear (kN) Moment (kN-m) Shear (kN) Moment (kN-m)
63.934 -56.631, +79.893 63.926 -44.340, +62.981 52.796 -11.526, +8.484
65.355 -65.387, +76.071 65.355 -44.858, +59.351 50.533 -14.499, +6.231,
54.795 -51.487, +65.532 54.795 -40.147, +55.660 46.903 -10.568, 7.556
62.357 -79.868, +67.117 62.357 -68.528, +57.643 54.465 -29.455, +10.627
48.657 -64.786, +53.479 48.657 -56.885, +43.256 41.501 -26.623, 13.775
Beam 3 Beam 4 Beam 5 Beam 6
Vud (542 mm) Reaction(kN) Vud (542 mm) Reaction(kN) Vud (542 mm) Reaction(kN)
97.390, 59.191 167.046 97.374, 59.193 134.763 74.755, 47.464 62.936, 164.328
165.714, 60.929 217.105 144.866, 59.176 141.912 84.420, 45.805 69.819, 161.965
109.142, 50.733 162.985 102.711, 50.729 123.762 70.446, 42.250 58.906, 153.280
134.391, 58.222 195.853(FB), 130.116(FA) 128.080, 58.177 156.631(FB), 90.893(FA) 95.730, 49.700 17.877, 159.974
87.911, 45.515 140.255(FB), 74.518(FA) 87.842, 45.527 119.502(FB), 53.764(FA) 73.312, 37.971 0.576, 112.537

ROOF BEAM
Member (+)Mu (-)Mu
B1 59.888 72.161
B2 81.116 80.445
B3 79.893 80.850
B4 79.893 79.868
B5 62.981 68.528
B6 13.775 29.455
B7 13.077 34.588
B8 10.259 31.672
B9 9.390 33.442
B10 11.300 30.097
B11 9.737 33.166
B12 10.019 90.365
B13 10.291 33.978

Beam 3 Beam 4 Beam 5 Beam 6


Vu2h Vud(342mm) Vu2h Vud(342mm) Vu2h Vud(242mm)
56.190 61.172 56.227 49.534 44.478 16.295
59.036 62.877 58.069 47.670 43.052 16.125
48.149 52.421 48.196 44.117 39.68 14.643
55.666 59.936 55.735 51.661 47.183 24.553
43.660 46.803 43.665 39.409 36.119 20.571
59.036 62.877 58.069 51.661 47.183 24.553

Beam 3 Beam 4 Beam 5 Beam 6


Vu2h Vud(542mm) Vu2h Vud(542mm) Vu2h Vud(342mm)
84.763 97.374 84.691 74.168 63.126 48.932
146.025 144.866 127.586 84.420 72.287 58.606
95.534 102.711 89.818 70.446 59.842 47.105
120.953 128.115 115.062 95.730 85.139 78.032
79.732 87.856 79.740 73.312 65.816 62.390
146.025 144.866 127.586 95.730 85.139 78.032

SECOND FLOOR
Within 2h Beyond 2h
123.330 105.334
168.745 149.049
165.714 146.025
144.866 127.586
95.730 85.139
78.032 68.671
82.810 71.687
90.527 80.914
72.924 61.862
51.681 46.132
73.483 62.355
68.415 59.309
72.689 62.141

168.745 149.049
90.527 80.914
2nd floor roof
1.2UDL 0.9UDL SL(KN) 1.4UDL 1.2UDL
15.602 11.702 32.719 9.024 7.735
5.947 4.460 32.719 6.938 5.947
5.947 4.460 32.719 6.938 5.947
5.947 4.460 32.719 6.938 5.947
9.924 7.443 32.719 9.024 7.735
15.602 11.702 81.797 5.390 4.620
19.134 14.351 81.797 8.239 7.062
15.602 11.702 81.797 5.390 4.620
19.134 14.351 81.797 8.239 7.062
7.178 5.384 81.797 5.390 4.620
19.134 14.351 81.797 8.239 7.062
15.602 11.702 81.797 5.390 4.620
19.134 14.351 81.797 8.239 7.062
5.947 4.460 0.000

r (kN/m)
Beam 8 Beam 9 Beam 10 Beam 11 Beam 12 Beam 13
32.221 36.341 22.393 36.341 32.221 36.341
42.978 46.510 34.554 46.510 35.298 38.830
32.418 35.950 23.994 35.950 30.018 33.550
32.418 35.950 23.994 35.950 30.018 33.550
20.714 23.362 14.396 23.362 20.714 23.362
N/m)
Beam 8 Beam 9 Beam 10 Beam 11 Beam 12 Beam 13
13.604 16.453 13.604 16.453 13.604 16.453
13.581 16.023 13.581 16.023 13.581 16.696
12.261 14.703 12.261 14.703 12.261 14.703
12.261 14.703 12.261 14.703 12.261 14.703
8.745 10.577 8.745 10.577 8.745 10.577

Second Floor
Beam 6 Beam 7 Beam 8 Beam 9
Shear (kN) Moment (kN-m) Shear (kN) Moment (kN-m) Shear (kN) Moment (kN-m)
55.610 -45.319, +25.885 62.496 -50.612,+33.405 76.109 -42.558, +21.585
84.037 -53.093, +31.219 70.303 -63.278, +38.254 84.037 -49.608, +25.978
52.986 -43.300, +25.010 58.799 -52.316, +31.640 71.111 -40.582, +20.839
83.890 -100.290, +37.617 89.704 -99.034, +40.755 73.928 -89.930, +27.219
66.669 -86.124, +35.094 71.081 -83.714, +32.103 74.693 -77.134, +22.842

ROOF
Beam 6 Beam 7 Beam 8 Beam 9
Shear (kN) Moment (kN-m) Shear (kN) Moment (kN-m) Shear (kN) Moment (kN-m)
17.697 -17.328, +10.140 24.260 -14.879, +6.120 18.187 -16.336, +9.008
17.594 -16.242, +9.458 22.522 -14.499, 6.231 17.594 -16.163, +8.824
15.851 -15.288, +8.935 21.335 -13.299, +5.554 16.216 -15.070, +8.063
25.768 -34.588, +13.077 31.459 -31.672, 7.088 25.438 -33.442, +9.390
21.461 -30.439, +11.630 25.720 -27.944, +10.259 20.912 -29.290, +9.356
Beam 6 Beam 7 Beam 8 Beam 9
Vud (342 mm) Reaction(kN) Vud (342 mm) Reaction(kN) Vud (342 mm) Reactions(kN)
48.996, 15.582 77.312, 169.032 54.489, 21.253 164.328, 143.968 69.653, 16.132 169.032, 163.585
58.570, 14.970 82.367, 180.616 62.910, 19.880 180.618, 161.965 78.084, 15.794 180.616, 175.039
47.123, 14.085 71.297, 156.051 51.771, 18.737 153.280, 135.4533 65.453, 14.448 156.051,151.115
78.046, 23.992 30.269, 162.745 82.718, 28.850 159.974, 135.477 90.581, 23.664 162.745,151.140
62.408, 20.140 8.673, 115.359 65.916, 23.787 112.537, 93.260 70.535, 19.600 115.359,105.188

ROOF
Beam 6 Beam 7 Beam 8 Beam 9
Vu2h Vud(242mm) Vu2h Vud(242mm) Vu2h Vud(242mm)
13.844 22.178 18.687 16.771 14.342 21.445
13.867 20.682 17.611 16.354 14.120 20.354
12.494 19.573 16.502 14.999 12.854 19.015
22.416 29.659 26.653 24.230 22.068 28.255
18.984 24.363 22.157 20.013 18.433 23.025
22.416 29.659 26.653 24.230 22.068 28.255

SECOND FLOOR
Beam 6 Beam 7 Beam 8 Beam 9
Vu2h Vud(342mm) Vu2h Vud(342mm) Vu2h Vud(342mm)
38.816 54.011 42.449 69.470 59.317 50.986
47.895 63.055 50.468 77.802 67.213 57.929
37.849 51.846 40.901 65.258 55.892 48.440
68.671 82.810 71.687 90.527 80.914 72.924
55.852 65.921 58.175 70.406 63.750 57.452
68.671 82.810 71.687 90.527 80.914 72.924
0.9UDL
5.801 FRAME 5
4.460 FRAME 4
4.460 FRAME 3
4.460 FRAME 2
5.801 FRAME 1
3.465 FRAME B
5.297 FRAME A
3.465 FRAME B
5.297 FRAME A
3.465 FRAME B
5.297 FRAME A
3.465 FRAME B
5.297 FRAME A

Beam 15 Beam 16 Pointload (KN) transfered to B2ct & B14


15.325 9.276 22.144
14.807 9.471 21.397
13.658 8.426 19.736
13.658 8.426 19.736
9.852 5.963 14.236
left right B2CT B14
28.331 25.983 4.956 2.815
35.381 30.796
27.752 24.935
27.752 24.935
18.213 16.703

Beam 9 Beam 10 Beam 11 Beam 12


Shear (kN) Moment (kN-m) Shear (kN) Moment (kN-m) Shear (kN) Moment (kN-m)
58.261 -30.385, +8.392, 32.406 -42.558, +21.585 59.067 -35.451, 24.006
66.052 -39.980, +15.072 43.798 -48.241, +26.655 65.708 -38.768, +24.597
55.450 -30.399, +9.655 32.783 -40.093, +21.045 55.309 -43.005, 21.832
79.830 -73.470, +20.352 54.628 -89.608, +26.506 80.375 -90.365, +23.593
62.566 -64.789, +31.092 43.750 -76.874, +24.352 63.039 -83.295, +33.812

Beam 9 Beam 10 Beam 11 Beam 12


Shear (kN) Moment (kN-m) Shear (kN) Moment (kN-m) Shear (kN) Moment (kN-m)
23.532 -12.718, +8.063 18.078 -16.983, +9.008 23.532 -14.829, 7.326
22.165 -12.894, 7.848 17.601 -16.087, +8.517 21.973 -13.973, 7.366
20.798 -11.525, +7.204 16.154 -15.026, +7.992 20.740 -13.105, 6.619
30.020 -30.097, 8.499 25.397 -33.166, +9.737 29.767 -31.219, +6.464
24.350 -26.759, +11.300 20.876 -29.074, +9.093 24.163 -28.429, +10.019
Beam 9 Beam 10 Beam 11 Beam 12
Vud (342 mm) Reaction(kN) Vud (342 mm) Reaction(kN) Vud (342 mm) Reaction(kN)
51.027, 20.178 143.968, 118.517 29.039, 15.230 163.585, 169.032 51.026, 20.182 118.517, 64.883
58.747, 19.101 161.965, 128.942 40.549, 14.729 175.039, 173.186 65.580, 19.313 128.942, 64.260
48.383, 18.175 135.453, 110.135 29.828, 13.580 151.115, 153.499 48.243, 17.907 110.135, 58.316
72.758, 27.420 135.477, 103.482 51.679, 23.629 151.140, 146.847 73.311, 27.153 103.482, 99.278
57.427, 22.406 93,260, 69.514 41.643, 19.553 105.188,102.013 57.841, 22.218 69.514, 82.666

Beam 9 Beam 10 Beam 11 Beam 12


Vu2h Vud(242mm) Vu2h Vud(242mm) Vu2h Vud(242mm)
18.019 16.657 14.225 21.433 17.948 17.336
17.252 16.359 14.118 20.170 17.025 16.651
15.939 14.937 12.807 18.935 15.941 15.248
25.229 24.184 22.024 27.992 24.977 23.958
20.799 19.981 18.382 22.827 20.602 20.069
25.229 24.184 22.024 27.992 24.977 23.958

Beam 9 Beam 10 Beam 11 Beam 12


Vu2h Vud(342mm) Vu2h Vud(342mm) Vu2h Vud(342mm)
38.893 29.131 23.445 51.016 38.927 45.982
45.690 40.559 33.711 58.392 45.974 47.892
37.436 29.850 24.344 48.300 37.391 42.042
61.862 51.681 46.132 73.483 62.355 68.415
49.585 41.629 37.975 57.969 50.196 57.433
61.862 51.681 46.132 73.483 62.355 68.415
B2ct & B14
FRAME 4 FRAME B
B8(landing)-FRAME B LANDING(KN) UDL(KN/M) -B2ct POINTLOAD(END) P(at B8) from B14
8.386 24.236 6.938 22.144 24.870
8.860 25.606 5.947 21.397 23.733
7.711 22.284 5.947 19.736 22.072
7.711 22.284 5.947 19.736 22.072
5.391 15.581 4.460 14.236 15.988
BEAM 14
Beam 16 (-)Moments Shear
2.130 30.355 27.596
28.677 26.070
26.849 24.409
26.849 24.409
19.514 17.740

Beam 12 Beam 13
Shear (kN) Moment (kN-m) Shear (kN)
52.568 -45.319, +25.859 62.496
53.790 -47.347, +26.153 62.328
47.787 -41.498, +23.432 56.309
74.109 -93.025, +28.007 79.715
61.693 -85.306, +25.063 65.905

Beam 12 Beam 13 Beam 2 (cantilever beam)


Shear (kN) Moment (kN-m) Shear (kN) Moment (kN-m)
18.741 -17.328, +10.141 24.260 -28.556
17.886 -16.535, +10.291 23.304 -27.135
16.634 -15.227, +9.039 21.358 -25.308
25.169 -33.978, +9.695 30.212 -25.308
20.973 -30.506, +9.165 24.758 -18.359
-28.556
Beam 12 Beam 13 Deflection
Vud (342 mm) Reaction(kN) Vud (342 mm) 0.781
45.850, 16.689 169.032,77.312 54.420, 21.228 1.959
47.874, 16.082 173.186,75.546 55.231, 20.642 1.093
42.026, 14.872 153.499, 68.965 49.348, 18.748 0.052
68.335, 23.395 146.847,109.928 72.775, 27.612 -0.54
57.415, 19.650 102.013, 90.664 60.739, 22.819 1.959

Beam 12 Beam 13
Vu2h Vud(242mm) Vu2h
14.884 22.140 18.694
14.411 21.451 18.277
13.173 19.588 16.511
21.796 28.435 25.388
18.483 23.446 21.161
21.796 28.435 25.388

Beam 12 Beam 13
Vu2h Vud(342mm) Vu2h
35.724 54.469 42.409
38.147 55.164 43.882
33.000 49.435 38.767
59.309 72.689 62.141
50.874 60.730 52.995
59.309 72.689 62.141
FRAME B
UDL(B14)
2.478
2.124
2.124
2.124
1.593
Beam 2 (cantilever beam)
Shear (kN)
29.776
27.939
26.278
26.278
19.142
29.776
Vud Vu2h
26.013 22.144
24.711 21.397
23.054 19.736
23.054 19.736
16.721 14.236
26.013 22.144
Basic Load Combinations BEAM 1
1.4D 2.50511
1.2D+ 1.6L 2.24384
1.2D + f1L 2.17728
1.2D + 1.0E + f1L 2.19237
0.9D + 1.0E 1.6312

Basic Load Combinations BEAM 1


1.4D 4.85384
1.2D+ 1.6L 6.41608
1.2D + f1L 4.86499
1.2D + 1.0E + f1L 4.95994
0.9D + 1.0E 3.26328

CANTILEVER BEAM
Basic Load Combinations BEAM 2
1.4D 0.78099
1.2D+ 1.6L 1.95913
1.2D + f1L 1.09308
1.2D + 1.0E + f1L 0.43995
0.9D + 1.0E 0.30649

SUMMARY
ROOF BEAM (7.5M) 3.37451 mm
ROOF BEAM (4M) 0.70117 mm
SECOND FLOOR BEAM (7.5M) 8.79208 mm
SECOND FLOOR BEAM (4M) 1.95913 mm
CANTILEVER BEAM 1.9943 mm
ROOF BEAMS
BEAM 2 BEAM 3 BEAM 4 BEAM 5 BEAM 6 BEAM 7
3.37451 3.28435 3.28435 2.61922 0.58848 0.65999
3.10462 3.00836 3.1309 2.4645 0.58892 0.63832
2.75152 2.66051 2.69872 2.3136 0.53078 0.58841
2.76719 2.67315 2.17735 2.32723 0.5904 0.65616
2.19053 2.12553 2.12609 1.70296 0.45753 0.5079

SECOND FLOOR BEAMS


BEAM 2 BEAM 3 BEAM 4 BEAM 5 BEAM 6 BEAM 7
4.72112 4.99197 4.99148 3.75203 0.96323 1.24455
8.5332 8.79208 7.64762 4.32905 1.19858 1.45693
5.46757 5.70615 5.34854 3.56391 0.94217 1.18869
5.56669 5.78834 5.4363 2.02196 1.50568 1.7134
3.19667 3.34486 3.34572 2.58853 1.22423 1.36917
F BEAMS
BEAM 8 BEAM 9 BEAM 10 BEAM 11 BEAM 12 BEAM 13
0.50623 0.67705 0.59901 0.67705 0.45804 0.65999
0.54527 0.69253 0.61059 0.6646 0.47155 0.67011
0.46872 0.61521 0.54378 0.60785 0.41724 0.59115
0.58377 0.70117 0.62109 0.66508 0.4768 0.64236
0.45496 0.53739 0.47802 0.50882 0.37014 0.4905

LOOR BEAMS
BEAM 8 BEAM 9 BEAM 10 BEAM 11 BEAM 12 BEAM 13
1.62749 1.03989 0.37535 1.03989 1.15807 1.24455
1.80168 1.19358 0.64693 1.23373 1.16057 1.23197
1.52212 0.98593 0.42332 0.99782 1.0451 1.11863
1.61858 1.14894 0.74089 1.22729 1.02309 1.07298
1.9943 0.89086 0.62009 0.95389 0.79936 0.83332
base=
SBC = 150 KPa assumed, t=
Fy = 275 MPa assumed height from NGL=
f'c = 21 MPa column width=
main bar, ⌀=
concrete cover=

DESIGN LOADS :
ROOF LOADS :
COLUMN: @AC25

DEAD LOADS :
Footing Self-Weight
Column Weight
Beam Weight
Slab weight
Ceiling 0.008
Floor finish 0.023
Partition
Windows, Glass, Frames & Sash

TOTAL =
Live Load (type of occupancy)
1 Office
2 Store

TOTAL FACTORED LOAD:


w1 = 9.84792
w2 = 13.68792
2.6 m
450 mm
1.5 m
350 mm
20 mm

71.7912 kn
36.08145 kn
2.360 kn/m
2.950 kpa
0.102 kpa
0.575 kpa
1.00 kpa
0.38 kpa

5.007 x 1.2 = 6.00792

2.4 x 1.6 = 3.84


4.8 x 1.6 = 7.68

TOTAL UNFACTORED FACTORED LOAD:


kpa w1 = 7.407
kpa w2 = 9.807
DESIGNATION
F1
F2
F3
F4
F5
F6
F7
F8
F9
F10

kpa

kpa
kpa

kpa
kpa
LOADS NEEDED
# STOREY Mux, UNFACTORED MOMENT Muy, UNFACTORED MOMENT
2 15.622 4.969
2 18.453 0.376
2 20.316 0
2 17.919 0.376
2 10.555 4.969
2 69.907 3.972
2 171.949 2.598
2 152.214 3.778
2 119.873 1.252
2 62.395 4.139

PROGRAMMED :
P= 393.881
qe = 122.58
L= 2.55919307470322
Vu qu= 68.59618343
Mu qu= 158.7412676
PUNCHING STRESS AT CRITICAL
Vu= 428.6421161

Vp=Vu/(Φb₀d)
Vp= 0.5474880942
Vall= 1.512249979

Vp < Vall
SAFE

Spacing of 20 mm main bars


Mu= 261.1789919
Rn= 0.8377929
ρ= 0.003121580348
ρmin= 0.005090909091
Use ρ= 0.005090909091

As= 4831.272727
N= 15.37841872
S= 162.5

UNFACTORED LOADS
P Mx
393.881 35.792

qe =
Equation=
L=

FA
FB
FC
FD

qave=
qu=

Spacing o
Mu=
Rn=
ρ=
ρmin=
Use ρ=

As=
N=
S=
LOADS NEEDED FOR CALCULATION
uy, UNFACTORED MOMENT P, UNFACTORED POINT LOAD (KN) Factor
4.969 209.0242 1.2DL + 1.6LL
0.376 318.989 1.2DL + 1.6LL
0 317.1021 1.2DL + 1.6LL
0.376 308.591 1.2DL + 1.6LL
4.969 176.589 1.2DL + 1.6LL
3.972 143.7042 1.2DL + 1.6LL
2.598 204.294 1.2DL + 1.6LL
3.778 178.7191 1.2DL + 1.6LL
1.252 151.7684 1.2DL + 1.6LL
4.139 112.7592 1.2DL + 1.6LL

Mx= 35.792
My= 108.972 Pu=

Equation= 868.5839131
Result= 868.584

Vp > Vall

kN-m
Mpa
mm²
bars ≈
mm ≈

D LOADS FACTORED LOADS


My Pu Mux
108.972 391.919 159.974

122.58
122.58(L³)- (P+footing weight) Result= 868.584
2.55919307470322

EQUIVALENT VALUES OF PRESSURES SIDES


-21.5489007737824 KPa
49.5191465634957 KPa
158.741267637688 KPa
87.6732203004096 KPa

68.5961834319527 kPa
158.741267637688 kPa

CHECK FOR ADEQUACY:

PUNCHING SHEAR AT CRITICAL


d= 0.365 m
Vu= 428.642116125
Vp=Vu/(Φb₀d)
Vp= 0.547488094166108
Vall= 1.51224997933543
ADEQUACY : OK!

Spacing of 20 mm main bars


261.1789919 kN-m
0.8377929 MPa
0.00312158034797671
0.00509090909090909
0.00509090909090909

4831.27272727273 mm²
15.3784187194103 ≈ 16 bars
162.5 ≈ 150 mm
Pu, POINT LOAD (KN) MuXx, FACTORED MOMENT Muy, FACTORED MOMENT
266.6917 20.608 6.308
415.394 25.81 0.619
413.2635 28.102 0.009
390.2905 24.267 0.416
217.4583 13.54 5.473
254.1437 20.608 5.435
450.228 27.097 2.122
400.1895 28.102 3.784
346.0465 24.267 1.35
206.1723 13.54 5.07

Mux= 159.974
391.919 Muy= 104.091

≈ 2.6 2600

d= 0.365
16
150

LOADS
Muy
104.091
VALUES CALCU
EFFECTIVE SOIL PRESSURE LENGTH OR WIDTH (m)
122.58 1.6
122.58 1.9
122.58 1.9
122.58 1.8
122.58 1.5
122.58 1.9
122.58 2.4
122.58 2.3
122.58 2.1
122.58 1.8

2.6

mm

m
VALUES CALCULATED
Mu(KN-m), ULTIMATE MOMENT
47.4575562
83.5615738
84.0643726
72.9055843
34.3955029
57.8818128
127.9238155
108.9221516
83.0638464
43.0673813

68.59618343 261.1789919

EQUIVALENT VALUES OF PRESSURES SIDES


FA -21.54890077
FB 49.51914656
FC 158.7412676
FD 87.6732203
N, NUMBER OF BARS S(mm), SPACING OF BARS DESIGNATION
10 150 F1
12 150 F2
12 150 F3
11 150 F4
9 150 F5
12 150 F6
15 150 F7
14 150 F8
13 150 F9
11 150 F10

16 150

ESSURES SIDES
KPa
KPa
KPa
KPa
# STOREY Mux, UNFACTORED MOMENT Muy, UNFACTORED MOMENT
2 30.722 74.018
2 38.766 71.187
2 37.789 69.324
2 37.726 71.694
2 39.931 79.058
2 31.72 105.095
2 35.792 108.972
2 41.567 109.789
2 36.749 107.366
2 39.1 100.002
P, UNFACTORED MuXx,
Pu, POINT LOAD Muy, FACTORED
uy, UNFACTORED MOMENT POINT LOAD Factor FACTORED
(KN) MOMENT
74.018 (KN)
157.55 1.2DL + 1.0E +f1L 149.055 MOMENT
81.702 71.705
71.187 287.5 1.2DL + 1.0E +f1L 296.246 93.735 71.327
69.324 282.811 1.2DL + 1.0E +f1L 287.856 91.839 69.19
71.694 271.513 1.2DL + 1.0E +f1L 276.763 92.232 70.388
79.058 159.373 1.2DL + 1.0E +f1L 200.821 89.885 76.137
105.095 215.141 1.2DL + 1.0E +f1L 202.401 82.534 102.512
108.972 393.881 1.2DL + 1.0E +f1L 391.919 159.974 104.091
109.789 344.95 1.2DL + 1.0E +f1L 337.93 135.477 202.453
107.366 298.423 1.2DL + 1.0E +f1L 299.335 90.515 103.83
100.002 214.529 1.2DL + 1.0E +f1L 255.909 89.453 98.081
VALUES CALCULATED
Mu(KN-m),
EFFECTIVE SOIL LENGTH OR N, NUMBER OF S(mm), SPACING
ULTIMATE
PRESSURE WIDTH (m) BARS OF BARS
122.58 2.1 MOMENT
115.6084479 13 150
122.58 2.1 148.5104531 13 150
122.58 2.3 157.9094455 14 150
122.58 2.3 157.0138184 14 150
122.58 2.2 137.0962245 14 150
122.58 2.3 153.1972477 14 150
122.58 2.6 261.1789919 16 150
122.58 2.6 289.5262397 16 150
122.58 2.5 192.3278952 15 150
122.58 2.3 165.5963807 14 150
WALL THICKNESS (interior) = 100 mm
WALL THICKNESS (exterior) = 150 mm
FULL GROUT = 2.82 KPa a.) Effective Soil Pressure: CHECK FOR ADEQUACY:
HEIGHT = 3.2 m qe = qa - pressure due to wt. of soil and concrete Check for Wide Beam ( ONE-WAY SHEAR)
COMP. STRENGTH OF CONCRETE= 20.7 Kn/m^3 qe = 147.6 qu = 74.66666667 d= 0.069
YIELDING STRENGTH = 275 Kn/m^3 ΦVc= 40.02620803
CONCRETE COVER = 75 mm b.) Length of Wall Footing Vu= 0.448 OKAY, PROCCEED TO THE NEXT STEP
DIAMETER (MAIN) = 12 mm L = (Total unfactored Load)/(qe*1 meter strip)
DIAMETER (TEMP.) = 10 mm L= 0.1756097561 ≈ 0.3
SUMMARY
LOAD CALCULATION USE 4 PCS 12 mm MAIN BARS c.) Spacing of Bars at Critical Section:
UNIFORM DISTRIBUTED LOAD = 25.92 kn/m USE 2 PCS 10 mm TEMP. BARS qu = 74.66666667
IDEAL SBC = 150 KPa Mu = 0.21
FACTORED LOAD = 22.4 kn/m Rn = 0.04900931177
wt. of soil = 16 kn/m ρ= 0.0001784645749
wt. of concrete = 23.6 kn/m ρmin= 0.005090909091
assumed height from NGL = 0.3 m use, ρ= 0.005090909091 ≈ 0.005091
considering, length = 1 m strip As= 351.279
Thickness = 150 mm N= 3.105988292 ≈ 4 BARS
S= 250 ≈ 250 mm

DESIGN TEMP. BARS


As = 90
N = 1.14591559 ≈ 2 mm

LOAD CALCULATION
UNIFORM DISTRIBUTED LOAD = 25.504 kn/m
IDEAL SBC = 150 KPa
FACTORED LOAD = 35.7056 kn/m
wt. of soil = 16 kn/m a.) Effective Soil Pressure: CHECK FOR ADEQUACY:
wt. of concrete = 23.6 kn/m qe = qa - pressure due to wt. of soil and concrete Check for Wide Beam ( ONE-WAY SHEAR)
assumed height from NGL = 1.5 m qe = 147.6 qu = 119.0186667 d= 0.069
considering, length = 1 m strip ΦVc= 40.02620803
b.) Length of Wall Footing Vu= 3.689578667 OKAY, PROCCEED TO THE NEXT STEP
L = (Total unfactored Load)/(qe*1 meter strip)
L= 0.1727913279 ≈ 0.3

c.) Spacing of Bars at Critical Section:


qu = 119.0186667
Mu = 1.039204494
Rn = 0.2425271287
ρ= 0.0008880801953
ρmin= 0.005090909091
use, ρ= 0.005090909091 ≈ 0.005091
As= 351.279
N= 3.105988292 ≈ 4 BARS
S= 250 ≈ 250 mm

DESIGN TEMP. BARS


As = 90
N = 1.14591559 ≈ 2 mm
WALL THICKNESS (interior) = 100 mm
WALL THICKNESS (exterior) = 150 mm
FULL GROUT = 2.82 KPa a.) Effective Soil Pressure: CHECK FOR ADEQUACY:
HEIGHT = 3.2 m qe = qa - pressure due to wt. of soil and concrete Check for Wide Beam ( ONE-WAY SHEAR)
COMP. STRENGTH OF CONCRETE= 20.7 Kn/m^3 qe = 144.06 qu = 74.66666667 d= 0.069
YIELDING STRENGTH = 275 Kn/m^3 ΦVc= 40.02620803 a.) Effective Soil Pressure:
CONCRETE COVER = 75 mm b.) Length of Wall Footing Vu= 0.448 OKAY, PROCCEED TO THE NEXT STEP qe = qa - pressure due to wt. of soil and concrete
DIAMETER (MAIN) = 12 mm L = (Total unfactored Load)/(qe*1 meter strip) qe = 144.06
DIAMETER (TEMP.) = 10 mm L= 0.1799250312 ≈ 0.3
b.) Length of Wall Footing
LOAD CALCULATION c.) Spacing of Bars at Critical Section: L = (Total unfactored Load)/(qe*1 meter strip)
UNIFORM DISTRIBUTED LOAD = 25.92 kn/m qu = 74.66666667 L= 0.179925031237 ≈ 0.3
IDEAL SBC = 150 KPa Mu = 0.21
FACTORED LOAD = 22.4 kn/m Rn = 0.04900931177 CHECK FOR ADEQUACY:
wt. of soil = 16 kn/m ρ= 0.0001784645749 Check for Wide Beam ( ONE-WAY SHEAR)
wt. of concrete = 23.6 kn/m ρmin= 0.005090909091 qu = 74.66666666667 d= 0.069
assumed height from NGL = 0.3 m use, ρ= 0.005090909091 ≈ 0.005091 ΦVc= 40.02620803143
considering, length = 1 m strip As= 351.279 Vu= 0.448 OKAY, PROCCEED TO THE NEXT STEP
Thickness = 150 mm N= 3.105988292 ≈ 4 BARS
S= 250 ≈ 250 mm c.) Spacing of Bars at Critical Section:
qu = 74.66666666667
DESIGN TEMP. BARS Mu = 0.21
As = 90 Rn = 0.049009311769
N = 1.14591559 ≈ 2 mm ρ= 0.000178464575
ρmin= 0.005090909091
LOAD CALCULATION use, ρ= 0.005090909091 ≈ 0.005091
UNIFORM DISTRIBUTED LOAD = 25.504 kn/m As= 351.279
IDEAL SBC = 150 KPa N= 3.10598829191 ≈ 4 BARS
FACTORED LOAD = 35.7056 kn/m S= 250 ≈ 250 mm
wt. of soil = 16 kn/m a.) Effective Soil Pressure: CHECK FOR ADEQUACY:
wt. of concrete = 23.6 kn/m qe = qa - pressure due to wt. of soil and concrete Check for Wide Beam ( ONE-WAY SHEAR) DESIGN TEMP. BARS
assumed height from NGL = 1.5 m qe = 144.06 qu = 119.0186667 d= 0.069 As = 90
considering, length = 1 m strip ΦVc= 40.02620803 N = 1.145915590262 ≈ 2 mm
b.) Length of Wall Footing Vu= 3.689578667 OKAY, PROCCEED TO THE NEXT STEP
L = (Total unfactored Load)/(qe*1 meter strip)
L= 0.1770373456 ≈ 0.3

c.) Spacing of Bars at Critical Section:


qu = 119.0186667
Mu = 1.039204494
Rn = 0.2425271287
ρ= 0.0008880801953
ρmin= 0.005090909091
use, ρ= 0.005090909091 ≈ 0.005091
As= 351.279
N= 3.105988292 ≈ 4 BARS
S= 250 ≈ 250 mm

DESIGN TEMP. BARS


As = 90
N = 1.14591559 ≈ 2 mm

SUMMARY
USE 4 PCS 12 mm MAIN BARS
USE 2 PCS 10 mm TEMP. BARS
STAIRS FOUNDATION

NEEDED FOR CALCULATIONS:


SBC = 150 KPa
Fy = 275 MPa
f'c = 20.7 MPa DESIGNATION
c = 0.1 m WF3

t = 300 mm
D = 0.9 m
diameter, ⌀ = 16 mm PROGRAMMED:
LOADS NEEDED FOR CALCUL
P, UNFACTORED POINT LOAD (KN)
16.053525

PROGRAMMED:

P= 16.053525
qe = 133.32
w= 0.24537056684 Equation= 16.05351851
Result= 16.053525
qu (max) = 27.791328

CHECK FOR ONE WAY SHEAR


qu= 27.791328 d=
Vu= 6.21830964
Vu=ΦVc
d= 0.01715129706 OKAY, PROCCEED TO THE NEXT STEP
@SHORT
DESIGN MOMENT:
qu= 27.791328
Mu= 2.871408694
Rn= 0.1084059 Mpa
ρ= 0.00039542528
ρmin= 0.005090909091
Use ρ= 0.005090909091

As= 690.4545455 mm²


N= 2.197785078 bars ≈

@LONG
Mu= 1.196872622 d=
Rn= 0.0263332 Mpa
ρ= 9.58287793E-05
ρmin= 0.005090909091
Use ρ= 0.005090909091

As= 1279.090909 mm²


N= 6.361676276 bars ≈ 7
N2= 2.927637092 bars ≈ 3
LOADS NEEDED FOR CALCULATION
OINT LOAD (KN) P, FACTORED POINT LOAD (KN)
525 21.711975

Pu= 21.711975

≈ 0.625
L= 1.25

0.217

ED TO THE NEXT STEP

0.201
As1= 690.4545455
As2= 588.6363636
bars
bars
P, FACTORED POINT LOAD (KN)
21.711975

21.711975

625 mm
600 mm
VALUES CALC
EFFECTIVE SOIL PRESSURE LENGTH OR WIDTH (m)
qu(KPa), ULTIMATE UPWARD SOIL PRESSURE
133.32 0.6, 0.3 27.791328

SU
USE 7 PCS
USE 3 PCS
ALUES CALCULATED
Mu(KN-m), ULTIMATE MOMENT (LONGER SIDE) N, NUMBER OF BARS
2.8714087 7

SUMMARY
16 mm
16 mm
(SHORTER SIDE) N, NUMBER OF BARS
3

X-DIRECTION
Y-DIRECTION
STAIRS FOUNDATION

NEEDED FOR CALCULATIONS:


SBC = 150 KPa
Fy = 275 MPa
f'c = 20.7 MPa DESIGNATION
c = 0.1 m WF3

t = 300 mm
D = 0.9 m
diameter, ⌀ = 16 mm PROGRAMMED:
LOADS NEEDED FOR CALCULATION
P, UNFACTORED POINT LOAD (KN)
16.053525

PROGRAMMED:

P= 16.053525 Pu=
qe = 133.32
w= 0.24537056684494 Equation= 16.05351851
Result= 16.053525
qu (max) = 27.791328

CHECK FOR ONE WAY SHEAR


qu= 27.791328 d= 0.217
Vu= 6.21830964
Vu=ΦVc
d= 0.01715129706 OKAY, PROCCEED TO THE NEXT STEP
@SHORT
DESIGN MOMENT:
qu= 27.791328
Mu= 2.871408694
Rn= 0.1084059 Mpa
ρ= 0.0003954252795
ρmin= 0.005090909091
Use ρ= 0.005090909091

As= 690.4545455 mm²


N= 2.197785078 bars ≈ 3

@LONG
Mu= 1.196872622 d= 0.201
Rn= 0.0263332 Mpa
ρ= 0.00009582877925
ρmin= 0.005090909091
Use ρ= 0.005090909091
As1=
As= 1279.090909 mm² As2=
N= 6.361676276 bars ≈ 7 bars
N2= 2.927637092 bars ≈ 3 bars

UNFACTORED LOADS
P
16.053525
L = 2W
qe = 133.32
Equation= 122.58(L²)
W= 0.625 m
qu= 27.791328

CHECK FOR ONE-WAY SHEAR:

WIDE BEAM SHEAR AT CRIT


d=
Vu=
Vu=ΦVc
d1=
d1 < d

DESIGN MOMENT ALONG SH


Mu= 2.87140869375
d= 0.217
Rn= 0.1084059
ρ= 0.000395425279516193
ρmin= 0.00509090909090909
Use ρ= 0.00509090909090909

As= 690.454545454545
N= 2.19778507778717
S= 208.333
DESIGN MOMENT ALONG L
Mu= 1.196872621875
d= 201
Rn= 0.0263332
ρ= 9.58287792507666E-05
ρmin= 0.00509090909090909
Use ρ= 0.00509090909090909

As= 1279.09090909091
As1= 690.454545454545
As2= 588.636363636364
N= 6.36167627642888
N2= 2.92763709238643
S= 178.571428
CULATION
P, FACTORED POINT LOAD (KN)
21.711975

21.711975

≈ 0.625 625 mm
L= 1.25 600 mm
690.4545455
588.6363636

FACTORED LOADS
Pu
21.711975
L = 2W
kPa
Result= 16.053525
L= 1.25 m
27.791328 kPa

FOR ONE-WAY SHEAR:

BEAM SHEAR AT CRITICAL


0.217 m
6.21830964 kN
Vu=ΦVc
0.0171512970630893
Okay!

GN MOMENT ALONG SHORT


2.87140869375 kN-m
0.217 m
0.1084059 MPa
0.000395425279516193
0.00509090909090909
0.00509090909090909

mm² mm²
bars 3 bars
≈ 200 mm
GN MOMENT ALONG LONG
1.196872621875 kN-m
201 mm
0.0263332 MPa
9.58287792507666E-05
0.00509090909090909
0.00509090909090909

mm²
mm²
mm²
bars 7 bars
≈ 3 bars
≈ 175 mm
VALUES CALC
EFFECTIVE SOIL PRESSURE LENGTH OR WIDTH (m)
qu(KPa), ULTIMATE UPWARD SOIL PRESSURE
133.32 0.6, 0.3 27.791328

SU
USE 7 PCS
USE 3 PCS
ALUES CALCULATED
Mu(KN-m), ULTIMATE MOMENT (LONGER SIDE) N, NUMBER OF BARS
2.8714087 7

SUMMARY
16 mm
16 mm
(SHORTER SIDE) N, NUMBER OF BARS
3

X-DIRECTION
Y-DIRECTION