DATASHEET NO : TPE/TD/TTR-61

SR. NO. ITEM DESCRIPTION UNIT


Manufactured ,Tested and supplied by Transpower Electronics , Vadodara
Make TRANSPOWER
Item Code
Capacity (Kva) KVA 75
Type AUXILLARY TRANSFORMER
Cooling Air-cooled
1 TYPE OF TRANSFORMER 75
1.1 Service INDOOR
1.2 Applicable Standards IS 2026
2 SITE CONDITIONS
2.1 Design Ambient Temperature 50
3 SPECIFICATIONS
3.1 Rated KVA at site condition KVA 75
3.2 Quantity of Transformers NOS 1
3.3 Number of Phases NOS 3
3.4 Frequency - Hz Hz 50 ( +/- 5 % )
3.5 Vector Group Dyn11
3.6 Voltage Ratio at no load - V V 415 / 415
3.7 Tapping on Secondary side V Taps +/-5 % in steps of 2.5 % 1.25 %
3.8 Off circuit tap changer Offload Tap links
4 No load loss in W at ambient (W) Watts 400
4.1 Full load loss in W at 75°C (W) Watts 1500
Regulation in percentage at unity power factor
4.2 and rated current. % 2.05
4.3 Regulation in percentage at 0.8 % 3.49
4.4 % Impedance at rated VA ( IS TOLL.) % 3.73
4.5 % Resistance % 0.00
4.6 % Reactance with respect to above rating % 0.00
4.7 Efficiency in percentage at Unity Power Factor
4.8 a) at 100% rated current % 97.53
4.9 b) at 75% rated current % 98.01
4.1 c) at 50% rated current % 98.49
5 Temperature rise of following :
5.1 Winding temp. rise @ambient of 50 deg c C 90
5.2 Parts at rated KVA above ambient C 90
5.3 Permissible overload and duration 16.66 Times For 1 Sec
5.4 Noise level at 1 meter distance DB As per NEMA STD.
5.5 No load current at rated voltage & frequency < 5 % of Rated H.v current
5.6 Rated full load current
5.7 a) On Primary A 104.34
5.8 b) On Secondary A 104.34
6 Insulation Level kVp/kV rms
6.1 A) kVp/kV rms -/3 kV
6.2 B) kVp/kV rms -/3 kV
6.3 Operating Altitude 1000m above sea level at rated operation
7 ITEM DESCRIPTION
7.1 Overfluxing allowed for cont duty / 5 sec. 1.2
7.2
7.3
8 COOLANT AND COOLING SYSTEM
8.1 a) Type of cooling Air natural with proper cooling arrangement
9 WINDINGS
9.1 Material Cu / AL CU
9.2 Insulation class F
9.3 Type AN
10 ACCESSORIES
10.1 With alarm winding temperature N.A
10.2 Incoming protection N.A
10.3 Outgoing protection 250 AMCCB TPN 36 KA L&T /SCHNEIDER MAKE
10.4 Surge Arrestor N.A
Cooling Fans at Inlet and Outlet YES
10.5 Other Assessories Lifting Lugs,Mounting channel,Name Plate
11 TERMINATION
11.1 Primary Side 20*5 CU
Cable box / bushing for primary side suitable for
11.2 185mmsq*3.5c armd alu. Cable connection 20*5 CU
11.3 Secondary Side 20*5 CU
Cable box / bushing for primary side suitable for
11.4 185mmsq*3.5c armd alu. Cable connection 20*5 CU
12 DIMENSIONS ( Without enclousure)
12.1 L*W*H mm 800*400*750
12.2 DIMENSIONS ( With enclousure)
12.3 L*W*H 1000*750*1000
IP 00 (IP CLASS OF TRANSFORMER) ,IP 54 (IP
CLASS OF ENCLOSURE)
12.4 Enclosure Protection Class
12.5 Enchosure Shade RAL 7035
13 WEIGHT SCHEDULE
13.1 Total Weight of Transformer Kg 370
13.2 Total Weight with Enclosure Kg 500

Note :
All guaranteed figures are subject to tolerances as per IS 2026.
It is considered that rating includes the effects of Harmonics currents due to non linear loads.
Efficiency and regulation values are calculated based on nominal values.
Weight and dimensions are approximate and shall be confirmed after detailed engineering.