D-26-2022
D-26-2022
Baghdad – IRAQ
Specification No. D-26
Technical Specification
Distribution Transformerof
11/ 0.416 kV
Revision Year 2022
Technical Specification ofDistribution Transformers (11/0.416 kV) Ministry ofElectricity (MoE)/IRAQ
Table of Contents:
Clause Item
1 Scope of the Tender
2 General Requirements
3 System Composition
4 Technical Specifications
5 Fittings and Accessories
6 Painting
7 Insulating oil
8 Tender Price Evaluation (losses considerations)
9 Test
10 Drawing , Instruction Book and Literature
11 Packing
12 Spare parts and special tools for each rating
1- Scope of the Tender
Tenderer are invited for the design , manufacture , testing and supply of
a 11000/416 volt, oil immersed copper winding outdoor type (Directly
under the sun) transformers to be supplied complete with all necessary
fittings , accessories off-load tap changer , insulating oil and spare parts .
. . etc.
The transformer is to be hermetically sealed (without conservator tank)
bolted cover with bushing insulators on both H.T and L.T sides for the
following ratings: 100, 250, and 400. For 630, and 1000 kVA should be
plug in type (according to the tender requirements), a valid ISO 9001
certificate required.
2- General Requirements
The transformers shall be of first class quality and design for continuous
satisfactory operation as continuity of supply is of prime consideration.
The design shall be allow all necessary precaution for the safety of
operation and maintenance personnel. The transformers shall operate
satisfactorily under variations of load, voltage or short circuit or other
conditions which may occur on the system provided that these variations
are within the assigned rating of the apparatus. All the equipment shall
be designed to obviate the risk of accidental short circuit.
3- System Composition
The transformer shall operate in distribution systems where most of the
network is overheadlines and comprising partly underground cable.
4- Technical Specification
4.1 The transformers shall be copper winding. Hermetically sealed of the
bolted cover and should have the following characteristics:-
Rated outputs …… … … … . 100, 250, 400, 630, and 1000 kVA
Duty …… … …… … … … … . Step-down, outdoor bushing type for
100, 250, and 400 kVA. Plug in type for
630 and 1000 kVA (according to the
tender requirements)
Type …… … …… … … … … . 3-phase
Rated voltage at no load ... HV side -11kV
LV side - 416 volts
System Highest Voltage … HV side 12 kV
System frequency … … … ... 50 HZ
Interphase Connection … .. HV side - Delta
LV side - star with neutral brought out
Vector Group … … … … … .. Dyn 11
Type of cooling … … … … .. ONAN
Temperature rise ………… ( i ) 45 K in top oil by thermometer
( ii ) 50 K in winding by resistance
4.2 The efficiency (at unity power factor and 100% of rated power) of the
transformer should be not less than the following:
1. 100 kVA … … . 98.1 %
2. 250 kVA … … . 98.6 %
3. 400 kVA … … . 98.7 %
4. 630 kVA … … . 98.8 %
5. 1000 kVA … ... 98.9 %
4.3 The duration of the short circuit to rise the temperature of windings
from 105 0C to 250 0C should be not less than (5 Sec.) according to IEC
60076, part 5 , clause (4.1.5).
4.4 The thickness of the radiator plates should be shock resistant and do
not affect heat dissipation according to tender requirements as follows:
. For 250 and 400 kVA transformer, not less than 1.2 mm.
. For 630 and 1000 kVA transformer, not less than 1.5 mm.
4.5 The noise level should be ≤ 55 dB at 0.3 meter distance according to IEC
standards
4.6 The low voltage winding must be of copper foil for 250, 400, 630, and
1000 kVA transformers.
4.7 Off-load tap changer should be five tapping for (± 2.5 %, ± 5 %) on the
HV winding for off-circuit operation externally. The mechanical
operation must be of the robust and definite position type with a click
indicating position arrived during tap changing with suitable pad-lock.
4.8 Terminal arrangement of transformers.
4.8.1 The HV side:
. Terminal is to be a clamp type with eyebolt or flat bar type
with nut suitable for conductors up to 70 mm2 copper (for 100,
250, 400 kVA).
4.8.2 The low voltage terminals are to be flat bar type with holes
suitable for compression type thimble the sizes of LV side:
a) Type tests
The type tests prescribed shall be carried out on one unit of each
capacity:
1- Test of temperature rise according to the latest IEC 60076.
2- Full wave impulse voltage withstand test according to the latest
IEC 60076.
3- Cost of these tests to be borne by the manufacturer.
b) Routine tests
Each transformer shall be subjected to all the routine tests specified
according to the latest IEC 60076.
c) Special tests
(If required according to the tender requirements).
9.3 Test reports
Five copies of the test reports will be mailed within 8 days after the
tests have taken place. These reports will indicate:
a) The results of the tests.
b) The calculation of performance of the items.
c) The guarantee figures to show that each apparatus performs the
conditions of the specification within the guaranteed values
(schedules A & B).
9.4 Test Certificates
a) The tenderer shall furnish the Ministry of Electricity (MOE) with
six copies of test certificates.
Table of Dimension
Transformer Length Width Height
(kVA) (mm) (mm) (mm)
100 1250 700 1200
250 1350 900 1300
400 1450 1100 1400
630 1500 1200 1600
1000 1700 1400 1800
10.5 Approval of drawings:
The successful tenderer shall prepare and submit to the (MoE) all
necessary drawings and specifications (schedule A & B) complete
with explanations in due time and obtain approval of the same
before commencing manufacture.
The method of packing shall be such as to protect all the items against
excessive corrosion of dampness, and shall afford adequate protection
against breakage or other injury, or loss due to breakage of cases or crates
from the time the items leaves the factory until finally installed at the
substation during which time, the apparatus will travel by rail by a long
sea voyage again by rail or truck to the site of the substation. The
equipment will also undoubtedly stand on wharves and in the open
during and in between periods of transportation and will thereby be
exposed to heavy rain, hot sun, humid climate and sudden changes of
temperature.
Owing to the numerous handlings, the containers should be very strong
also extra ordinary care should be given to the packing of the equipment
and especially the items having insulating material to prevent the injury
due to moisture, from sources external to the packing or from excessive
condensation with the packing.
. Secondary kV 0.416Y/0.24
2.3 Number of phase 3
2.4 Frequency Hz 50
2.5 Vector group symbol Dyn11
2.6 Cooling method ONAN
2.7 Maximum temperature rise at
rated power
4 Design Details
4.1 Off-load tap changer
. manufacturer To be filled in
. Tapping range +5%/-5%
. Tapping step 2.5%
4.2 Exciting current referred to HV
side and 50 Hz
8 Acidity(Neutralization
Value):
. Total mgKOH/g To be filled in
. Inorganic
Page no.
3
3
5
6
8
8
8
9
10
11
13
14
ral
n is made for
an earthling
ms to limit the
to 300 Amp.
utral solidly
rt circuit level
e rated power
ltage of the
or
or
he
3
n.
.
r,
gle
e
me
.
ormer shall be
special tools
the tender.
Specifications
Proposed
pecifications
Proposed