Tuzla Factory Overview - Conventional
Tuzla Factory Overview - Conventional
Manpower
140
Product supplied
DETC – MESA - BUSHING – TXPERT
ECOSYSTEM
Voltage range
Up to 72 kV for DETC – Up to 52 kV for BUSHING
Supplied to
Exports to more than 61 countries and around 170
OEM customer all over the world.
HITACHI ENERGY
ELMEK was Entered the Certified for ELMEK has Moved to its ELMEK were ABB Power HITACHI ABB
founded. international ISO 9001 by signed a new acquired by Grids becomes Power Grids
market. BVQI. framework facilities in ABB. HITACHI ABB will become
agreement Tuzla, Power Grids. HITACHI
with ABB BA Istanbul. ENERGY.
Europe
Africa for
the entire
production
range.
Sales & Marketing Team Sales & Marketing Team Hub Digital Center Tuzla
Corporate Integrated Management System Certificates ISO 9001 - ISO 14001 - ISO 45001 – ISO 37001
Our Processes ;
- CNC Machining
- Robotic Produc. Cell
- Pressing
- CNC Machining
- Painting
- Coating
- Welding
- Silicone & Epoxy Injec.
- Manuel Vs Auto. Assembly
Line
- Test Laboratories
By adapting technological innovations and automation to production processes, we constantly improve ourselves and
make lean and agile production.
9 © 2020 Hitachi Energy. All rights reserved.
Transformer accessories overview
TCS , Istanbul Turkey
• Non shattering silicone insulator, reduced risk of damage in transportation DRY NC®
non-condenser
bushings
• Compact and lightweight bushing
• Self-cleaning behavior in harsh environment and better
suppression of leakage due to hydrophobic SiR2 surface.
Adapter
• Durable packaging
All bushings are tested in both mineral and ester oil according to IEC 60137.
Rated frequency
Highest voltage
Rated thermal
Routine Test 9.2 measurement of dielectric dissipation factor (tan δ) and capacitance
(level II)
(level II)
Routine Test 9.4 dry power-frequency voltage withstand test
Routine Test 9.5 measurement of the partial discharge quantity
Routine Test 9.11 visual inspection and dimensional check
Type Test 8.2 wet power-frequency voltage withstand test
kV A Hz kV kV kA mm mm N N
Type Test 8.2 dry power-frequency voltage withstand test
1250 31,25 1360 625 1250
Type Test 8.4 dry lightning impulse voltage withstand test
8.8 temperature rise test 2000 50 515 1000 2000
Type Test 1500
Type Test 8.9 verification of thermal short-time current withstand 24 3150 150 55 78,75 1575 3150
Type Test 8.10 cantilever load withstand test (Class II) 5000 100
1300 490 1575 3150
Type Test 8.14 verification of dimensions 6300 100
1250 31,25 1360 625 1250
2000 50/60 50 515 1000 2000
1500
36 3150 200 77 78,75 1575 3150
5000 100
1300 490 1575 3150
6300 100
1250 31,25 800 1600
52 2000 250 105 50 1630 563 1250 2500
3150 78,75 1575 3150
IEC 60137 Mineral / Ester Oil Test BIL 200kV Mineral / Ester Oil Test Summary Mineral / Ester Oil Test
Long Reports Extention Reports Short Reports
DIN LV Bushings
Um=1,2kV DIN HV Bushings
From Ir=250A to 3150A
From Um=12kV to 52kV
From Ir=250A to 3150A
Um=3,6kV
Bushings – Product availability DIN Standard
From Ir=250A to 3150A
EN LV Bushings EN HV Bushings
Um=1,2kV From Um=12kV to 36kV
From Ir=250A to 4000A From Ir=250A to 8000A
Why?
The Integrated Measurement Relay (IMR) enables rapid action on hermetically
sealed liquid-filled distribution and small power transformers. The operator will
receive an alarm if any of the transformer’s pressure, temperature, oil level or
gassing increased above predetermined thresholds.
How?
- Intergareted solution ; oil level abd gassing , temperature , presure ( 0,1 – 0,5 bar)
Additional Features & Improvements
- Easy installation
- Double insulation system, no need to make earthing connection
- Air venting valve for draining the moisture inside the terminal box
- Withstand a DC magnetic field up to 25 mT (militesla)
- No need of anti-magnetism shielding.
- UV color resistance performance have been improved with nano technology
coating.
- Vacuum problem at the top valve has been dealt with. (predecessor)
- Rohacell floater material to ensure no oil suction and performance improve.
- First product to be confirmed to use Hitachi logo.
- Suitable for solar and wind transformers.
Adhesive
3M 2214
“T2” Temperature Relay
(Alarm) 30÷120 °C
O-Ring
“T1” Temperature Relay
(Tripping) 30÷120 °C
Terminal
Reed Switch / CO
Screw + DP190
PRD 100÷500 mbar
EPDM Gasket
Probes of
Thermometer&Thermostats
Thermal Compound
Open
Symetrically
Open
Symetrically
4 Studs at 90°
3 Studs at 120°
Specifications Tests
Technical Data Leakage test 2,5x105 Pa 5 min. with air HITACHI TUZLA
Standard IEC 60076-22-1
Dielectric Strength IEC 60255-27
Degree of protection IP66 – EN 60529
Insulation test (60 s) PFWV HITACHI TUZLA
Degree of shock tightness IK07 – EN 50102 Impulse withstand test of electrical circuits
UV-Ray Resistance 500h – EN ISO 4892-3 / ISO 105-A02
Routine Functional test
Operating ambient temperature -40°C to 60°C 50 kpa HITACHI TUZLA
Test Operating pressure
Thermometer display range 30°C to 160°C ± 3°C
Temperature indicator
Temperature relay measuring range 30°C to 120°C ± 4°C
Functional test : Temperature switches HITACHI TUZLA
Temperature relay max bulb temperature 130°C Functional test : Thermometer
Cable gland 1 x M25x1.5 (1 additional cable gland upon request)
Functional test: Liquid loss volume HITACHI TUZLA
Terminal Block EN 50005 / EN 60998-2-1
Wire section to be used on clamp box Up to 2.5 mm² Vacuum withstand test 24 h at 2,5 kPa HITACHI TUZLA
Max. rated pressure 500 mbar Pressure Test 250 kpa, 2 min, with oil at 100 °C HITACHI TUZLA
1 x Oil Level & Gas Bleed,
No of Contacts 1 x Pressure Switch, 2 x Temperature Relay (Alarm & Max inclination max inclination : 5 º HITACHI TUZLA
Tripping) Type test
Pressure switch precision ± 10% accuracy tolerance of end scale Magnetic field test 25 mT Tubitak
Electrical characteristics Insulated enclosure Vibration withstand test 4M4 BIAS
https://library.abb.com/
No of Drw : 1 (1ZTE010001B)
Upper Body
1-Terminal / Teminal Box
2-Cable Gland / Plug
3-Test Button
4-Discharge Valve
5-Flow Direction Arrow
Lower Body
1-Upper / Lower Float
2-Switch
3-Window / Cover
4-Cap
Hermetic Relays
It's main purpose is to monitor the oil level in hermetically sealed transformers.
Falling oil level in the hermetically sealed transformer operates a switch contact.
Why?
- Transformer protection, avoiding the development of serious issues like dielectric
failure inside the equipment.
How?
- With a reliable, high performances solution suitable for all the application.
What?
The device is intended to detect
− complete loss of oil in the transformer.
How?
- With a reliable, easy to install and maintain solution suitable for oil filled
transformer.
What?
The device is intended to provide:
- Visual indication of oil level
- Electrical switches to alarm
KYS A KYS B
Thermometers
Thermometers is designed for indication of oil temperature in both transformers w/
or w/o expansion conservator or hermetically sealed type transformers.
Why?
- Transformer reliability and failures prevention.
How?
- Avoiding critical temperature on the oil (e.g. managing the activation of the
cooling systems (pumps or fans)).
What?
The device is intended to provide:
- Oil temperature measurement
- Electrical switches to alarm / Trip
Why?
- Transformer reliability
How?
- Prevention of transformer explosion in case of abnormal pressure increasing due
to an internal problem.
- Protect the ambient against the oil dissipation
What?
The device is intended to provide:
- Overpressure relief
Standard T-50 Pressure Relief Valve Standard T-80 Pressure Relief Valve
Presure relief devices – Product availability (with contact models) / How to order?
Presure relief devices – Product availability (with contact models) / How to order?
V 50-80-125 T 0.5 – T 10
Silica gel : silica salt able to adsorb humidity Silica breather : box with silica gel
Metal Accessories
Butterfly Valve (NW 80) DIN 42560 Flanged Ball Valves Cable Glands
NW80 Ball Valves Cable Glands
• Long Lever • Without Flange • M12x1.5 to M90x1.5
• Short Lever • With single Flange • NPT 1/4" to NPT 3"
• With Double Flange • M72x2 to M110x2
Standard features
– Max. oil temperature: 120°C
– Oils compatibility: all
– Standard tap adjustment is 2.5 % of the rated voltage for each position setting
Maximum
Rated Current Number of
Product Figure Type Voltage Connection
Ir (A) Position
Um (kV)
KDM 2–7
Delta, Star,
Linear 24 / 36 30 / 63 / 150
Series-Parallel
KDZ 2 – 11
Delta, Star,
KDF IV Linear 24 / 36 800 – 1800 2–5
Series-Parallel
Delta
Star
Common output
Serial / Parallel
Star-Delta
Linear
Standard features
– Combined the well known product KDR & TKC.
– Easy Assembly
– Cost Advantage
– The different type KDR and TKC knobs can be used at the same tap
changer base.
Linear - KDM
Standard features
– Maximum Voltage Um (kV)=24 / 36
– Rated Current Ir (A) = 30 / 63 / 150
– Number of Position = 2-7
– Connection = Delta, Star, Series-Parallel
Linear – KDZ
Standard features
– Maximum Voltage Um (kV)=24 / 36
– Rated Current Ir (A) = 30 / 63 / 150
– Number of Position = 2-11
– Connection = Delta, Star, Series-Parallel
Linear - KDFII
Standard features
– Maximum Voltage Um (kV)=24 / 36 / 72
– Rated Current Ir (A) = 150 / 400
– Number of Position = 2-11
– Connection = Delta, Star, Series-Parallel, Common Output,
Star-Delta
Standard features
– Maximum Voltage Um (kV)=24 / 36
– Rated Current Ir (A) = 400 / 800
– Number of Position = 2-6
– Connection = Delta, Star, Series-Parallel, Common Output,
– Star-Delta
Linear – KDF IV
Standard features
– Maximum Voltage Um (kV)=24 / 36
– Rated Current Ir (A) = 800 / 1800
– Number of Position = 2-5
– Connection = Delta, Star, Series-Parallel