4CX1.5 Cable - LBV
4CX1.5 Cable - LBV
7 Individual Shielding
a i Material Not Applicable
ii Coverage %
iii Overlap %
b Drain Wire
i Material Not Applicable
ii Nominal area of cross section Sqmm
8 Laid up Cores laid up suitably & made circular
9 Overall Shielding
a i Material Al. Mylar Tape (Approx Thick: 0.02 mm)
ii Coverage % 100%
iii Overlap % 25%
b Drain Wire
i Material Annealed Tinned Copper
ii Nominal area of cross section Sqmm 0.5
10 Rip Cord Provided below Inner Sheath
11 Inner Sheath
a Material PVC ST II
b Tape / Extruded Extruded
c Minimum Inner Sheath Thickness mm 0.3
d Colour Black
12 Mechanical Protection
a Type GI Armoured
b Material GI Wire
c Armour Dimension mm 0.90
13 Separator Tape
a Material Not Applicable
b Coverage % Not Applicable
14 Outer Sheath
a Material PVC ST II
b Additional Property Not Applicable
c Outer Sheath Thickness(mm) Mininium 1.24
d Outer Sheath Colour Black
15 Approx. Overall Diameter of Cable mm 13.1
16 Minimum Bending Radius 15 Times The OD
Format No : IMS-PE-F-002 Rev-01 Dt 01-Sep-2023 LAPP INDIA PVT. LTD., Plot no.98, J, Jigani Industrial Area, II Phase, Bangalore South-560105.
Page 1 of 2 Ph No: 08110 304800-03
Guaranteed Technical Particulars 824830116019
Instrumentation Cable Valid from: 1-Jul-2024
Sr. No. Specification UOM 4C x 1.5
17 Approx. Weight of cable Kg / Km 318
18 Electrical Properties
a Max D.C.Resistance at 20⁰C
i Max Conductor D.C.Resistance at 20⁰C Ω / KM 14.0
ii Max Drain Wire D.C.Resistance at 20⁰C Ω / KM 36.7
b Mutual Capacitance (Core to Core) pF / m < 250
c L/R ratio µH/Ω <40
d High Voltage Test
i Core to Core KV/Min 2 KV for 1 Minute
ii Core to Screen KV/Min 1 KV for 1 Minute
19 Maximum Temperature of Conductor
a For Continuous Operation ⁰C 85°C
b Under Short Circuit Condition ⁰C 160°C
20 Printing on the Cable LAPP KABEL STUTTGART ÖLFLEX® INSTRUM 4x1.5 FT EN Y3 OS
Y2 SWA Y2 1 <METER MARKING>
Revision No : 07
Details of Changes : Design Revalidated. For Details Refer Design Document Olflex Instrum dt 1-Jul-2024
Note:
This GTP supersedes all other previous revisions released so far.
This GTP is a Design Document & is not valid for Inspection without QAP. QAP is must incase of Customer Inspection
Format No : IMS-PE-F-002 Rev-01 Dt 01-Sep-2023 LAPP INDIA PVT. LTD., Plot no.98, J, Jigani Industrial Area, II Phase, Bangalore South-560105.
Page 2 of 2 Ph No: 08110 304800-03