Protection Training Course
Protection Training Course
Protection
Training Course
For Transmission Engineers
And Distribution Engineers
At NEC Training Center
07-10-20 – 07-10-27
By:
Mashair Abdou, NEC Protection
and Rolf Gorzolla, NEC Transmission
-2-
Content
→ Example Transformer:
OCEF HV, OCEF MV, OCEF LV = Back Up Prot. = time delayed trip
→ Example OHL:
(Pilot ware)
DIST or PW- Prot = Prim. Prot. = inst. trip
→ Example Generator:
Gen DIFF, Stator EF, Rotor EF, LoE = Prim. Prot. = inst. trip
→ Example Busbar:
-4-
Formula to calculate the TMS for given current and tripping time:
In the past the directional relays have been added to the OCEF, three single
phase directional units or one three phase unit to the OC unit and one single
phase directional unit to the EF unit. With the current flow in forward direction the
directional element enables the current relay to trip. With the current flow in
reverse direction the directional element blocks the current relay.
Each OC directional element is “polarized” by one current (e.g. red phase) and
the two voltages rectangular to the current (e.g. yellow to blue).
Each EF directional element is “polarized” by the zero sequence current (of
Holmgreen) and the zero sequence voltage. This zero sequence voltage may be
available either from an open delta connected VT winding, or from a separate set
of three interposing VTs (110V/110V) with primary connection to star and
secondary connection to open delta. Advanced numerical DEF relays generate
the zero sequence voltage by calculation.
→ Selective tripping for “inzone faults” between current transformers, stable for
faults “outside”, “through faults”!
→ Due to the fact that the power transformer shifts the angle (vector group) and
the amplitude (CT- mismatch) of the currents phase shift- and amplitude
matching interposing current transformers are necessary. Only numerical relays
perform the angle and amplitude shift by Software
→ Energizing of transformer produces harmonics and single side inrush currents
(and therefore differential currents, also called “spill currents”). DIFF relays must
be stabilized against unwanted inrush- current trips.
→ The setting calculation has to consider the spill current producing effect of the
tap changer extreme positions (additional current unbalance).
→ Transformer differential schemes connected to a “one and a half breaker
system” (e.g. at 500kV) need both sets of CT to be connected to separate inputs
of the differential relay
→ Usually differential schemes are “low impedance schemes” with nearly
adapted CT ratio on each voltage level.
→ In some countries also “high impedance differential schemes” are used. But
this requires for special CT cores: all voltage levels must have identical CT-
cores with identical data:
CT ratio identical to LV (three winding DIFF: to tertiary V)
Class X acc. to BS
Identical knee point voltage
Identical magnetizing current (magnetising curve)
Identical secondary resistance
Stability:
- 10 -
- 11 -
→ Very fast protection for one (solidly grounded) transformer winding (or delta
winding with earthing transformer)
→ performed with high impedance protection relays
→ uses the three main CT´s and one CT in the transformer neutral to ground
connection
→ Identical CT- cores for neutral CT and main CT:
Identical ratio
Class X acc. to BS
Identical knee point voltage
Identical magnetizing current (magnetising curve)
Identical secondary resistance
→ Connection of high impedance relay between “∑inside” and “∑outside”
→Stabilizing resistor adjustable (value acc. to calculation: e.g. 0 - 1200Ω) in
series with relay
→ Voltage dependent resistor (VDR) to protect the high impedance relay
against overload, in parallel to relay
→ REF relay to trip the transformer lockout relay (LOR)
- 14 -
→ For lines (OHL or cable or mixed), usually long lines >5km up to extremely
long lines (2x more km as kV)
→ Directional protection (DIST “looking into the line”)
→ Impedance measurement with different characteristics (quadrilateral, offset-
MHO circular, offset- MHO lenticular), most of the relays offer different settings
for phase to ground and for phase to phase faults
→ DIST provides time graded backup protection by additional distance “zones” in
forward direction and one long time delayed “backward zone)
→ Modern DIST have a lot of additional features: fuse failure blocking (FF),
switch onto fault (SOTF), power swing blocking (PSB), block from external side
(VT- MCB trip), FIFO event recording, fault recording and fault location
calculation. Numerical DIST offer a comprehensive amount of service data, all
currents and voltages and her phase angles, current MVA, MVAr, cos phi…
Provided the relay has a communication card or may be optionally equipped with,
it may be linked to a RTU (Remote Terminal Unit) and from there to SCADA
(System Control and Data Acquisition) or to PDMS (Protection Data
Management System).
As mentioned the distance relay is working in PUTT: zone1 settings cover 80%
of the line. For a zone1 instantaneous trip the distance relay not only trips his CB,
also a “Communication Send” (CS) signal will be transmitted to remote end
distance relay (older name “HF send” = high frequency send by carrier). At
remote end the incoming signal will be evaluated as: “Communication Receive”
(CR), older name “HF receive”. The distance relay has a very simple logic, an
and- gate with two inputs: CR + Start Forward = trip instantaneous
The results:
Substation A: DIST trip in zone1 + CS, start AR, AR operated, CB closed
Substation B: Start FWD + CR = inst. trip, start AR, AR operated, CB closed
The consequence: despite the fault was in zone2 for Substation B distance relay
(with no AR start), the aided trip logic operated, tripped and start the AR. After
transient fault, the line is back to normal service. Both distance relays will show
the signals: DIST operated, AR operated.
12. Busbar protection (BBP) in general
→ Need identical CT- cores for all feeders and the bussection / buscoupler:
Identical ratio (usually the highest ratio available from bussection /
buscoupler)
Class X acc. to BS
Identical knee point voltage
Identical magnetizing current (magnetising curve)
Identical secondary resistance
→ Cheapest system for single busbar schemes (all voltage levels), e.g. with
MCAG34 from AREVA
→ Need CT supervision, e.g. MVTP31 from AREVA
→ Need lockout relay, e.g. MVAJ25 from AREVA
The upper figure shows the solution for MV feeders, the lower figure shows the
solution for HV (e.g. Wod Elbeshir Substation)
Double busbar:
→ current changeover to another discriminating zone (through isolator image
contactors)
→ check zone necessary
- 24 -
- 25 -
During busbar change of one feeder- the buscoupler must be closed to close the
second busbar isolator- both isolator- image contactors are closed and the
current of this feeder is connected to zone I and to zone 2. Booth zone
discriminating relays may trip but the check zone remains stable and inhibit the
operation of the lockout relays:
Flag indication on MCAG34 from zone I and zone II, no flag on check
zone MCAG34, no flag on any MVAJ = indication of a busbar change.
Flag indications on one zone MCAG34 plus check zone MCAG34 plus
one MVAJ = BBP trip.
In general:
Analogue electronic type (BBC INX2 and INX5) or today: numerical type (ABB
REB 500, Siemens…)
Very low burden
No need for special CTs, may be connected in series with any backup
protection
CTs of different feeders may have different CT ratio
No switching of CT secondary circuits (the switching takes place at
electronic level)
Implemented breaker failure available with factory tested tripping logic
Differential current alarm available
Isolator image alarm available
Self testing facilities available
The BBP also provides differential current alarms (CT supervision) and a
wide range of self supervision features (watchdog, data transfer between
central and bay unit)
Internal event recorder as standard (switching operations, protection
events, system events, test events)
Breaker failure protection as an option (was not specified for Gaili- and Eid
Babiker- REB500, available now within Siemens BBP (KNPS, Kuku,
KiloX).
Future feeders may be pre-engineered and pre-wired (REB500 only), at
the time only the bay unit has to be inserted and released by SW
Numerical BBP is practically maintenance free
Optional time synchronization with GPS
Optional communication card to SCADA or PDMS
Communication to laptop
If one circuit breaker fails by any reason (broken isolated activator rod, trip coil
burnt out, spring charge failure…) an existing protection trip will be transferred
to all adjacent feeders of this busbar and an intertrip will be sent to remote end
(line breakers) or to MV (transformer breakers)
In the past the BFP was included in the feeder protection panel: 1x MCTI39 (or
MCTI40) three phase current detector relay plus 1x (or 2x) MVTT14 time relay(s)
plus 1x MVAJ25 lockout relay for single (two) step BFP. The tripping logic for
single busbar switchgears was hard wired within protection panels. The BFP-
tripping logic for double busbar switchgears must be routed through busbar
isolator image contactors. For switchgears like Magirus 110kV with BB1A, BB1B,
BB2 and only one bus coupler at one end this BFP- tripping logic is very
complex.
Today more and more implemented solutions are available: either the BFP is
integrated within a protection relay (within DIST P441 at Chinese 110kV line
feeders in Faroug, Mugren, with DOC/DEF P142 at Schneider line feeders at
110kV Wod Elbeshir) or the BFP is integrated as a SW package within a
numerical BBP
The function principle: each protection trip of one feeder (…main protection trip,
back up protection trip, BBP trip, DTT received trip…, single pole trips from DIST
as well as all three phase trips) has to be sent to a starting input of the BF-
current detector relay. If the CB didn’t do his job and the feeder current is still
available, the current detector relay will close his contact and energize a timer.
When the time of the timer has elapsed (usually after 100ms) the timer will close
his contact and will energize the BF- lockout relay. This lockout relay sends the
trip to all adjacent CBs.
- 28 -
voltage transformers (CVTs) are used. To inhibit that the HF signals waste the
complete network, the OHL is closed at booth ends with a “wavetrap”, a 50 Hz
bandpass. The PLC must be powerful enough to push the signal to remote end
also during a lightning stroke interconnecting phase to ground. A broken
conductor- condition usually inhibit the transfer of signals. On double OHLs
things are better: the protection signaling signals of line 1 are crossed over to line
2 and vice versa.
Back up protection
Underfrequency
Overfrequency
Overcurrent (voltage restraint)
Minimum impedance
16. CT coordination
Usually, the contractor of a new switchgear has to prepare a CT calculation for
each CT core, for identical equipped feeders the worst case has to be applied,
e.g. for OHL the shortest line. Depending on each relay connected to one core,
the requirements of the relay manufacturer have to be fulfilled, to ensure the
- 34 -
proper function of the relay. Whenever two different relays are connected to one
CT, the worst case has to be applied or a combination of two conditions.
Example: a transformer feeder CT core is used for the differential- and the REF-
protection. The DIFF requests for a DIN/IEC core (like 5P20, 30VA), the high
impedance REF relay requests for a class X CT according to BS. The result of
booth calculations has to be checked with the CT manufacturer for feasibility.
The result may be a very special CT 400/1A, with 5P105, 2.2VA, max. 2.8 Ohms.
The supplier has to calculate with either short circuit currents after 20 years or
simply with the specified SHC level of the equipment (31,5kA for 3s). Estimated
SHC levels have to be confirmed by NEC.
52 Circuit breaker CB
55 Power factor relay cosφ
59 Overvoltage relay U> OV
59N Neutral displacement relay Ursd NDR
64 Earth fault relay Used for REF
64N
67 Directional over- current relay DOC
„Value“ Window:
D Trip
B Trip blocked
H Trip with HFR (PLC)
3P Three Pole Trip
- 36 -
„Mode“ Window:
D Trip
H Trip with HFR (PLC)
I Trip of Back Up Protection
F RE93 started (Current Release)
FUSE VT MCB tripped
---------------------------------------------------------
1 Relay ready 9
2 Gen trip 10
3 Gen start 11
4 Diff trip L1 12
5 Diff trip L2 13
6 Diff trip L3 14
7 15
8 Backup trip SCU 16 Test output block
Right hand side eight user programmable LED´s: to be programmed with MICOM
S1 SW inside PSL (programmable switching logic)
Conventional BCU
Control of devices (CB, Is, ES) with Choose device on display and operate
- 38 -
-----------------------------------------------------
REF542 >40
REF542plus >140
P139 14
7SJ632 11
SEPAM ?
FCK-801 5?
Abbreviation Explanation
- 41 -
/conversion/tmp/activity_task_scratch/838645210.doc
- 42 -
SC Synchrocheck
SDEF Sensitive directional earth fault
SI Standard inverse (IDMT characteristic)
SOTF Switch on to fault (→ DIST)
T = LV Tertiary voltage side (of a transformer), lowest voltage level
TCS Trip circuit supervision
TMS Time multiplier setting (IDMT characteristic)
UV Undervoltage protection relay
VDR Voltage dependent resistor
VI Very inverse (IDMT characteristic)
VT Voltage Transformer
WT Winding temperature
/conversion/tmp/activity_task_scratch/838645210.doc