IAQ_Review and Extension of CO2-Based Methods
IAQ_Review and Extension of CO2-Based Methods
Environmental Research
and Public Health
Article
Review and Extension of CO2-Based Methods to
Determine Ventilation Rates with Application to
School Classrooms
Stuart Batterman
Environmental Health Sciences, School of Public Health, University of Michigan, Ann Arbor, MI 48109, USA;
[email protected]; Tel.: +1-734-763-2417
Abstract: The ventilation rate (VR) is a key parameter affecting indoor environmental quality (IEQ)
and the energy consumption of buildings. This paper reviews the use of CO2 as a “natural” tracer gas
for estimating VRs, focusing on applications in school classrooms. It provides details and guidance for
the steady-state, build-up, decay and transient mass balance methods. An extension to the build-up
method and an analysis of the post-exercise recovery period that can increase CO2 generation rates are
presented. Measurements in four mechanically-ventilated school buildings demonstrate the methods
and highlight issues affecting their applicability. VRs during the school day fell below recommended
minimum levels, and VRs during evening and early morning were on the order of 0.1 h−1 , reflecting
shutdown of the ventilation systems. The transient mass balance method was the most flexible and
advantageous method given the low air change rates and dynamic occupancy patterns observed in
the classrooms. While the extension to the build-up method improved stability and consistency, the
accuracy of this and the steady-state method may be limited. Decay-based methods did not reflect the
VR during the school day due to heating, ventilation and air conditioning (HVAC) system shutdown.
Since the number of occupants in classrooms changes over the day, the VR expressed on a per person
basis (e.g., L·s−1 ·person−1 ) depends on the occupancy metric. If occupancy measurements can be
obtained, then the transient mass balance method likely will provide the most consistent and accurate
results among the CO2 -based methods. Improved VR measurements can benefit many applications,
including research examining the linkage between ventilation and health.
Keywords: ventilation; air change rate; carbon dioxide (CO2 ); schools; classrooms; indoor air quality
1. Introduction
The ventilation rate (VR) affects indoor environmental quality (IEQ) and the energy consumption
of buildings. Ventilation with outdoor air is intended to remove moisture and pollutants emitted
from indoor sources, and sufficiently high VRs are needed so as to not compromise IEQ and cause
health, comfort, absenteeism and productivity problems [1–10]. Buildings are large contributors to
energy consumption and greenhouse gas emissions, and heating, ventilation and air conditioning
(HVAC) systems are the most demanding component among building energy services, accounting
for an estimated 50% of building energy consumption and 20% of total energy consumption in the
U.S. [11]. Excessively high VRs increase energy consumption and incur additional energy-related
costs, however, the health benefits of higher VRs may greatly outweigh these costs [5]. In schools, for
example, increasing the VR to be consistent with minimum recommended levels has been estimated to
decrease absences related to illness and to yield a net economic benefit [6].
VRs should be consistent with minimum targets specified in building codes. Outdoor air rates
specified for classrooms in ANSI/ASHRAE Standard 62.1 are the sum of personal (5 L·s−1 ·person−1 )
Int. J. Environ. Res. Public Health 2017, 14, 145; doi:10.3390/ijerph14020145 www.mdpi.com/journal/ijerph
Int. J. Environ. Res. Public Health 2017, 14, 145 2 of 22
and area (0.6 L·s−1 ·m−2 ) minimum values [12]. Using the default occupant densities of 25 and
35 persons per 100 m2 for ages 5 to 8 and 9 and older, respectively, noted in the standard, the minimum
VRs are 7.4 and 6.7 L·s−1 ·person−1 for the two age groups. With a ceiling height of 3 m, this is
equivalent to air change rates of 2.22 and 2.01 h−1 . For residential dwelling units, the same standard
prescribes 2.5 L·s−1 ·person−1 and 0.3 L·s−1 ·m−2 . For a 200 m2 area, 600 m3 volume, 3-bedroom
dwelling with 4 occupants, the VR is equivalent to 20 L·s−1 ·person−1 and an air change rate of
0.48 h−1 , similar to a minimum of 0.5 h−1 recommended for homes [5].
Ventilation metrics, including the VR (m3 ·h−1 ), VR per person (L·s−1 ·person−1 ), the outdoor air
change rate (A, h−1 ) and others [13], can be determined using air flow measurements [14], pulse or
constant injections of tracer gases [15–18], occupant-generated carbon dioxide (CO2 ) as a “natural
tracer” gas [19–26], and the comparison of indoor and outdoor concentrations, concentration trends,
and sometimes temperatures [27,28]. Air flow measurements from fan pressurization tests [29] provide
a related measurement, the “tightness” of the building envelope. A recent review describing the use
and history of air change rate measurements highlights the use of the constant tracer injection method
with perfluorocarbon tracers like SF6 [13]; this method also allows multizone analyses [30]. VRs
are measured for many purposes, e.g., to inform complaint-driven building investigations, to verify
building system performance (e.g., commissioning), and as part of epidemiologic studies. However,
obtaining accurate VR measurements can be challenging [19], and relatively few IEQ studies have
adequately measured VRs or otherwise appropriately characterized the ventilation performance of
buildings under study [13]. Additional information is needed to improve the understanding of the
linkage between ventilation and health [31].
Occupant-generated CO2 has been widely used as a tracer gas for estimating the VR. CO2 -based
methods are convenient since CO2 is inert, emission sources (people) are present in all buildings
and usually well dispersed throughout occupied spaces, and inexpensive and reasonably accurate
measurement and logging instrumentation is available. CO2 is especially suitable for high occupancy
spaces like schools since indoor levels can far exceed outdoor concentrations [32]. In addition,
occupant-generated CO2 does not raise issues associated with the injection of a tracer gas, especially
a potent greenhouse gas like SF6 , that can concern school officials and require parental permission.
CO2 -based methods have been classified by the occupancy phase or the concentration trend into
build-up (or “step-up” or “charge-up”), steady-state (or equilibrium), and decay (or “step-down”)
phases [15,25,32]. Other CO2 -based methods include pulse injections, techniques that combine multiple
occupancy phases, and transient mass balance methods that can model multiple occupancy phases
as well as arbitrary occupancy patterns. Guidance and standards for several of these methods is
available [24,26,33]. These methods have different assumptions, strengths and limitations [24,25] and,
as shown later, can produce different results.
While convenient, CO2 is not an ideal tracer gas [24]. CO2 sources are not unique, e.g., replacement
air contains CO2 whether it is outside air where the global level currently averages 400 ppm, or if
replacement air arises from other portions of the building. In addition, outdoor CO2 levels fluctuate
daily and diurnally, e.g., levels tend to be lowest in the early afternoon and highest in the early
morning with average diurnal changes from 50 to 100 ppm in large urban areas such as Baltimore, and
levels vary by location, largely due to traffic-related emissions that can produce yet larger increments
over the global level [34]. Also, CO2 generation rates in buildings vary over time and the time
window considered for VR measurements, depending on the number of occupants and the level of
metabolic activity. Generation rates are rarely measured, but instead estimated based on relationships
established between occupant weight, height (or age and gender) and metabolic activity. Finally,
sensor performance can be a concern. While the non-dispersive infrared (NDIR) sensors commonly
used to measure CO2 are considered stable, durable and robust against interferences from other air
components and pollutants, these sensors can be affected by temperature, atmospheric pressure and
length of use [35].
Int. J. Environ. Res. Public Health 2017, 14, 145 3 of 22
This paper reviews and critiques CO2 -based methods for estimating the VR with specific
application to school classrooms. We present techniques presented in the literature, propose
enhancements to the build-up method, extend the transient mass balance method, provide school
grade- and age-specific emission rates needed for these methods, and discuss the effect of post-exercise
recovery periods on CO2 generation. The methods are demonstrated for classrooms in four schools.
Because the literature contains very few if any reports that compare CO2 -based VR methods to
reliable or “reference” methods for relatively large buildings like schools under real-life conditions,
a difficult task but a clear gap in the literature, this review focuses on a comparison of the CO2 -based
methods. The paper consolidates methods and experience in the literature, and provides guidance for
applications in classrooms, a critical environment with known ventilation issues.
dC
V = E + Q CR − Q C (1)
dt
where V = room (or zone) volume (m3 ); C = CO2 concentration in the room (mg·m−3 ); CR = CO2
concentration in outdoor air or replacement air (mg·m−3 ); Q = flow rate of outdoor or replacement air
(m3 ·h−1 ), and E = CO2 emission rate of indoor sources (mg·h−1 ). Generally, E is calculated as n GP ,
where n = number of persons in the space, and GP = CO2 generation rate per person (L·h−1 ), which is
age- and activity level-specific (as described later). The air change rate, A (h−1 ), is Q/V. Concentrations
throughout the zone are assumed to be equal; this should be confirmed using measurements at multiple
locations [24]. This assumption can be violated by the uneven distribution of CO2 sources and by
limited air distribution effectiveness. The CO2 methods discussed in this paper apply only to a single
and fully mixed zone. Also, VRs derived using CO2 -methods will include outdoor air delivered via
both the ventilation system and infiltration. Finally, most applications of tracer gas methods assume
that the VR is constant over a specific time window, i.e., the period over which the CO2 concentration
trend or peak level is measured and analyzed.
The outdoor air flow rate per person, V0 (L·s−1 ·person−1 ), is obtained from air flow rate Q
(m ·h−1 ) or A (h−1 ):
3
where the constant accounts for the volume and time conversions. If the number of occupants varies
over the time when the VR is determined, then the choice of n is critical. In schools, students and staff
often leave for lunch, recess and for other reasons, thus the average occupancy over the school day
can be much lower than the maximum occupancy. In consequence, V0 determined using the average
occupancy is higher, and often considerably (by about 50%) than that based on the maximum occupancy.
To assess the adequacy of ventilation by reference to VR guidelines expressed as L·s−1 ·person−1 , the
use of the maximum occupancy appears most consistent. To understand contaminant exposures, the
use of the average occupancy is preferable. This difference does not appear to have received attention
in the literature, possibly because prior studies have not had continuous occupancy information,
however, this issue appears important based on our recent experience in school classrooms [36].
VRs in both naturally- and mechanically-ventilated buildings can be affected by time-varying
factors including internal heating and cooling loads, outdoor temperature and the indoor-outdoor
temperature difference, and wind speed and direction [37]. In buildings using variable air volume
(VAV) systems, air flow and the VR will depend on thermal load. If the VR varies in the study time
window used to estimate the VR, then the assumption of a constant VR required by most of the
CO2 -based methods will be violated, although the VR estimate may be useful if the variation is small.
Int. J. Environ. Res. Public Health 2017, 14, 145 4 of 22
where n = number of persons in the space; GP = average CO2 generation rate per person
(L·min−1 ·person−1 ); V = volume of the room or space (m3 ); CS = steady-state indoor CO2 concentration
(ppm); and CR = CO2 concentration in replacement or outdoor air (ppm) (Given the widespread
practice, the remainder of this paper uses concentration units of ppm). Steady-state methods assume
that the CO2 generation rate (i.e., the number and physical activity of occupants) over the study
time window is constant for a sufficiently long period to reach the indoor equilibrium concentration
CS . (If CR changes over the time window, then the difference between CS and CR should approach
a steady-state level.) ASTM [24] suggests that the measured CS should reflect at least 95% of the
equilibrium value (i.e., as attained after three complete air changes), and provides comprehensive
guidance for this method including methods to estimate uncertainty. As noted, steady-state methods
assume the VR is constant over the study time window, and most assume that the outdoor CO2
concentration is constant.
In practice, the average age and average activity level of occupants are used to estimate Gp , the
replacement air concentration CR is preferentially measured [24] or assumed to be 400 ppm [38], and
CS is determined as the maximum 5- to 20-min average concentration over the study time window [1].
Some spaces may not reach steady-state conditions over the workday or study period. For this reason,
the steady-state method is not recommended in schools if classes last 45 min or less and the air change
is below 4 h−1 [21,25]. Many schools have much lower VRs, thus, the number of occupants must be
constant for at least several hours to approach steady-state levels. If occupancy varies around the time
of the peak concentration, then the method’s assumptions are not met. In classrooms, averaging the
number of occupants n and the generation rate GP just prior to the observed CO2 peak may avoid
anomalies if the occupancy fluctuates widely.
Steady-state methods may be used to estimate the VR per person using Equation (2) or as:
where V0,S = outdoor air flow rate per person (L·min−1 ·person−1 ), and the constant converts the
generation rate from hours to seconds and concentrations CS and CR from ppm to a mixing ratio. For
example, using a generation rate for a moderately active adult (1.7 MET; GP = 0.46 L·min−1 ·person−1
(Section 2.5), CS = 1479 ppm, and CR = 400 ppm, Equation (4) gives V0,S = 7.1 L·s−1 ·person−1 , the
minimum VR recommendation for many indoor spaces, including classrooms [12].
where ∆t = period between measurements (h); C0 and C1 = measured CO2 concentrations over
the decay period (ppm); and CR = CO2 concentration (ppm) in replacement air or the steady-state
concentration at the lower occupancy in the case of stepwise decrease in occupancy. The stability of
this 2-point estimate can be checked using an upper bound estimate of AD , obtained by selecting C1
Int. J. Environ. Res. Public Health 2017, 14, 145 5 of 22
and C0 as the maximum and minimum concentrations, respectively, occurring near the nominal times
specified, e.g., within ±1 h.
Alternatively, a sequence of CO2 concentrations over a portion of the decay period, Ct , may be
used to fit a solution to Equation (1) using regression or other means:
where CS = the steady-state CO2 concentration. The estimated decay air change rate AD is the slope of
the regression of ln(C1 − CR ) against time t. The regression intercept is ln(CS − CR ), thus CS is equal
to exp(intercept) + CR .
Decay methods have been used to estimate VRs in schools [21,32,39–41]. The decay method is
simple, and the regression approach does not require knowledge of CR , CS , GP , n or even V. However,
there are important caveats. First, the appropriate time window for analysis can require careful
selection [39,42]. The concentration change over the period must be large relative to the variation in
CR and CO2 measurement error; typically, changes of 100 ppm or more may be sufficient, but at least
several hundred ppm are desirable given the performance of typical instrumentation. (Many CO2
instruments report accuracies of ±50 ppm plus 1% to 2% of readings.). Second, while CO2 decay curves
often display near ideal behavior in many spaces, in rooms that utilize natural ventilation, opening
windows during class breaks can overestimate VRs during classes [32]. Conversely, if windows are
opened during occupancy but closed afterwards, VRs will be underestimated. Opened windows
also can lead to significant variation in concentrations in the space, thereby violating the well-mixed
assumption. Third, in mechanically-ventilated school buildings, while windows are rarely opened
(and sometimes not openable), HVAC systems typically are shut down at the end of the school day.
Because of the shut-down, decay air change rates will not apply to the occupied portion of the day.
This applies to most U.S. schools where shut-down may occur immediately following the last class, e.g.,
as early as 14:20 (2:20 p.m.). (24-h time notation is used throughout this paper.) Fourth, VAV systems
will provide less ventilation air if the thermal load diminishes after the space becomes unoccupied,
which would have the effect of lowering the VR during the decay period even if the HVAC system
is not shutdown. This especially applies to densely occupied spaces, including some classrooms.
Fifth, in both naturally- and mechanically-ventilated buildings, VRs and/or infiltration rates will
depend on the indoor-outdoor temperature difference, wind speed, heating and cooling load, and other
factors that may change over time. For these reasons, the decay-based VR may not reflect conditions
during the (occupied) school day, although it may provide information regarding the infiltration rate.
Finally, while both the two-point and multipoint methods provide identical results under idealized
circumstances, the former is more sensitive to measurement error and thus may be less accurate.
There are many approaches to solving the single zone mass balance for the build-up period.
One approach calculates the build-up air change rate AB (h−1 ) using two sequential CO2 measurements:
Appropriate times for measuring C0 , C1 and CM in classrooms and other applications will depend
on occupancy patterns and building system operation. Because build-up curves may not follow the
expected approach due to time-varying occupancy or other reasons, Equation (9) can be sensitive to
the time period selected (e.g., the estimated CS can be negative and meaningless if CM is less than the
average of C0 and C1 ).
A second solution technique for the build-up method is proposed that circumvents some of the
issues associated with the 3-point method. This uses an estimate of CS obtained by simultaneously
solving Equations (3) and (8) so that AS = AB . Using the average number of occupant n (persons),
age-adjusted CO2 generation rate GP (L·min−1 ·person−1 ), zone volume V (m3 ), replacement air
concentration CR (ppm), and an initial air change rate estimate denoted as ÂB (h−1 ), an initial estimate
of the steady-state concentration ĈS follows from Equation (3):
By substituting Equation (10) into Equation (8) and simplifying, ÂB can be solved for as the root
of the following equation:
While no analytical solution exists, Equation (11) can be solved by numerical root-finding methods.
Because Equation (11) has local minima and inflection points, a robust algorithm and an appropriate
starting solution should be used. Since CS must exceed C1 , ÂB is bounded and an upper bound
estimate (that can be reduced slightly to use as a starting estimate) is:
Equation (11) was solved using a modified Newton-Raphson method (described in Supplementary
Materials). This implicit solution to the build-up method will yield results identical to the 3-point or
other (exact) build-up methods under ideal circumstances. However, it may be more stable and less
sensitive to the time window selected. It somewhat resembles a steady-state method encompassing a
“correction factor” to account for measurements taken prior to reaching steady-state conditions [26].
A third solution method can be adopted from the ASTM E471 Standard, which includes a build-up
method for a continuous injection of a tracer gas [16]. This is adopted for CO2 by subtracting CR from
the series of CO2 observations measured over the study period, Ct at times t = 1 . . . T, expressing
concentrations in ppm, and calculating the air change rate (rather than the air flow):
where T = number of measurements in the summation, i.e., the expression T−1 Σt (Ct − CR )−1
is the average of the inverse of the CO2 measurements after subtracting CR . The first term in
Equation (13) is equivalent to the steady-state solution shown as Equation (3), but with the use
of multiple measurements; the second term provides a “correction” given that concentrations C0 and
C1 , taken at the beginning and ending of the study time window, respectively, are not at steady-state.
This solution to the non-steady-state problem can be sensitive to the time window selected, e.g., using
the early part of the build-up curve can inflate the summation term due to relatively large values of
inverse Ct , which leads to an overestimate of AB .
A fourth solution technique for the build-up VR also uses the series of concentration measurements
Ct over the build-up period with a solution to the fully mixed model
allowing AB to be obtained as the (negative) slope of ln(CS − Ct ) versus time t. The regression intercept
is equal to ln(CS − CR ), thus, CR is estimated as CS – exp(intercept). This approach requires an estimate
of CS , along with the sequence of CO2 measurements. A fifth and related solution method might use
a non-linear solver to simultaneously estimate AB and CS in Equation (15), e.g., by minimizing the
squared residuals.
Only a few applications of the build-up method in schools were identified [43,44]; these appear to
have used the 3-point method (Equations (8) and (9)) to estimate CS . The build-up method may be
used with relatively short occupied classroom periods and with low air change rates [32].
Build-up methods can be sensitive to the time window selected, as noted. In U.S. schools, the
school day in primary and secondary schools generally starts about 07:30 to 08:00 and lasts till about
14:30 or 15:00, however, there can be considerable variation and many classrooms have substantial
drops in occupancy during midday (e.g., due to lunch), in the afternoon, and at other times. In addition
to sensitivity to the time window, the build-up air change rate may be more affected by incomplete
mixing than the decay method [32]. The method assumes a constant CO2 generation rate, which
requires that the number of occupants in the space and level of physical activity are unchanged over
the time window, assumptions that are examined in Section 2.7. Finally, while the various solution
techniques for the build-up method can provide identical results under idealized circumstances, the
three point method requires that concentrations closely follow the expected trend; this method as well
as the implicit method can be sensitive to measurement error; the implicit method also depends on the
accuracy of the occupancy and emission estimates; and the ASTM method requires near-steady-state
conditions to minimize errors. In contrast, the multipoint solution method using Equations (14)
and (15) is potentially more robust. These issues are explored in Section 3.
where Ct = observed CO2 concentration at time t (ppm); nt = sequence of occupancy rate observations
at time t (persons); GP = average CO2 emission rate (L·min−1 ·person−1 ); Q = replacement air flow rate
(m3 ·h−1 ), V = volume of the space (m3 ); CR = replacement air CO2 concentration (ppm); and ∆t = time
interval for CO2 and occupancy observations (h). The estimated air change rate, ATMB (h−1 ), is Q/V.
The CO2 build-up from emission sources present in the space during the period ∆t is expressed as
Int. J. Environ. Res. Public Health 2017, 14, 145 8 of 22
the first exponential term, and the CO2 decay as the second term. If flow rate Q is constant, then the
expression exp(−A/V ∆t) in both terms is constant. Equation (16) is exact for step-wise changes in
occupancy at ∆t intervals (as obtained by occupant survey data). The key unknown, Q, is determined
as the value that meets an error criterion, e.g., a numerical solver may be used to fit Q by minimizing
the sum of squares between predicted and observed concentrations. We also recommend fitting the
CO2 concentration at the beginning of the study time window using constraints, e.g., minimum of
375 ppm. Estimating this concentration, rather than selecting the CO2 measurement, will increase
model fit and may avoid issues associated with an anomalous measurement, minor sensor errors, and
in cases, CO2 levels above CR that remain elevated from the previous day. The term exp(−Q/V ∆t),
which does not change with time, may be precomputed to increase the optimization speed.
The feasibility of using transient mass balance methods with CO2 to estimate VRs was shown
for a university library in England in 1980 [45]; more recently, the method was used to determine
outdoor air flow rates per person (V0 ) in 16 classrooms in nine schools (seven naturally ventilated) in
England [46]. Applications of the method using tracer gases other than CO2 may be more common, e.g.,
the method was used with SF6 to determine VRs in 62 naturally ventilated classrooms in 27 schools in
Greece; results showed strong correlation between VRs and CO2 concentrations [47]. CO2 simulations
have been used to evaluate VRs in a few mechanically- and naturally-ventilated school rooms in the
U.S. [22]. Smith [23] presents additional analyses, including extensions to multizone applications.
Methods to estimate uncertainty using transient methods have been discussed elsewhere [23,45].
The transient mass balance method is very flexible. It does not require steady-state conditions,
and it can be used with arbitrary (but known) occupancy patterns. It can estimate the VR for different
portions of the day and different occupancy phases, e.g., morning, afternoon and evening periods,
and include occupied and unoccupied periods, either separately or combined. (However, periods that
might have different VRs should be analyzed separately.). The method has less sensitivity to the time
window selected, any time interval ∆t can be used, and the replacement air concentration CR can vary
in time (if known). In addition, other unknown or uncertain parameters can be estimated, e.g., the
replacement air concentration CR and the metabolic activity level used to determine GP (as well as
the initial CO2 concentration mentioned). Such applications, however, should constrain estimated
variables to ensure plausible values, aid convergence, and limit the sensitivity of results. While
application-specific parameters should be used, for example, CR if estimated might be constrained
to the range of 350 to 500 ppm, reflecting measurement uncertainty of ±50 ppm and an urban
increment over average global levels of 50 ppm. Potentially the method can be used to account for
the post-exercise recovery period that may temporally increase GP (see Section 2.5). Finally, fitting
criteria can be calculated as a quality check, e.g., a minimum fraction of variance explained (R2 ) might
be required, thus ensuring acceptable agreement between predicted and observed CO2 concentrations.
where S = skin area (m2 ); H = height (m); and W = weight (kg) of an individual. The CO2 generation
rate per person, GP (L·min−1 ·person−1 ), is the O2 consumption rate multiplied by the respiratory
coefficient (0.83):
GP = (60) (0.83) (0.00276) S MET/{(0.23) (0.83) + (0.77)} (18)
Table 1. Height and weight data, surface area, and estimated CO2 generation rate GP by grade level
(for children) and age (for adults).
Physical activity levels depend on task and intensity, and standard MET-based definitions have
long been used to classify physical activity levels into sedentary (<1 to 1.5 MET), light (1.5 to <3 MET),
moderate (3 to <6 MET) and vigorous (>6 MET) classifications. For youth (8–18 years of age), recent
analyses suggest that resting energy expenditures exceed adult METS by about 33%, thus increasing
the ranges stated; consequently, sedentary behaviors of children may range of up to 2.0 MET [50].
Int. J. Environ. Res. Public Health 2017, 14, 145 10 of 22
The recent compendium of physical activity for children most commonly lists 1.4 MET for children
sitting quietly, studying, taking notes and writing, and having class discussion [51]. This value exceeds
the “typical” MET levels stated in the guidance for using CO2 for ventilation evaluations, i.e., 1.0 to
1.2 MET for reading, writing and typing while seated [24]. For adults, the most recent compendium
lists 1.5 MET for sitting tasks with light effort, e.g., office work, reading, computer work and talking;
standing tasks with light effort, e.g., directing traffic, filing, talking and teaching physical education,
range from 2.0 to 3.0 MET [52]. Again, these exceed values in the guidance noted earlier (1.0 to
1.2 MET for sitting activities noted earlier, and 1.4 and 2.0 MET for filing while standing and walking,
respectively). Teachers and other adults in classrooms are expected to engage in a combination of
sitting, standing and walking activities, thus a blend of sedentary and light activity levels is appropriate,
e.g., 1.7 MET may be appropriate for a teacher who occasionally stands and walks about the classroom.
Using a physical activity value of 1.4 MET and averaging across boys and girls, the CO2
generation rate GP in classrooms ranges from 0.147 L·min−1 ·person−1 for pre-kindergarten children
to 0.343 L·min−1 ·person−1 for 12th graders (Table 1). Several studies have used a single generation
rate for 5th grade children, equivalent to 0.258 L·min−1 ·person−1 [1,6,8]; the strong dependence on
age is important to recognize. For women, using a physical activity value of 1.7 MET and averaging
across ages, GP is 0.442 L·min−1 ·person−1 . GP estimates for adults have little sensitivity to age (<3%
variation), unlike for children. The assumption of female teachers, used since most teachers (88%)
in our school surveys have been women, is not significant since the total CO2 generation rate in
classrooms is usually dominated by students. The total classroom emission rate can be calculated as
the sum of emissions from children (grade level-specific GP multiplied by the number of students
present) and adults (adult GP multiplied by the number of adults present).
The variability of the population’s height and weight can affect GP , as demonstrated using a
limited sensitivity analysis. Using the relative variability described earlier and examining 6th grade
children, a 6% increase in height over the nominal case (Table 1) would increase GP by 4% (average for
boys and girls); 22% and 30% increases in weights of boys and girls, respectively, would increase GP
by 10%, and increasing both height and weight by these amounts would increase GP by 15%. In most
classrooms with a mix of children and imperfect correlation between height and weight, uncertainties
due to height and weight variation are expected to be smaller. Uncertainties related to physical activity
and metabolism levels, discussed below, are likely much more significant.
In most applications, the physical activity level of building occupants is unknown, and the
actual value might considerably exceed the assumed level. Also, if the activity level changes, the
assumption of a single and constant activity level might not adequately represent the CO2 generation
rate GP . In addition, energy expenditures of occupants depend on activity levels prior to entering
the space. In schools, for example, students may enter a classroom following more vigorous activity,
e.g., walking/running to class, playing at recess, etc. Factors that affect the post-exercise recovery
time needed to reach resting (or sedentary) metabolism levels include the duration and intensity of
the preceding exercise and the individual’s condition and age, e.g., recovery periods for children are
about half that of adults [53]. Information relevant to previous activity levels and the corresponding
GP pertaining to students entering a classroom in the recovery period is not directly available, but can
be inferred from several sources. For example, guidance for measuring the resting metabolic rate in
adults in clinical settings suggests a minimum rest period of 10 to 20 min, and an abstention period of
2 h following moderate aerobic or anaerobic exercise [54]. The duration of excess post-exercise oxygen
consumption (EPOC) for short and low intensity exercise across a number of studies examining adults
listed in a comprehensive review of EPOC studies ranged between 6 and 30 min [55]. Comparable
EPOC studies for healthy children engaged in low intensity exercise relevant for schools were
not identified.
To evaluate effects of prior physical activity, we analyzed several scenarios that considered
children exercising just prior to entering a classroom. For exercise, we assumed walking with light to
hard effort, equivalent to 2.9 to 4.6 MET [51], and a nominal value of 3.5 MET. For recovery periods,
Int. J. Environ. Res. Public Health 2017, 14, 145 11 of 22
we assumed a recovery time tREC (h) from 0.1 to 0.5 h, and a nominal period of 0.25 h (only adult
values were available). The literature often represents recovery trajectories as a first-order (exponential
decay) trend, but recovery durations have been reported using different methods. We assumed that
the reported recovery time reached the resting metabolism rate within 5% of the pre-exercise value,
and thus the recovery time rate constant KREC (h−1 ) = ln(0.05)/tREC (Larger percentages, 10% and
15%, were are also tested). With these assumptions, an individual’s instantaneous activity level after
entering a classroom, METt , will exponentially decline to the sedentary level, METSED :
where METEXER = physical activity level during exercise (MET); and t = time elapsed since entering the
classroom and the cessation of exercise (h). To gauge the importance of the recovery effect over the CO2
monitoring time window, METt is averaged over the time period the student is in the classroom and
compared to METSED (assumed to be 1.4 MET), and expressed as a relative bias (%). This represents
the amount of additional activity resulting from the post-exercise recovery period, and also the extent
to which CO2 emissions will be underestimated if the post-exercise recovery effect is ignored.
2.7. Application
Four classrooms in different primary schools were selected to demonstrate the VR methods,
several of which have not been applied previous in schools, and to show a range of ventilation and
occupancy conditions. The selected schools are a subset of those in a larger (Environmental Quality
and Learning in Schools or EQUALS) study. These schools were located in the U.S. Midwestern states
of Michigan, Illinois, Ohio and Indiana; all are mechanically-ventilated, and all were constructed or
fully renovated in the past 15 years. Schools were visited and monitored in winter during the heating
season (November 2015 to February 2016) when window or door opening was at a minimum. Our
technicians conducted walk-through surveys of each classroom, ventilation system, school building,
and grounds. Classroom dimensions were obtained using a laser tape measure. HVAC information,
including system type, configuration, design and minimum air flow rates, were obtained from HVAC
drawings, schedules and photos, as well as manufacturer’s specifications; this information was used
to calculate VRs for comparison with those determined using the CO2 -based methods. The studied
spaces are summarized in Table 2.
CO2 concentrations in each classroom were measured at a central location away from
windows and doors using NDIR sensors (C7632A, Honeywell Corp., Morristown, NJ, USA); similar
instrumentation on the school grounds or rooftop measured outdoor CO2 concentrations. CO2 data
were reduced to 15 min averages. CO2 sensors were calibrated quarterly using zero air and a certified
standard. Drift per season was typically below 25 ppm. Teachers in the selected classrooms were asked
to maintain an occupancy log by recording the number of adults and children present every 15 min.
This information was used to estimate CO2 generation rates on a 15 min basis using metabolic activity
levels of 1.4 and 1.7 MET for children and adults, respectively, and the generation rates in Table 1.
The effect of post-exercise recovery was not modeled, although a sensitivity analysis is performed in
Section 3.3. One day with full data in each school was selected for analysis. To calculate build-up,
steady-state and decay air change rates, study days were separated into several periods (see below) in
which the VR was assumed to be constant. The 06:00 to 08:00 and 15:00 to 18:00 periods were excluded
since the ventilation systems were turned on and off during these periods, which would change the VR.
In addition, during these periods, occupancy rates changed dramatically, and the collected occupancy
data may have been incomplete.
Int. J. Environ. Res. Public Health 2017, 14, 145 12 of 22
Table 2. Summary of tested classrooms, schools, ventilation systems and prevailing weather
conditions. Local (airport) temperature and wind speed (mean and range in parentheses) for school
day (08:00–15:00) and evening and morning period (18:00–06:00).
ID Room, School, HVAC, Weather HVAC Description and Calculated Air Change Rate
Building uses conventional variable air volume (VAV)
Large mixed-grade classroom (299 m3 ) in a
system with central air handling units (AHUs) and energy
midsize conventional building (9012 m2 ,
recovery (ER). Five ceiling mounted diffusers in the room
29 classrooms) constructed in 2005.
collectively discharge 142 to 519 L·s−1 (minimum of
S07C4 School day: Temp: 13 (11–15) ◦ C Wind speed:
236 L·s−1 during the heating season) with a minimum of
9 (7–11) m/s
30% outside air (OA).
Eve + Morn: Temp: 10 (9–11) ◦ C Wind speed:
Given building/HVAC data, estimated air change rates are
12 (8–15) m/s
0.85 to 1.45 h−1 in the heating season.
Large prekindergarten/ kindergarten classroom
Classroom uses vertical unit ventilator (UV) with multiple
(322 m3 ) in a smaller (7430 m2 , 22 classrooms)
fan speeds, fully adjustable dampers, and rated capacity of
and newer building constructed in 2011.
755 L·s−1 . UV had dirty filters (reportedly changed
S14C2 School day: Temp: 5 (4–5) ◦ C Wind speed:
twice yearly).
5 (4–6) m/s
Assuming a minimum flow of 40% of capacity and a
Eve + Morn: Temp: 8 (5–9) ◦ C Wind speed:
minimum of 30% OA, the air change rate is 1.01 h−1 .
7 (5–12) m/s
2nd grade classroom (213 m3 ) in a midsize
Building uses geothermal heat pumps for each classroom
(10,400 m2 , 36 classrooms) EnergyStar building
and centralized make-up air (100% OA) discharged
constructed in 2005.
through four ceiling diffusers. Design drawings show the
S19C3 School day: Temp: −11 (−17–−6) ◦ C Wind
maximum OA flow rate to the room of 566 L·s−1 .
speed: 6 (3–8) m/s
Assuming a minimum of 30% of rated flow, the air change
Eve + Morn: Temp: −12 (−17–−8) ◦ C Wind
rate is 2.87 h−1 ; at maximum flow, the rate is 9.56 h−1 .
speed: 5 (3–8) m/s
Large 4th grade classroom (281 m3 ) in a smaller
(5760 m2 , 21 classrooms) EnergyStar building that
has had several expansions since original Building uses a UV in each classroom with a maximum
construction in 1975. Complete building flow of 519 L·s−1 discharged through four ceiling diffusers.
S30C4 renovation in 2007. Assuming a minimum of 50% of the rated flow and 30%
School day: Temp: −6 (−7–−4) ◦ C Wind speed: OA, the air change rate is 1.00 h−1 ; at maximum flow, the
4 (3–6) m/s air change rate is 2.00 h−1 .
Eve + Morn: Temp: −4 (−6–−2) ◦ C Wind speed:
6 (4–7) m/s
Steady-state VRs were calculated using Equation (3), the maximum 15-min CO2 concentration
over the school day (08:00 to 15:00), the measured room volume, the average generation rate over the
2 h prior to the time of the maximum CO2 concentration (determined from the 15-min average data),
and 400 ppm for the measured outdoor CO2 concentration, which was confirmed using the outdoor
measurements. V0,S was calculated using Equation (4), the average per person CO2 generation rate in
the classroom, and the number of persons in the classroom in the 2 h period just prior to the peak CO2
concentration. We determined the sensitivity to the time period and outdoor air concentration.
Decay air change rates were estimated using Equation (5), 15-min average CO2 measurements
measured at 18:00 and 24:00 for the “evening” period, and concentrations at 24:00 and 06:00 for the
“early morning” period. We searched for the maximum and minimum concentrations occurring within
±1 h of the nominal period, which were used as C0 and C1 in Equation (5). Comparable decay air
change rates were found using regression to fit Equation (7) (results not shown). In addition, transient
mass balance air change rates were estimated for the same periods using the sequence of 15 min
average CO2 measurements.
Build-up air change rates were determined using the 2-point method in Equation (8) with an
implicit estimate of CS determined using Equations (10) and (11), C0 and C1 measured as 15-min
averages, a starting estimate given as 0.9999 × ÂB,0 from Equation (12), and the Newton-Raphson
search method, described earlier (also see Supplemental Information). Given the occupancy patterns
noted, we selected a nominal period from 08:00 to 12:00, but allowed actual start and end times to vary
by ±1 h (as described earlier). The average CO2 generation rate over the selected time window was
Int. J. Environ. Res. Public Health 2017, 14, 145 13 of 22
used to estimate CS . The build-up method was also implemented using the 3-point and ASTM methods
(Equations (8), (9) and (13), respectively), the same selected times, and the 15-min concentration at
the midpoint time (or the average of two consecutive 15-min concentrations given an even number of
observations between C0 and C1 ).
Transient mass balance air change rates were determined using Equation (16) for three periods: the
school day (8:00 to 15:00 p.m.), an evening period (18:00 to 24:00), and an early morning period 24:00 to
06:00). We used an interval of 15 min (∆t = 15 min) for observed and simulated CO2 concentrations, and
the CO2 generation rate (using teacher-reported occupancy data). In addition to ATMB , we estimated
the replacement air concentration (CR ) with constraints (375 ppm < CR < 450 ppm), the children’s
metabolic equivalent level within constraints (1.2 < MET < 1.6), and the CO2 concentration at the
beginning of the simulation period with a constraint (C > 375 ppm). A generalized reduced gradient
solver using central derivatives estimated these unknown parameters by minimizing the sum of
squares between observed and simulated CO2 concentrations. VRs were estimated separately for each
period. Each problem used the same initial solution. We also tested the sensitivity of results to the start
and stop times and other parameters. Lastly, V0 is reported using both the average and the maximum
number of occupants, and the estimated VR.
Outdoor temperatures and wind speeds measured at the airport nearest each school are shown in
Table 2. During the school day (08:00–15:00), average temperatures varied considerably (−11 to 13 ◦ C),
depending on the day studied. Several days had moderately high wind speeds (up to 9 m/s for the
school day average).
Table 3. Estimated air change rates (h−1 ) in four classrooms based on transient mass balance,
steady-state, build-up and decay methods.
1. Observed
Figure 1. Observed and
and simulated
simulated CO CO22 concentration trends over 24-h periods in classrooms in two
conventional school buildings (A,B) and two EnergyStar school buildings (C,D). Red circles show
observed (15-min) levels; colored areas show show predicted
predicted CO
CO22 levels using simulated air change rate
rate
estimates fitted for the
the school
school day (blue),
(blue), evening
evening (green), and
and early
early morning
morning (yellow)
(yellow) periods.
periods. Time
shows hour
axis shows hour of
of day
day (starting
(starting at
at 07:00).
07:00).
Table 3. Estimated air change rates (h ) in four classrooms based on transient mass balance, steady-
−1
Figure 1A shows trends for room S07C4. During the study period, the room contained as many
state, build-up and decay methods.
as three adults and 41 children. Children were present continuously from 9:30 to 15:00 except for the
lunch period (12:00 to 13:00), but the number of occupants fluctuated
Conventional considerably,
Buildings EnergyStarandBuildings
the maximum
Period of Day Method
occupancy occurred at the end of the school day when S07C4 students S14C2
from anotherS19C3 S30C4
class briefly joined the
School day (occupied)
room (doubling the number of students). The “pointed” peak at the maximum CO2 concentration
reveals that a steady-stateTransient
level was mass
notbalance 0.51 the school
reached. During 0.77 day (08:002.42
to 15:00), 0.70
CO2 levels
Steady-state 0.52 0.67
(15-min average) reached 2100 ppm, the transient mass balance air change rate was 0.51 1.41 0.80h−1 , the
Build-up-3 point 0.31 0.77 0.70 0.22
“steady-state” rate using the observed maximum CO2 level was 0.52 h−1 , and build-up rates were 0.31,
Build-up-implicit 0.43 0.57 2.10 0.62
0.43 and 0.52 h−1 for the 3-point, implicit and ASTM methods, respectively. All VRs calculated using
Build-up-ASTM 0.52 0.68 13.19 1.34
CO2 fell well below those based on the HVAC schedule (shown in Table 2). Air change rates dropped to
Evening (unoccupied)
0.14 h−1 in the evening (18:00 to 24:00)
Transient and
mass then to 0.10
balance h−1 in the early
0.14 0.18 morning0.27 (24:00 to 06:00).
0.72 In the
unoccupied period, CO2 trendsDecay followed the expected exponential
0.13 decay,
0.13 and the
0.17decay and transient
0.57
mass Early
balance methods
morning gave comparable results. Based on the latter, V0 was 2.6 L·s ·person−1 using
(unoccupied)
− 1
in the afternoon. During the school day, CO2 levels reached 1440 ppm, the transient mass balance and
3-point build-up VR estimates were both 0.77 h−1 ; the steady state and other build-up VR estimates
were lower (Table 2). V0 was 5.5 L·s−1 ·person−1 using the average occupancy (12.6 persons) and
3.1 L·s−1 ·person−1 using the maximum occupancy (22 persons). During the (unoccupied) evening
and early morning periods, VRs dropped 5- to 10-fold, and the transient mass balance and decay air
change rates matched closely, although CO2 levels in the early morning had only small changes, which
increased uncertainty and decreased fit (e.g., R2 = 0.82). Like Figure 1A, CO2 levels the following
morning remained (slightly) elevated over outdoor levels, a result of a particularly low VR during
this period.
Figure 1C displays trends in room S19C3, a classroom that contained one or two adults and
22 children for most of the morning. This room emptied at lunch, and then was re-occupied with about
the same number of students in the afternoon. This pattern produced two “well-formed” CO2 build-up
curves in the morning and in the afternoon that reached 1080 ppm. During the occupied period, the
transient mass balance air change rate was 2.4 h−1 , close to that estimated using the HVAC schedule
(Table 2). The estimated V0 was 5.5 L·s−1 ·person−1 for the average occupancy (15.1 persons) and
9.5 L·s−1 ·person−1 for maximum occupancy (26 persons), the highest V0 among the four classrooms.
The steady-state and 3-point build-up methods gave lower VRs; the ASTM build-up method gave
a very high and spurious result, a result of initially low then rapidly rising CO2 levels. During the
unoccupied evening and early morning periods, VRs dropped over 10-fold, e.g., transient mass balance
and decay air change rates in the evening period were 0.27 and 0.17 h−1 , respectively. The divergence
between these VRs, larger than usual, reflects the low CO2 levels during the unoccupied periods that
increased uncertainty (R2 = 0.88).
Lastly, Figure 1D depicts 30C4. The room had one teacher and 27 students, but occupancy varied,
i.e., most students left in the early afternoon, but about half were reported to have returned for their
final class around 15:00. A second CO2 peak occurred in the late afternoon around 16:00 (this fell
beyond the 15:00 cut-off used in the transient mass balance simulation). CO2 levels reached 1900 ppm in
the morning and 2060 ppm in the afternoon. Like Figure 1A, the “pointed” peaks at the maximum CO2
concentration reveal that steady-state levels were not reached. For the occupied period, the transient
mass balance air change rate was 0.71 h−1 , the “steady-state” rate was 0.80 h−1 , and again, the 3-point
build-up rate was low and the ASTM build-up rate was high. The transient mass balance simulations
capturing both peaks (running from 08:00 to 17:00, not shown) obtained a slightly air change rate
(0.60 h−1 ), but the morning CO2 peak was over-predicted and the afternoon peak was under-predicted
(both by about 300 ppm), suggesting that additional (and unreported) students had returned, that
activity levels increased, or that the VR decreased. In this room, V0 was 3.3 L·s−1 ·person−1 using the
average occupancy (16.6 persons) and 2.0 L·s−1 ·person−1 using the maximum occupancy. The evening
trend in this classroom is unusual because the HVAC system was operated until midnight, thus the
evening VR was relatively high (0.72 and 0.57 h−1 for the transient mass balance and decay methods,
respectively). The air change rate dropped to very low levels (0.01 to 0.05 h−1 ) in the early morning
when the HVAC system was shutdown.
160
Case 2: Krec=0.50 h; METexer=4.6 MET
140
Case 1: Krec=0.25 h; METexer=3.5 MET
120
Figure
Figure 2. Effect
2. Effect of post-exercise
of post-exercise recoveryon
recovery onCO
CO2 generation
generation and
andmetabolic
metabolic activity rates,
activity expressed
rates, expressed
2
as relative bias for periods of 0 to 3 h, compared to classroom activity of 1.4 MET. Assumes children
as relative bias for periods of 0 to 3 h, compared to classroom activity of 1.4 MET. Assumes children
undergoing light to moderate exercise (2.9 to 4.6 MET) prior to entering the classroom. Three cases
undergoing light to moderate exercise (2.9 to 4.6 MET) prior to entering the classroom. Three cases
shown: Case 1 uses nominal parameters; Case 2 uses “maximal effect” parameters; Case 3 uses
shown: Case 1 uses nominal parameters; Case 2 uses “maximal effect” parameters; Case 3 uses
“minimal effect” parameters.
“minimal effect” parameters.
While the analysis is approximate and uncertain given the data gaps (particularly those for
While the
children) analysis
and is approximate
the simplified assumptions,and uncertain
results suggestgiven the dataofgaps
that estimates physical(particularly
activity andthose
thus for
GP applying
children) and thetosimplified
a student entering in a classroom
assumptions, will be underestimated
results suggest that estimates ifofthe preceding
physical exercise
activity andisthus
of high intensity
GP applying (>4 METS)
to a student and the
entering in ameasurement
classroom will timebe
window is short (<1 if
underestimated orthe
2 h)preceding
and immediately
exercise is
follows the students’ entry into the classroom. To significantly affect the total
of high intensity (>4 METS) and the measurement time window is short (<1 or 2 h) and immediately CO 2 generation rate,
this must apply to most students entering the classroom. In such cases, the recovery effect will be
follows the students’ entry into the classroom. To significantly affect the total CO2 generation rate,
significant and GP will be significantly underestimated, leading to an overestimate of the VR. The
this must apply to most students entering the classroom. In such cases, the recovery effect will be
build-up method may be especially prone to the post-exercise recovery effect since it emphasizes the
significant and GP will be significantly underestimated, leading to an overestimate of the VR. The
early portion of the CO2 trend; results for the transient mass balance and steady-state methods may
build-up method
also be may
affected, be especially
although smallerprone
effectstoare
theexpected
post-exercise recovery
since these effect
methods since
tend it emphasizes
to emphasize the the
earlyhigher
portionCO2 concentrations that occur several hours after students enter the classroom. Figure 2 alsomay
of the CO 2 trend; results for the transient mass balance and steady-state methods
also be affected, although smaller effects are expected since these methods tend to emphasize the higher
CO2 concentrations that occur several hours after students enter the classroom. Figure 2 also suggests
that the time window selected for analysis, if possible, should exclude the first hour after students enter
the space. In many situations, however, the bias may be modest (<10%) even with considerable traffic
into a classroom, a result of children’s quick recovery time (possibly underestimated since the analysis
used the adult values), and since VR determinations typically use multihour-long time windows.
Examination of CO2 trends in the sample classrooms did not show evidence of post-exercise
recovery effect, although effects could be obscured by other factors. In particular, physical activity
levels might not be elevated prior to school since few children are walking or cycling to school.
However, for students entering a classroom immediately following moderate to high level of physical
activity from sports or other vigorous activity, METEXER may be particularly elevated, and thus the
post-exercise recovery period should be excluded from the time window used to determine the VR.
the tested classrooms, all in modern mechanically-ventilated U.S. schools, are below recommended
levels of 6.7 L·s−1 ·person−1 (assuming default occupancy and children ages 9 and up) [12]. This has
been shown in other U.S. schools, e.g., V0 averaged 3.6 L·s−1 ·person−1 in elementary schools in the
southwest U.S. (determined using CO2 and the steady-state method [8], and similar results have been
reported in other countries [10,41]. Third, VRs were low (around 0.1 h−1 ) in the early morning (and
generally the evening) when the building was not occupied, reflecting the shutdown of the ventilation
system, and possibly a “tight” building envelope (Tightness was not measured in this study). Such
energy and cost-savings measures, taken in the design and operation of many modern buildings, were
anticipated for the EnergyStar buildings (Figure 1C,D), but also were apparent for the two conventional
buildings tested (not designed to meet EnergyStar or other energy-certification system; Figure 1A,B).
As discussed below, these issues have important consequences for VR estimates, which are below
by method.
Often, the steady-state CO2 concentration CS in classrooms may not be reached, and CS can
change over time, a result of low VRs and dynamic occupancy patterns. This was demonstrated in
two of the classrooms (Figure 1A,D) that had ‘pointed’ peaks at the maximum CO2 concentration.
In the two others (Figure 1B,C), CO2 trends began to plateau, an indication of the approach of
steady-state conditions, but trends never became horizontal. The potential to overestimate VRs when
the steady-state concentration is not attained has been recognized for many years, though this method
continues to be widely used [26]. For CO2 measurements, we do not recommend averaging periods
shorter than 5 to 10 min (or the use of instantaneous measurements) for CS , especially in schools and
where instrumentation is unattended, given instrument noise and the possibility of unrepresentative
spikes (e.g., children breathing on sensors). This also applies to CO2 measurements used in the
build-up and other methods.
For classrooms that have just been vacated, CO2 levels tend to decline smoothly and exponentially,
and decay and transient mass balance methods give comparable results. For the 2-point decay method
(Equation (5)), selecting C0 and C1 as the maximum and minimum concentrations, respectively, within
±1 h of the nominal times for a 6 h time window, also gave similar estimates of AD as the nominal
times. The decay method provided consistent results for evening and early morning time windows
using 15-min average CO2 measurements and time windows as short as 2 h. However, VRs determined
for the unoccupied period did not reflect conditions during the occupied period (see Section 2.2). Thus,
decay-rate VRs may be less relevant to health and comfort investigations, although VRs estimated for
the unoccupied period may relate to the build-up of emissions associated with building materials and
furnishings (e.g., formaldehyde) and they may have energy-related and other implications.
The build-up method does not require steady-state conditions and can provide consistent results
given a step-wise increase in CO2 generation rates. The method requires the identification of an
appropriate time window, which must exclude changes in occupancy, and specifically the lunch period
when students typically leave the classroom. Given patterns observed in the elementary schools,
we recommend a nominal time window from 08:00 to 12:00 with flexible start and end times (±1 h)
so as to minimize C0 and maximize C1 . The classroom must be continuously occupied during the
selected period. This protocol excludes the lunch hour and improves reliability. A 2 h time window
was usually sufficient, which may allow analysis of both morning and afternoon build-up periods
(again excluding the lunch period). Still, results can remain sensitive to the time window selected. This
applied particularly to the ASTM and 3-point methods, which did not obtain consistent results, an
unsurprising result given the irregularity of the observed build-up curves. In addition, the 3-point
method failed when Equation (9) yielded a negative value of CS (as discussed in Section 2.3). Of the
build-up methods, the implicit solution approach (Equations (10)–(12)) is recommended. This approach
requires only two CO2 measurements, converged rapidly in each classroom tested using the modified
Newton-Raphson method and the suggested starting solution, provided good stability, and obtained
VR estimates that were more consistent with those of the transient mass balance method. However, this
approach requires an estimate of occupancy over the sampling period. Only the morning period was
Int. J. Environ. Res. Public Health 2017, 14, 145 18 of 22
used with the build-up method; longer periods gave poor outcomes due to occupancy changes. Even
with the flexible start and stop times suggested, build-up air change rates provided by the implicit
method were typically smaller (by 20% to 35%) than those calculated using the transient mass balance
method, again, likely due to the irregular occupancy patterns. For each of the build-up methods, a CO2
concentration trend that follows the expected build-up curve is a necessary but not sufficient condition
of a step-wise increase in occupancy and constant CO2 generation rate, assumptions of this method.
To confirm results of the build-up method, the CO2 trend must follow the expected pattern, occupancy
records must show a stepwise increase, and the physical activity level of students in the classroom
must be constant. To minimize possible effects of the post-exercise recovery period, the selected time
window might be lagged by at least one hour following periods when students undertake moderate to
high intensity exercise, e.g., gym class.
The transient mass balance method, which uses a simple fully-mixed model and a straightforward
optimization, yielded results that closely fitted observed CO2 levels in most cases. When occupancy
patterns are irregular and steady-state levels are not achieved, the transient method generally provided
larger and more potentially more accurate VRs than those from the steady-state and build-up methods.
Because steady-state conditions or knowledge of CS are not required, and because all CO2 data
are used (not just the measurements that border the analysis time window), the transient mass
balance method may provide the most accurate and robust results among CO2 -based methods for
periods when classrooms are occupied. However, discrepancies can result from errors in reported
occupancy and unknown activity levels of the children. Still, the overall agreement observed is
excellent, demonstrating the feasibility and performance possible when using teacher−reported
occupancy and 15-min block data. In most cases, results were not sensitive to the period selected,
e.g., VRs for the 08:00 to 14:30 period were generally within 5% of those for the 08:00 to 16:00 period.
Greater sensitivity can result if simulated and observed concentrations diverge (e.g., in the afternoon
in Figure 1D), but this was the exception. As with the other methods, the time window should not
bridge periods in which HVAC operation is changed.
3.4. Limitations
Several limitations apply to the methods and results. First, each room is assumed to be a
single well-mixed zone that could be characterized by measurements at a central, but single location.
Guidance for VR measurements using CO2 specifies that CO2 concentrations at representative locations
should differ by less than 10% [24]. In the test classrooms, measurements that could evaluate this
assumption were not obtained, but our experience in schools and other mechanically-ventilated
spaces suggests that a central monitoring site is likely to provide measurements representative of
the space. This is less likely when the HVAC system is turned off and mixing is reduced; however,
the well-behaved decay curves as well as similar VRs determined for other classrooms in the same
building at the same time [36] suggest that the CO2 measurements remained representative. The single
zone model applied to classrooms has other limitations, e.g., classrooms can be connected together
and HVAC zones can include hallways and other spaces in the building. In these cases, multizone
models and additional parameters, e.g., multiple tracer gases and/or air flow measurements, may be
needed to evaluate air change rates between building spaces as well as outdoors.
Second, measurements also need to be accurate, and errors will increase as CO2 levels decrease
and approach outdoor levels. We did not evaluate the validity of the single zone assumption, i.e.,
interzone air and CO2 transport were neglected. Third, the steady-state and decay methods assumed
that CO2 levels in replacement air CR are constant and known (or estimated), and the former method
also requires attainment (or near-attainment) of steady-state CO2 levels. CO2 levels in replacement air
should be based on contemporaneous outdoor measurements near the air intake of the space, thus
accounting for possible differences in outdoor levels due to CO2 emissions from vehicle exhaust and
other sources. Fourth, the decay, build-up and transient mass balance methods require measurements
taken over a long enough period to observe a meaningful CO2 concentration change. This is rarely an
Int. J. Environ. Res. Public Health 2017, 14, 145 19 of 22
issue in classrooms. Fifth, CO2 generation rates depend on the physical activity level of children in the
classroom as well as the activity just prior to entering the classroom. The true activity level is unknown,
may considerably exceed the default value assumed or the range considered, and may vary over time.
This can affect VR estimates determined using the simulation, build-up and steady-state methods.
Sixth, our analysis of the post-exercise recovery period was modeled, and supporting observations for
children are not available. Further analysis of this issue is suggested. Seventh, each of the methods
discussed require that the true VR does not change during the time window considered. As mentioned,
VRs can vary for many reasons, especially in buildings that are naturally ventilated, that use variable
air volume systems, that turn on or off HVAC systems during the time window, or if the infiltration
rate varies during the time window (e.g., due to changes in outdoor temperatures and winds).
Examples were provided for a small set of classrooms with the intention of demonstrating the
variability of CO2 patterns in schools. The sample is not necessarily representative. All studied
classrooms were mechanically-ventilated and in relatively new buildings. We did not address
day-to-day variability in the studied classrooms and among classrooms in the school, or quantify the
uncertainty of results. However, we discussed uncertainties resulting from variations in occupant
heights, weights and activity levels, occupancy data, method variation and the applicability of its
assumptions, CO2 measurement errors, and the adequacy of mixing, among other factors.
Finally, it can be difficult to evaluate the performance of CO2 -based and other methods to
determine VRs. An independent and “reference” method, e.g., using a different and unique tracer gases
or air flow measurements, was not utilized to confirm the results. Even these methods involve many
assumptions and few if any intercomparisons of different methods have been conducted in parallel
measurements under real-life conditions [15]. While VRs were estimated using information obtained
from HVAC drawings, schedules and manufacturer’s material, this information was incomplete and
does not necessarily reflect actual performance. In all cases, even the minimum VRs estimated using
this information consistently exceeded the in-use VRs determined using the CO2 -based methods.
4. Conclusions
Ventilation rates are critical parameters that relate to building energy performance and the
health and comfort of occupants. Ventilation rates determined using CO2 -based methods, which are
commonly applied, were reviewed and critiqued, with special attention to classroom applications.
The methods were demonstrated in primary school classrooms in modern and mechanically-ventilated
buildings. As shown in the literature, ventilation rates in the tested classrooms during the school day
fell below minimum recommendations. Air change rates during evening and early morning, when the
ventilation system was shut down, were far lower (around 0.1 h−1 ).
VRs determined using transient mass balance methods are flexible, robust and advantageous
given the low VRs and dynamic occupancy patterns often found in classrooms. These methods require
information pertaining to changes in occupancy, some basic building and occupancy parameters,
and numerical methods to estimate air change rates. Several updates to the build-up method were
presented, namely, an implicit method to find AB and CS simultaneously using occupancy information,
and an adaptive approach to selecting the analysis time window. The utility of the steady-state and
build-up methods may be limited in classrooms for several reasons: the steady-state CO2 concentration
may not be reached, measured or estimated accurately; a step-wise increase in occupancy may not be
observed or confirmed; and post-exercise recovery can alter the CO2 generation rate, particularly with
vigorous physical activity immediately prior to entering a classroom. During unoccupied periods, the
decay and transient mass balance methods can provide equivalent results, however, VRs determined
for such periods will not be representative of the occupied portion of the school day if the HVAC
system is shut-down or a VAV system is utilized and the heating or cooling load changes significantly
when occupants leave. In the schools examined, most HVAC systems were shut down immediately
after students left. Thus, VRs determined at the end of the school day will likely be of less interest for
many types of building investigations.
Int. J. Environ. Res. Public Health 2017, 14, 145 20 of 22
If occupancy measurements can be obtained, then VRs determined using transient mass balance
methods will provide the most accurate and robust results. Without occupancy measurements, CO2
concentration trends must be carefully examined to determine whether the steady-state or build-up
method can be used, and to determine an appropriate time window for analysis. Still, sufficient
occupancy data should be collected to confirm that the method’s assumptions and results are correct.
Better VR measurements would improve a number of applications, including research aimed at
understanding the linkage between ventilation and health.
References
1. Haverinen-Shaughnessy, U.; Moschandreas, D.J.; Shaughnessy, R.J. Association between substandard
classroom ventilation rates and students’ academic achievement. Indoor Air 2011, 21, 121–131. [CrossRef]
[PubMed]
2. Shendell, D.G.; Prill, R.; Fisk, W.J.; Apte, M.G.; Blake, D.; Faulkner, D. Associations between classroom CO2
concentrations and student attendance in Washington and Idaho. Indoor Air 2004, 14, 333–341. [CrossRef]
[PubMed]
3. Wargocki, P.; Wyon, D.P. The effects of outdoor air supply rate and supply air filter condition in classrooms
on the performance of schoolwork by children (rp-1257). HVAC&R Res. 2007, 13, 165–191.
4. Sundell, J.; Bronswijk, V.J.; Dijken, V.F. Indoor environment and pupils’ health in primary schools.
Build. Res. Inform. 2006, 34, 437–446.
5. Sundell, J.; Levin, H.; Nazaroff, W.W.; Cain, W.S.; Fisk, W.J.; Grimsrud, D.T.; Gyntelberg, F.; Li, Y.; Persily, A.K.;
Pickering, A.C.; et al. Ventilation rates and health: Multidisciplinary review of the scientific literature.
Indoor Air 2011, 21, 191–204. [CrossRef] [PubMed]
6. Mendell, M.J.; Eliseeva, E.A.; Davies, M.M.; Spears, M.; Lobscheid, A.; Fisk, W.J.; Apte, M.G. Association of
classroom ventilation with reduced illness absence: A prospective study in California elementary schools.
Indoor Air 2013, 23, 515–528. [CrossRef] [PubMed]
7. Rosbach, J.T.M.; Vonk, M.; Duijm, F.; van Ginkel, J.T.; Gehring, U.; Brunekreef, B. A ventilation intervention
study in classrooms to improve indoor air quality: The FRESH study. Environ. Health 2013, 12, 110. [CrossRef]
[PubMed]
8. Haverinen-Shaughnessy, U.; Shaughnessy, R.J. Effects of classroom ventilation rate and temperature on
students’ test scores. PLoS ONE 2015, 10, e0136165. [CrossRef] [PubMed]
9. Gaihre, S.; Semple, S.; Miller, J.; Fielding, S.; Turner, S. Classroom carbon dioxide concentration, school
attendance, and educational attainment. J. Sch. Health 2014, 84, 569–574. [CrossRef] [PubMed]
10. Chatzidiakou, L.; Mumovic, D.; Summerfield, A.J. What do we know about indoor air quality in school
classrooms? A critical review of the literature. Intell. Build. Int. 2012, 4, 228. [CrossRef]
Int. J. Environ. Res. Public Health 2017, 14, 145 21 of 22
11. Pérez-Lombard, L.; Ortiz, J.; Pout, C. A review on buildings energy consumption information. Energy Build.
2008, 40, 394–398. [CrossRef]
12. ASHRAE. ANSI/ASHRAE Standard 62.1-2013, Ventilation for Acceptable Indoor Air Quality; American Society
of Heating, Refrigerating and Air-Conditioning Engineers, Inc.: Atlanta, GA, USA, 2013.
13. Persily, A.K. Field measurement of ventilation rates. Indoor Air 2016, 26, 97–111. [CrossRef] [PubMed]
14. Persily, A.K.; Gorfain, J.; Brunner, G. Survey of ventilation rates in office buildings. Build. Res. Inform. 2006,
34, 459–466. [CrossRef]
15. Sherman, M.H. Tracer-gas techniques for measuring ventilation in a single zone. Build. Environ. 1990, 25,
365–374. [CrossRef]
16. ASTM. Standard Test Method for Determining Air Change in a Single Zone by Means of a Tracer Gas Dilution;
ASTM International: West Conshohocken, PA, USA, 2011.
17. ISO. ISO 12569:2012: Thermal Performance of Buildings and Materials—Determination of Specific Airflow Rate in
Buildings—Tracer Gas Dilution Method; International Organization for Standardization: Geneva, Switzerland,
2012; p. 54.
18. Etheridge, D. Natural Ventilation of Buildings: Theory, Measurement and Design; John Wiley & Sons Inc./Wiley
Wiley-Blackwell: West Sussex, UK, 2012.
19. Bekö, G.; Gustavsen, S.; Frederiksen, M.; Bergsøe, N.C.; Kolarik, B.; Gunnarsen, L.; Toftum, J.; Clausen, G.
Diurnal and seasonal variation in air exchange rates and interzonal airflows measured by active and passive
tracer gas in homes. Build. Environ. 2016, 104, 178–187. [CrossRef]
20. Chatzidiakou, E. Is CO2 A Good Proxy for Indoor Air Quality in School Classrooms? ProQuest Dissertations
Publishing: London, UK, 2014.
21. Hänninen, O.; Shaughnessy, R.; Turk, B.; Egorov, A. Evaluation of Ventilation Rates in European Schools Using
CO2 Measurements as Part of a Proposed WHO School Survey; Healthy Buildings: Brisbane, Australia, 2012.
22. Scheff, P.A.; Paulius, V.K.; Huang, S.W.; Conroy, L.M. Indoor air quality in a middle school, part I: Use of
CO2 as a tracer for effective ventilation. Appl. Occup. Environ. Hyg. 2000, 15, 824–834. [CrossRef] [PubMed]
23. Smith, P.N. Determination of ventilation rates in occupied buildings from metabolic CO2 concentrations and
production rates. Build. Environ. 1988, 23, 95–102. [CrossRef]
24. ASTM. Standard Guide for Using Indoor Carbon Dioxide Concentrations to Evaluate Indoor Air Quality and
Ventilation; ASTM International: West Conshohocken, PA, USA, 2012.
25. Hänninen, O. Novel second-degree solution to single zone mass-balance equation improves the use of
build-up data in estimating ventilation rates in classrooms. J. Chem. Health Saf. 2013, 20, 14–19. [CrossRef]
26. Mudarri, D.H. Potential correction factors for interpreting CO2 measurements in buildings. ASHRAE Trans.
1997, 103, 244–254.
27. Carrilho, J.D.; Mateus, M.; Batterman, S.; da Silva, M.G. Air exchange rates from atmospheric CO2 daily
cycle. Energy Build. 2015, 92, 188–194. [CrossRef] [PubMed]
28. Hänninen, O.O.; Lebret, E.; Ilacqua, V.; Katsouyanni, K.; Künzli, N.; Srám, R.J.; Jantunen, M. Infiltration
of ambient PM2.5 and levels of indoor generated non-ETS PM2.5 in residences of four European cities.
Atmos. Environ. 2004, 38, 6411–6423.
29. ASTM. E779-10 Standard Test. Method for Determining Air Leakage Rate by Fan Pressurization; American Society
for Testing and Materials: West Conshohocken, PA, USA, 2010.
30. Du, L.; Batterman, S.; Godwin, C.; Chin, J.-Y.; Parker, E.; Breen, M.; Brakefield, W.; Robins, T.; Lewis, T. Air
change rates and interzonal flows in residences, and the need for multi-zone models for exposure and health
analyses. Int. J. Environ. Res. Public Health 2012, 9, 4639–4662. [CrossRef] [PubMed]
31. Carrer, P.; Wargocki, P.; Fanetti, A.; Bischof, W.; De Oliveira Fernandes, E.; Hartmann, T.; Kephalopoulos, S.;
Palkonen, S.; Seppänen, O. What does the scientific literature tell us about the ventilation-health relationship
in public and residential buildings? Build. Environ. 2015, 94, 273–286. [CrossRef]
32. Hänninen, O. Combining CO2 Data from Ventilation Phases Improves Estimation of Air Exchange Rates;
Healthy Buildings: Brisbane, Australia, 2012.
33. WHO. Methods for Monitoring Indoor Air Quality in Schools: Report from the Meeting 4–5 April 2011 Bonn,
Germany; World Health Organization: Copenhagen, Denmark, 2011; p. 32.
34. George, K.; Ziska, L.H.; Bunce, J.A.; Quebedeaux, B. Elevated atmospheric CO2 concentration and
temperature across an urban-rural transect. Atmos. Environ. 2007, 41, 7654–7665. [CrossRef]
Int. J. Environ. Res. Public Health 2017, 14, 145 22 of 22
35. Yasuda, T.; Yonemura, S.; Tani, A. Comparison of the characteristics of small commercial NDIR CO2 sensor
models and development of a portable CO2 measurement device. Sensors 2012, 12, 3641–3655. [CrossRef]
[PubMed]
36. Batterman, S.; Su, F.-C.; Wald, A.; Watkins, F.; Godwin, C.; Thun, T. Ventilation rates in recently constructed
U.S. elementary school classrooms. Indoor Air 2017. under review.
37. Breen, M.S.; Schultz, B.D.; Sohn, M.D.; Long, T.; Langstaff, J.; Williams, R.; Isaacs, K.; Meng, Q.Y.; Stallings, C.;
Smith, L. A review of air exchange rate models for air pollution exposure assessments. J. Expo. Sci.
Environ. Epidemiol. 2014, 24, 555–563. [CrossRef] [PubMed]
38. Lawrence, T.M. Selecting CO2 criteria for outdoor air monitoring. ASHRAE J. 2008, 50, 18.
39. Morse, R.G.; Haas, P.; Lattanzio, S.M.; Zehnter, D.; Divine, M. A cross-sectional study of schools for
compliance to ventilation rate requirements. J. Chem. Health Saf. 2009, 16, 4–10. [CrossRef]
40. You, Y.; Niu, C.; Zhou, J.; Liu, Y.; Bai, Z.; Zhang, J.; He, F.; Zhang, N. Measurement of air exchange rates in
different indoor environments using continuous CO2 sensors. J. Environ. Sci. 2012, 24, 657–664. [CrossRef]
41. Turanjanin, V.; Vutiaevic, B.; Jovanovic, M.; La Mirkov, N.; Lazovic, I. Indoor CO2 measurements in Serbian
schools and ventilation rate calculation. Energy 2014, 77, 290–296. [CrossRef]
42. Mundt, E.; Mathisen, H.M.; Nielsen, P.V.; Moser, A. Ventilation Effectiveness; REHVA Federation of European
Heating Ventilation and Air Conditioning Associations: Brussels, Belgium, 2004.
43. Canha, N.; Mandin, C.; Ramalho, O.; Wyart, G.; Ribéron, J.; Dassonville, C.; Hänninen, O.; Almeida, S.M.;
Derbez, M. Assessment of ventilation and indoor air pollutants in nursery and elementary schools in France.
Indoor Air 2016, 26, 350–365. [CrossRef] [PubMed]
44. Hänninen, O.; Canha, N.; Dume, I.; Deliu, A.; Mata, E.; Egorov, A. P-217. Epidemiology 2012, 23, 1. [CrossRef]
45. Penman, J.M. An experimental determination of ventilation rate in occupied rooms using atmospheric
carbon dioxide concentration. Build. Environ. 1980, 15, 45–47. [CrossRef]
46. Mumovic, D.; Palmer, J.; Davies, M.; Orme, M.; Ridley, I.; Oreszczyn, T.; Judd, C.; Critchlow, R.; Medina, H.A.;
Pilmoor, G.; et al. Winter indoor air quality, thermal comfort and acoustic performance of newly built
secondary schools in England. Build. Environ. 2009, 44, 1466–1477. [CrossRef]
47. Santamouris, M.; Synnefa, A.; Asssimakopoulos, M.; Livada, I.; Pavlou, K.; Papaglastra, M.; Gaitani, N.;
Kolokotsa, D.; Assimakopoulos, V. Experimental investigation of the air flow and indoor carbon dioxide
concentration in classrooms with intermittent natural ventilation. Energy Build. 2008, 40, 1833–1843.
[CrossRef]
48. National Center for Health Statistics. Percentile Data Files with LMS Values, CDC Growth Charts. Available
online: http://www.cdc.gov/growthcharts/percentile_data_files.htm (accessed on 1 October 2016).
49. U.S. Environmental Protection Agency. Exposure Factors Handbook: 2011 Edition; U.S. Environmental
Protection Agency: Washington, DC, USA, 2011.
50. Saint-Maurice, P.F.; Kim, Y.; Welk, G.J.; Gaesser, G.A. Kids are not little adults: What MET threshold captures
sedentary behavior in children? Eur. J. Appl. Physiol. Occup. Phys. 2016, 116, 29–38. [CrossRef] [PubMed]
51. Ridley, K.; Ainsworth, B.E.; Olds, T.S. Development of a compendium of energy expenditures for youth.
Int. J. Behav. Nutr. Phys. Act. 2008, 5, 45. [CrossRef] [PubMed]
52. Ainsworth, B.E.; Haskell, W.L.; Herrmann, S.D.; Meckes, N.; Bassett, D.R., Jr.; Tudor-Locke, C.; Greer, J.L.;
Vezina, J.; Whitt-Glover, M.C.; Leon, A.S. 2011 compendium of physical activities: A second update of codes
and MET values. Med. Sci. Sports Exerc. 2011, 43, 1575–1581. [CrossRef] [PubMed]
53. Buchheit, M.; Laursen, P.B.; Ratel, S.; Duché, P. Postexercise heart rate recovery in children: Relationship with
power output, blood pH, and lactate. Appl. Physiol. Nutr. Metab. 2010, 35, 142–150. [CrossRef] [PubMed]
54. Compher, C.; Frankenfield, D.; Keim, N.; Roth-Yousey, L. Best practice methods to apply to measurement
of resting metabolic rate in adults: A systematic review. J. Am. Diet. Assoc. 2006, 106, 881–903. [CrossRef]
[PubMed]
55. Laforgia, J.; Withers, R.T.; Gore, C.J. Effects of exercise intensity and duration on the excess post-exercise