0% found this document useful (0 votes)
20 views

33ZC-3XA

Uploaded by

jonasousajunior
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
20 views

33ZC-3XA

Uploaded by

jonasousajunior
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 40

3V™ Control System

Variable Volume and Temperature (VVT®)


33ZC

Application Data
Part Numbers: 33ZCVVTZC-01, 33ZCBC-01, 33ZCVAVTRM, 33ZCFANTRM
CONTENTS Page
SPACE TEMPERATURE SHARING . . . . . . . . . . . . . . . . . . 18
Page
SENSOR GROUPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2,3
Zone Controller Control Strategy . . . . . . . . . . . . . . . . . . . .2 CALIBRATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
PRODUCT DESCRIPTION. . . . . . . . . . . . . . . . . . . . . . . . . 4-12 CARRIER NETWORK ALARMS . . . . . . . . . . . . . . . . . . 18,19
VVT Zone Controller (33ZCVVTZC-01) . . . . . . . . . . . . . . .4 Space Temperature Limit Alarm . . . . . . . . . . . . . . . . . . . . 18
Bypass Controller (33ZCBC-01) . . . . . . . . . . . . . . . . . . . . .5 Linkage Failure (Failure to
System Pilot (33PILOT-01) . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Communicate With Linkage Coordinator) . . . . . . . . 18
VAV Zone Controller (33ZCVAVTRM). . . . . . . . . . . . . . . . .6 Linkage Failure (Failure to Communicate
VAV Fan Terminal Zone Controller with Air Source) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
(33ZCFANTRM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 Supply Air Temperature Sensor Failure . . . . . . . . . . . . 19
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 Primary Air Temperature Sensor Failure. . . . . . . . . . . . 19
Sensor Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 Pressure Sensor Low Airflow
• SPACE TEMPERATURE SENSORS Pressure Alarm (PI Only) . . . . . . . . . . . . . . . . . . . . . . . . . 19
• 33ZCT55 SPT SENSOR Pressure Sensor High Velocity
• 33ZCT56 SPT SENSOR Pressure Alarm (PI Only) . . . . . . . . . . . . . . . . . . . . . . . . . 19
• SUPPLY AIR TEMPERATURE SENSOR Relative Humidity Sensor Alarm. . . . . . . . . . . . . . . . . . . . 19
(33ZCSENSAT) IAQ Sensor Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
• DUCT TEMPERATURE SENSOR (33ZCSENDAT) Failure to Zero Calibrate Pressure Transducer
• PRIMARY AIR TEMPERATURE SENSOR (PAT) (PI and Bypass Controller Only). . . . . . . . . . . . . . . . . . 19
Damper Position and Actuator Installation . . . . . . . . . 19
INPUTS/OUTPUTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-14
Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-40
Triac Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Relay Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 Typical VVT System Overview . . . . . . . . . . . . . . . . . . . . . . 20
VVT Pressure Independent System Overview . . . . . . 22
NETWORK SYSTEM DESIGN INFORMATION . . . . 14,15 VVT Pressure Dependent and Pressure
Design Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 Independent System Overview . . . . . . . . . . . . . . . . . . . 23
Network Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 Fan Powered and Reheat VVT System
• COMMUNICATION LIMITATIONS Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
• COMMUNICATION ADDRESSING Compatibility of Carrier Systems . . . . . . . . . . . . . . . . . . . 25
• OCCUPANCY SCHEDULING • 3V AND GEN-III VVT PRODUCT COMPATIBILITY
Network Addressing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 • VVT GEN-III CONVERSION (Manufactured
Zone Controller User Interfaces . . . . . . . . . . . . . . . . . . . .15 prior to July 1995)
LINKAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15,16 General Heating Information . . . . . . . . . . . . . . . . . . . . . . . 26
Air Sources Which Support Linkage. . . . . . . . . . . . . . . .15 Disabling Reheat From Carrier
• AIR TERMINAL MODES Communicating Network . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Air Sources That Do Not Support Linkage . . . . . . . . . .15 Non-Ducted Heat Control
• OFF MODE (Single or Staged Heat) . . . . . . . . . . . . . . . . . . . . . . . . . . 26
• HEAT MODE Modulating Baseboard Heating. . . . . . . . . . . . . . . . . . . . . 26
• COOL MODE Ducted Heat Control (Staged or
• FREE COOLING MODE Modulating Device). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Communications Alarms with Linkage . . . . . . . . . . . . .16 Modulating Hot Water/Steam Valve CV . . . . . . . . . . . . . 27
OCCUPANCY (LOCAL/GLOBAL). . . . . . . . . . . . . . . . . 16,17 Central Heating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16 VAV Central Heating with
Local Occupancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16 Ducted Zone Heat (PI Only) . . . . . . . . . . . . . . . . . . . . . . 27
Global Occupancy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17 Damper Override . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Remote Occupancy Contact . . . . . . . . . . . . . . . . . . . . . . . .17 Nighttime Free Cooling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Occupancy Override. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17 Single Duct Terminal Applications . . . . . . . . . . . . . . 28
Manual Occupancy Override Function. . . . . . . . . . . . . .17 • COOLING
Occupancy Table Format . . . . . . . . . . . . . . . . . . . . . . . . . . .17 • HEATING
Optimal Start Operation . . . . . . . . . . . . . . . . . . . . . . . . . . .17 • COOLING ONLY
SYSTEM OVERRIDE MODES . . . . . . . . . . . . . . . . . . . . 17,18 • STAGED ELECTRIC AND COMBINATION HEAT
Pressurization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17 • HOT WATER OR STEAM HEAT
Evacuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17 33ZCVVTZC-01 VVT Zone Controller and
Night Time Free Cooling (NTFC) . . . . . . . . . . . . . . . . . . . .18 33ZCFANTRM VAV Zone Controller Information. . 32
SET POINT GROUPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 New Book 1 PC 111 Catalog No. 513-362 Printed in U.S.A. Form 33ZC-3XA Pg 1 105 9-04 Replaces: New
Tab 11a Tab 1CS1
CONTENTS (cont) (PI) control functions for single duct terminals with modulating
heat or up to 2 stages of heat.
Page
The VAV Fan Terminal Zone Controller (33ZCFANTRM)
Series Fan Terminal Applications. . . . . . . . . . . . . . . . 32 provides dedicated pressure independent control functions for
• COOLING series fan or parallel fan powered terminals, single duct termi-
• HEATING nals with up to 3 stages of heat or modulating heat.
• COOLING WITH FAN
• STAGED ELECTRIC OR COMBINATION HEAT Carrier’s 3V control system provides optimized equipment
• HOT WATER OR STEAM HEAT and component control through airside linkage. Linkage refers
Parallel Fan Terminal Applications . . . . . . . . . . . . . . 35 to the process through which data is exchanged between the air
• COOLING terminals and the air source that provides the supply air to those
• HEATING terminals. The process “links” the terminals and the air source
• COOLING ONLY to form a coordinated system. Linkage allows the air source to
• STAGED ELECTRIC OR COMBINATION HEAT operate efficiently and reliably while responding to and satisfy-
• HOT WATER HEAT ing changing conditions in the zones. Linkage also allows the
Demand Controlled Ventilation (DCV) terminals to respond properly to changes in the air source. A
Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 VVT zone controller configured as the Linkage Coordinator
• DEMAND CONTROLLED VENTILATION AND manages the flow of data between the air source and the VVT
MINIMUM DAMPER POSITIONS system zones.
Rooftop units, air handlers, fan coils, and water source heat
GENERAL pumps feature product integrated or factory-installed controls
that are directly compatible with the 3V control system. The
The 3V™ control system is a VVT® (Variable Volume and rooftop units, air handlers, fan coils, and water source heat
Temperature) zoning system for constant volume equipment. pumps do not require any special hardware to be compatible
The 3V system is used to condition a space containing rooms with the Carrier linkage system. Consult your local Carrier
or areas of diverse loading. One VVT zone controller may be representative for the complete list of compatible air source
configured to manage a group of linked zone controllers. This controllers.
VVT zone controller is called the linkage coordinator. See
Fig. 1. The linked zone controllers may be managed by either Zone Controller Control Strategy — The primary
pressure dependent or pressure independent zone controllers. goal of the zone controller control strategy is to satisfy the tem-
When configured as a 3V linkage coordinator, the zone con- perature and ventilation requirements of each zone in a timely
troller decides what zones to condition by requesting the air and energy efficient manner. Secondary control strategies in-
conditioning equipment to provide heated or cooled air. clude high humidity control and demand controlled ventilation
(DCV). The controllers provide pressure independent or pres-
The VVT zone controller (33ZCVVTZC-01) is a compo- sure dependent operation. To achieve these goals, the control
nent of Carrier’s 3V system and is used to provide zone level strategy is broken into two parts: local zone control and system
temperature and ventilation control for Variable Volume and control.
Temperature Applications. The VVT zone controller is a pres-
sure dependent device that maintains space temperature by The method for achieving local zone control is through the
modulating the amount of supply airflow through its primary use of an electronic control in each damper or air terminal (zone
damper. Zone conditions are continuously monitored and elec- controller). The control functions of the zone controller are:
tronically communicated to the VVT Linkage Coordinator. • temperature control of the space (cooling and optional
All VVT zone controllers can be configured as the Linkage heating)
Coordinator, however only one is required per VVT system. • ventilation of the space
The Linkage Coordinator is responsible for communicating • fan control (for series and parallel type fan powered ter-
with the other zones, determining the required system mode minals)
and providing the proper information to the air source. • participation in the control of the entire air system
When the option board is (33ZCOPTBRD-01) installed on The method for achieving system control is to ensure that
a VVT zone controller, the zone controller is capable of con- the air source operation is based on the demands of the occu-
trolling staged or modulating heat or a fan powered terminal. pied zones. In this concept, the air source produces only the
amount of conditioned air (at a temperature and pressure) that
VVT Zone Controllers are available factory-mounted to is necessary to satisfy the current load requirements. It does this
Carrier’s round and rectangular VVT dampers. Round dampers by varying either the amount of air it delivers, at a constant
are available in 6, 8, 10, 12, 14, and 16-in. sizes. Rectangular temperature, into the duct (maintaining duct pressure) or by
dampers are available in 8 x 10, 8 x 14, 8 x 18, and 8 x 24-in. varying the quality (temperature, humidity, quantity of outside
sizes. All damper assemblies are equipped with an integrated air) of air it delivers into the duct. Its control parameters come
duct temperature sensor. from its own internal sources (configuration parameters, sen-
The 3V bypass controller (33ZCBC-01) with integrated ac- sors) and from feedback information that it receives from the
tuator is used to control the bypass damper for the system. The zones that it is supplying. The feedback allows the air source to
purpose of the bypass damper is to account for the fluctuations adjust its quantity of outdoor air and occupancy schedule,
in the supply air pressure caused by zone dampers modulating which allows it to run in the most efficient manner.
to satisfy individual set points. The bypass system allows a In addition the air source shall provide its operating mode to
constant volume HVAC (heating, ventilation and air condition- the zone controllers to aid in the control of the dampers and air
ing) unit to supply variable volumes of air to the system. The terminals. Specifically the system shall utilize the following
bypass damper is installed in the supply ductwork. functions in its control of the air source:
Carrier’s 3V control system provides seamless integration of • Occupancy — Determining when the air source is oper-
pressure independent zones for use with VVT systems. Simply ating based on the occupancy status of the zones. Over-
use Carrier’s family of VAV zone controllers (ComfortID™) to ride of zone occupancy is also available from space
regulate the flow of conditioned air into the space. temperature sensor.
The VAV (variable air volume) Zone Controller • Mode determination — Determining the air source oper-
(33ZCVAVTRM) provides dedicated pressure independent ating mode based on the demands of the zones.

2
CARRIER
NETWORK
PRIMARY BUS (BUS 0) MONITORING
SOFTWARE

ZONE
CONTROLLER

TYPICAL
FAN COIL UNIT

BRIDGE
(RECOMMENDED)

VAV ZONE
EQUIPPED CONTROLLER
SECONDARY BUS AIR TERMINAL
(1 OF UP TO 31)
BYPASS ADDRESSED
CONTROLLER SEQUENTIALLY
(ADDRESS 1 ABOVE BELOW LINKAGE TYPICAL
LINKAGE COORDINATOR) COORDINATOR FAN COIL UNIT

FULLY COMPATIBLE
ROOFTOP UNIT 3V VVT ZONE
SUPPORTING CONTROLLER
LINKAGE CONFIGURED AS
LINKAGE COORDINATOR

LEGEND
VAV — Variable Air Volume
VVT — Variable Volume and Temperature
Fig. 1 — Typical VVT® Application

3
PRODUCT DESCRIPTION • Carrier linkage system capability
• Global set point and occupancy scheduling
VVT® Zone Controller (33ZCVVTZC-01) — The • Sensor averaging
VVT zone controller is a component of Carrier’s 3V™ system • Foreign language support for ASCII based character sets
and is used to provide zone level temperature and air quality • Capable of high-speed 38.4K baud communications net-
control for Variable Volume and Temperature Applications. work operation
The VVT zone controller is a pressure dependent device that • VVT control for terminals up to 2.7 sq ft inlet
maintains space temperature by modulating the amount of sup- • Up to 32 Zone Controllers per system
ply airflow through its primary damper. Zone conditions are • System can include one or more Zone Controllers
continuously monitored and electronically communicated to • Dedicated port for System Pilot connection
the VVT Linkage Coordinator. • Uses thermistor type sensors
All VVT zone controllers can be configured as the Linkage • Mounts directly onto pressure-dependent box damper
Coordinator, however only one is required per VVT System. shaft
The Linkage Coordinator is responsible for communicating • Can drive up to 4 linked damper actuators
with the other zones, determining the required system mode • Designed for vertical or horizontal mounting
and providing the proper information to the air source. • Both controller housing and actuator are UL94-5V ple-
Carrier’s optional relay board (33ZCOPTBRD-01) may be num rated
used with VVT zone controllers to provide control functions • Control complies with ASHRAE 62.1
for heat or fan air terminals. Heating capabilities include modu- FUNCTIONS — Functions of the VVT zone controller are:
lating heat, up to 3 stages of ducted heat or combination base- • Pressure dependent space temperature control for single
board and ducted heat control. duct, series fan powered and parallel fan powered air
The VVT zone controller control assembly contains an inte- terminals
gral actuator assembly that is field mounted to the VVT termi- • Auxiliary heat functions including two-position hot
nal damper shaft, similar to the mounting of a standard actua- water valve, 3 stages of electric heat, modulating hot
tor. The actuator is rated at 35 lb.-in. (3.95 N-m) torque, a water valve and combination radiant/ducted heat stages
90-degree stroke, and provides a 90-second nominal time at • Wall-mounted space temperature sensor interface
60 Hz. The actuator is suitable for mounting onto a 3/8-in. • Space temperature set point reset (slide potentiometer)
(9.5 mm) square or round damper shaft, or onto a 1/2-in. • Timed override (T55/T56 pushbutton) with one-minute
(13 mm) round damper shaft. The minimum damper shaft granularity
length is 13/4-in. (45 mm). The zone controller is designed for • Space temperature and set point reset sharing
vertical or horizontal mounting. • Display of relative humidity based on local or remote
The zone controller is provided with removable connectors sensor
for power and communications. The zone controller has non- • Local occupancy control
removable screw type connectors for inputs. The removable • Remote occupancy override
connectors are designed so that they can be inserted one way so • Airside linkage
as to prevent installation errors. The zone controller also • Linkage function for multiple terminals with and without
provides an RJ-11 modular phone jack for the Network an air source
Service tool connection to the module via the Carrier network • Adaptive optimal start (AOS)
communications. • Sensor grouping function
• Commissioning functions
The VVT zone controller operates on the 3V system • System-wide air balancing
network and is compatible with all Carrier communicating • Damper calibration
devices. A user interface is not required for everyday operation • Sensor trim
of the zone controller. The zone controller can be configured or • Carrier proprietary network tables and alarms
operated through the Carrier network with optional interface • Demand control ventilation
tools including the System Pilot or Carrier software. • Analog CO2 monitoring and control
The zone controller provides the following features and • Loadshed/redline response
benefits: • System Pilot interface
• Provides pressure dependent VVT control WIRING CONNECTIONS — Field wiring is 18 to 22 AWG
• Supports zone level Demand Controlled Ventilation with (American Wire Gage). The zone controller is a NEC (National
field-installed CO2 sensor. Electrical Code) Class 2 rated device.
• Capable of stand-alone operation with supply-air temper- INPUTS
ature sensor.
• Quick and easy commissioning and balancing process • Space temperature sensor
via a dedicated maintenance table for system wide air • Wall-mounted space temperature sensor interface
balancing. • Space temperature set point reset (slide potentiometer)
• Communicates to all communicating 3V system devices • Optional supply air temperature sensor (required for
• Capable of Proportional Integral Derivative (PID) reheat and stand alone operation)
control • Optional primary air temperature sensor (one required
• Optional terminal fan control per system that does not utilize a linkage compatible air
source)
NOTE: Terminal fan control requires the VVT Zone Con- • Optional CO2 sensor
troller Option Board P/N 33ZCOPTBRD-01. • Optional relative humidity sensor (for monitoring only)
• Optional auxiliary heating control of: two-position hot • Optional remote occupancy contact input
water; one, two, or three-stage electric; modulating hot OUTPUTS
water valve; or combination radiant/ducted heat stages
• Integrated factory-wired pressure dependent damper
NOTE: Auxiliary heating requires the VVT Zone Control- actuator
ler Option Board P/N 33ZCOPTBRD-01. • Heating (requires VVT Zone Controller Option Board)
• Provides a remote occupancy contact input for a field- • Two-position hot water
supplied occupancy sensor • One to three stages of heat

4
• Modulating hot water valve as to prevent installation errors. The bypass controller also
• Combination radiant/ducted heat stages provides an RJ-11 modular phone jack for the Network
• Terminal fan (requires VVT® Zone Controller Option Service tool connection to the module via the Carrier network
Board) communications.
• Damper position output (0 to 10 v) for linked dampers Field-installed actuators may also be used. Belimo Multi-
WIRING CONNECTIONS — Field wiring is 18 to 22 AWG Function technology actuators may be ordered direct from
(American Wire Gage). The VVT zone controller is a NEC Belimo. The following accessory actuators may be used
(National Electronic Code) Class 2 rated device. instead of the integrated actuator:
POWER SUPPLY — The 33ZCVVTZC-01 zone controller • NM24-MFT US P-30002 — 70 in.-lb actuators with
requires a 24 vac ± 10% at 40 va (60 Hz) power source. floating point control and 0 to 10 vdc feedback.
COMMUNICATIONS — The number of controllers is limit- • AM24-MFT US P-30002 — 160 in.-lb actuators with
ed to 128 devices maximum, with a limit of 8 systems floating point control and 0 to 10 vdc feedback.
(Linkage Coordinator configured for at least 2 zones). Bus The following actuators may be used as linked actuators.
length may not exceed 4000 ft (1219 m), with no more than Up to four actuators may be linked to the master actuator:
60 devices on any 1000 ft (305 m) section. Optically isolated • LM24-MFT US P-10002 — 35 in.-lb actuators with
RS-485 repeaters are required every 1000 ft (305 m). 0 to 10 vdc control and 0 to 10 vdc feedback.
At 19,200 and 38,400 baud, the number of controllers is • NM24-MFT US P-10002 — 70 in.-lb actuators with
limited to 128 maximum, with no limit on the number of Link- 0 to 10 vdc control and 0 to 10 vdc feedback.
age Coordinators. Bus length may not exceed 1000 ft (305 m). • AM24-MFT US P-10002 — 160 in.-lb actuators with 0
ENVIRONMENTAL RATINGS to 10 vdc control and 0 to 10 vdc feedback.
Operating Temperature . . . . . . . . . 32 F to 131 F (0° C to 55 C) The Bypass Controller operates on the 3V system network
and is compatible with all Carrier communicating devices. A
Storage Temperature . . . . . . . . . . . 32 F to 158 F (0° C to 70 C) user interface is not required for everyday operation of the by-
Operating Humidity. . . . . . . . . . .10% to 95%, non-condensing pass controller. The Bypass Controller can be configured or op-
Storage Humidity. . . . . . . . . 10% to 41% at 158 F, condensing erated through the Carrier Network with optional interface
tools including the System Pilot or Carrier software.
POWER CONSUMPTION — The power requirement siz-
ing allows for accessory water valves and for the fan contactor. The bypass controller provides the following features and
Water valves are limited to 15 va. The fan contactor is limited benefits:
to 10 va (holding). • Primary air temperature and pressure sensors determine
VIBRATION system operating mode to ensure proper operation in
case of communication failure.
Performance Vibration: • Air Source leaving air temperature protection minimizes
1.5 G measured at 20 to 300 Hz the occurrence of heating and/or cooling lockouts based
CORROSION — Office environment. Indoor use only. on unacceptable discharge temperatures.
APPROVALS • Quick and easy commissioning and balancing process
via a dedicated maintenance table.
• NEC Class 2 • Stand-alone or linked system operation
• UL 916-PAZX and UL 873 • Carrier linkage system capability
• Conforms to requirements per European Consortium • Foreign language support for ASCII based character sets
standards EN50081-1 (CISPR 22, Class B) and • Carrier communicating network
EN50082-1 (IEC 801-2, IEC 801-3, and IEC 801-4) for • High-speed (38.4K baud) communications network
CE mark labeling • Thermistor type duct temperature sensor
• UL94-5V (actuator) • 0 to 2 in. wg pressure sensor
Bypass Controller (33ZCBC-01) — The VVT By- • UL94-5V plenum rated controller housing
pass Controller is a component of Carrier’s 3V™ system and is FUNCTIONS — Functions of the bypass controller are:
used to regulate the supply duct static pressure for Variable • Auto pressure sensor zero calibration
Volume and Temperature Applications. The Bypass Controller • Manual pressure sensor calibration
is an essential system component that allows constant volume • High end pressure transducer calibration
HVAC equipment to provide zone level temperature control. • Bypass damper calibration
The Bypass Controller provides the following features: • Bypass damper modulation
• System or stand-alone operation • Leaving air temperature protection
• Integrated pressure sensor • Network tables and alarms
• Determines system-operating mode • System Pilot interface
• Air source leaving air temperature lockouts INPUTS
The bypass controller control assembly contains an integral • Duct temperature sensor
actuator assembly that is field mounted to the VVT terminal • Damper position feedback potentiometer (factory installed)
damper shaft, similar to the mounting of a standard actuator. • System pressure (factory installed)
The actuator is rated at 35 lb.-in. (3.95 N-m) torque, a
90-degree stroke, and provides a 90-second nominal time at OUTPUTS
60 Hz. The actuator is suitable for mounting onto a 3/8-in. • Integrated factory-wired pressure dependent damper
(9.5 mm) square or round damper shaft, or onto a 1/2-in. actuator
(13 mm) round damper shaft. The minimum damper shaft PHYSICAL CHARACTERISTICS
length is 13/4-in. (45 mm). The bypass controller is designed for Dimensions. . . . . . . . . . . . . . 2.36 in. H x 9.2 in. W x 4.84 in. D
vertical or horizontal mounting. (60 mm x 233.7 mm x 123 mm)
The bypass controller is provided with removable connectors ELECTRICAL CHARACTERISTICS — Input Volts 40 va
for power and communications. The bypass controller has non- at 24 vac + 10% (60 Hz)
removable screw type connectors for inputs. The removable
connectors are designed so that they can be inserted one way so

5
The power requirement sizing allows for accessory water CARRIER NETWORK SYSTEM
valves and for the fan contactor. Water valves are limited to • Broadcast time/date and holiday status
15 va. The fan contactor is limited to 10 va (holding). • Support 30 holidays with holiday broadcast
ENVIRONMENTAL REQUIREMENTS • Generate network alarm messages for trouble conditions
Operating Temperature . . . . . . . . .32 F to 131 F (0° C to 55 C) • Provide capability to fully commission 3V zoning, air
sources and Universal Controllers
Storage Temperature . . . . . . . . . . . 32 F to 158 F (0° C to 70 C
CONTROL AND MONITORING
Operating Humidity . . . . . . . . . . . 10% to 95% non-condensing
• Display or send space temperature to a specified Carrier
Storage Humidity . . . . . . . . . .10% to 41% at 158 F condensing network device
COMMUNICATIONS CHARACTERISTICS — Local com- • Modify set points in Carrier network devices
munications between Carrier communicating network devices • Allow display of bus scan information
at up to 38.4 KB. Computer access available. • Display OAT as received from the network
Remote access through modem at up to 38.4 KB. Computer • Provide two types of 3V Zone Controller access via ded-
access available. icated local bus or via network bus.
WIRING REQUIREMENTS MOUNTING — The System Pilot can be mounted into a
standard 2 x 4-in. junction box. Optional wall plates are also
Communication Bus — 3-Conductor, 18-Gage, Stranded, with available that allow for flush mounting or for retrofit applications.
Shield
SPECIFICATIONS
Power — 2-Conductor, 18-Gage, Stranded, with Shield Power Requirements . . . . . . . . . . . . . . . . . . . . . . 24 vac + 6 vac
VIBRATION (18 to 32 vac) (60 Hz)
Performance Vibration: Dimensions. . . . . . . . . . . . . . . 6.0 in. H x 3.5 in. W x 1.25 in. D
1.5 G measured at 20 to 300 Hz (150 mm x 87.5 mm x 31.25 mm)
Operating Temp . . . . . . . . . . . . . . .32 F to 104 F (0° C to 40 C)
CORROSION — Office environment. Indoor use only. Storage Temp . . . . . . . . . . . . . . –40 F to 140 F (–40 C to 60 C)
AGENCY APPROVALS Operating Humidity . . . 10% to 95%, at 104 F, non-condensing
NEC Class 2 Storage Humidity . . . . . . . . . 10% to 41% at 140 F, condensing
UL 916-PAZX and UL 873 VIBRATION
Conforms to requirements per European Consortium standards Performance Vibration:
EN50081-1 (CISPR 22, Class B) and EN50082-1 (IEC 801-2, 1.5 G measured at 20 to 300 Hz
IEC 801-3, and IEC 801-4) for CE mark labeling. CORROSION — Office environment.
UL94-5V (actuator)
VAV Zone Controller (33ZCVAVTRM) — Carrier’s
System Pilot (33PILOT-01) — The System Pilot is a 3V control system provides seamless integration of pressure
component of Carrier’s 3V™ system and serves as the user- independent zones for use with VVT systems. Simply use
interface and configuration tool for all Carrier communicating Carrier’s family of VAV zone controllers (ComfortID™) to
devices. The System Pilot can be used to install and commission regulate the flow of conditioned air into the space. The VAV
a 3V zoning system, linkage compatible air source, universal Zone Controller provides dedicated pressure independent con-
controller, and all other devices operating on the Carrier network. trol functions for single duct terminals with modulating heat or
Additionally, the System Pilot can serve as a wall-mounted up to 2 stages of heat.
temperature sensor for space temperature measurement. The The 33ZCVAVTRM VAV Single Duct Zone Controller pro-
occupant can use the System Pilot to change set points and vides the following features and benefits:
cause occupancy overrides. A security feature is provided to • capable of demand control ventilation
limit access of features for unauthorized users. • provides Pressure Independent (VAV) control
The System Pilot consists of a backlit alphanumeric Liquid • uses Proportional Integral Derivative (PID) control
Crystal Display (LCD) with adjustable contrast and backlight- • mounts directly onto VAV box damper shaft
ing. It features six pushbuttons and two rotary knobs with • for terminals up to 9000 cfm or 3.4 sq ft inlet (primary
pushbuttons that allow the user to navigate through the menus, air)
select desired options, and modify data. • auxiliary heating control of modulating (floating) hot
The System Pilot provides the following features and water, single or two-position hot water, single or two-
benefits: stage electric, or zone perimeter heat
• quick and easy commissioning and balancing process
ZONE OCCUPANT USER INTERFACE • automatic self calibration of airflow transducer
• Modify zone operating set points during occupied and • capable of stand-alone operation
unoccupied modes • actuator preassembled to housing
• Provide occupancy override capability • capable of demand controlled ventilation support with
• Display local occupancy status field-installed IAQ (indoor air quality) sensor
• Display current operating mode • easy access to airflow sensor pneumatic connections
USER INTERFACE • capable of high-speed 38.4 kilobaud communications
• Communicate with Carrier network devices network operation
• Access configuration, maintenance, service, set point, • 128 controller maximum system (must be located on
time schedule, alarm history and status data in Carrier same Carrier network bus segment)
network devices • capable of zone humidity control (dehumidification)
• Force and auto points in Carrier network devices with field-installed humidity sensor
• Modify address of Carrier network devices • Carrier Linkage System capability
• Modify time/date in Carrier network devices • global set point and occupancy scheduling
• Display metric or customary U.S. units • capable of local set point adjustment with field-installed
• Allow four security levels temperature sensor (with temperature offset)
• Support foreign language • both controller housing and actuator are UL94-5V ple-
num rated

6
The VAV zone controller is a single duct, variable air vol- POWER SUPPLY — The 33ZCVAVTRM zone controller re-
ume (VAV) terminal control with a factory-integrated actuator. quires a 24 vac ± 10% at 40 va (50/60 Hz) power source.
The zone controller maintains precise temperature control in POWER CONSUMPTION — The power requirement siz-
the space by regulating the flow of conditioned air into the ing allows for accessory water valves or heat contactors. Water
space. valves are limited to 15 va on both two-position and modulat-
Buildings with diverse loading conditions can utilize reheat ing hot water. The heat contactors are limited to 10 va (holding)
or supplemental heating control. The zone controller can sup- each.
port two position hot water, modulating hot water, 2-stage elec- ACCURACY — Terminal airflow (nominal cfm) is rated at
tric, or perimeter heat. 1-in. wg (249 kPa) measured velocity pressure. The zone con-
The VAV zone controller provides additional control fea- troller is capable of controlling to as low as 10% or as high as
tures such as Occupied/Unoccupied scheduling initialized via 125% of nominal airflow with an accuracy of ± 3% (nominal)
the network. The zone controller offers override invoked from at any point within the range.
a wall sensor during unoccupied hours from 1 to 1440 minutes HARDWARE (MEMORY)
in 1-minute increments. Optional indoor air quality (IAQ) or
relative humidity monitoring and control are also available. FLASH EPROM
The Occupied Override function supports Carrier’s Tenant DIFFERENTIAL PRESSURE RANGE — 0 to 2.0 in. wg
Billing if the override time is set to values of 1, 2, 3, or 4 hours (0 to 498 kPa) maximum for the onboard flow sensor.
(60, 120, 180, or 240 minutes). SPECIFIED SENSING TEMPERATURE RANGE — The
The VAV zone controller control assembly contains an inte- zone controller space temperature, supply air temperature, and
gral actuator assembly that is field mounted to the VAV termi- primary air temperature sensing range is –40 to 245 F (–40 to
nal damper shaft, similar to the mounting of a standard actua- 118 C). The zone controller has an allowable control set point
tor. The actuator is rated at 35 in.-lb (3.95 N-m) torque, a range from 40 to 90 F (4 to 32 C) for heating and 45 to 99 F
90-degree stroke, and provides a 90-second nominal time at (7 to 37 C) for cooling.
60 Hz. The actuator is suitable for mounting onto a 3/8-in. COMMUNICATIONS — The number of controllers is limit-
(9.5 mm) square or round damper shaft, or onto a 1/2-in. ed to 128 zones maximum, with a limit of 8 systems (Linkage
(13 mm) round damper shaft. The minimum damper shaft Coordinator configured for at least 2 zones). Bus length may
length is 13/4-in. (45 mm). The zone controller is designed for not exceed 4000 ft (1219 m), with no more than 60 devices on
vertical or horizontal mounting. any 1000 ft (305 m) section. Optically isolated RS-485 repeat-
The zone controller is provided with removable connectors ers are required every 1000 ft (305 m).
for power and communications. The zone controller has non- At 19,200 and 38,400 baud, the number of controllers is
removable screw type connectors for inputs. The removable limited to 128 maximum, with no limit on the number of Link-
connectors are designed so that they can be inserted one way so age Coordinators.
as to prevent installation errors. The zone controller also
ENVIRONMENTAL RATINGS
provides an RJ-11 modular phone jack for the Network
Service tool connection to the module via the Carrier network Operating Temperature: 32 to 140 F (0° to 60 C) at 10 to 90%
communications. RH (non–condensing)
An optional Conduit Box Cover (Part Number Shipping Temperature: –40 to 185 F (-40 to 85 C) at 0 to 90%
33ZCCONBOX) allows field wiring connection via conduit. RH (non–condensing)
The conduit box is designed to accept two 1/2-in. (13 mm) VIBRATION
EMT conduits. Performance vibration:
The 33ZCVAVTRM is designed to allow a service person • 0.014-in. (0.356 mm) Peak-to-Peak displacement mea-
or building owner to configure and operate the unit through the sured at 5 to 31 Hz
Carrier network user interfaces. A user interface is not required • 0.75 G measured at 31 to 300 Hz
for day-to-day operation. All maintenance, configuration, set- CORROSION — Office environment. Indoor use only.
up, and diagnostic information is available through the Level II
communications port to allow data access by the System pilot VAV Fan Terminal Zone Controller
or an attached computer running Carrier software. (33ZCFANTRM) — Carrier’s 3V™ control system pro-
WIRING CONNECTIONS — Field wiring is 18 to 22 AWG vides seamless integration of pressure independent zones for
(American Wire Gage). The zone controller is a NEC (National use with VVT systems. Simply use Carrier’s family of VAV
Electrical Code) Class 2 rated device. zone controllers (ComfortID™) to regulate the flow of
INPUTS conditioned air into the space. The VAV Fan Terminal Zone
Controller provides dedicated control functions for series fan
• space temperature sensor or parallel fan powered terminals, single duct terminals with
• primary air damper position (factory-installed) 3 stages of heat, or as a primary controller for dual duct or zone
• airflow sensor (factory-installed) pressurization applications.
• remote wall sensor set point adjustment
• optional supply temperature sensor (required for ducted heat) The 33ZCFANTRM VAV Fan Terminal Zone Controller
• optional primary air temperature sensor (required for provides the following features and benefits:
systems which do not utilize a linkage compatible air • provides Pressure Independent (VAV) control
source system) • uses Proportional Integral Derivative (PID) control
• optional IAQ sensor or relative humidity sensor • mounts directly onto VAV box damper shaft
• optional remote occupancy contact • terminal fan control
OUTPUTS • for terminals up to 9000 cfm or 3.4 sq ft inlet (primary
air)
• internally factory-wired damper actuator • auxiliary heating control of modulating (floating) hot
• heating (ducted or non-ducted) water; two-position hot water; single, two, or three stage
— modulating (floating) heat electric; or zone perimeter heat
— up to 2 stages of electric heat (if 3 stages are required, • quick and easy commissioning and balancing process
the 33ZCFANTRM should be used) • automatic self calibration of airflow transducer
— two-position heat • capable of stand-alone operation

7
• actuator preassembled to housing The 33ZCFANTRM is designed to allow a service person
• capable of demand controlled ventilation or building owner to configure and operate the unit through the
• capable of individual zone pressure control for individ- Carrier proprietary network user interfaces. A user interface is
ual supply and exhaust control in conjunction with sec- not required for day-to-day operation. All maintenance, config-
ondary terminal controller (required) uration, setup, and diagnostic information is available through
• easy access to airflow sensor pneumatic connections the Level II communications port to allow data access by an at-
• capable of high-speed 38.4 kilobaud communications tached computer running Network Service Tool, Comfort-
network operation VIEWTM, or ComfortWORKS® software.
• 128 controller maximum system (must be located on WIRING CONNECTIONS — Field wiring is 18 to 22 AWG
same Carrier communicating network bus segment) (American Wire Gage). The zone controller is a NEC (National
• capable of zone humidity control (dehumidification) Electrical Code) Class 2 rated device.
• Carrier Linkage System compatibility
• global set point and occupancy scheduling INPUTS
• capable of local set point adjustment with field-installed • space temperature sensor
temperature sensor (with temperature offset) • primary air damper position (factory-installed)
• both controller housing and actuator are UL94-5V ple- • airflow sensor (factory installed)
num rated • field-installed remote wall sensor set point adjustment
• optional supply temperature sensor (required for ducted
The zone controller is a single duct or fan powered, variable
air volume (VAV) terminal control with a factory-integrated ac- heat and supply air monitoring)
• optional primary air temperature sensor (one per system
tuator. The zone controller maintains precise temperature con- is required for systems which do not utilize a linkage
trol in the space by operating the terminal fan and regulating
compatible air source)
the flow of conditioned air into the space. • optional IAQ sensor or relative humidity sensor
Buildings with diverse loading conditions can be supported • optional secondary airflow (zone pressure or dual duct)
by controlling reheat, ducted heat, or non-ducted supplemental • optional remote occupancy contact
heat. The zone controller can support two-position hot water, OUTPUTS
modulating hot water, or up to 3-stage electric heat.
• internally factory-wired damper actuator
With the addition of a secondary exhaust or return air termi- • heating (ducted or non-ducted)
nal and the 33ZCSECTRM controller, zone pressurization — modulating (floating) heat
applications can be supported. — up to 3 stages of electric heat
Supply and exhaust airflow control is provided on an — two-position heat
individual zone basis in order to maintain the desired zone • fan start/stop
pressure. • secondary damper actuator
The 33ZCSECTRM in conjunction with the fan terminal POWER SUPPLY — The 33ZCFANTRM requires a 24 vac
zone controller are used to provide control for constant volume ± 10% power source rated at 40 va (50/60 Hz).
dual duct applications. POWER CONSUMPTION — The power requirement siz-
When linked to a Carrier Linkage System, the zone control- ing allows for accessory water valves and for the fan contactor.
ler provides numerous features and benefits such as weighted Water valves are limited to 8 va on both two-position and
average demand for system operation, intelligent supply air modulating hot water. The fan contactor is limited to 11 va
temperature reset, set point averaging, global set point sched- (holding).
ule, and occupancy scheduling. Duct static pressure reset for NOTE: If a water valve or fan contactor exceeds these limits,
the air source is provided, based on terminal requirements. or external contactors are required for electric heat, then it is
The zone controller provides additional control features recommended a 60 va transformer be used. The maximum rat-
such as Occupied/Unoccupied scheduling initialized via the ing for any output is 20 va.
network. The zone controller offers override invoked from a ACCURACY — Terminal airflow (nominal cfm) is rated at
wall sensor during unoccupied hours from 1 to 1440 minutes in 1 in. wg (249 kPa) measured velocity pressure. The zone con-
1-minute increments. Optional indoor air quality (IAQ) or rela- troller is capable of controlling to as low as 10% or as high as
tive humidity monitoring and control are also available. 125% of nominal airflow with an accuracy of ± 3% (nominal)
The zone controller assembly contains an integral VAV ac- at any point within the range.
tuator that is field mounted to the VAV terminal damper shaft, HARDWARE (MEMORY)
similar to the mounting of a standard actuator. The actuator is
rated at 35 in.-lb (3.95 Nm) torque, a 90-degree stroke, and FLASH EPROM
provides a 90-second nominal running time at 60 Hz. The actu- DIFFERENTIAL PRESSURE RANGE — 0 to 2.0 in. wg
ator is suitable for mounting onto a 3/8-in. (9.5 mm) square or (0 to 498 kPa) maximum for the onboard flow sensor.
round damper shaft, or onto a 1/2-in. (13 mm) round damper SPECIFIED SENSING TEMPERATURE RANGE — The
shaft. The minimum damper shaft length is 13/4 in. (45 mm). zone controller space temperature, supply temperature, and pri-
The zone controller is designed for vertical or horizontal mary air temperature sensing range is –40 to 245 F (–40 to
mounting. 118 C). The zone controller has an allowable control set point
The zone controller is provided with removable connectors range from 40 to 90 F (4 to 32 C) for heating and 45 to 99 F
for power and communications. The zone controller has non- (7 to 37 C) for cooling.
removable screw type connectors for inputs. The removable COMMUNICATIONS — The number of controllers is limit-
connectors are designed so that they can be inserted one ed to 128 zones maximum, with a limit of 8 systems (Linkage
way so as to prevent installation errors. The zone controller Coordinator configured for at least 2 zones). Bus length may
also provides an RJ-11 modular phone jack for the Network not exceed 4000 ft (1219 m), with no more than 60 devices on
Service tool connection to the module via the Carrier network any 1000 ft (305 m) section. Optically isolated RS-485 repeat-
communications. ers are required every 1000 ft (305 m).
An optional conduit box cover (Part Number At 19,200 and 38,400 baud, the number of controllers is
33ZCCONBOX) allows field wiring connection via conduit. limited to 128 maximum, with no limit on the number of Link-
The conduit box is designed to accept two 1/2-in. (13 mm) age Coordinators.
EMT (Electrical Metal Tubing) conduits.

8
ENVIRONMENTAL RATINGS INDOOR AIR QUALITY SENSOR — Three different CO2
Operating Temperature: 32 to 140 F (0° to 60 C) at 10 to 90% sensors are available for optional demand control ventilation.
RH (non-condensing) The 33ZCSENCO2 sensor is an indoor, wall-mounted sen-
Shipping Temperature: –40 to 185 F (–40 to 85 C) at 0 to 90% sor with an LED (light-emitting diode) display.
RH (non-condensing) The 33ZCT55CO2 sensor is an indoor, wall-mounted sen-
VIBRATION — Performance vibration: 0.014-in. (0.356 mm) sor without display. The CO2 sensor also includes a space tem-
peak to peak displacement, 5 to 31 Hz; 0.75 G, 31 to 300 Hz perature sensor with override button.
CORROSION — Office environment. Indoor use only. The 33ZCT56CO2 sensor is an indoor, wall-mounted sen-
sor without display. The CO2 sensor also includes a space tem-
APPROVALS — Listed under UL 916-PAZX, UL 873, and perature sensor with override button and temperature offset.
UL94-5V.
NOTE: The relative humidity sensor and CO2 sensor cannot be
Accessories used on the same zone controller.
SUPPLY AIR TEMPERATURE SENSOR —The 33ZCSENSAT Sensor Information
supply air temperature sensor is required for reheat applications
or stand-alone operation. The sensor has an operating range of SPACE TEMPERATURE SENSORS — The sensor housing
–40 to 245 F (–40 to 118 C) and includes a 6-in. stainless steel is plastic ABS. The connections are screw terminals. The
probe and cable. weight is 0.18 lb See Fig. 2 for sensor dimensions.
DUCT AIR TEMPERATURE SENSOR — The 33ZCSENDAT The 33ZCT56SPT space temperature sensor has a set point
Duct Air Temperature Sensor is required for cooling only appli- potentiometer that provides a set point input. The set point
cations on non-33CS or existing non-Carrier dampers. The sen- potentiometer range for each sensor can be adjusted from –15°
sor is used for supply air monitoring. The sensor has an operating to 15° F. Adjustment direction is indicated by COOL and
range of –40 to 245 F (–40 to 118 C) and includes a mounting WARM on the sensor cover.
grommet and 75-in. cable. The temperature sensor uses a 10K ohm thermistor to sense
PRI MARY AI R TEMPERATURE SENSOR — The ambient temperature. See Table 1 for resistance vs. temperature
values for the thermistor.
33ZCSENPAT Primary Air Temperature sensor is required on
a master Zone Controller if the Zone Controller is not using a The sensor is designed to be mounted in a vertical mounting
Carrier network, linkage compatible air source. The sensor is position for proper operation.
used to monitor the equipment’s supply-air temperature. The 33ZCT55SPT SENSOR — The 33ZCT55SPT space sensor is
temperature is broadcast to the system Zone Controllers which a basic space temperature sensor for use with the zone control-
receive information from the linkage coordinator. The sensor ler. It contains a thermistor to sense room temperature, override
has an operating range of –40 to 245 F (–40 to 118 C) and in- button for initiating a timed override, and an RJ11 jack for the
cludes a 6-in. stainless steel probe with conduit box. connection of a CCN Network Service Tool. The sensor com-
VVT® ZONE CONTROLLER OPTION BOARD — The munications connection (RJ11) is concealed behind a remov-
33ZCOPTBRD-01 VVT Zone Controller Option Board is re- able cover. The sensor is field installed.
quired for use of auxiliary heat and fan control functions. The Space Temperature Sensor Wiring — In order to provide
Option Board is field installed and provides four triac discrete temperature sensing and override functions, the 33ZCT55SPT
outputs, three for supplemental heat and one for the fan output. sensor must be connected to the zone controller using 20 AWG
CONDUIT BOX — The 33ZCCONBOX conduit box pro- twisted pair cables. Pressing the timed override button on the
vides two conduit connections to the VAV zone controller for 33ZCT55SPT sensor produces the required short-circuit signal.
installations requiring the use of conduit due to local electrical See Fig. 3 for internal schematic. The sensor has a screw termi-
codes. nal connector to facilitate wiring. All wiring from the zone con-
troller to the sensor is field supplied.
SPACE TEMPERATURE SENSOR WITH OVERRIDE
BUTTON — The 33ZCT55SPT space temperature sensor
with override button is required for all applications. The space
temperature sensor monitors room temperature which is used
by the zone controller to determine the amount of conditioned
air that is allowed into the space.
SPACE TEMPERATURE SENSOR WITH OVER-
RIDE BUTTON AND SET POINT ADJUSTMENT —
The 33ZCT56SPT space temperature sensor with override
button and set point adjustment can be used in place of the
33ZCT55SPT space temperature sensor if local set point
adjustment is required. A space temperature sensor is
required for all applications. The space temperature sensor
monitors room temperature which is used by the zone con-
troller to determine the amount of conditioned air that is
allowed into the space. The set point adjustment bar allows
up to a ± 15° F (8° C) temperature adjustment by the room
occupant.
RELATIVE HUMIDITY SENSOR — The 33ZCSENSRH-01
(indoor space) or 33ZCSENDRH-01 (duct) relative humidity
sensor is required for zone humidity control (dehumidification)
on pressure independent applications. The relative humidity
sensor is used for monitoring only on pressure dependent
applications.
NOTE: The relative humidity sensor and CO2 sensor cannot be
used on the same zone controller. Fig. 2 — Space Temperature Sensor and Wall
Mounted Humidity Sensor Dimensions

9
T56 ONLY

RJ-11
SEN SET

SERVICE JACK

S1

10K R3
0 OHMS 100K
PUSH BUTTON J3 SENSOR
5 4 3 2 1 OVERRIDE
6
(CCN GND)

J4
(UNUSED)
(24 VAC +)

(24 VAC -)
(CCN +)

(CCN -)

SW1

INTERNAL SCHEMATIC

Fig. 3 — Temperature Sensor Internal Wiring

Sensor terminals 1 and 2 are used for space temperature SUPPLY AIR TEMPERATURE SENSOR (33ZCSENSAT) —
sensing. The space temperature sensor range is 32 to 120 F, The supply air temperature sensor (SAT) is required for reheat
with a nominal resistance of 10,000 ohms at 77 F. applications or stand-alone operation. The SAT sensor consists
33ZCT56SPT SENSOR — The 33ZCT56SPT space temper- of a thermistor encased within a stainless steel probe. The
ature sensor is field-installed. The 33ZCT56SPT is a wall- probe is 6-in. nominal length. See Fig. 4. The sensor has
mounted sensor capable of measuring the ambient temperature 114-in. of unshielded, plenum-rated cable (2 conductors,
at its location, and is equipped with an override button. The 22 AWG). The range of the sensor is –40 to 185 F with a nom-
override button (when pressed) provides a short across the inal resistance of 10,000 ohms at 77 F. The sensor measures
internal thermistor. The sensor is also equipped with an RJ11 temperature with an accuracy of ± 0.36 F (0.2 C) from 0° to
service jack with a 6-pin termination block for network 70 C. The sensor is supplied with a gasket and two self-drilling
connection. The sensor is equipped with a 100K ohm (nomi- mounting screws.
nal) linear slide potentiometer. DUCT TEMPERATURE SENSOR (33ZCSENDAT) — The
Space Temperature Sensor Wiring — In order to provide duct (supply) temperature sensor is required for cooling-only
temperature sensing and the override functions, the applications on non-33CS or existing non-Carrier dampers.
33ZCT56SPT sensor must be connected to the zone controller The duct temperature sensor must be installed in the supply air
using 3-conductor, 18 to 20 AWG cables. (The network com- duct. The 33ZCSENDAT is the recommended sensor. See
munication cable may be used.) Pressing the timed override Fig. 5 for sensor details.
button the 33ZCT56SPT sensor produces the required short- The duct temperature sensor should be moved to a location
circuit signal. See Fig. 2 for internal schematic. The sensor has which will provide the best sensing of the supply-air tempera-
a screw terminal connector to facilitate wiring. All wiring from ture during heating and cooling.
the zone controller to the sensor is field supplied. The sensor’s For systems using a ducted supply, the duct temperature
thermistor has a range of 32 to 158 F with a nominal resistance sensor should be located in the supply duct downstream of the
of 10,000 ohms at 77 F. discharge of the air source and before the bypass damper to
Remote Timed Override — Pressing the timed override but- allow good mixing of the supply airstream.
ton on the 33ZCT55SPT or 33ZCT56SPT sensors initiates a The 33ZCSENDAT duct sensor is a small epoxy sensor that
timed override. If the override is activated in a zone that is us- is 11/4-in. long. A grommet is provided for filling the hole
ing a network time schedule, then the override will be reported around the sensor cable after the sensor is located in the duct.
to the global schedule. When using a global schedule, all the
zones assigned to that schedule will go occupied when any of PRIMARY AIR TEMPERATURE SENSOR (PAT) — The
the space temperature override buttons are pressed by the user. PAT sensor consists of a thermistor encased within a stainless
For zones that require individual override, those zones are re- steel housing with 5-in. of exposed length. See Fig. 6. The sen-
quired to use a local schedule. sor has 2 Teflon insulated, stranded conductors (24 AWG).
The range of the sensor is –40 to 185 F with a nominal resis-
If the mode is currently unoccupied and the override func- tance of 10,000 ohms at 77 F. The sensor measures temperature
tion is activated, the mode will change to occupied for the peri- with an accuracy of ± 0.36 F (0.2 C) from 0° to 70 C.
od of time configured. The control will interpret a 1 to 10 sec-
ond button press as a user initiated timed override command.
If the override button is held for less than 1 second or more
than 10 seconds, the control will not enter override. If the over-
ride button is held for more than 60 seconds, a Space Tempera-
ture alarm will be generated.

10
.08
.39

FOAM GASKET

3.90
.40'' O.D.

.250 ±.01Dia

3.00 5.5 ±.5


.175 DIA
x .600
PLENUM RATED CABLE
114'' +/-6

3.00

1.50

ø0.50 ENGAGEMENT HOLE FOR


CLEARANCE HOLE MOUNTING SCREW (2)

Fig. 4 — Supply Air Temperature Sensor Dimensions

.225/ .245
(5.72/6.22)

0.06 1.00 75.0 .5


(1.5) (25.4) (1905)

1.25
(31.8)

NOTE: Dimensions are in inches (millimeters).


Fig. 5 — 33ZCSENSDAT Duct Sensor

2.13
1.70 7/8'' DIA KNOCKOUTS (8)

5.50'' X .250'' DIA.


STAINLESS STEEL PROBE

4.00

.40 O.D.

.175 DIA .125 FOAM PAD


X .600

2.75-3.50 MOUNTING

Fig. 6 — Primary Air Temperature Sensor Dimensions

11
Table 1 — Thermistor Resistance vs INPUTS/OUTPUTS
Temperature Values for Space Temperature
Sensor, Return-Air Temperature Sensor, and The VVT® Zone Controller (33ZCVVTZC-01) inputs are
Supply-Air Temperature Sensor shown in Table 2. The VVT Zone Controller (33ZCVVTZC-
01) outputs are shown in Table 3. The Bypass Controller
TEMP (C) TEMP (F) RESISTANCE (Ohms) (33ZCBC-01) inputs are shown in Table 4 The Bypass Con-
–40 –40 335,651 troller (33ZCBC-01) outputs are shown in Table 5. The VAV
–35 –31 242,195 Zone Controller (33ZCVAVTRM) inputs are shown in Table 6.
–30 –22 176,683
–25 –13 130,243 The VAV Zone Controller (33ZCVAVTRM) outputs are shown
–20 –4 96,974 in Table 7. The VAV Fan Terminal Zone Controller
–15 5 72,895 (33ZCFANTRM) inputs are shown in Table 8. The VAV Fan
–10 14 55,298
–5 23 42,315 Terminal Zone Controller (33ZCFANTRM) outputs are shown
0 32 32,651 in Table 9.
5 41 25,395
10 50 19,903 Analog Inputs — The analog inputs consist of four ther-
15 59 15,714 mistor type inputs and two 0 to 10 vdc inputs. The thermistor
20 68 12,494
25 77 10,000 inputs conform to the nominal 10K thermistor values in
30 86 8,056 Table 1.
35 95 6,530
40 104 5,325 Triac Outputs — The controllers have four 24-vac triac
45 113 4,367 outputs on the baseboard. These outputs are capable of switch-
50 122 3,601
55 131 2,985 ing 24 vac at 1 amp with a power factor of 0.8. Two triacs
60 140 2,487 control the primary output damper. One drives the damper
65 149 2,082 clockwise and the other counterclockwise. The two other triacs
70 158 1,752
are dedicated to the control of either proportional or two-
position heat.
Relay Outputs (33ZCFANTRM Only) — These re-
lays are designed to switch 24 vac as a maximum voltage at up
to 1 amp with a power factor of 0.8. The relays provide fan off/
on control and control a third stage of electric heat if used.

Table 2 — VVT Zone Controller (33ZCVVTZC-01) Inputs


CHANNEL NAME TERMINATION DESCRIPTION DEVICE
REMTCIN J4 1,2 Remote Time Clock Input 0/24 VAC
SAT J4 6,8 Supply Air Temperature 10K Thermistor
SPT J4 10,8 Space Temperature 10K Thermistor
SP_OFFST J4 4,8 Setpoint Offset Adjust Input 100K Potentiometer
PATEMP J4 5,3 Primary Air Temperature Input 10K Thermistor
J4 12 (24 vdc)
RH/IAQ J4 11 (+) RH/IAQ Sensor Input 2-10 vdc
J4 9 (–)
J5 4 (10 vdc)
DMPPOS J5 5 (W+) Damper Position Input 0-10 vdc
J5 6 (–)

Table 3 — VVT Zone Controller (33ZCVVTZC-01) Outputs


CHANNEL NAME TERMINATION DESCRIPTION DEVICE
CHAN_10 J5 1,2 Damper CCW Output 24 vac 1A
CHAN_10 J5 3,2 Damper CW Output 24 vac 1A
V_OPEN J7 1,2 Heat Open, 1st Stage Output 24 vac 1A
V_CLOSE J7 3,4 Heat Close 2nd Stage Output 24 vac 1A
HEAT_3 J7 5,6 Heat 3rd Stage Output 24 vac 1A
FAN J6 1,2 Fan Output 24 vac 1A

Table 4 — Bypass Controller (33ZCBC-01) Inputs


CHANNEL NAME J4 TERMINATION DESCRIPTION DEVICE
DUCT_TMP 10, 12 Duct Temperature 10K Thermistor
DMP_POS 9 (10v), 7(W+), 5(–) Damper Position 0-10 vdc
SP_SENSR 3, 1 System Pressure 0-5 vdc

Table 5 — Bypass Controller (33ZCBC-01) Inputs


CHANNEL NAME J5 TERMINATION DESCRIPTION DEVICE
DMPR_CCW 1 (A), 2 Damper CCW 24 vac 1A
DMPR_CW 3 (A), 2 Damper CW 24 vac 1A

12
Table 6 — VAV Zone Controller Inputs (33ZCVAVTRM)
CHANNEL
J4 TERMINATION DESCRIPTION DEVICE
NAME
SPT 14,12 (ground) Space Temperature Sensor (33ZCT55SPT), field installed and wired 10K Thermistor
SAT 10,12 (ground) Supply Air Temperature Sensor, required for heat, field installed and wired* 10K Thermistor
SP_OFFST 12 (ground), 8 Set Point Offset Adjust, requires the use of field-installed 33ZCT56SPT 100K Potentiometer
space temperature sensor
PATEMP 4, 6 (ground) Primary Air Temperature Factory option field installed and wired† 10K Thermistor
RH/IAQ** 16 (24v), 15 (+), 13 (–) RH/IAQ Sensor Factory option, field installed and wired 0-10 vdc
DMPPOS 9 (10v), 7 (W+), 5 (–) Primary Damper Position Factory Supplied and wired with zone controller 0-10 vdc
TEST Airflow Sensor
3, 1 (GND) Used to test the output of the airflow transducer.
(1-5 vdc)
Dry contact switch
REMOTE 2 (24 vac), J1 Pin 1
Remote Occupancy Contact with 24 vac supplied
(24 vac†)
by power connection
LEGEND †Primary air sensor is required whenever unit is configured as a linkage
W — Wiper of Potentiometer coordinator zone controller and a non-Carrier proprietary network air
source is used.
*Required whenever ducted heat is to be controlled. If monitoring of sup- **24 v connection (J4-16) is required for RH sensor only.
ply air is required the zone controller must be configured for heat even
if the box does not contain heat. It is also required for stand-alone
operation.

Table 7 — VAV Zone Controller Outputs (33ZCVAVTRM)


CHANNEL (10-13) J5 TERMINATIONS DESCRIPTION
DMPR_CCW 1*,2 Primary Damper CCW (factory wired)
DMPR_CW 2,3* Primary Damper CW (factory wired)†
HEAT_ST1 4, 5 (24 vac externally supplied) Heat Open, First Stage (field wired)
HEAT_ST2 6, 5 (24 vac externally supplied) Heat Close, Second Stage (field wired)
LEGEND †The zone controller comes wired and configured for clockwise closure
CCW — Counterclockwise of the primary air damper. Do not change wiring to change rotation. The
CW — Clockwise installer should configure the rotation decision with Carrier software to
ensure transducer calibration integrity.
*These terminals provide 24 vac-output power to the load.

Table 8 — VAV Fan Terminal Zone Controller Inputs (33ZCFANTRM)


CHANNEL J4 DESCRIPTION DEVICE
NAME TERMINATION
SPT 14,12 (ground) Space Temperature Sensor (33ZCT55SPT), field installed and wired 10K Thermistor
SAT 10,12 (ground) Supply Air Temperature Sensor, required for heat, field installed and wired* 10K Thermistor
Set Point Offset Adjust, requires the use of field-installed 33ZCT56SPT space 100K Potentiometer
SP_OFFST 12 (ground), 8 temperature sensor
PATEMP 4, 6 (ground) Primary Air Temperature Factory option field installed and wired† 10K Thermistor
RH/IAQ** 16 (24v), 15 (+), 13 (–) RH/IAQ Sensor Factory option, field installed and wired 0-10 vdc
DMPPOS 9 (10v), 7 (W+), 5 (–) Primary Damper Position Factory Supplied and wired with zone controller 0-10 vdc
TEST 3, 1 (GND) Airflow Sensor
Used to test the output of the airflow transducer.
(1-5 vdc)
SECFLO 9 (10v), 11 (+), 13 (–) Secondary Airflow Sensor†† 1-5 vdc

2 (24 vac), J1 Pin 1 Dry contact switch


REMOTE Remote Occupancy Contact with 24 vac supplied
(24 vac†)
by power connection
LEGEND †Primary air sensor is required whenever unit is configured as a linkage
W — Wiper of Potentiometer coordinator zone controller and non-Carrier proprietary network air
source is used.
*Required whenever ducted heat is to be controlled. If monitoring of sup- **24v connection (J4-16) is required for RH sensor only.
ply air is required the zone controller must be configured for heat even ††Option required on Constant Volume Dual Units for zone pressure
if the box does not contain heat. It is also required for stand-alone control. 33ZCSECTRM is required.
operation.

Table 9 — VAV Fan Terminal Zone Controller Outputs (33ZCFANTRM)


CHANNEL (NUMBER) J5 TERMINATION’S DESCRIPTION
DMPR_ CCW 1*, 2 Primary Damper CCW (factory wired)
DMPR_CW 2, 3* Primary Damper CW (factory wired)†
HEAT_ST1 4, 5 (24 vac externally supplied) Heat Open or Heat First Stage (field wired)
HEAT_ST2 6, 5 (24 vac externally supplied) Heat Close or Heat Second Stage (field wired)
FAN J6-1(24 vac externally supplied), J6-2 (Common, N/O) FAN Fan Start/Stop
HEAT_ST3 J7-1 (24 vac externally supplied), J7-3 (Common, N/O) Heat Third Stage
2_DMP_CCW J8-1, J8-2 Secondary Damper CCW
2_DMP_CW J8-2, J8-3 Secondary Damper CW
LEGEND *These terminals provide 24 vac-output power to the load.
CCW — Counterclockwise †The zone controller comes wired and configured for clockwise closure
CW — Clockwise of the primary air damper. Do not change wiring to change rotation. The
installer should configure the rotation decision with Carrier software to
ensure transducer calibration integrity.

13
NETWORK SYSTEM DESIGN that the linkage coordinator addresses be spaced about 30 ele-
INFORMATION ment numbers apart. This address spacing between linkage
coordinators allows about seven seconds of separation between
Design Considerations — A 3V™ system consists of linkage coordinators starting to poll their associated zones. A
a number of dampers, air terminals, an air source, and one or full system of 32 zones will take slightly less than seven sec-
more Carrier communicating network bus segments. The onds to poll. If the systems are less than 32 zones, the linkage
Carrier network bus is used by the terminals and air sources to coordinator addresses can be closer to each other as long as
exchange information. The information shared between the air enough time is given to poll devices without overlapping other
source and the air terminals is called linkage information. The linkage coordinators. The spacing of linkage coordinators
Carrier communicating network bus segments should follow 10 addresses or less apart has an undesirable effect on bus
all specifications for a Carrier network bus, except as noted utilization, although the systems will function normally. It is
within this application document. simple to determine if linkage coordinators are overlapping by
Air terminals that make up a 3V system must be connected using the Bus Diagnostics Utility that is part of Service Pack.
to the same Carrier network bus. If the entire Carrier network Bus utilization will increase at times when two or more linkage
system consists only of these terminals and their air sources, coordinators are polling and then drop off again in between.
then this bus may be the primary bus. Proper spacing of linkage coordinators can keep bus utilization
Typically there will be other devices on the network system. even. This also makes it easier to add future zones to a system
In this case, the terminals will be placed on a secondary bus. if gaps of unused addresses are left in between systems.
This secondary bus will be isolated from the primary bus by a Each controller will default to an address of 0, 140 when its
network bridge device. Isolation of the secondary bus allows application software is initially loaded. Since multiple control-
the 3V system to have complete access to the network bus lers will be on the same bus, a unique address must be assigned
without regard to bus traffic caused by other Carrier communi- to each controller before the system can operate properly. The
cating devices that are outside of the 3V system. This is impor- assignment of controller addresses will be performed through
tant since proper operation of the 3V system requires timely the System Pilot or Carrier software.
communications between the linkage coordinator and its linked OCCUPANCY SCHEDULING — Each zone controller is
dampers or terminals and the air source. Air sources (when equipped with a software clock and is capable of performing its
Linkage compatible) may be connected to either the primary or own occupancy scheduling once set up properly. If the control
secondary bus. Multiple VVT systems may occupy the same is configured to use a global occupancy schedule, a global
bus. The bus will operate at 9600, 19200, or 38400 baud. schedule in an air terminal or networked device is used to
determine occupancy status.
Network Design
In order to provide occupancy status, the software clock
COMMUNICATION LIMITATIONS needs to be initialized by a Carrier communicating device that
At 9600 Baud — The number of controllers per bus are limit- contains a hardware clock. The software timeclock will
ed to 128 zones maximum, with a limit of 8 systems (Linkage require periodic updates from a time broadcaster in a net-
Coordinators configured for at least 2 zones). There is a worked device (with hardware clock). Devices such as System
maximum of 32 zone controllers per linkage coordinator. Bus Pilot and PICs all have hardware clocks. A device with a hard-
length is required not to exceed 4000 feet with any more than ware clock must be set up as a time broadcaster. If the software
60 devices on any 1000-foot section. Repeaters are required clock has not been initialized, the zone controller will default to
every 1000 feet with a maximum of 3 repeaters per bus. the occupied mode.
At 19,200 and 38,400 Baud — The number of controllers are The zone controller supports the broadcast function. The
limited to 128 maximum. There is a maximum of 32 zone zone controller will broadcast its schedule occupancy status
controllers per linkage coordinator. Bus length is required not upon transition and every 5 minutes when configured with a
to exceed 4000 feet with any more than 60 devices on any global schedule (schedule number 65 or greater). Global sched-
1000-foot section. Repeaters are required every 1000 feet with ule enables the global schedule zone controller to provide
a maximum of 3 repeaters per bus. occupancy scheduling to all the zone controllers within a given
→ COMMUNICATION ADDRESSING — The air terminal system.
that has the linkage coordinator function enabled will be the Global schedule may be set up independent of the Linkage
highest addressed terminal within its linked group of terminals. Coordinator function. When global schedules are used, all the
All terminals within the linked group will be addressed with zone controllers and other devices that are part of that global
consecutive descending addresses starting from the linkage co- schedule will become occupied, unoccupied and participate in
ordinator. The bypass controller must be addressed one address occupancy override together. When individual schedules are
above the linkage coordinator. Each linkage coordinator will used, each zone determines its own occupied and unoccupied
utilize broadcast to transmit data to all the zones in its system, times based on its internal schedule and clock and occupancy
therefore a single zone controller per bus, which is not the link- overrides occur on an individual basis. As the linkage coordi-
age or schedule coordinator, must be designated as the broad- nator scans its associated zones, it checks the occupancy status
cast acknowledger. One broadcast acknowledger is required of each zone.
per bus. The software timeclock must be initialized after any power
Linkage coordinators are designed to synchronize the time failure, either by receiving a Time Broadcast (the controller
to poll their associated zone controllers. This synchronization will request time from the network), or by a manually updating
takes place every hour on the hour. Each linkage coordinator the time, through the controller time function.
will calculate a time to start polling its associated zones based
on its own element address. For this purpose it is recommended

105 14
Network Addressing — Use the following method zone. Only those zones with a valid temperature are be includ-
when all the zone controllers are installed and powered, and the ed in the polling process.
SPT sensors are wired and functioning properly. This method In each linked system, one zone controller should be identi-
can be used if no addresses have been set previously. The fied as the linkage coordinator. The linkage coordinator periodi-
address of an individual zone controller may be set by using cally polls the other zones in the group to acquire their tempera-
the System Pilot. This is the standard method of setting the ture, set points, occupancy information, and damper position. The
address. linkage coordinator processes this information into a composite
Each zone controller will default to an address of 0, 140 view of the system and sends this information to the air source.
when its application software is initially loaded. Since multiple These modes determine the operating and control modes of
controllers will be on the same bus, a unique address must be the zone controller. The operating mode will be used to provide
assigned to each controller before the system can operate status information about the zone controller’s operation. The
properly. The assignment of controller addresses will be control modes will be used to affect the operation of the
performed through the System Pilot, as follows: corresponding control functions (airflow, heating, and fan con-
1. The System Pilot recognizes that the Zone Controller’s trol). The current operating and control modes will be based on
address, stored in the zone controller memory, has not the following inputs: the air source mode, the temperature con-
been written yet (this will be true when the unit is first trol requirement of the zone, and the terminal type.
powered up on the job, or after a jumper-initiated reset). The air terminal operating mode will indicate the current
2. Press the override button on the SPT (terminals J4-14 and HVAC mode of operation. The modes and their meanings are
J4-12 are shorted) for 1 to 10 seconds. defined in Table 10.
3. The zone controller address changes from 0, 140 to 239, AIR TERMINAL MODES — The heating mode will deter-
239 for a period of 15 minutes. mine whether the heat function should be enabled or disabled.
4. Use System Pilot to change the address from 239, 239 to The fan control will control the fan as required for heat.
a valid system address within 15 minutes. The air source mode is used by the zones to determine their
NOTE: If the address is not changed from 239, 239 to a valid terminal operating mode and which minimum and maximum
system address within 15 minutes, the controller will revert to airflow requirements to utilize. For stand-alone units without
address 0, 140 and use of the override button will cause the linkage, the supply air temperature sensor performs this function.
address function to repeat. The operator MUST actively set the The optimal start bias time will be used by the occupancy control
address even if the final desired address is 0, 140. in each terminal to adjust the terminal’s occupied start time.
If the Linkage Coordinator zone controller is enabled, then
Zone Controller User Interfaces — The Zone Con- that zone controller will poll the indicated number of zones, in-
troller is designed to allow a service person or building owner cluding itself. With the information obtained, the linkage coor-
to configure and operate the unit through the System Pilot user dinator will calculate the system control information and send
interface. A user interface is not required for day-to-day opera- them to the air source at the indicated address. The linkage co-
tion. All maintenance, configuration, set up, and diagnostic in- ordinator computes the composite occupancy, set point, and
formation is available through the Level II communications zone temperature data.
port on the zone controller. The data port allows data access by
a System Pilot or Carrier software. Air Sources That Do Not Support Linkage —
In systems with central air sources which do not support Link-
LINKAGE age, the zone coordination function of Linkage can still be pro-
vided by the Linkage function contained within a linkage
Linkage is defined as the process that links the terminals coordinator zone controller. In these cases, the zone configured
and air source to form a coordinated HVAC system. Linkage as the Linkage Coordinator will determine the operational
allows the air source to respond to changing conditions in the mode of the air source through its bypass pressure sensor and
zones. Linkage also allows the terminals to respond properly to either a primary air temperature measurement or the bypass
changes in the air source operating mode. Linkage operation is controller duct temperature sensor. A field-supplied primary
different between a Carrier communicating device that sup- air temperature sensor (33ZCSENPAT) may be used in place
ports linkage (i.e., PIC controlled air handler or rooftop unit, of the bypass controller duct sensor if no bypass controller is
AirManager™, Universal Controller, ComfortLink™ con- installed. The modes that can be determined are either Cooling,
trolled unit, PremierLink™ controlled unit), versus that which Heating, free cooling, or Off.
does not support Linkage. The Linkage Coordinator will determine if the air source is
Air Sources Which Support Linkage — All damp- operational (the fan is on/off) by determining if bypass pressure
ers and terminals that are serviced by an air source are linked can be measured. If no pressure is read at the bypass, then the
together to form a single virtual load to the air source. As such, linkage coordinator zone controller concludes that the air
the linked system provides the following information to the air source is off. If pressure is measured, then the linkage coordi-
source equipped with a Carrier communicating control that nator concludes that the air source in on. If no bypass controller
supports linkage: is present, then the system will be considered to be always on.
• reference zone temperature Once the air source is determined to be operational, the link-
• occupied temperature of occupied and biased occupied age coordinator will attempt to determine the air source mode
reference zone serviced by the air source (heating or cooling) by measuring the supply-air temperature
• the occupied and unoccupied heating and cooling space from the air source. A primary air duct temperature sensor
temperature set points for selected zones serviced by the must be connected to the primary air temperature input of the
air source linkage coordinator zone controller. The sensor should be
• composite occupancy information placed in the supply air duct at a point where airflow is not de-
pendent on any specific terminal. If a sensor is not installed, or
To account for variations in the size of the space serviced by the sensor fails, then the linkage coordinator will default the
each zone, the space temperature and set point information pro- mode to cooling.
vided to the air source is weighted. The weighting is propor-
tional to the size of the zone and is determined by the config- If the PAT sensor is installed and operational, the linkage
ured damper size for each pressure dependent zone and maxi- coordinator determines the air source mode (Heating or Cool-
mum cooling capacity (cfm) for each pressure independent ing On/Off) based on the temperature reading.

15
Table 10 — Air Terminal Operating Modes
AIR TERMINAL
OPERATING MODE AIR TERMINAL ACTION
OFF No active control of temperature or cfm in the zone.
VENT Temperature requirement of the zone is satisfied. Minimum cooling cfm or damper position is maintained.
VENT and FAN Temperature requirement of the zone is satisfied and cfm is below fan ON limit (parallel fan only).
COOL Zone Controller is attempting to cool the zone by using supply air.
DEHUMIDIFY Zone Controller is attempting to dehumidify the zone by overriding temperature control cfm requirements.
IAQ Zone Controller is attempting to increase zone ventilation by overriding temperature control cfm requirements.
HEAT Zone Controller is attempting to heat the zone by using supply air or local heating.
WARMUP Zone Controller is attempting to heat the space during the morning warm up period.
REHEAT Zone Controller is attempting the heat the zone by locally re-heating the supply air (single duct only).
PRESSURE Zone Controller is participating in the Pressurization mode of the system.
EVACUATION Zone Controller is participating in the Evacuation mode of the system.

OFF MODE — When no pressure is determined at the bypass is no longer responding, then it will generate a network alarm
damper, then the linkage coordinator zone controller will de- message indicating the loss of communications with that
clare the primary air source’s fan OFF. The linkage coordinator terminal.
will then issue the OFF mode to all zone controllers associated If a terminal that was previously polled by a linkage coordi-
(linked) with that linkage coordinator. nator stops being polled, it will generate a network alarm mes-
If the pressure increases at least 10% above the bypass pres- sage indicating a loss of communications from the linkage co-
sure set point, then the linkage coordinator zone controller will ordinator. It will then operate in stand-alone mode (Linkage in
determine the primary air source’s fan is on. Once the Master effect = NO). A return to normal will not be issued until suc-
zone controller determines the fan is on, it then proceeds to de- cessful communication updates have been received.
termine if the equipment is operating in Heating, Cooling, or If the linkage coordinator fails to communicate with the
Free Cooling mode. configured network air source, then an air source communica-
HEAT MODE — When the fan is determined to be on, the tion alarm message will be generated. The linkage coordinator
linkage coordinator zone controller reads the primary air tem- will operate as defined for a non-Carrier air source to deter-
perature value. If the duct temperature is 5° F greater than the mine the air source operating mode.
reference zone temperature and the reference zone is greater
than 65 F, the mode is determined to be heating. If the reference OCCUPANCY (LOCAL/GLOBAL)
zone is less than 65 F, and the duct temperature is 10° F greater
than the reference zone temperature, then the mode is deter- Overview — Each zone controller has a software time-
mined to be heating. clock. The software timeclock must be initialized after any
In Heating mode, the zone controller will modulate the pri- power failure, either by receiving a Time Broadcast (the con-
mary air damper between the minimum and maximum Heating troller will request time from the network), or by a manually
damper positions. updating the time, through the controller time function.
COOL MODE — When the fan is determined to be on, the When designing a system with an air source (that has a PIC
linkage coordinator zone controller reads the primary air tem- that supports linkage), the linkage coordinator zone controller
perature value. If the temperature is less than the average occu- will determine the system scheduling if local occupancy sched-
pied zone temperature, as calculated by the linkage coordinator ules are used at each zone controller.
zone controller, minus 2 degrees F, the mode is determined to NOTE: The PIC must be configured with a similar time sched-
be cooling. ule as the linkage coordinator, so in the event of a failure the
FREE COOLING MODE — The following conditions must PIC will automatically revert back to its configured schedule.
be present for Free Cooling mode: The system occupancy function will provide to the air
• the fan is determined to be on by the linkage coordinator source a composite view of the current occupancy status of all
zone controller the zones. If any zone is occupied, the system will indicate to
• the average zone temperature value is greater than the the air source that it should be in occupied mode. If no zones
average unoccupied zone cooling temperature set point, are occupied then the system will indicate to the air source that
as determined by the linkage coordinator zone controller it should be in unoccupied mode. In addition the system will
• the current time is between 3:00 AM and 7:00 AM provide a composite view of the next occupied time, next unoc-
• the equipment is providing cooling to the system cupied time, and last unoccupied time for the zones.
If the above conditions are true, then the mode is deter- NOTE: If a single global occupancy schedule is used, it should
mined to be Free Cooling. This mode is then communicated to be configured in the linkage coordinator or air source, although
all the zone controllers associated (linked) with that linkage co- it is not required.
ordinator zone controller. Local Occupancy — Each zone controller will have its
NOTE: For pressure independent operation, any time a zone own time schedule through which its occupancy state is
controller is not receiving an update from a linkage coordinator controlled.
zone controller, that zone controller will determine the air When the control is configured to use its local occupancy
source mode based upon its supply air sensor. In this case, no schedule, and the zone controller’s software timeclock has
determination for heat, cool and on/off modes is made until been initialized, then the local schedule shall determine occu-
after the heating operation ceases. In other cases where a sup- pancy status.
ply air temperature sensor is not used, the mode will default to
cooling. The software timeclock will require periodic updates from a
time broadcaster in a networked device (with hardware clock).
Communications Alarms with Linkage — If the If the software clock has not been initialized, the zone control-
linkage coordinator detects that a previously polled air terminal ler will default to the occupied state.

16
Global Occupancy — A zone controller’s occupancy time is configured in hour and minutes in military time. See
state can be controlled through the network. This will be Table 11 for a typical example of the occupancy table.
referred to as global occupancy. Any zone can be configured Optimal Start Operation — For local occupancy, the
to broadcast a global occupancy schedule to any zone control- occupancy function will factor in the occupancy bias time sup-
ler on any bus with the same schedule number. Each Carrier plied by the linkage function. This bias time will cause the oc-
system can support up to a maximum of 35 global occupancy cupancy period to start earlier by the amount indicated by the
schedules. bias time. The occupancy function will provide information so
The schedule coordinator broadcasts its occupancy status that the rest of the zone controller functions can differentiate
upon transition and every 5 minutes, whenever it is configured between biased occupied periods and configured occupied
as a global schedule (schedule number 65 to 99). periods.
All the controllers on any Carrier communicating bus that are The Start Bias Time (in minutes) is calculated by the air
using the same global schedule need to be configured for the source as needed to bring the temperature up or down to meet
same schedule number. the set point under the optimal start routine. This value will be
sent to all associated zones for optimal start of zone controllers.
Remote Occupancy Contact — The remote occu-
pancy contact can be used to provide a room occupancy sensor
input to the zone controller. If the remote occupancy contact in- SYSTEM OVERRIDE MODES
put is in the off position the zone controller will transition to The system will react to three override modes reported by
unoccupied. If the remote contact input is in the on position the the air source compatible with linkage: pressurization, evacua-
zone controller will follow its local occupancy schedule. tion, and nighttime free cooling (NTFC).
If the zone controller is broadcasting a global schedule then Pressurization — In Pressurization mode, the system will
all the zones following its schedule will also follow its occu- bring in as much outside air as possible in order to pressurize the
pancy state based on the remote occupancy contact. area. This mode is used for smoke control and prevents smoke
Occupancy Override — The occupancy function will from entering into an area that is adjacent to an area of smoke.
support a timed override function. The timed override will be Each zone controller will modulate its damper to provide
activated through the space temperature sensor override button. maximum cooling airflow into the space. If the terminal con-
If the override is activated in a zone that is receiving a global tains a series fan, the fan will be turned on. If the terminal con-
time schedule, then the override will be reported to the device tains a parallel fan it will be turned off. If the terminal contains
issuing the global schedule. The device will then update the oc- auxiliary heat, the heating will be controlled so as to maintain
cupancy status of the zones receiving the schedule. the current heating set point. Secondary dampers in a zone
NOTE: All zones sharing a global occupancy schedule will be pressurization application will closed.
overridden to the occupied mode if any one of the space tem- Evacuation — In Evacuation mode, the system will at-
perature sensors report an override. For zones that require indi- tempt to remove smoke from an area by creating a negative
vidual overrides, those zones will have to use a local schedule. pressure. Either a return air fan in the air source, or some other
Manual Occupancy Override Function — By us- fan mechanism will be used to exhaust the smoke filled return
ing a Carrier network user interface, the user is able to com- air from the space. The terminals will respond by closing their
mand a timed override by entering the number of hours of dampers and turning off all fans. Secondary dampers in a zone
override hours (0 to 4 hours). A manual entry greater than 0 pressurization application will open.
will bring the zone controller schedule into the occupancy
mode. This function is defined as manual override. Table 11 — Occupancy Configuration Table
If the occupancy schedule is occupied when the manual
override is downloaded, the current occupancy period will be DESCRIPTION VALUE UNITS NAME
extended by the number of hours downloaded. If the current Manual Override Hours 0 hours OVRD
occupancy period is unoccupied when the occupancy override Period 1: Day of Week 11111111 DOW1
is initiated, the mode will change to occupied for the duration Period 1: Occupied from 00:00 OCC1
of the number of hours downloaded. Period 1: Occupied to 24:00 UNOCC1
If the occupancy override is due to end after the start of the Period 2: Day of Week 00000000 DOW2
next occupancy period, the mode will transition from occupan- Period 2: Occupied from 00:00 OCC2
cy override to occupied without becoming unoccupied, and the Period 2: Occupied to 24:00 UNOCC2
occupancy override timer will be reset. Period 3: Day of Week 00000000 DOW3
An active manual occupancy override or a pending occu- Period 3: Occupied from 00:00 OCC3
pancy override may be canceled by downloading a zero to this Period 3: Occupied to 24:00 UNOCC3
configuration. Once a number other than zero has been down- Period 4: Day of Week 00000000 DOW4
loaded to this configuration, any subsequent downloads of any Period 4: Occupied from 00:00 OCC4
value other than zero will be ignored by the zone controller. Period 4: Occupied to 24:00 UNOCC4
Once the override period has expired, the value is reset to 0 Period 5: Day of Week 00000000 DOW5
and the manual override function is complete. If the override is Period 5: Occupied from 00:00 OCC5
activated in a zone utilizing local occupancy scheduling, then Period 5: Occupied to 24:00 UNOCC5
only that zone is affected. The override will occur for the time
Period 6: Day of Week 00000000 DOW6
configured for that device.
Period 6: Occupied from 00:00 OCC6
Occupancy Table Format — The occupancy table is Period 6: Occupied to 24:00 UNOCC6
common to both a local and global occupancy function. For Period 7: Day of Week 00000000 DOW7
flexibility of scheduling the occupancy programming is split Period 7: Occupied from 00:00 OCC7
into eight separate periods. The configuration consists of eight
Period 7: Occupied to 24:00 UNOCC7
fields corresponding to the seven days of the week and a holi-
day field in the following order: Monday, Tuesday, Wednesday, Period 8: Day of Week 00000000 DOW8
Thursday, Friday, Saturday, Sunday, Holiday. The occupancy Period 8: Occupied from 00:00 OCC8
Period 8: Occupied to 24:00 UNOCC8

17
Nighttime Free Cooling (NTFC) — In NTFC mode, Carrier network devices as required by setting the appropriate
the system is attempting to use cool nighttime (3 AM to 7 AM) routing bits in the alarm routing configuration. No alarms will
outside air to cool down the space. In this mode, the air source be transmitted if alarm routing is set to 00000000 (default). The
will operate its fan and mixed air dampers to provide outside control implements and uses a standard alarm configuration
air to the system. The air terminals will act as if they are in the table, specifying routing, re-alarm, etc. Alarms use level 6
Occupied Cooling mode except that the temperature control set (control) for limit-exceeded alarms, and level 2 (service) for all
point will be the midpoint between the occupied cooling and other alarms. Alarm activity is stored in an Alarm History
heating set points rather than the occupied cooling set point. Table, containing the 5 most recent alarm messages.

SET POINT GROUPING Space Temperature Limit Alarm — During occupied


periods, an alarm value is used to define the allowable devia-
Each zone controller will contain a set point schedule. This tion from set points before an alarm condition is detected. This
schedule will contain temperature, humidity, and air quality set value is added to the occupied cooling set point and subtracted
points. The set point data may be unique to the zone controller from the occupied heating set point during occupied periods.
or multiple zone controllers may be grouped together to share This allows the set points to be easily changed without having
the same temperature set points. to change the alarm limits. During normal steady state opera-
The controller contains a Set Point Group Number configu- tion, whenever the space temperature deviates outside of this
ration parameter and a Set Point Group Master configuration defined range, a timer will begin. If after 5 minutes the alarm
parameter. When a zone controller is configured as Set Point condition still exists, the alarm will be generated. An alarm val-
Master, the zone controller will broadcast its set points to other ue of 1 degree F (non-adjustable) is used to determine when the
zone controllers that are configured to accept the Broadcast Set space temperature has returned to normal.
Point Schedule. If a zone controller is not configured to use During unoccupied and biased start periods, the alarm set
global set points, the zone controller will use its own onboard points are defined by two configured values (unoccupied low
set point schedule. The Set Point Master is independent of the and unoccupied high). The alarm detection and return to nor-
Master Linkage zone controller. There can be 16 Set Point mal operates as specified above for occupied conditions, ex-
Group functions per network bus. Global set points will not be cept unoccupied alarm values are used.
transmitted through bridges. To prevent false alarms during a transition from Unoccu-
pied or Biased Occupied operation to Occupied operation (or if
SPACE TEMPERATURE SHARING a set point is changed), an alarm delay is calculated each time
Each zone controller has the capability to share its local sen- the control set point changes. The value of the delay is equal to
sor and temperature offset with other zone controllers. Each 15 minutes, plus 15 minutes per degree difference between
zone controller can be configured as a broadcaster of its sensor the new heating or new cooling set point and the current space
or a receiver of another zone’s sensor information. Zone con- temperature. The alarm delay has a maximum value of
trollers sharing a common sensor must all be installed on the 255 minutes.
same Carrier communicating bus. Sharing of sensor informa- Linkage Failure (Failure to Communicate With
tion cannot be accomplished through bridges. Linkage Coordinator) — If a terminal has established
communications from a linkage coordinator, then the linkage
SENSOR GROUPING coordinator will exchange information with each of the config-
A zone controller that is set up as a Linkage linkage coordi- ured zones each minute. If a zone fails to receive updates from
nator has the ability to poll its linked controllers and collect the the linkage coordinator for 5 sequential times (greater than
high, low or average value of any variable within its linked 5 minutes without successful communications), then a Linkage
controllers. Once the high, low or average is determined, the Failure communication alarm is generated. The alarm is gener-
linkage coordinator can then transfer that value to a configured ated from the zone that indicated loss of communication with
bus number, element number and point name. Typically this Linkage Master. To determine when communications have
feature is used to determine a system’s highest indoor air quali- returned to normal, the controller will continue to monitor the
ty reading for use in a Demand Controlled Ventilation (DCV) communication status. After 5 sequential successful communi-
system. cations, then a return to normal message is generated, although
In order to utilize this feature, the Carrier network Variable normal operation will resume after the first successful
Name being collected from the linked zone controllers must be communication.
supplied. Also the data transfer rate must be specified and Linkage Failure (Failure to Communicate with
whether the high, low or average value is being calculated. Fi- Air Source) — If a zone controller has been configured as
nally, a valid point name and Carrier network address must be the linkage coordinator, and an air source address has been
entered. configured to a value other than the default, then the linkage
coordinator zone controller will exchange information with the
CALIBRATION configured air source once each minute. The air source must be
The zone controller provides a Commissioning mode that Linkage compatible.
calibrates the damper position feedback sensor and the airflow If the air source fails to respond, then the linkage coordina-
sensor. This commissioning should be performed once when tor will attempt to retry communication. If unsuccessful,
the terminal is installed. In addition, the zone controller will the linkage coordinator will log the attempt as a failure. If
perform an ongoing auto-calibration of the airflow sensor to 5 sequential failures occur (more than 5 minutes without suc-
maintain airflow measurement accuracy. Refer to installation cessful communication), then a Linkage Failure communica-
and start-up instruction for more details. tion alarm is generated for the air source. The alarm indicates a
Linkage Air Source Failure at address X, X (where X, X is the
CARRIER NETWORK ALARMS failed air source address). To determine when communications
have returned to normal, the controller will continue to monitor
The zone controller will support the detection of alarm con- the communication status. After 5 sequential successful com-
ditions and the reporting of those conditions through the munications occur, a return to normal message is generated.
Carrier network. No local indication of any alarms will be pro-
vided at the zone controller itself. Alarms will be routed to

18
Supply Air Temperature Sensor Failure — This 20%. The high Relative Humidity alarm has a configuration
alarm is generated only on pressure dependent applications range from 0% to 100% and a default of 70%. A fixed hystere-
when a SAT is present or on pressure independent applications sis of 2% is used to determine when the conditions have
where a ducted heat is configured. If the supply air temperature returned to normal. Alarms can be generated during occupied
sensor fails then a Supply Air Temperature Sensor Failure and unoccupied times.
alarm for that zone is generated. The zone controller will wait
2 minutes before generating the alarm. A return to normal (or IAQ Sensor Alarm — If the zone controller is config-
reset of the time delay) occurs immediately upon the detection ured for IAQ control and the value of the sensor exceeds the
of a normal temperature or if the ducted heat is configured IAQ High Alarm Limit or falls below the IAQ Low Alarm
to No. Limit during occupied periods, then an alarm is generated. The
alarm condition has a delay of 5 minutes before the alarm to be
Primary Air Temperature Sensor Failure — For generated.
any linkage coordinator where the air source address is NOT The alarm is generated only if the IAQ control is Enabled.
configured (default value), if the primary air temperature sen- A 2-hour delay is applied whenever the zone controller transi-
sor fails then a Primary Air Temperature Sensor Failure alarm tions to an occupied mode, in order to prevent false alarms.
is generated. The alarm is generated after a 2-minute delay. A The low IAQ alarm limit has a configuration range of 0 to
return to normal (or reset of the time delay) occurs immediately 5000 (ppm) with a default of 0. The high IAQ alarm limit has a
upon the detection of a normal temperature or if an air source configuration range of 0 to 5000 (ppm) with a default of 2000.
address is configured. For flexibility, the limits for the IAQ alarm do not include
Pressure Sensor Low Airflow Pressure Alarm units, but the IAQ sensor alarm descriptions (24-character text)
include the default units (‘PPM’) as part of the description.
(PI Only) — Any time the value of the input channel volt-
age falls below a minimum acceptable value (0.89 V), then a To determine when normal conditions have returned, the
Low Airflow Pressure alarm will be generated for that zone. zone controller will apply a 2% hysteresis to the alarm limits,
For all control types except Dual Duct or Room Pressure Con- and generate a return to normal message when the sensor re-
trol, the alarm indicates an Airflow Sensor Low Pressure turns within range (2% of the alarm limit value).
alarm. Failure to Zero Calibrate Pressure Transducer
For Dual Duct and Zone Pressure Control applications, both (PI and Bypass Controller Only) — During the zero
primary airflow and secondary airflow sensors are monitored calibration procedure, if the airflow pressure input voltage fails
for this condition. The appropriate alarm message is generated, to decrease to within the allowable zero pressure range, the
based upon the sensor failure detected. zone controller will generate a Failure to Zero Calibrate Pres-
To determine when normal conditions have returned, the sure Transducer alarm.
zone controller will continue to monitor the input. When the
voltage rises to within tolerance (above 0.91 v), a return to nor- Damper Position and Actuator Installation —
mal message is generated. During the damper calibration procedure of the Commission-
ing Mode or during the zero calibration, after the damper is
NOTE: A value of 0.89 volts is the minimum acceptable driven closed, the control will generate a Damper Actuator
0 in. wg value. Failure to Close alarm if the corresponding damper position is
Pressure Sensor High Velocity Pressure not within the specified closed position range. The acceptable
Alarm (PI Only) — Any time the calculated value of the input voltage range is above 8.5 vdc for clockwise open and
measured velocity pressure exceeds the configured maximum below 1.5 vdc for counterclockwise open. The damper position
value for more than 5 minutes, then a High Velocity Pressure sensor has a 0 to 10 vdc range.
alarm is generated for that zone. The range is 0.250 in. wg to
2.000 in. wg. The default is 1.200 in. wg. For Dual Duct and APPLICATION
Room Pressure Control applications, both primary airflow and
secondary airflow sensors are monitored for this condition. The General — The VVT® zone controller is a Carrier commu-
appropriate alarm message is generated, based upon the appro- nicating device that conforms to standard Carrier communica-
priate sensor measurement. tions protocol. The zone controller is capable of controlling
Carrier and many non-Carrier air terminal units in networked
The zone controller will continue to monitor the input, and or stand-alone applications. The zone controller includes an in-
when the pressure falls below the alarm limit minus 0.1 in. wg, tegrated modulating damper actuator.
a return to normal message is generated.
Each zone controller can operate in a stand-alone mode
Relative Humidity Sensor Alarm based on the sensors installed.
PRESSURE DEPENDENT APPLICATIONS — If the con- If the supply air sensor is not installed, the controller will as-
troller is configured for a relative humidity sensor for monitor- sume that the air source is on and that the air source’s operating
ing only, and the value is not within the range of 0 to 100% (a mode is cooling. The zone controller will operate using only its
short or open), then a sensor failure alarm will be generated. minimum and maximum cooling damper position configura-
PRESSURE INDEPENDENT APPLICATIONS — If the tion limits. If the zone controller is equipped with ducted type
controller is configured for Relative Humidity control and the heat, then when local heating is not active, the temperature read
value of the sensor exceeds the Relative Humidity High alarm from the SAT sensor will be used to determine if the air source
limit or falls below the Relative Humidity Low alarm limit dur- is heating or cooling. The appropriate minimum and maximum
ing occupied periods, then an alarm is generated. The condition cfm limits (heating or cooling) or damper position will be used
must exceed the alarm limit for 5 minutes before the zone con- based on the air source operating mode.
troller will issue the alarm. NOTE: In this mode of operation, the minimum heat and cool
The alarm will be generated only if Humidity Control is En- limits must NOT be set to zero.
abled. A delay is applied whenever the control transitions to an Finally, a primary air temperature (PAT) sensor can be con-
occupied mode or if the control set point is changed in order to nected to any stand-alone zone controller and mounted in the
prevent false alarms. The delay is similar to the Space Temper- supply air duct where it is not affected by the airflow of a spe-
ature Alarm Limit Delay. The low Relative Humidity alarm cific zone. In this case, the zone controller is configured as a
has a configurable range from 0% to 100% and a default of Linkage Coordinator zone with a system size of 1. In this con-
figuration, the zone will determine the air source operating

19
mode (OFF, COOLING, HEATING, or FREE COOLING). d. radiant/baseboard and ducted heat (pressure
Because the PAT sensor is not affected by airflow at the zone, dependent only)
minimum airflow limits may be set to 0 cfm. 3. Parallel fan terminal applications
Each zone controller supports the following set points: a. Cooling only
• occupied cooling b. Staged electric heat
• occupied heating c. Hot water/steam heat (modulating or two-position)
• unoccupied cooling d. radiant/baseboard and ducted heat (pressure
• unoccupied heating
dependent only)
NOTE: The minimum differential between the heating and
This section of the manual describes operating sequences
cooling set points is 1.0 degree F. for the zone controller in its various configurations and modes.
For pressure independent applications and the bypass con- It presents separate descriptions for single duct, series fan pow-
troller, to provide an accurate low-end airflow or pressure mea- ered, and parallel fan powered air terminals in the following
surement, the control performs an automatic zero calibration configurations: without local heat, with staged electric heat,
(ZeroCal) feature. The controller does this to account for any and with hot water or steam heat (two-position or proportion-
offset, which may be inherent in the airflow sensor. al). The system in which the zone controllers operate should
The ZeroCal procedure will be performed every time the air also contain a control with linkage coordination or an air
source mode transitions to OFF. Additionally, for systems source with either linkage compatible controls.
which operate continuously, a ZeroCal procedure will be per- Each description is accompanied by figures depicting the
formed every 72 hours. To prevent all the dampers from clos- hardware configuration and the sequence of control events for
ing simultaneously, an offset time delay based upon the zone the application being described. In the control sequence dia-
controller address is used. grams the vertical axis represents airflow and the horizontal
NOTE: When the Bypass Controller is requested to do a axis represents space temperature. The sequence of events for
ZeroCal procedure, it will cause the Linkage Coordinator to cooling operation reads from right to left, and the sequence of
send out unoccupied and satisfied zone conditions for 5 min- events for heating operation reads from left to right.
utes so the air source will shut off the fan. The zone controller employs proportional/integral/
The zone controller can be used in the following derivative (PID) control routines to provide precise, efficient,
applications: and stable control. The PID calculations take into account both
1. Single duct terminal applications the space temperature deviation from set point and the rate at
which the temperature is changing.
a. Cooling only
b. Staged electric heat Typical VVT® System Overview — The VVT sys-
c. Hot water/steam heat (modulating or two-position) tem is a control system designed to provide multiple zones of
d. radiant/baseboard and ducted heat (pressure temperature control using a single, constant volume heating
dependent only) and cooling packaged unit. Traditionally, the VVT system has
been primarily a pressure dependant system that adjusts
2. Series fan terminal applications damper position based on space temperature variation from set
a. Cooling only point.
b. Staged electric heat Typical VVT applications include medical and dental
c. Hot water/steam heat (modulating or two-position) offices, 1 to 3 story commercial buildings, and strip mall and
retail stores. See Fig. 7 and Table 12.

Table 12 — Typical VVT System Components


(Pressure Dependent Control Only)
REQUIRED COMPONENTS OPTIONAL COMPONENTS
Devices Part Number Usage Devices Part Number Usage
VVT Zone Controller 33ZCVVTZC-01 1 per pressure PremierLink™ 33CSPREMLK 1 required per system if non-
dependent zone Controller communicating air source.
Supply Air 1 required for bypass
Bypass Controller 33ZCBC-01 1 per system Temp Sensor 33ZCSENSAT Option for zones
1 per system on com bus. 33ZCT55CO2
System Pilot 33PILOT-01 CO2 Sensors as required per zone for DCV
Optional for space sensors 33ZCT56CO2
33ZCT55SPT
Relative Humidity 33ZCSENSRH-01 Optional to Monitor RH
Space Sensor 33ZCT56SPT 1 per zone
33ZCT59SPT Sensor 33ZCSENDRH-01 only (if no DCV sensor).

Primary Air Temp Sensor 33ZCSENPAT 1 per Linkage Outside Air Temp
HH79NZ039
Required with field-installed
Coordinator Sensor PremierLink control
LEGEND
DCV — Demand Controlled Ventilation
RH — Relative Humidity

20
Carrier Communicating RTU Supply Air
Sensor

(Use PremierLink Retrofit Control for non Carrier communicating RTU)

Communication Bus 120 vac


20/3/Shielded cable
(See Notes 1,2) 24vac 24vac 24vac 24vac
(See Note 2)
40va 40va 40va 40va

Duct Sensor Primary Air


(Locate upstream of damper) Sensor
24vac
(See Note 5) 40va
20/2/Shielded cable
(See Note 2)

System Pilot Bypass VVT Linkage VVT Zone VVT Zone


(See Note 6) Coordinator
(See Note 3)
Comm Bus Comm Bus
(Optional 20/3/Shielded Cable 32 zones max
for Linkage (See Note 2) including Linkage
Coordinator) Coordinator

T55/56/59 T55/56/59 T55/56/59


LEGEND CO2/T55/56
CCN — Carrier Comfort Network (Optional for DCV)
DCV — Demand Controlled Ventilation See Note 2,4)
PAT — Primary Air Temperature Sensor
RTU — Rooftop Unit
VVT — Variable Volume/Variable Temperature
NOTES:
1. 239 devices maximum per bus. Repeater required every 1000 ft or 60 devices. Maximum of 3 repeaters per bus.
2. Communication bus and sensor wiring MUST be separate from AC power wiring.
3. Up to 32 total zones per system. Maximum of 8 Linkage Coordinators with a total of 128 devices per single bus.
4. Combination CO2/T55/T56 sensor may be used in place of T55/T56/T59 on any zone requiring DCV. RTU must be capable of controlling
economizer for DCV conditions.
5. Locate PAT in supply air duct from air source unit.
6. System Pilot can share power with Bypass Controller or VVT Zone Controller.

Fig. 7 — VVT Pressure Dependent System

21
VVT® Pressure Independent System Over- calculated by the controller, based on space temperature varia-
view — Pressure Independent VVT systems are used when tion from set point. Therefore, even though the supply duct
the airflow into the zone is critical and must be maintained. static pressure changes, the airflow volume at the zone remains
With a pressure independent strategy, zone damper position constant. See Fig. 8 and Table 13.
is modulated to maintain zone airflow at a cfm flow rate

Table 13 — VVT Pressure Independent Only System Components


(Pressure Independent Control Only)
REQUIRED COMPONENTS OPTIONAL COMPONENTS
Devices Part Number Usage Devices Part Number Usage
1 for Linkage PremierLink™ 1 required per system if non-
VVT Zone Controller 33ZCVVTZC-01 Function Only Controller 33CSPREMLK communicating air source.
VAV Zone Controller 33ZCVAVTRM 1 per pressure Supply Air 33ZCSENSAT 1 required for bypass
(ComfortID) independent zone Temp Sensor Option for zones
33ZCT55CO2 as required per zone for
Bypass Controller 33ZCBC-01 1 per system CO2 Sensors
33ZCT56CO2 DCV
1 per system on
com bus. Relative Humidity 33ZCSENSRH-01 Optional to Monitor RH only
System Pilot 33PILOT-01 Optional for space Sensor 33ZCSENDRH-01 (if no DCV sensor).
sensors
33ZCT55SPT
Outside Air Temp Required with field-installed
Space Sensor 33ZCT56SPT 1 per zone Sensor HH79NZ039 PremierLink control
33ZCT59SPT
1 per Linkage
Primary Air Temp Sensor 33ZCSENPAT Coordinator
LEGEND
DCV — Demand Controlled Ventilation

Carrier Communicating RTU Supply Air


Sensor

(Use PremierLink Retrofit Control for non Carrier communicating RTU)

Communication Bus 120 vac


20/3/Shielded cable 24vac
(See Note 2) 24vac 24vac 24vac
(See Notes 1,2) 40va 40va 40va 40va

Duct Sensor Primary Air


(Locate upstream of damper) Sensor
24vac
(See Note 5) 40va
20/2/Shielded cable
(See Note 2)

System Pilot Bypass VVT Linkage ComfortID Zone ComfortID Zone


(See Note 7) Coordinator
(See Note 3,6)
Comm Bus
Comm Bus 20/3/Shielded Cable 32 zones max
(See Note 2) including Linkage
Coordinator
LEGEND
T55/56/59 T55/56/59
CCN — Carrier Comfort Network CO2/T55/56
DCV — Demand Controlled Ventilation (Optional for DCV)
PAT — Primary Air Temperature Sensor See Note 2,4)
RTU — Rooftop Unit
VVT — Variable Volume/Variable Temperature
NOTES:
1. 239 devices maximum per bus. Repeater required every 1000 ft or 60 devices. Maximum of 3 repeaters per bus.
2. Communication bus and sensor wiring MUST be separate from AC power wiring.
3. Up to 32 total zones per system. Maximum of 8 Linkage Coordinators with a total of 128 devices per single bus.
4. Combination CO2/T55/T56 sensor may be used in place of T55/T56/T59 on any zone requiring DCV. RTU must be capable of controlling
economizer for DCV conditions.
5. Locate PAT in supply air duct from air source unit.
6. VVT zone controller is required for Linkage Coordinator functions if all zones are pressure independent.
7. System Pilot can share power with Bypass Controller or VVT Zone Controller.

Fig. 8 — VVT Pressure Independent System

22
VVT® Pressure Dependent and Independent available. Simply use Carrier’s VAV Zone Controller, to pro-
System Overview — In many applications VVT Sys- vide pressure independent control for critical airflow zones.
tems require both pressure dependent and independent zone See Fig. 9 and Table 14.
control. With 3V™ control system both forms of control are

Table 14 — VVT Pressure Dependent and Independent System Components


REQUIRED COMPONENTS OPTIONAL COMPONENTS
Devices Part Number Usage Devices Part Number Usage
1 required per system if
1 per pressure PremierLink™
VVT Zone Controller 33ZCVVTZC-01 33CSPREMLK non-communicating air
dependent zone Controller
source.
VAV Zone Controller 1 per pressure 1 required for bypass
33ZCVAVTRM Supply Air Temp Sensor 33ZCSENSAT
(ComfortID) independent zone Option for zones
33ZCT55CO2 as required per zone for
Bypass Controller 33ZCBC-01 1 per system CO2 Sensors 33ZCT56CO2 DCV
1 per system on
com bus. 33ZCSENSRH-01 Optional to Monitor RH only
System Pilot 33PILOT-01 Optional for Relative Humidity Sensor 33ZCSENDRH-01 (if no DCV sensor).
space sensors
33ZCT55SPT
Required with field-installed
Space Sensor 33ZCT56SPT 1 per zone Outside Air Temp Sensor HH79NZ039
PremierLink control
33ZCT59SPT
1 per Linkage
Primary Air Temp Sensor 33ZCSENPAT Coordinator
LEGEND
DCV — Demand Controlled Ventilation

Carrier Communicating RTU Supply Air


Sensor

(Use PremierLink Retrofit Control for non Carrier communicating RTU)

Communication Bus 120 vac


20/3/Shielded cable 24vac
(See Note 2) 24vac 24vac 24vac
(See Notes 1,2) 40va 40va 40va 40va

Duct Sensor Primary Air


(Locate upstream of damper) Sensor
24vac
(See Note 5) 40va
20/2/Shielded cable
(See Note 2)

System Pilot Bypass VVT Linkage VVT Zone ComfortID Zone


(See Note 6) Coordinator
(See Note 3)
Comm Bus Comm Bus
20/3/Shielded cable 32 zones max
(Optional for Linkage (See Note 2) including Linkage
Coordinator) Coordinator

LEGEND T55/56/59 T55/56/59 T55/56/59


CCN — Carrier Comfort Network CO2/T55/56
DCV — Demand Controlled Ventilation (Optional for DCV)
PAT — Primary Air Temperature Sensor See Note 2,4)
RTU — Rooftop Unit
VVT — Variable Volume/Variable Temperature
NOTES:
1. 239 devices maximum per bus. Repeater required every 1000 ft or 60 devices. Maximum of 3 repeaters per bus.
2. Communication bus and sensor wiring MUST be separate from AC power wiring.
3. Up to 32 total zones per system. Maximum of 8 Linkage Coordinators with a total of 128 devices per single bus.
4. Combination CO2/T55/T56 sensor may be used in place of T55/T56/T59 on any zone requiring DCV. RTU must be capable of controlling
economizer for DCV conditions.
5. Locate PAT in supply air duct from air source unit.
6. System Pilot can share power with Bypass Controller or VVT Zone Controller.

Fig. 9 — VVT Pressure Dependent and Independent System

23
Fan Powered and Reheat VVT® Ssystem controller and your system is ready. New reheat flexibility
Overview — Adding supplemental heat and fan-powered offers floating-point control for hot water valves and combina-
terminals has never been simpler than with 3V™ control sys- tion 2-position baseboard with ducted staged heat. See Fig. 10
tem. Simply add a stackable option board to any VVT zone and Table 15.

Table 15 — Fan Powered and Reheat VVT Systems Components


(Pressure Dependent and Independent Control Capability)
REQUIRED COMPONENTS OPTIONAL COMPONENTS
Devices Part Number Usage Devices Part Number Usage
VVT Zone Controller 33ZCVVTZC-01 1 per pressure PremierLink™ 33CSPREMLK 1 required per system if non-
dependent zone Controller communicating air source.
1 per pressure
VAV Zone Controller 33ZCFANTRM independent zone
Supply Air
33ZCSENSAT
1 required for bypass
(ComfortID) with fan or reheat
Temp Sensor Option for zones
33ZCT55CO2
Bypass Controller 33ZCBC-01 1 per system CO2 Sensors
33ZCT56CO2
as required per zone for DCV
1 per system on com bus. Relative Humidity 33ZCSENSRH-01 Optional to Monitor RH only
System Pilot 33PILOT-01
Optional for space sensors Sensor 33ZCSENDRH-01 (if no DCV sensor).
33ZCT55SPT
Strap-on Pipe Optional if baseboard heat ONLY.
Space Sensor 33ZCT56SPT 1 per zone Temp Sensor 33ZCSENCHG (Not required with zone ducted heat)
33ZCT59SPT
1 per Linkage Outside Air Required with field-installed
Primary Air Temp Sensor 33ZCSENPAT HH79NZ039
Coordinator Temp Sensor PremierLink control
1 required per
Fan/Reheat Option Board 33ZCOPTBRD-01 VVT Zone
with Reheat
LEGEND
DCV — Demand Controlled Ventilation
PD — Pressure Dependent
RH — Relative Humidity

Carrier Communicating RTU


Supply Air
Sensor

(Use PremierLink Retrofit Control for non Carrier communicating RTU)

Communication Bus 120 vac


20/3/Shielded cable
(See Notes 1,2) 24vac 24vac 24vac 24vac
(See Note 2)
40va 40va 40va 40va
Primary Air Supply Air
Supply Air Sensor Sensor
Duct Sensor
Sensor
(Locate upstream of damper)
(See Note 6) 24vac
(See Note 5)
40va
20/2/Shielded cable
(See Note 2) H

C Pipe Sensor
12

Opt Opt Opt


Brd Brd Brd

System Pilot Bypass VVT Linkage VVT Zone w/2 ComfortID Zone
Coordinator w/ Position HW w/Series FP and
(See Note 8) Modulating HW Baseboard Heat 2 Stage Electric Heat
(See Note 3,7) (See Note 7) (See Note 7)

Comm Bus Comm Bus 32 zones max


(Optional 20/3/Shielded Cable
for Linkage (See Note 2) including Linkage
LEGEND Coordinator) Coordinator
CCN — Carrier Comfort Network
DCV — Demand Controlled Ventilation T55/56/59 T55/56/59 T55/56/59
PAT — Primary Air Temperature Sensor CO2/T55/56
RTU — Rooftop Unit (Optional for DCV)
VVT — Variable Volume/Variable Temperature See Note 2,4)

NOTES:
1. 239 devices maximum per bus. Repeater required every 1000 ft or 60 devices. Maximum of 3 repeaters per bus.
2. Communication bus and sensor wiring MUST be separate from AC power wiring.
3. Up to 32 total zones per system. Maximum of 8 Linkage Coordinators with a total of 128 devices per single bus.
4. Combination CO2/T55/T56 sensor may be used in place of T55/T56/T59 on any zone requiring DCV. RTU must be capable of controlling
economizer for DCV conditions.
5. Locate PAT in supply air duct from air source unit.
6. Locate downstream of ducted reheat.
7. Option Board required for all VVT zones with heat and/or fan powered mixing box.
8. System Pilot can share power with Bypass Controller or VVT Zone Controller.

Fig. 10 — VVT Pressure Dependent/Pressure Independent with Fan Powered Zones and/or Reheat System

24
Compatibility of Carrier Systems which may remain in place. The existing 5-wire control wiring
3V™ AND GEN-III VVT® PRODUCT COMPATIBIL- from the thermostat to the damper may be used for the System
ITY — Refer to Table 16 for the compatibility of Carrier’s 3V Pilot communication wire or for a T55, T56, or T59 space sen-
control system and GEN-III VVT products. sor. The wiring must be 18 to 20 AWG (American Wire Gage)
stranded, shielded cable and conform to 3V control system and
VVT GEN II CONVERSION (Manufactured prior to July Carrier communicating network wiring guidelines. Any wiring
1995) — There is no compatibility between VVT Gen II sys- that does not conform to these guidelines must be replaced.
tems and 3V control systems. A complete change of system
components is required with the exception of physical dampers

Table 16 — 3V and GEN-III VVT Product Compatibility


COMPATIBLE FOR USE
GEN III PRODUCT DESCRIPTION
WITH 3V CONTROL SYSTEM
TEMP SYSTEMS
Working Gen-III TEMP systems may reside on same bus with a 3V control system. If an existing Gen-III TEMP system needs component replacement,
refer to the components below.
33CSTM(T)-01 TEMP Monitor No. Replace with PremierLink™ control
33CSUCE-06 TEMP System Relay Pack No. Replace with PremierLink control
VVT GEN-III SYSTEM COMPONENTS
Working Gen-III VVT systems may reside on same bus with a 3V control system. If an existing Gen-III system needs component replacement,
refer to the components below.
33CSVM(T)-32 VVT Monitor Thermostats Yes for a 3V Zone(s)*
33CSBC-00 Bypass Controllers Yes. †
33CSZC-01 Pressure Dependent Zone Controller No. Use 33ZCVVTZC-01.**
33CSZC-PI Pressure Independent Zone Controller No. Use 33ZCVAVTRM-01.††
DAMPERS
33CSDCDR Round or Rectangular Yes – sheet metal only
33CASDCARPL, M08 Damper Actuators No
33CSDCA060,090 High Torque Damper Actuators No
RELAY PACKS
33CSZRP-06 Universal Damper Relay Pack No
33CSUCE-06 Monitor-only Relay Pack No
SENSORS
920238 (HS) Humidity Sensor No, 3V system uses 2 to 10 vdc humidity sensor.
920247 (RAS) Refrigerated Air (DX) Sensor No. 3V system uses standard 10K sensors.
920076 (RDS) Remote Duct Sensor No. 3V system uses standard 10K sensors.
920077 (RDS) Remote Room Sensor No. 3V system uses standard 10K sensors.
920089 (OAS) Outside Air Sensor No. 3V system uses standard 10K sensors.
Pressure Sensor No, 3V static pressure sensor is integrated into Bypass
33CSPS-01 Controller. For PI zones, velocity pressure sensor is
integrated into the VAV (ComfortID™) controller.
Pressure Sensor No, 3V static pressure sensor is integrated into Bypass
33CSPS-02 Controller. For PI zones, velocity pressure sensor is
integrated into the VAV (ComfortID) controller.
33ZCSENCO2 CO2 Sensor Yes
EXISTING WIRING
Non-Shielded device, bus or sensor wiring No
Shielded device, bus or sensor wiring Yes
24 VAC power wiring Yes
LEGEND available, 3V bypass controller may be substituted with compatible
DX — Direct Expansion sensors. Existing damper may be re-used, but with new 3V actuator.
PI — Pressure Independent **A Gen-III Pressure Dependent Zone Controller is not compatible in 3V
VVT — Variable Volume/Variable Temperature system. However, a 3V zone controller is compatible in a Gen-III sys-
tem. If the Gen-III Zone Controller needs replacement and compo-
*A Gen-III VVT Monitor will scan new 3V zones. No special configura- nents are not available, 3V zone controller may be substituted with
tion is required. Address 3V zone within the Gen-III Monitor’s scan- compatible sensors. Existing damper may be re-used, but with new
ning range. If the Gen-III VVT monitor needs replacement and 3V actuator.
components are not available, 3V zone controller(s) may be substi- ††A Gen-III Pressure Independent Zone Controller is not compatible with
tuted for all zones with compatible sensors. Existing damper may be 3V systems. If the Gen-III PI Zone Controller needs replacement and
re-used, but with new 3V actuator(s). components are not available, ComfortID controller may be substi-
†An Integrated Gen-III Bypass Controller and damper may remain in tuted when configured for Standalone only out of Gen-III Monitors
3V system, but must be re-addressed out of the 3V system’s scanning scanning range, and with compatible sensors. Existing damper may
range, and must be configured for Standalone operation. If the Gen-III be re-used, but with new ComfortID actuator.
Bypass Controller needs replacement and components are not

25
General Heating Information — Heating may be This will prevent more cool air from entering into the space
one of two types, ducted or non-ducted. In a ducted heat type when heating is actually required.
system, the heating mechanism is located within the air termi- The HEAT ENABLED variable is located in the display ta-
nal, upstream of the supply air temperature (SAT) sensor. The ble for each zone controller and can be forced from the Carrier
heating device may be either a hot water/steam heating coil or network. Normally when the zone controller is in heating, this
up to three stages of electric heat. Use of a air terminal heating variable will indicate ENABLE. To disable heating when the
coil will require that the zone controller be wired to a supply air central heat source is off, this variable must be forced to DIS-
temperature sensor. The SAT sensor will measure the supply ABLE. This force should occur at least once an hour and sent
air temperature into the zone. The SAT sensor will provide to all zone controllers that are supplied heat from the central
feedback to the auxiliary PID heating control loop and ensures source. This application will require the use of a Comfort Con-
that the supply air temperature does not exceed the configured troller or data transfer module to accomplish this function.
maximum temperature.
NOTE: For pressure dependent applications, the option board Non-Ducted Heat Control (Single or Staged
is required for heat. Heat) — Any zone controller can support the non-ducted
heat function. The non-ducted heat function can be configured
There are five types of heat a zone controller can be config- for either single duct units, fan powered parallel, or fan pow-
ured for use with: ered series applications. Non-ducted heat can also be used with
• modulating hot water/steam valve (VAV) (pressure inde- constant volume dual duct applications where auxiliary perim-
pendent applications only) eter heat is provided. Heat needs to be controlled within the
• modulating hot water/steam valve (CV [constant zone that is controlled by the terminal unit. Non-ducted heat
volume]) can be applied to zone controller units configured as Dual Duct
• two-position hot water/steam valve Units which have additional perimeter heating.
• electric heat (1 to 3 stages) In a non-ducted heat application, the heating controlled de-
• radiant/baseboard and ducted heat (pressure dependent vice is located within the space. The heating device is typically
applications only) either a two position (On-Off) device like a hot water valve or
If a Heating Type is configured, but Ducted Heating is NOT electric baseboard heater. For this application, no heating con-
selected, the heating control algorithm will not utilize an SAT trol loop feedback is required. The installation of the supply air
sensor. A two-position heating valve or single-stage electric sensor is not required when the unit is configured for non-
heat are most common, although the zone controller can oper- ducted heat.
ate up to 3 non-ducted electric heat stages. The zone controller Additionally, the zone controller can control a single stage,
will maintain the space temperature at the heating set point. two-position, or multistage electric supplemental heat devices.
The zone controller will wait for the Heat On Delay to expire The zone controller will only use space temperature as feed-
before energizing any heating device. back into the temperature control loop to maintain the heating
For non-ducted, modulating hot water baseboard applica- set point in these applications.
tions, the zone controller requires a 10K ohm leaving water When the 33ZCVVTZC-01, 33ZCVAVTRM, or
sensor which is attached to the baseboard heater and wired to 33ZCFANTRM zone controllers are applied and configured
the SAT sensor input. This device is field supplied. It is strong- for heat, and heating is being called for in the space, the zone
ly recommended that the valve and sensor be installed on the controller reads the space sensor and the output is adjusted to
leaving water side of the hydronic heater. satisfy conditions. The number of stages (if applicable) is
NOTE: A 33ZCENSCHG changeover sensor can be used as a determined by comparing space temperature with the current
leaving water sensor. biased heating set point.
If the zone controller is configured as a parallel fan type ter- Configuration determines the logic output type for normally
minal, the zone controller will utilize the fan as the first stage of open or normally closed type two-position valves. Hysteresis is
heat, regardless of the heat type configured. The amount of determined by the Heating Proportional Gain configured.
time the fan will operate as the first heat stage is determined by A terminal unit equipped with heating will provide the min-
the value configured for the Heat On Delay (10 to 20 minutes imum heating cfm configured for the zone whenever the air
recommended). source is in heat mode unless VAV central heating is enabled.
The Heat On Delay is used to prevent mechanical heating The heating control maintains the current heating set point
from being operated for a configured period of time. For single (plus any offset from a 33ZCT56SPT sensor slide bar during
duct type terminals, a delay of 2 minutes (default value) allows occupied periods).
the zone controller to increase the airflow to the desired reheat
cfm or desired reheat damper position before operating heat. Modulating Baseboard Heating — The zone con-
For parallel fan type terminals, the default value is typically in- troller can provide control of modulating hot water (hydronic)
creased to 15 minutes to allow the fan to utilize heat from the baseboard heating which provides perimeter heating for a zone.
ceiling plenum, before any additional mechanical heating is The zone controller can be used with single duct, fan powered,
energized. or dual duct terminals using perimeter hydronic heating. A
field-supplied modulating (floating point type) water valve is
Disabling Reheat From Carrier Communicat- used to control the flow of water through the baseboard hy-
ing Network — The zone controller provides a means to dronic heating coil. A field-supplied accessory temperature
disable the reheat function from the Carrier network. This is sensor (33ZCSENCHG) attached to the leaving water side of
used to prevent zones that use a central heat source from using the hydronic baseboard heating coil is required to properly
local heat. When the central heating source is not producing hot modulate the hot water valve.
water or steam heat to the terminals (the boiler is disabled for
example), a system mode broadcast can prevent these terminals NOTE: It is strongly recommended to mount both the temper-
from entering reheat mode. By preventing reheat, the zone con- ature sensor and the modulating water valve to the leaving side
troller will control to the minimum cooling cfm or damper of the hydronic heater. This will minimize installation time and
position rather than the higher reheat cfm or damper position. improve valve life.

26
Ducted Heat Control (Staged or Modulating For pressure dependent applications, the minimum and
Device) — The zone controller can support a ducted heat maximum damper positions are used to maintain the space
function. The ducted heat function can be configured for either temperature during central heating.
single duct units, fan powered parallel, or fan powered series
applications where heat needs to be controlled within the zone
that is supplied by the terminal unit.
When using central heating, it is the system designer’s
For this application, heating control loop feedback is re- responsibility that the central apparatus is protected during
quired. The installation of the supply air sensor is required heating to provide proper airflow over the central heating
when the unit is configured for ducted heat. device. Ensure that there will be a minimum system air-
The zone controller can control a single stage, two-position, flow that will allow the air source to operate safely in the
multistage electric heat, or a modulating hot water valve. heating mode. The zone controller (pressure independent
When the 33ZCVVTZC-01, 33ZCVAVTRM, or only) will allow for the option of disabling the central heat-
33ZCFANTRM zone controllers are applied and configured ing function in a given zone. This means that a central air
for heat, and heating is being called for in the space, the zone source may provide heating for the entire system, or possi-
controller reads the space sensor and the output is adjusted to bly only provide it for those terminals without heat at the
satisfy conditions. The number of stages (if applicable) is zone level.
determined by comparing space temperature with the current
biased heating set point. In a system with a Linkage compatible air source, the
Configuration determines the logic output type for normally zone controller will notify the corresponding linkage coordina-
open or normally closed type two-position valves. tor zone controller that the unit is Heat mode.
A terminal unit equipped with heating will provide the min- In the case of a non-Linkage compatible air source, the zone
imum heating cfm configured for the zone whenever the air controller should be set up as the linkage coordinator for
source is in heat mode unless VAV central heating is enabled. that air source. The zone controller will determine if the
The heating control maintains the current heating set point primary-air temperature is greater than the weighted average
(plus any offset from a 33ZCT56SPT sensor slide bar during space temperature, and if higher, then declares the central air
occupied periods). source in heating.

Modulating Hot Water/Steam Valve CV — The VAV Central Heating with Ducted Zone Heat
Modulating Hot Water/Steam Valve CV mode is designed to (PI Only) — When heating is available at the zone (ducted),
use modulating heat valve with a constant volume airflow. This and central heating is also available, the zone heat will work in
mode of operation allows all cfm set points to be set to the parallel to provide heating to the space. This heating function
same cfm value. The zone reheat will temper the supply air to provides the required volume of heated air from the central
maintain proper zone temperature at the configured constant apparatus. This volume is determined by a PID airflow control,
volume of air. the space temperature, and the desired set point. In addition, the
temperature of the air can be supplemented by the local heat
Central Heating — The use of the zone controller in a source, if the current air temperature cannot meet zone require-
system allows for the application of heating utilizing the heat ments. Each zone controller configured for heat (ducted or non
from a central air source. The zone controller provides the abil- ducted) will operate its heating control loop when ever the
ity to add heat to a system during the occupied mode from a space temperature is below the heating set point to determine a
central source. Terminal units designed without any local heat desired supply air discharge temperature that is necessary to
(ducted or non ducted), should utilize heating. During heating, maintain space temperature at the heating set point.
the zone controller modulates its primary air damper to provide NOTE: Central heat with ducted zone heat requires a supply
heat when the air source is in Heat Mode. The airflow is con- air sensor.
trolled so that the zone achieves and maintains the desired heat-
ing set point. Damper Override — Damper Override mode is initiat-
NOTE: Central heating is always set to YES on VVT® zone ed by the air source in response to input from a field-supplied
controllers. No central heating configuration is available if it is smoke control panel. When the air source enters an override
changed to NO. mode the linkage coordinator signals the zone controllers to
take corresponding action. The override can take either of two
In central heating, the terminal provides a variable volume forms: pressurization or evacuation. In Pressurization mode,
into the zone. The central supply air will be a source of heating the zone controller commands the air terminal’s supply air
when the air source is in the heating mode. damper to maximum cool cfm. In Evacuation mode, it com-
For pressure independent applications, the zone controller mands the damper completely closed.
temperature control loop determines the airflow set point that is Damper Override supersedes the cfm setting the zone con-
required to maintain space temperature at the heating set point. troller would otherwise maintain based on space temperature.
Each zone controller modulates between the minimum heating The smoke control panel that commands the override mode
cfm and the maximum heating cfm during central heating. This must be in accordance with local codes, as must its installation.
cfm should be limited to a configured range of values that al-
lows the air source to operate properly in the heating mode.

27
Nighttime Free Cooling — Nighttime Free Cooling maximum cooling airflow limits or damper position. A temper-
(NTFC) is an air source cooling function that can be employed ature control loop that maintains space temperature determines
during unoccupied periods when conditions permit. If outside the airflow set point. As the space temperature falls below the
air is acceptable, based on temperature and enthalpy, during cooling set point, the PID loop will reduce the airflow. When
unoccupied early morning hours, the air handler will deliver the space temperature drops and remains below the cooling set
the cool outside air to the air terminals. When the air source in- point, the zone controller will hold the airflow at minimum
dicates that NTFC is operating, the zone controller at each air cooling limit.
terminal controls to midway between the occupied heating and In its standard operating mode the zone controller follows
occupied cooling set points, rather than to the higher unoccu- the same control sequence for cooling during both occupied and
pied cooling set point that would otherwise be in effect at that unoccupied periods. The zone controller’s Occupancy schedule
time. determines which set point the zone controller will use.
For series fan terminal applications, the zone controller HEATING — There are two ways to use local heat. Reheat
turns on the air terminal’s fan during NTFC operation. operates when the zone controller’s zone requires heat and the
NOTE: This feature is only available to Carrier communicat- air source is supplying cool air to satisfy cooling demand in
ing systems where fully compatible linkage air source controls other zones. Heat is also used to supplement air source heating
are used. while the air source is supplying heated air, but the temperature
is inadequate to maintain the desired set point.
Single Duct Terminal Applications — When ap-
plying the 33ZCVVTZC-01 or 33ZCVAVTRM zone control- When the space temperature is below the Heating set point
ler, ducted heat can only be used when the air source is on, and the air source is in the Heat mode, the zone controller modu-
since the air source is providing the only means of airflow into lates the air terminals damper to supply airflow between mini-
the zone. mum and maximum heating cfm (if configured for VAV central
heating) or damper position (for pressure dependent applica-
tions), otherwise the minimum heating airflow is maintained.
During VAV heating, space temperature PID loop determines the
The minimum airflow required by the heat at each terminal airflow set point. As the space temperature goes above the heat-
must be configured properly to protect and ensure proper ing set point, the PID loop will start reducing the airflow. When
heat transfer for the heating coil. If the minimum cooling the space temperature remains above the heat set point, the zone
cfm limit or damper position is below the terminal’s rec- controller will hold the airflow at minimum heating cfm.
ommended minimum value, use the reheat cfm limit for Reheat — When the zone controller is applied to a Single Duct
this configuration. The minimum heat cfm limit or damper terminal unit and configured for heat, and heating is being
position should also be set to this value. called for in the space, the zone controller reads the space sen-
sor and compares the temperature to the current heating set
All zone controllers types can support the Reheat function point. The zone controller then calculates the required supply-
for single duct terminals. air temperature (submaster reference temperature) to satisfy
With a single duct terminal application, if the central air conditions. The calculated value is compared to the actual tem-
source is on and in cooling mode and the terminal is equipped perature supply air and the output is adjusted to satisfy condi-
with heat, then the heat will be used to reheat the supply air to tions. The reference temperature is determined by comparing
prevent over cooling of the space. Reheat will occur when the space temperature with the current biased heating set point.
space temperature drops below the heating set point. The zone A Proportional/Integral/Derivative (PID) loop is used
controller will enable the heating control algorithm. At this whenever the mode is heating (occupied, unoccupied, or
point the zone controller will provide primary airflow equiva- warm-up).
lent to the larger of either the minimum cooling damper posi- The heating PID loop maintains the current heating set point
tion or cfm requirement (to satisfy the minimum air flow for (configured value plus any offset from a 33ZCT56SPT sensor
the air source) or the reheat damper position or cfm require- slide bar).
ment (to provide minimum airflow for the heating coil).
In a single duct terminal unit equipped with heating, the ter-
COOLING — The primary control function of zone controller minal will provide sufficient airflow for heating (greater of
is to provide cooling to the space by modulating the amount of cooling minimum or reheat values or damper positions) to the
supply airflow through its primary damper. zone whenever heating is required, as determined by the space
The Zone Controller uses pressure independent or pressure temperature sensor and the set point, if the equipment is sup-
dependent operation to control the amount of cool air entering plying cool air. The reheat damper position or cfm is used to
the space. The control variable is terminal airflow (cfm) for ensure that proper airflow across the heater is maintained, if the
pressure independent applications or damper position for pres- minimum cooling airflow is too low for safe heating operation.
sure dependent applications. A PID temperature control loop NOTE: In a system, when the central air source fan is operat-
determines the airflow set point needed to maintain space tem- ing (detected by the linkage coordinator zone controller)
perature at the cooling set point. ducted heat will be available to operate.
The airflow set point is limited to a configured range of val- The zone controller performs reheat when the space temper-
ues that allow the air source to operate properly in the cooling ature in its zone is below the heating set point and the air source
mode. These configured limits are listed in the Installation In- is delivering cooled air.
structions for the zone controller. The minimum limit ensures
that the sum of all air terminal minimum requirements fall During this process, the zone controller also uses the tem-
within the minimum cooling operating range of the air source. perature deviation from the heating set point in a PID calcula-
The maximum limit ensures that airflow will not increase tion to determine a supply-air temperature which will satisfy
above the maximum design value and that the noise level gen- the heat demand in the space.
erated at this maximum airflow will be acceptable to the occu- COOLING ONLY — Figure 11 shows the hardware configu-
pants of the zone. ration for a zone controller applied to a single duct air terminal
The sequence of operation is as follows: when the space that is not equipped with heat. The diagram in Fig. 12 shows
temperature is above the cooling set point and the air source is how the zone controller controls this type of air terminal.
in the cooling mode, the zone controller modulates the air The terminal provides cooling by modulating its primary air
terminal’s damper to supply airflow between minimum and damper.

28
A single duct air terminal without local heat can only per- baseboard and second and third stages ducted heat). The heat
form heating functions while its air source is delivering heated source can be installed in the air terminal (ducted), or as perim-
air. The control sequence for heating is similar to that for cool- eter heat. Figure 13 shows the hardware configuration for a
ing. When the space temperature is below the Heating set zone controller applied to a single duct air terminal equipped
point, the air source is in the Heat mode, and VAV heating is with ducted staged electric heat. The diagram in Fig. 14 shows
enabled (pressure independent only), the zone controller modu- how the zone controller controls this type of air terminal.
lates the air terminal’s damper to provide supply airflow be- The figures depict the electric heat source installed in the air
tween minimum and maximum heating set points. A tempera- terminal. When the zone controller is used to control perimeter
ture PID loop that maintains space temperature determines the heat it follows the same control routines that it uses for terminal
damper position or airflow set point. As the space temperature heat. Heat is used in two ways. Heat operates when the zone
goes above the heating set point, the PID loop will start to re- controller’s zone requires heating and the air source is supplying
duce the airflow. For pressure dependent applications, heating cool air to satisfy cooling demand in other zones (reheat). Heat
is always enabled. can also be energized to supplement air source heating while the
As with cooling operation, the standard heating mode is the air source is supplying heated air.
same for occupied and unoccupied periods, differing only in Staged (electric) heating (1 or 2 stages) is provided by the
the set point that the zone controller uses. 33ZCVAVTRM zone controller. Staged (electric) heating
Damper Override supersedes the cfm setting the zone con- (3 stages) is provided by the 33ZCFANTRM zone controller.
troller would otherwise maintain based on space temperature. Three stages of heat with the 33ZCVVTZC-01 zone controller
The smoke control panel that commands the override mode is provided by the zone controller and the option board
must be in accordance with local codes. (33ZCOPTBRD-01). The staging function compares the sub-
STAGED ELECTRIC HEAT AND COMBINATION master reference with the supply-air temperature to calculate
HEAT — The zone controller can be configured to control up the required number of outputs to energize.
to three stages of electric heat. The zone controller can also The percent output capacity for electric staged heat control
be configured to control up to three stages of heat (first stage is calculated and displayed.

SUPPLY LEAVING
SUPPLY AIR
AIR AIR
DAMPER
AIRFLOW
SENSOR DAMPER
ACTUATOR

ZONE
CONTROLLER
24 VAC
SPACE
TEMPERATURE
SENSOR
NETWORK BUS

Fig. 11 — Single Duct Air Terminal — Cooling-Only

% AIRFLOW

100%
MAX COOL LIMIT
(DAMPER OVERRIDE
PRESSURIZATION FULL COOLING
MODE)
MAX HEAT LIMIT
FULL HEATING

VENT POSITION

MIN HEAT LIMIT

MIN COOL LIMIT


DEADBAND

0% < >
DAMPER OCCUPIED NTFC OCCUPIED WARM
COOL OVERRIDE- HEATING & SETPOINT COOLING
EVACUATION MORNING
MODE WARM-UP SPACE TEMPERATURE (DEGREES)
SETPOINT

LEGEND NOTE: Ventilation mode occurs when air source mode is in cooling and
NTFC — Nighttime Free Cooling air source supply air temperature is above 65 F and below 75 F.
Air Source Supplying Heated Air
Air Source Supplying Cooled Air
. . . . . . Ventilation Mode
Fig. 12 — Sequence of Operation for Single Duct Air Terminal — Cooling-Only

29
ELEC HEAT
PLENUM
AIR

SUPPLY LEAVING
SUPPLY AIR
AIR AIR
DAMPER
AIRFLOW LEAVING AIR
SENSOR DAMPER TEMPERATURE
ACTUATOR STAGES
SENSOR
1 2 3
RELAY

ZONE
CONTROLLER
24 VAC
SPACE
TEMPERATURE
SENSOR
NETWORK BUS

*Stage 1 is radial or baseboard heat with combination heat.


NOTE: For 1 or 2 stage heat — use 33ZCVAVTRM. For 3-stage heat — use 33ZCFANTRM.
Fig. 13 — Single Duct Air Terminal with Staged Electric Heat

% AIRFLOW

100%
MAX COOL LIMIT
(DAMPER OVERRIDE
PRESSURIZATION FULL COOLING
MODE)
MAX HEAT LIMIT
FULL HEATING
VENT POSITION
321
REHEAT LIMIT
ELECTRIC
MIN HEAT LIMIT HEAT
STAGES
MIN COOL LIMIT
DEADBAND

0% < >
DAMPER OCCUPIED NTFC OCCUPIED WARM
COOL OVERRIDE- HEATING & SETPOINT COOLING
EVACUATION MORNING
MODE WARM-UP SPACE TEMPERATURE (DEGREES)
SETPOINT

LEGEND NOTE: Ventilation mode occurs when air source mode is in cooling and
NTFC — Nighttime Free Cooling air source supply air temperature is above 65 F and below 75 F.
Air Source Supplying Heated Air and Zone Controller
is Configured for Central Heating Only
Air Source Supplying Cooled Air
. . . . . . Ventilation Mode
*Stage 1 is radial or baseboard heat with combination heat.
Fig. 14 — Sequence of Operation for Single Duct Air Terminal with
Staged Electric or Combination Heat

30
HOT WATER OR STEAM HEAT — The zone controller will be left at the current position until the error gets larger than
can be configured to control local heat provided by heating the deadband.
coils carrying hot water or steam, governed either by a two- For modulating type heat, the floating point function com-
position (on/off) valve or by a proportional (floating modulat- pares the submaster reference from the PID loop to the supply
ing) valve. The heating coils can be installed in the air terminal air temperature to calculate the direction and time to position
(ducted), or as perimeter heat. Figure 15 shows the hardware the valve. The control prevents both outputs from operating si-
configuration for a zone controller applied to a single duct air multaneously.
terminal equipped with ducted hot water or steam heating coils.
The diagram in Fig. 16 shows how the zone controller controls Configuration determines the logic output type for normally
an air terminal equipped with two-position hot water or steam open or normally closed type two-position valves. Hysteresis is
heat. The diagram in Fig. 17 shows how the zone controller determined by the Heating Proportional Gain configured.
controls an air terminal equipped with proportional hot water Heating with IAQ Control — A feature is provided for situa-
or steam heat. tions in which additional primary air is required for ventilation
The figures depict the heating coils installed in the air termi- (IAQ).
nal. When the zone controller is used to control perimeter heat The heating set point is calculated as the midpoint between
it follows the same control routines that it uses for terminal the current heating and cooling set points.
heat. Modulating perimeter heating must be hot water, but two- The standard heating algorithm is used except the control
position may either be hot water or steam heat. set point is raised. The algorithm prevents the space tempera-
For modulating control, the supply air needed is compared ture from falling below the set point before heating is activated.
to the actual supply air to either drive the valve open or closed. The air terminal must be in the cooling mode and the equip-
There is a deadband on the supply air deviation where the valve ment must be providing cooling.

HEAT COIL

SUPPLY LEAVING
SUPPLY AIR
AIR AIR
DAMPER
AIRFLOW LEAVING AIR
SENSOR DAMPER HEAT TEMPERATURE
ACTUATOR VALVE SENSOR

ZONE
CONTROLLER
24 VAC
SPACE
TEMPERATURE
SENSOR
NETWORK BUS

Fig. 15 — Single Duct Air Terminal with Hot Water or Steam Heat

% AIRFLOW

100%
MAX COOL LIMIT
(DAMPER OVERRIDE TWO-POSITION
PRESSURIZATION HOT WATER HEAT FULL COOLING
MODE)
MAX HEAT LIMIT
FULL HEATING
ON OFF
VENT POSITION
REHEAT LIMIT

MIN HEAT LIMIT

MIN COOL LIMIT


DEADBAND

0% < >
DAMPER OCCUPIED NTFC OCCUPIED WARM
COOL OVERRIDE- HEATING & SETPOINT COOLING
EVACUATION MORNING
MODE WARM-UP SPACE TEMPERATURE (DEGREES)
SETPOINT

LEGEND NOTE: Ventilation mode occurs when air source mode is in cooling and
NTFC — Nighttime Free Cooling air source supply air temperature is above 65 F and below 75 F.
Air Source Supplying Heated Air
Air Source Supplying Cooled Air
. . . . . . Ventilation Mode
Fig. 16 — Sequence of Operation for Single Duct Air Terminal with
Two-Position Hot Water or Steam Heat

31
% AIRFLOW

100%
MAX COOL LIMIT
(DAMPER OVERRIDE
PRESSURIZATION FULL COOLING
MODE)
MAX HEAT LIMIT
FULL HEATING
VENT POSITION

REHEAT LIMIT OPEN CLOSED

MIN HEAT LIMIT PROPORTIONAL


HOT WATER HEAT
MIN COOL LIMIT
DEADBAND

0% < >
DAMPER OCCUPIED NTFC OCCUPIED WARM
COOL OVERRIDE- HEATING & SETPOINT COOLING
EVACUATION MORNING
MODE WARM-UP SPACE TEMPERATURE (DEGREES)
SETPOINT

LEGEND NOTE: Ventilation mode occurs when air source mode is in cooling and
NTFC — Nighttime Free Cooling air source supply air temperature is above 65 F and below 75 F.
Air Source Supplying Heated Air
Air Source Supplying Cooled Air
. . . . . . Ventilation Mode
Fig. 17 — Sequence of Operation for Single Duct Air Terminal with
Proportional Hot Water or Steam Heat

therefore, must be running in order to achieve proper airflow.


33ZCVVTZC-01 VVT® Zone Controller and The series fan terminal allows for a variable temperature, con-
33ZCFANTRM VAV Zone Controller Informa- stant volume airflow. Maintaining constant volume airflow is
tion — The zone controller will control the operation of the not a function of the zone controller. The fan itself will main-
fan (start and stop), whenever the zone controller is configured tain a constant airflow. Therefore, as the primary airflow is
for use with a series or parallel fan terminal. The control algo- modulated to control temperature, more or less air will be in-
rithm determines the required fan state, based on the local duced from the return air plenum to maintain constant volume
mode, equipment mode, and the terminal type configuration. airflow.
For parallel or intermittent fan powered terminals (type 2 The fan is turned on whenever the central air source is on, or
configuration), the fan operates as follows: whenever unoccupied heating is required. The zone controller
1. The fan is energized: will energize the fan. Since the fan is located in the primary air
a. When ever SPT< current heating set point stream, the fan may be rotating even if the fan is not energized.
Due to the nature of the fan blade geometry, the fan will actual-
The primary air damper is set to the fully closed ly rotate backwards. Energizing the fan motor while the blades
position if the air source mode is OFF and heating are rotating backwards will cause the fan to run backwards.
is required. After heating is disabled, or if the The zone controller handles this condition by closing the pri-
equipment begins to operate, the primary air mary damper before starting the fan. Closing the damper will
damper returns to normal operation. stop any airflow which may cause the fan to rotate in reverse.
b. If the Primary Damper Reference drops below the Once the fan is started, the damper will be controlled normally.
configured Parallel Fan On value When the zone controller is controlling a series fan, if the air
2. The fan is deenergized: source transitions from OFF to any other mode, the zone con-
a. Whenever SPT > current heating set point and troller will implement a series fan start-up sequence. In this se-
heating is disabled quence, the zone controller will cause the damper to be driven
closed. Once the damper is closed, the zone controller will wait
b. If the Primary Damper Reference rises above the 30 seconds and then enable the fan. The zone controller will
configured Parallel Fan ON value then allow the damper to modulate. Mode control will wait a
For series or constant volume fan powered terminals (type 3 number of minutes (between 0 and 20) before initiating the fan
configuration), the fan operates as follows: start-up sequence to prevent all series fan terminals from clos-
1. The fan is energized: ing their dampers at once. The delay time is calculated from the
a. During occupied periods zone controller’s address and ensures that only two fans will
turned off at one time.
b. Whenever SPT < current heating set point
In a series fan terminal, the fan must be able to deliver the
c. Whenever the air source mode is not off zone’s rated airflow and must be running whenever the air
NOTE: Whenever the terminal fan transitions to source is operating.
ON, a fan start-up routine will run to ensure the The 33ZCFANTRM and 33ZCVVTZC-01 Zone Control-
fan rotates in the proper direction. lers provide heating control in three different ways:
2. The fan is deenergized: • positioning the primary air damper to a minimum air-
a. If in Unoccupied mode and heating is not flow when the air source is in cooling mode to deliver
required, or if the air source is off maximum induced plenum air to the zone
b. During the fan start-up routine. • controlling an optional auxiliary heater mechanism to
provide heating
Series Fan Terminal Applications — In a series
fan terminal, the fan is located in the primary airstream and,

32
• modulation of the primary air damper when the air When the space temperature is below the Heating set point
source is in its heating mode (VAV Central Heating) and the air source is in the Heat mode, the zone controller mod-
The 33ZCFANTRM and 33ZCVVTZC-01 (with option ulates the air terminals damper to supply airflow between min-
board) Zone Controllers support three methods to control heat- imum and maximum heating set point (if configured for VAV
ing. These methods are as follows: central heating for pressure independent applications, always
on for pressure dependent applications). A space temperature
• two-position (on/off) control using a normally open or PID loop determines the airflow set point. As the space temper-
normally closed heating valve ature rises above the heating set point, the PID loop will reduce
• modulating control using a normally open or normally the airflow.
closed floating point heating valve
• modulating control using up to 3 stages of electric heat As with cooling operation, the standard heating mode is the
same for occupied and unoccupied periods, differing only in
The series terminal fan operates based upon the air source the set point that the zone controller works to satisfy. The zone
mode (when it is in an operating mode other than OFF) or if the controller turns on the air terminal’s fan while working to satis-
zone needs unoccupied heating. fy the unoccupied heating set point.
If the space temperature drops below the unoccupied heat- The zone controller provides heat when the space tempera-
ing set point, the terminal fan will start unless it is already run- ture in its zone is below the heating set point and the air source
ning due to the air source operating. With unoccupied cooling, is delivering cool air. To accomplish this, the zone controller
the terminal fan will only start after the air source starts, based closes its air terminal’s supply-air damper to the configured
on the average space temperature exceeding the average unoc- minimum cooling cfm or damper position.
cupied cooling set point.
During this process, the zone controller also uses the tem-
COOLING — The primary control function of zone controller perature deviation from the heating set point in a PID calcula-
is to provide cooling to the space by modulating the amount of tion to determine a supply-air temperature which will satisfy
supply airflow through its primary damper. the heat demand in the space (for optional ducted heat). If the
The Zone Controller uses pressure independent or pressure supply air is not warm enough, another control loop calculates
dependent operation to control the amount of cool air entering the required amount of heat to energize.
the space. The control variable is terminal airflow for pressure The configured Heat On Delay must expire (except if heat is
independent and damper position for pressure dependent. A energized during the Commissioning mode) before any me-
PID temperature control loop determines the airflow set point chanical heat is energized. The fan is energized (on) when the
needed to maintain space temperature at the cooling set point. terminal is occupied and any time a call for heat from the space
The set point is limited to a range of values that allow the air occurs during Unoccupied mode.
source to operate properly in the cooling mode. These config- If VAV central heating is enabled, the PID loop that controls
ured limits are listed in the Installation Instructions for the zone space temperature will maintain the current heating set point
controller. The minimum limit ensures that the sum of all air (configured value plus any offset from a 33ZCT56SPT sensor
terminal minimum airflow requirements fall within the mini- slide bar) whenever the central equipment is heating. It will
mum cooling operating range of the air source. The maximum modulate the damper between the minimum and maximum
limit ensures that airflow will not increase above the maximum heating limits in order to maintain the desired heating set point.
design value and that the noise level generated at this maxi-
mum airflow will be acceptable to the occupants of the zone. When in unoccupied heating, the terminal’s fan will be
turned on to provide airflow to the zone. Also, in the unoccu-
The sequence of operation is as follows: when the space pied mode, the primary damper will be held in its last com-
temperature is above the cooling set point and the air source is manded position. If the air source becomes active (on) during
in the Cooling mode, the zone controller modulates the air ter- this mode, the damper will be controlled normally.
minal’s damper to supply airflow between the control mini-
mum and maximum cooling airflow limits. A PID temperature NOTE: In a Linkage system, when the central fan is operating,
control loop that maintains space temperature determines the the terminal fan will also be running.
airflow set point. As the space temperature falls below the COOLING WITH FAN — Figure 18 shows the hardware
cooling set point, the PID loop will start to reduce the airflow. configuration for a zone controller applied to a series fan pow-
When the space temperature drops and remains below the cool- ered air terminal that is not equipped with local heat. The dia-
ing set point, the zone controller will hold the airflow at mini- gram in Fig. 19 shows how the zone controller controls this
mum cooling limit. type of air terminal. The fan runs constantly in all modes dur-
In its standard operating mode the zone controller follows ing occupied periods.
the same control sequence for cooling during both occupied and STAGED ELECTRIC OR COMBINATION HEAT — The
unoccupied periods. The zone controller’s Occupancy schedule zone controller can be configured to control up to three stages
determines which set point the zone controller will use. of electric heat. The heat source can be installed in the air ter-
HEATING — There are two ways to use local heat. Heat oper- minal (ducted), or as perimeter heat. Figure 20 shows the hard-
ates when the zone controller’s zone requires heat and the air ware configuration for a zone controller applied to a series fan
source is supplying cool air to satisfy cooling demand in other powered air terminal equipped with staged electric heat. The
zones. Heat is also used to supplement air source heating while diagram in Fig. 21 shows how the zone controller controls this
the air source is supplying heated air, but the temperature is in- type of air terminal. The fan runs constantly in all modes dur-
adequate to maintain the desired set point. ing occupied periods. During unoccupied periods the fan runs
while the air terminal is operating to satisfy an unoccupied
If the space temperature in the zone falls below the zone heating demand or if the air source is operating.
controller’s heating set point while the air source is supplying
cooled air, the zone controller keeps the supply-air damper The percent output capacity for electric staged heat control
closed to the configured minimum cooling cfm. This enables is calculated and displayed.
plenum air, induced by the fan, to raise the space temperature Staged (electric) heating (1, 2, or 3 stages), is provided by
of the zone. the 33ZCFANTRM or 33ZCVVTZC-01 zone controller. The
A series fan powered air terminal without local heat can staging function compares the submaster reference with the
provide heating while its air source is delivering heated air. The supply-air temperature to calculate the required number of out-
control sequence for heating is similar to that for cooling, ex- puts to energize.
cept that the heating set point is used.

33
PLENUM
AIR
LEAVING
SUPPLY FAN AIR
SUPPLY AIR
AIR DAMPER
AIRFLOW
SENSOR DAMPER FAN
ACTUATOR RELAY
OUTPUT

ZONE
CONTROLLER
24 VAC
SPACE
TEMPERATURE
SENSOR
NETWORK BUS

Fig. 18 — Series Fan Powered Air Terminal — Cooling-Only

% AIRFLOW

100%
MAX COOL LIMIT
(DAMPER OVERRIDE
PRESSURIZATION FULL COOLING
MODE)
MAX HEAT LIMIT
FULL HEATING
VENT POSITION

MIN HEAT LIMIT

MIN COOL LIMIT


DEADBAND

0% < >
DAMPER OCCUPIED NTFC OCCUPIED WARM
COOL OVERRIDE- HEATING & SETPOINT COOLING
EVACUATION MORNING
MODE WARM-UP SPACE TEMPERATURE (DEGREES)
SETPOINT
LEGEND
NOTE: Ventilation mode occurs when air source mode is in cooling and
NTFC — Nighttime Free Cooling air source supply air temperature is above 65 F and below 75 F.
Air Source Supplying Heated Air
Air Source Supplying Cooled Air
. . . . . . Ventilation Mode
Fig. 19 — Sequence of Operation for Series Fan Powered Air Terminal — Cooling-Only

ELEC HEAT
PLENUM
AIR
LEAVING
SUPPLY FAN AIR
SUPPLY AIR
AIR DAMPER LEAVING AIR
TEMPERATURE
AIRFLOW SENSOR
SENSOR DAMPER FAN
ACTUATOR RELAY STAGES
OUTPUT
1 2 3
RELAY

ZONE
CONTROLLER
24 VAC
SPACE
TEMPERATURE
SENSOR
NETWORK BUS

*Stage 1 is radial or baseboard heat with combination heat.


Fig. 20 — Series Fan Powered Air Terminal with Staged Electric or Combination Heat

34
% AIRFLOW

100%
MAX COOL LIMIT
(DAMPER OVERRIDE
PRESSURIZATION FULL COOLING
MODE)
MAX HEAT LIMIT
FULL HEATING
VENT POSITION

ELECTRIC
MIN HEAT LIMIT HEAT
STAGES
MIN COOL LIMIT
DEADBAND
321
0% < >
DAMPER OCCUPIED NTFC OCCUPIED WARM
COOL OVERRIDE- HEATING & SETPOINT COOLING
EVACUATION MORNING
MODE WARM-UP SPACE TEMPERATURE (DEGREES)
SETPOINT
LEGEND NOTE: Ventilation mode occurs when air source mode is in cooling and
NTFC — Nighttime Free Cooling air source supply air temperature is above 65 F and below 75 F.
Air Source Supplying Heated Air
Air Source Supplying Cooled Air
. . . . . . Ventilation Mode
*Stage 1 is radial or baseboard heat with combination heat.
Fig. 21 — Sequence of Operation for Series Fan Powered Air Terminal with Staged Electric Heat

HOT WATER OR STEAM HEAT — The zone controller NOTE: In a Linkage system the when the central fan is operat-
can be configured to control local heat provided by heating coils ing, the terminal fan will also be operating.
carrying hot water or steam, governed either by a two-position
(on/off) valve or by a proportional (floating modulating) valve. Parallel Fan Terminal Applications — The paral-
The heating coils can be installed in the air terminal (ducted), or lel fan terminal provides three capabilities to the zone. First, it
as perimeter heat. If modulating baseboard is used, refer to the allows for unoccupied heating if auxiliary heating is available.
General Heating Information section for additional information. Secondly, it allows CV heating when occupied (the fan is on
Figure 22 shows the hardware configuration for a zone control- when ducted heating is on). Thirdly, it provides a means to pre-
ler applied to a series fan powered air terminal equipped with vent cold air from “dropping” into the zone during cooling
hot water or steam heating coils. The diagram in Fig. 23 shows mode.
how the zone controller controls an air terminal equipped with The 33ZCFANTRM or 33ZCVVTZC-01 (with option
two-position hot water or steam heat. The diagram in Fig. 24 board) Zone Controllers provide heating control in three differ-
shows how the zone controller controls an air terminal equipped ent ways:
with proportional hot water or steam heat. The fan runs con- • positioning the primary air damper to a minimum air-
stantly in all modes during occupied periods. flow when the air source is in cooling mode and starting
For modulating control, the supply air needed is compared the fan to utilize plenum heat as a first stage
to the actual supply air to either drive the valve open or closed. • controlling an optional auxiliary heater mechanism to
There is a deadband on the supply air deviation where the valve provide heating
will be left at the current position until the error gets larger than • modulation of the primary air damper when the air
the deadband. source is in its heating mode (VAV Central Heating)
For modulating type heat, the floating point function com- The 33ZCFANTRM or 33ZCVVTZC-01 (with option
pares the submaster reference from the PID loop to the supply board) Zone Controllers support three methods to control heat-
air temperature to calculate the direction and time to position ing. These methods are as follows:
the valve. The control prevents both outputs from operating • two-position (on/off) control using a normally open or
simultaneously. normally closed heating valve
Configuration determines the logic output type for normally • modulating control using a normally open or normally
open or normally closed type two-position valves. closed floating point heating valve
Heating with IAQ Control — A feature is provided for situa- • modulating control using up to 3 stages of electric heat
tions in which additional primary air is required for ventilation COOLING — The primary control function of zone controller
(IAQ). is to provide cooling to the space by modulating the amount of
The heating set point is calculated from the midpoint be- supply airflow through its primary damper.
tween the current heating and cooling set points. The airflow set point is limited to a range of values that al-
The standard heating algorithm is used. The algorithm pre- low the air source to operate properly in the Cooling mode.
vents the space temperature from falling below the set point These configured limits are listed in the Installation Instruc-
before heating is activated. The air terminal must be in the tions for the zone controller. The minimum limit ensures that
cooling mode and the equipment must be providing cooling. the sum of all air terminal minimum airflow requirements fall
When in unoccupied heating, the terminal’s fan will be within the minimum cooling operating range of the air source.
turned on to provide airflow to the zone. Also, in the unoccu- The maximum limit ensures that airflow will not increase
pied mode, the primary damper will be held in its last com- above the maximum design value and that the noise level gen-
manded position. If the air source becomes active (on) during erated at this maximum airflow will be acceptable to the occu-
this mode, the damper will be controlled normally. pants of the zone.

35
HEAT
PLENUM COIL
AIR
LEAVING
SUPPLY FAN AIR
SUPPLY AIR
AIR DAMPER LEAVING AIR
HEAT TEMPERATURE
AIRFLOW SENSOR
SENSOR DAMPER FAN VALVE
ACTUATOR RELAY
OUTPUT

ZONE
CONTROLLER
24 VAC
SPACE
TEMPERATURE
SENSOR
NETWORK BUS

Fig. 22 — Series Fan Powered Air Terminal with Hot Water or Steam Heat

% AIRFLOW

100%
MAX COOL LIMIT
(DAMPER OVERRIDE
PRESSURIZATION FULL COOLING
MODE)
MAX HEAT LIMIT
FULL HEATING

ON OFF
VENT POSITION
MIN HEAT LIMIT TWO-P0SITION
HOT WATER HEAT
MIN COOL LIMIT
DEADBAND

0% < >
DAMPER OCCUPIED NTFC OCCUPIED WARM
COOL OVERRIDE- HEATING & SETPOINT COOLING
EVACUATION MORNING
MODE WARM-UP SPACE TEMPERATURE (DEGREES)
SETPOINT
LEGEND NOTE: Ventilation mode occurs when air source mode is in cooling and
NTFC — Nighttime Free Cooling air source supply air temperature is above 65 F and below 75 F.
Air Source Supplying Heated Air
Air Source Supplying Cooled Air
. . . . . . Ventilation Mode
Fig. 23 — Sequence of Operation for Series Fan Powered Air Terminal with
Two-Position Hot Water or Steam Heat

% AIRFLOW

100%
MAX COOL LIMIT
(DAMPER OVERRIDE
PRESSURIZATION FULL COOLING
MODE)
MAX HEAT LIMIT FULL HEATING

OPEN CLOSED
VENT POSITION
MIN HEAT LIMIT PROPORTIONAL
HOT WATER HEAT
MIN COOL LIMIT
DEADBAND

0% < >
DAMPER OCCUPIED NTFC OCCUPIED WARM
COOL OVERRIDE- HEATING & SETPOINT COOLING
EVACUATION MORNING
MODE WARM-UP SPACE TEMPERATURE (DEGREES)
SETPOINT

LEGEND NOTE: Ventilation mode occurs when air source mode is in cooling and
NTFC — Nighttime Free Cooling air source supply air temperature is above 65 F and below 75 F.
Air Source Supplying Heated Air
Air Source Supplying Cooled Air
. . . . . . Ventilation Mode
Fig. 24 — Sequence of Operation for Fan Powered Air Terminal with Proportional Hot Water or Steam Heat

36
The sequence of operation is as follows: when the space The zone controller provides heat when the space tempera-
temperature is above the cooling set point and the air source is ture in its zone is below the heating set point and the air source
in the Cooling mode, the zone controller modulates the air ter- is delivering cool air. To accomplish this, the zone controller
minal’s damper to supply airflow between the minimum and closes its air terminal’s supply air damper to the configured min-
maximum cooling airflow limits. A PID temperature control imum cooling cfm for pressure independent operation. For pres-
loop that maintains space temperature and determines the air- sure dependent operation, the supply damper is closed. This
flow set point. As the space temperature falls below the cooling minimizes the cool air entering its zone from the air source. The
set point, the PID loop will start to reduce the airflow. When fan is turned on to induce plenum air. The zone controller induc-
the space temperature drops and remains below the cooling set es plenum air for a configurable length of time in an attempt to
point, the zone controller will hold the airflow at minimum satisfy the heating set point without turning on local heat. The
cooling limit. If the minimum cooling set point is below the amount of time is determined by the Heat ON Delay parameter.
Parallel Fan On set point, the fan will operate to improve air During this process, the zone controller also uses the tem-
circulation. perature deviation from the heating set point in a PID calcula-
In its standard operating mode the zone controller follows tion to determine a supply air temperature which will satisfy
the same control sequence for cooling during both occupied and the heat demand in the space. If the heated air is not warm
unoccupied periods. The zone controller’s Occupancy schedule enough, another control loop calculates the required number of
determines which set point the zone controller will use. outputs to energize. For all terminals, the configured Heat ON
There are two ways to use local heat. Heat operates when Delay must expire (except if heat is energized during the Com-
the zone controller’s zone requires heat and the air source is missioning Mode) before any mechanical heat is energized.
supplying cool air to satisfy cooling demand in other zones. If VAV central heating is enabled, the PID loop that controls
Heat can also be energized to supplement air source heating space temperature will maintain the current heating set point
while the air source is supplying heated air, but the temperature (this is a configured value plus any offset from a 33ZCT56SPT
is inadequate to maintain the desired set point. sensor slide bar). Whenever the central equipment is heating, it
HEATING — If the space temperature in the zone served by a will modulate the damper between the minimum and maximum
parallel fan powered air terminal falls below the zone control- heating limits in order to maintain the desired heating set point.
ler’s heating set point while the air source is supplying cool air, NOTE: When applied on a parallel fan type terminal, the zone
the zone controller keeps the supply-air damper closed to the controller will utilize the fan as the first stage of heat even if no
configured minimum cooling cfm for pressure independent op- heat is configured. The amount of time the fan will operate as
eration. For pressure dependent operation, the supply damper is the first heat stage is determined by the value configured for
closed. The zone controller also turns on the fan to induce the Heat On Delay (10 to 20 minutes recommended).
warmer plenum air. COOLING ONLY — Figure 25 shows the hardware configu-
A parallel fan powered air terminal without local heat can ration for a zone controller applied to a parallel fan powered air
perform heating functions while its air source is delivering heat- terminal that is not equipped with heat. The diagram in Fig. 26
ed air. When the space temperature is below the heating set shows how the zone controller controls this type of air termi-
point and the air source is delivering heated air the zone control- nal. The fan runs while the air terminal is heating.
ler turns on the fan to induce plenum air. The zone controller STAGED ELECTRIC OR COMBINATION HEAT — The
modulates the air terminal’s damper to supply airflow between zone controller can be configured to control up to three stages
the minimum and maximum heating limits (if configured for of electric or combination heat. The heat source can be in-
VAV central heating). A space temperature PID loop determines stalled in the air terminal (ducted), or as perimeter heat.
the airflow set point. As the space temperature rises above the Figure 27 shows the hardware configuration for a zone control-
heating set point, the PID loop will reduce the airflow. When ler applied to a parallel fan powered air terminal equipped with
heat is no longer required, the parallel fan will be turned off. staged electric heat. The diagram in Fig. 28 shows how the
As with cooling operation, the standard heating mode is the zone controller controls this type of air terminal. The fan runs
same for occupied and unoccupied periods, differing only in while the air terminal is heating.
the set point that the zone controller works to satisfy.

PLENUM
AIR

SUPPLY
AIR FAN
DAMPER

SUPPLY LEAVING
AIR AIR

AIRFLOW
SENSOR DAMPER
ACTUATOR FAN
RELAY
OUTPUT

ZONE
CONTROLLER
24 VAC
SPACE
TEMPERATURE
SENSOR
NETWORK BUS

Fig. 25 — Parallel Fan Powered Air Terminal — Cooling-Only

37
% AIRFLOW

100%
MAX COOL LIMIT
(DAMPER OVERRIDE
PRESSURIZATION FULL COOLING
MODE)
MAX HEAT LIMIT FULL HEATING
FAN RUNNING
TO INDUCE
VENT POSITION PLENUM HEAT

MIN HEAT LIMIT

MIN COOL LIMIT


DEADBAND

0% < >
DAMPER OCCUPIED NTFC OCCUPIED WARM
COOL OVERRIDE- HEATING & SETPOINT COOLING
EVACUATION MORNING
MODE WARM-UP SPACE TEMPERATURE (DEGREES)
LEGEND SETPOINT

NTFC — Nighttime Free Cooling NOTE: Ventilation mode occurs when air source mode is in cooling and
Air Source Supplying Heated Air
air source supply air temperature is above 65 F and below 75 F.
Air Source Supplying Cooled Air
...... Ventilation Mode
Fig. 26 — Sequence of Operation for Parallel Fan Powered Air Terminal — Cooling-Only
PLENUM
AIR

SUPPLY
AIR FAN
DAMPER ELEC HEAT

SUPPLY LEAVING
AIR AIR

AIRFLOW LEAVING AIR


SENSOR DAMPER FAN
RELAY STAGES TEMPERATURE
ACTUATOR SENSOR
OUTPUT 1 2 3
RELAY

ZONE
CONTROLLER
24 VAC
SPACE
TEMPERATURE
SENSOR
NETWORK BUS

*Stage 1 is radial or baseboard heat for combination heat.


Fig. 27 — Parallel Fan Powered Air Terminal with Staged Electric or Combination Heat
% AIRFLOW

100%
MAX COOL LIMIT
(DAMPER OVERRIDE
PRESSURIZATION FULL COOLING
MODE)
MAX HEAT LIMIT FULL HEATING
FAN RUNNING
TO INDUCE
PLENUM HEAT
VENT POSITION
ELECTRIC
MIN HEAT LIMIT HEAT
STAGES
MIN COOL LIMIT
DEADBAND
321
0% < >
DAMPER OCCUPIED NTFC OCCUPIED WARM
COOL OVERRIDE- HEATING & SETPOINT COOLING
EVACUATION MORNING
MODE WARM-UP SPACE TEMPERATURE (DEGREES)
SETPOINT
LEGEND
NOTE: Ventilation mode occurs when air source mode is in cooling and
NTFC — Nighttime Free Cooling air source supply air temperature is above 65 F and below 75 F.
Air Source Supplying Heated Air
Air Source Supplying Cooled Air
...... Ventilation Mode
*Stage 1 is radial or baseboard heat for combination heat.

Fig. 28 — Sequence of Operation for Parallel Fan Powered Air Terminal with Staged Electric Heat
38
The figures depict the electric heat source installed in the air primary air duct. If the air source becomes active (on) during
terminal. When the zone controller is used to control perimeter this mode, the damper will be controlled normally.
heat it follows the same control routines that it uses for terminal → Demand Controlled Ventilation (DCV) Con-
heat.
trol — Each zone controller used in a single duct and fan
The percent output capacity for electric staged heat control powered application has the ability to provide DCV operation.
is calculated and displayed. The DCV function determines the zone ventilation airflow as a
Staged (electric) heating (1, 2, or 3 stages), is provided by function of the DCV zone sensor reading or damper position.
the 33ZCFANTRM or 33ZCVVTZC-01 (with option board) When the air quality control is enabled, the zone controller will
Zone Controller. The staging function compares the submaster override (increase) the primary airflow in order to provide De-
reference with the supply-air temperature to calculate the mand Controlled Ventilation if the airflow is insufficient to
required number of outputs to energize. meet the ventilation set point.
HOT WATER HEAT — The zone controller can be config- The control algorithm uses a P/I algorithm to determine the
ured to control local heat provided by heating coils carrying hot required airflow in order to prevent the DCV sensor value from
water or steam, governed either by a two-position (on/off) exceeding the desired Air Quality set point. The zone controller
valve or by a proportional (floating modulating) valve. The is designed to interface with the following DCV sensors that
heating coils can be installed in the air terminal (ducted), or as sense CO2:
perimeter heat. If modulating baseboard heat is used, refer to The 33ZCSENCO2 sensor is an indoor, wall mounted sen-
the General Heating Information section for additional infor- sor with an LED (light-emitting diode) display. The sensor has
mation. Figure 29 shows the hardware configuration for a zone an analog output (0 to 10 vdc) over a range of 0 to 2000 ppm.
controller applied to a parallel fan powered air terminal An SPDT (single-pole, double-throw) contact is provided to
equipped with hot water or steam heating coils. The diagram in close at 1000 ppm with a hysteresis of 50 ppm.
Fig. 30 shows how the zone controller controls an air terminal
equipped with two-position hot water or steam heat. The dia- The 33ZCT55CO2 sensor is an indoor, wall-mounted sen-
gram in Fig. 31 shows how the zone controller controls an air sor without display. The CO2 sensor also includes a space tem-
terminal equipped with proportional hot water or steam heat. perature sensor with override button.
The fan runs while the air terminal is heating. The 33ZCT56CO2 sensor is an indoor, wall-mounted sen-
For modulating control, the supply air needed is compared sor without display. The CO2 sensor also includes a space tem-
to the actual supply air to either drive the valve open or closed. perature sensor with override button and temperature offset.
There is a deadband on the supply air deviation where the valve The DCV function contains a provision to operate modulat-
will be left at the current position until the error gets larger than ing type heat, if required and supplied, to maintain the space
the deadband. temperature at the midpoint between the heating and cooling
Configuration determines the logic output type for normally set points during DCV operation. Operation is dependent upon
open or normally closed type two-position valves. the equipment mode of operation, so that the DCV function
Heating with IAQ Control — A feature is provided for situa- will only operate during Occupied periods when the outdoor-
tions in which additional primary air is required for ventilation air damper is actively providing ventilation. A user-configured
(IAQ). AQ Maximum % can be used to protect the zone from over-
cooling if local heating is not supplied. The DCV control is
The heating set point is calculated from the midpoint be- automatically suspended if the space temperature falls below
tween the current heating and cooling set points. the heating set point. The DCV control will be disabled if the
The standard heating algorithm is used. The effect is to pre- DCV sensor status fails.
vent the space temperature from falling below the set point be- → DEMAND CONTROLLED VENTILATION AND MINI-
fore heating is activated. The air terminal must be in the Cool-
ing mode and the equipment must be providing cooling. MUM DAMPER POSITIONS — With 3V™ VVT® sys-
tems, the user has the capability to set both a heat and cool min-
When in unoccupied heating, the terminal’s fan will be imum damper position. The defaults for both are 0%. When the
turned on to provide airflow to the zone. Also, in the Unoccu- air source is cooling and the local mode of the damper is cool-
pied mode, a parallel fan terminal zone controller will keep the ing, the zone controller can switch between vent control and
primary damper closed to prevent airflow back into the minimum position control to maintain the space conditions

PLENUM
AIR

SUPPLY
AIR FAN
DAMPER HEAT COIL

SUPPLY LEAVING
AIR AIR

AIRFLOW FAN LEAVING AIR


SENSOR DAMPER TEMPERATURE
ACTUATOR RELAY HEAT
OUTPUT SENSOR
VALVE

ZONE
CONTROLLER
24 VAC
SPACE
TEMPERATURE
SENSOR
NETWORK BUS

Fig. 29 — Parallel Fan Powered Air Terminal with Hot Water or Steam Heat
39 105
when the zone is satisfied. The desired damper position is de- the reference zone, then the zone controller will close the
termined by the temperature of the air being supplied. If the damper to minimum position. During the heating season, some
temperature is between 65 F and 75 F, the damper will be a dampers in a system can stay at minimum position for extend-
vent position. If the temperature is below 65 F or above 75 F, ed periods of time. For this reason it is highly recommended
the damper will go to minimum. This allows the system to pro- that a heat minimum position other than 0% be used to ensure
vide adequate ventilation to meet the base ventilation rates for adequate ventilation per ASHRAE 62. Typically values from
ASHRAE 62 without setting the cool minimum above 0%. 5% to 10% will provide the base ventilation rate as required. A
When the damper mode is (or has been) heating and the simple check of the fresh air entering the air source, while the
space temperature has not risen more than halfway between the dampers are all at minimum position and the bypass is modu-
occupied set points, then the local mode will be heat. In this lating at an open position to maintain pressure, can tell if the
case, if the air source switches modes to provide cooling, or if system is moving enough air into the occupied space to cause
the air source is providing heat to satisfy another zone that is the unit to draw in the appropriate fresh air.

% AIRFLOW

100%
MAX COOL LIMIT
(DAMPER OVERRIDE
PRESSURIZATION FULL COOLING
MODE)
MAX HEAT LIMIT FULL HEATING
FAN RUNNING
TO INDUCE
PLENUM HEAT ON OFF
VENT POSITION
MIN HEAT LIMIT TWO-POSITION
HOT WATER HEAT
MIN COOL LIMIT
DEADBAND

0% < >
DAMPER OCCUPIED NTFC OCCUPIED WARM
COOL OVERRIDE- HEATING & SETPOINT COOLING
EVACUATION MORNING
MODE WARM-UP SPACE TEMPERATURE (DEGREES)
SETPOINT
LEGEND
NTFC — Nighttime Free Cooling
Air Source Supplying Heated Air
Air Source Supplying Cooled Air NOTE: Ventilation mode occurs when air source mode is in cooling and
air source supply air temperature is above 65 F and below 75 F.
. . . . . . Ventilation Mode
Fig. 30 — Sequence of Operation for Parallel Fan Powered Air Terminal with
Two-Position Hot Water or Steam Heat

% AIRFLOW

100%
MAX COOL LIMIT
(DAMPER OVERRIDE
PRESSURIZATION FULL COOLING
MODE)
MAX HEAT LIMIT FULL HEATING
FAN RUNNING
TO INDUCE
PLENUM HEAT
OPEN CLOSED
VENT POSITION
MIN HEAT LIMIT PROPORTIONAL
HOT WATER HEAT
MIN COOL LIMIT
DEADBAND

0% < >
DAMPER OCCUPIED NTFC OCCUPIED WARM
COOL OVERRIDE- HEATING & SETPOINT COOLING
EVACUATION MORNING
MODE WARM-UP SPACE TEMPERATURE (DEGREES)
SETPOINT
LEGEND
NTFC — Nighttime Free Cooling
Air Source Supplying Heated Air
Air Source Supplying Cooled Air NOTE: Ventilation mode occurs when air source mode is in cooling and
. . . . . . Ventilation Mode air source supply air temperature is above 65 F and below 75 F.

Fig. 31 — Sequence of Operation for Parallel Fan Powered Air Terminal with
Proportional Hot Water or Steam Heat

Copyright 2004 Carrier Corporation

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 New Book 1 PC 111 Catalog No. 513-362 Printed in U.S.A. Form 33ZC-3XA Pg 40 105 9-04 Replaces: New
Tab 11a Tab 1CS1

You might also like