Operation_Assessment_of_a_Hybrid_Distribution_Tran
Operation_Assessment_of_a_Hybrid_Distribution_Tran
Article
Operation Assessment of a Hybrid Distribution Transformer
Compensating for Voltage and Power Factor Using
Predictive Control
Esteban I. Marciel 1 , Carlos R. Baier 2, * , Roberto O. Ramírez 2 , Carlos A. Muñoz 2,3 , Marcelo A. Pérez 4
and Mauricio Arevalo 5
1 Engineering Systems Doctoral Program, Faculty of Engineering, University of Talca, Campus Curicó,
Curicó 3344158, Chile; [email protected]
2 Department of Electrical Engineering, Faculty of Engineering, University of Talca, Campus Curicó,
Curicó 3344158, Chile; [email protected] (R.O.R.);
[email protected] or [email protected] (C.A.M.)
3 Estudiante de Doctorado, Departamento de Ingeniería Eléctrica, University of Jaén,
Campus Lagunillas s/n, Building A3, 23071 Jaén, Spain
4 Department of Electronics, Universidad Tecnica Federico Santa Maria, Valparaiso 2390123, Chile;
[email protected]
5 Electrical Engineering Sciences Doctoral Program, Faculty of Engineering, University of Talca,
Campus Curicó, Curicó 3344158, Chile; [email protected]
* Correspondence: [email protected]
Abstract: Hybrid Distribution Transformers (HDTs) offer a compelling alternative to traditional low-
frequency transformers (LFTs), providing auxiliary services in addition to standard functionalities.
By integrating LFTs with power converters, HDTs enhance the operational capabilities of the
system. The specific configuration in which converters are connected to the transformer allows for the
provision of multiple services. This can not only prevent network failures but also extend the lifespan
of its components, an outcome that is highly desirable in a distribution grid. This article discusses an
Citation: Marciel, E.I.; Baier, C.R.; HDT developed to mitigate voltage fluctuations in the grid and to decrease the reactive power drawn
Ramirez, R.O.; Muñoz, C.A.; Perez, from the secondary side of traditional LFTs. A finite-control-set model predictive control (FCS-MPC),
M.A.; Arevalo, M. Operation in conjunction with linear controllers, is utilized for the effective management of the HDT converters.
Assessment of a Hybrid Distribution Two separate control loops are established to regulate voltage and reactive power on the secondary
Transformer Compensating for side of the transformer. Results from Hardware-in-the-Loop (HIL) testing affirm the proficiency of
Voltage and Power Factor Using HDT in reducing grid voltage variations by 15% and in cutting reactive power consumption by up
Predictive Control. Mathematics 2024,
to 94%. The adopted control strategy and topology are demonstrated to be effective in stabilizing
12, 774. https://doi.org/10.3390/
voltage and reactive power fluctuations while concurrently facilitating the charging of the converters’
math12050774
DC link directly from the grid.
Academic Editors: Eduard Petlenkov
and Larbi Chrifi-Alaoui Keywords: hybrid distribution transformer; smart transformer; smart grids; CHB-MLI
Received: 5 February 2024
MSC: 93-10
Revised: 29 February 2024
Accepted: 1 March 2024
Published: 5 March 2024
1. Introduction
In electrical power distribution systems, one of the primary goals is to maintain voltage
Copyright: © 2024 by the authors. and current under control at various points within the grid. This ensures the grid’s capacity
Licensee MDPI, Basel, Switzerland. to provide a supply of energy that meets the quality standards set by regulatory limits,
This article is an open access article thereby reducing the likelihood of failures in these systems. Operating outside the nominal
distributed under the terms and
values for voltage amplitude or frequency can compromise the proper functioning or
conditions of the Creative Commons
integrity of equipment connected to the grid [1]. These potential failures pose significant
Attribution (CC BY) license (https://
challenges in distribution systems control due to the vast number and variety of connected
creativecommons.org/licenses/by/
elements [2].
4.0/).
delivered by the converter. This proposal utilizes a discrete-time LQR control, enabling the
HDT to contribute to voltage sag and swell control, power factor correction, and current
and voltage distortions.
Using a cascaded h-bridge multilevel converter (CHB-MLI) instead of a voltage source
converter can provide two main advantages to an HDT in the MV side. The first is the
ability to achieve a higher level of output voltage or to reach the same voltage levels while
subjecting the components to lower voltage levels. This is due to the use of two or more
modules connected in series instead of just one. The other advantage is the multilevel
voltage output of the converter, which can improve the quality of the compensation. An
additional advantage of this topology is the autonomy of each module. If one cell has a
problem, it can be isolated, and the rest of the modules can continue to operate as if it were
a CHB-MLI with a smaller number of modules [22].
This document presents the HIL implementation of an HDT with a voltage source
converter (VSI) and a CHB-MLI connected through a medium-frequency interface to
compensate for variations on the voltage grid and the reactive consumption on an LFT.
The converters are controlled by an FCS-MPC strategy, where the output models are used
and discretized using the forward Euler method. The compensation strategies are made
from lineal controllers, and the use of p-q calculation is needed. This technique permits to
control the voltage and reactive power at the same time in the same HDT.
This article is organized as follows. In Section 2, the fundamental aspects of hybrid
transformers are presented. Then, in Section 3, the proposed HDT topology is presented,
along with its corresponding control strategy. In Section 4, the results obtained that validate
the proposal are presented. Finally, Section 5 summarizes the main conclusions of this
work.
2. Hybrid Transformer
Hybrid transformers can be made up of one or more converters arranged to a low-
frequency transformer. This contributes to the control of variables such as voltage or
current. It helps to mitigate the effects of changes in voltage, harmonics, or reactive power,
especially in the face of small variations in the system [13,17].
Depending on the configuration used, the HDT can perform specific compensation
tasks, so the topology to be used is directly linked to the variables that need to be con-
trolled [14].
An example of an HDT topology is shown in Figure 1, in which a solid-state trans-
former made of voltage source converters is connected in parallel to a low-frequency
transformer. In this configuration, a converter is connected to the primary side of the
low-frequency transformer and can be used to obtain energy from the grid or to provide
voltage to the amplitude delivered by the grid, to regulate and ensure the desired voltage
on the secondary side of the transformer, even if the grid voltage varies [23]. The converter
at the other end is connected to the secondary side of the transformer and can compensate
for the load reactive power and can also control the active power to charge the converter
DC link or control the current harmonics. All this can be achieved by controlling the output
current [24].
Hybrid
Transformer
LFT
MV LV
grid grid
AC
AC
These type of configuration can obtain their energy from the grid, charging their DC
link capacitors using a power control strategy on the converters that perform compensation
tasks, or they can be charged from an external energy source, like a removable energy
source or a DC microgrid [25], or even a dedicated converter to obtain the energy from the
same grid [26,27].
The significant contribution of this work lies in the development of a control strategy
applied to a Hybrid Distribution Transformer operating with multilevel converters. The
proposed strategy enables the simultaneous implementation of two compensation actions
without interference between them. From both control and topological perspectives, the
proposal offers several advantages, including enhanced output voltage quality compared
to topologies with fewer levels, and the ability to harness the benefits of modularity in
cascaded converters.
2.2. Topology
As mentioned, the proposed hybrid transformer configuration consists of a double
compensator system in parallel with a low-frequency transformer (LFT), where the com-
pensators are a CHB-MLI connected in series to the grid on the higher-voltage side of the
Mathematics 2024, 12, 774 5 of 18
LFT, and a voltage source converter in parallel to the loads on the lower-voltage side as
shown in Figure 2.
In addition, each converter have their respective DC link composed of a capacitor, and
these DC links are connected to each other through a medium-frequency interface between
the converters to provide the necessary galvanic isolation [28], while the shunt converter
DC capacitor is used to charge the series converter DC capacitors to keep the multilevel
converter energized.
Hybrid
Transformer LFT
MV grid LV grid
Medium frequency
LC Filter Series converter Shunt converter L Filter
interface
AC DC AC DC
DC AC DC AC
AC DC Possible DC grid
conection or DC
DC AC storage
AC DC
DC AC
On the low-voltage side, a voltage source converter is connected in parallel to the grid
with the ability to control power flow, which aims to compensate for the reactive power
consumed by the loads, so the LFT receives only active power consumption. Additionally,
the converter is tasked with controlling the DC link voltage to maintain the load levels at
the configured values. This converter uses an L filter to connect it to the grid, which allows
for a sinusoidal current output.
Due to these characteristics, the proposed system has the advantages of improved
reliability in the event of failures in the series compensator modules, and also allows for the
possibility of reaching higher-voltage compensator levels than single-module topologies
with the same type of semiconductors. And the system presents the possibility of an
external connection for energy from other sources to carry out compensation operations to
reduce energy consumption from the main network.
It is necessary to emphasize that to ensure an improvement in the reliability of the
system, a separate study is necessary, which must be carried out considering a modeling
and evaluation of the proposal with strategies such as the Monte Carlo method [29], in
addition to taking into account the reliability of the same electrical network where the HDT
would operate [30].
s c ( t ) = s1 ( t ) − s2 ( t ), (1)
Mathematics 2024, 12, 774 6 of 18
and the output voltage vo can be expressed as the product from the DC voltage and the
switching function:
vosh (t) = VDCsh (t)sc (t). (2)
LFT
MV grid LV grid
Shunt converter
+ DC
- AC
Therefore, Table 2 presents the valid switching states for this converter, avoiding
combinations that simultaneously activate both semiconductors of one leg of the converter.
Such simultaneous activation could lead to a short circuit in the power supply.
By knowing the valid states of the converter, the voltage levels it can deliver can be
obtained in the same way, and with this information, a mathematical model can be obtained
that describes the converter’s output coupled to the filter, which can be represented by
dish 1
= (V (t)sc (t) − R f sh ish (t) − vsec (t)), (3)
dt L f sh DCsh
where ish is the output current, L f sh and R f sh are the filter inductance and resistance, and
vsec is the secondary-side voltage. This model can be used to implement a model-based
control strategy model, such as finite control set model predictive control (FCS-MPC).
Mathematics 2024, 12, 774 7 of 18
MV grid LV grid
Series converter
AC +
DC -
AC +
DC -
AC +
DC -
The topology implemented consists of three voltage source converter modules con-
nected in series, which are connected to the grid in series through an LC filter. Each module
is fed by a DC link consisting of a capacitor, so each module behaves like a voltage source
converter and has the same valid states as presented in Table 2. However, with three
modules in series, the output of the converter is the sum of the output voltages of each
module. Then, the output current model is:
dise 1
= (v + vom2 + vom3 − R f se ∗ ise − vCse ), (4)
dt L f se om1
where ise is the converter output current, L f se and R f se are the filter inductance and resis-
tance, vCse is the series capacitor voltage, and vomx is each module output voltage, which
can be obtained using VDCmx as each module DC link and scx as their respective switching
function:
vomx = VDCmx scx (5)
While the proposed multilevel topology initially involves three modules, the number
of modules can be adjusted based on the desired output voltage or the available components.
In this system, three modules are used because it is a low number of modules, considering
a future physical implementation of the proposal. This also allows the output voltage to be
tripled compared to a VSI, and the multilevel output waveform can have up to seven levels
Mathematics 2024, 12, 774 8 of 18
if the DC voltage in the modules is the same. In this case, the output current model can be
simplified as:
dise 1
= (V scT − R f se ise − vCse ), (6)
dt L f se DCm
where now there is only one switching function scT , which is defined as:
The activation of different modules can result in the same total switching function
and output voltage, but there are combinations that use three modules to generate the
same output which can be achieved with one module; these combinations are not desirable
because the efficiency is better when there is only one module active instead of three.In
Table 3, the different combinations that a balanced CHB-MLI can have and their respective
voltage output and total switching function are presented.
3. Control
The control strategies to use in an HDT are divided in two: primary control and
secondary control. The first is used to maintain each converter output current following a
reference, and the second is used to generate the primary control references to generate
the voltage and reactive power compensation. A general control scheme is presented in
Figure 5.
On the primary control of each compensator converter, an FCS-MPC strategy is an
option that guarantees robust operation and improves the dynamic characteristics for the
converters [31].
Mathematics 2024, 12, 774 9 of 18
HDT
LFT
Medium frequency
Series converter Shunt converter
interface
s1 ... s12 s1 s2 s3 s4 s1 s2 s3 s4
trasnform.
Ts
ise (k + 1) = (V (k)scseT (k) − R f se ∗ ise (k)
L f se DCm (10)
−vCse (k)) + ise (k)
With these functions, the FCS-MPC can select the state that delivers the optimal
system behavior in each control iteration to maintain the desired converters outputs. A
predictive horizon Np = 2 is used to take advantage of the tracking error reduction and
to improve the supply quality over a Np = 1 strategy [33]. One disadvantage is that the
number of evaluations performed by the algorithm depends on the number of states to
be evaluated and the prediction horizon by States Np , where a larger prediction horizon
leads to an exponential growth in the number of evaluations. Therefore, increasing the
prediction horizon results in a computational load that becomes too heavy for a controller
to implement in real-time; this is the reason that a longer prediction horizon is not chosen.
In the case of a series converter that use a balanced three-module cascaded multilevel
converter, there is redundancy in the switching states to obtain an output voltage level
equal to the DC voltage of one or two modules, or their negative cases as shown in Table 3.
These redundant states imply that to obtain a voltage different from 0V, 3VDC , or −3VDC
at the converter output, energy can be extracted in an unbalanced way if the predictive
control algorithm is left to select the switching state since it tends to use one state more than
the other redundant states, which is why an algorithm to balance the energy extraction in
these cases is used.
This algorithm operates by receiving a desired total switching function that can be
generated by different states in each case, and it applies those states sequentially, saving
the last state used for each output, then in the next cycle that requests the same output
voltage, the algorithm checks the memory to know the last stored state and applies the next
state in the possible sequence of states to obtain the requested output. Table 4 presents how
the next state to apply depends on the scT desired and the last state applied. Thanks to this,
all the modules can be activated the same amount of times in a period, and the energy can
be equally extracted.
Once the converters model and balancing algorithm are ready, the primary control
is ready to be implemented. The two algorithms will receive the output current reference
from a secondary control and will select the best switching combination to achieve the
references as shown in Figure 6.
Start Start
Meassurement: Meassurement:
No No
Delay compensation Delay compensation
Yes Yes
Define Define
Yes Yes
k+1 prediction k+1 prediction
eq. 9 eq. 10
No No
No No
a) b)
2ωo s
HPR (s) = K p r + Kr (11)
s2 + 2ωo s + ωo2
where K p r is the proportional gain, Kr is the resonant gain, and ωo is the grid fundamental
frequency.
The voltage reference to be followed is generated from the product of a unitary sine
wave and the amplitude of the expected nominal voltage on the low-voltage side:
√
v∗sec = ∗
2vrms sin(2pi f grid θ PLL ) (12)
This sine wave signal obtains its generation angle through a EPLL that follows the
voltage of the primary winding; consequently, the reference signal becomes synchronized
with the voltage of the medium-voltage grid to which the series compensator is connected.
Once the reference is obtained, it is compared with the measured voltage on the secondary
winding to calculate the error, and then sent to the PR controller, where this control function
generates the converter’s reference output current, which is sent to the FCS-MPC:
∗
ise = PR(v∗sec − vsec ) (13)
The active power that the converter consumes depends on the DC capacitor charge,
then a proportional-integral (PI) control is used to generate the active power reference from
the DC capacitor voltage. The PI controller transfer function can be written as:
Ki
HPI (s) = K p + (14)
s
where K p is the proportional gain, and Ki is the integral gain. With the controller model,
the DC voltage control reference can be obtained from the error between the desired and
actual DC capacitor voltages:
∗
Vctrl = PI (VDCsh − VDCsh ) (15)
The reactive power consumed to the LFT is calculated via alpha–beta theory:
With the power consumption calculated, a pi controller can be used to generate the
reactive power flow needed from the converter to mitigate this power from the LFT:
With the two types of power flows calculated, the shunt converter current reference
can be obtained from the p-q theory as:
The DC link voltage control loop is a loop that could be eliminated in the case of
having an external power supply path, such as a DC microgrid or an additional converter
dedicated to the DC link load. This would prevent power recirculation through the LFT.
In the event that this occurs, the DC capacitor voltage control can be eliminated without
affecting reactive power compensation.
An additional active power control loop can be incorporated into the secondary control
strategies as long as there is an energy storage element with sufficient capabilities or an
external power supply in the DC link of the converters. This additional control loop would
allow the HDT to contribute with inertia in case the grid in which it works has a low
percentage of synchronous generators, thereby improving its capability to provide auxiliary
services.
through the MFT. This is necessary for the compensators to carry out their activities correctly.
To do this, the Vsec PR control and Qsec PI control are limited to zero, and the only active
control on the shunt converter is the VDCsh PI control; this works until the DC voltage reach
the reference. Once the DC links are loaded, the voltage and reactive power compensator
controls start to act to compensate for any undue variation in the system.
4. Results
The results were derived from a Hardware-in-the-Loop (HIL) setup, utilizing the
MicroLabBox Compact prototyping DS1202 unit from dSpace GmbH (dSPACE, Paderborn,
Germany) to implement digital control and the OP4510 real-time digital simulation platform
from Opal-RT (OPAL-RT Technologies Inc., Montreal, Quebec, Canada) to simulate the
HDT power system. The set-up can be seen in Figure 7.
In this HIL setup, two tests were conducted to evaluate the responses of both LFT-only
and HDT systems: one test under variations of the grid voltage of 15% of its nominal value
and another test under impacts of the load consumption of 1 kW and 1 kVAR. These tests
demonstrate the performance of HDT in scenarios affecting the low-voltage grid’s voltage
and the reactive power delivered by the LFT. The system values for these tests are detailed
in Table 5.
500 V
1000 VAR
25 A
1000 VAR
25 A
25 A
Figure 8. System response to a 1000 W and 1000 VAR impact in charge: (a) LFT-only response.
(b) HDT response.
In the last two tests, it can be observed how variations of 15% in the nominal voltage
are implemented, resulting in an amplitude change of 185 [V], and this change is effectively
compensated for by the CHB-MLI, while all their modules have a voltage of 100 [V]. In
this topology, each module individually possesses a lower capacity than required for the
converter’s compensation. However, when all modules work together, the output capacity
meets the voltage requirements.
2000 V 2000 V
500 V
50 V
500 V
200 V
50 V
Figure 9. System response to a 15% sag in the primary grid: (a) LFT-only response. (b) HDT response.
2000 V 2000 V
500 V
50 V
500 V
200 V
50 V
Figure 10. System response to a 15% swell in the primary grid: (a) LFT-only response. (b) HDT
response.
5. Conclusions
This paper evaluates the operation of an HDT designed to supply secondary loads and
compensate for voltage and reactive power fluctuations at the Point of Common Coupling
(PCC). The approach integrates predictive control strategies alongside linear PI and PR
control techniques to effectively manage the converters in the HDT. The proposed HDT
system features a CHB-MLI on the medium-voltage side, medium-frequency transformers,
and a conventional inverter on the low-voltage side.
This study assesses the voltage and reactive power compensation capabilities of the
proposed HDT using HIL simulation. The HDT power converters employ FCS-MPC
schemes with an extended horizon to regulate their outputs. For voltage compensation,
Mathematics 2024, 12, 774 16 of 18
Author Contributions: Conceptualization, E.I.M. and C.R.B.; methodology, E.I.M.; software, M.A.;
validation, R.O.R., C.A.M. and M.A.P.; formal analysis, E.I.M.; investigation, E.I.M.; resources, C.R.B.
and M.A.P.; data curation, E.I.M.; writing—original draft preparation, E.I.M.; writing—review and
editing, C.R.B.; visualization, R.O.R.; supervision, C.R.B.; project administration, C.R.B.; funding
acquisition, C.R.B. All authors have read and agreed to the published version of the manuscript.
Funding: This research was mainly supported by two funding sources: the Fondecyt Project 1201308,
and a grant from the Council of Andalucía (Junta de Andalucía, Consejería de Transformación
Económica, Industria, Conocimiento y Universidades, Secretaría General de Universidades, Inves-
tigación y Tecnología) under Project ProyExcel_00381. Additional support was provided by the
Thematic Network RIBIERSE-CYTED (723RT0150) and the Fondecyt Project 1211826.
Data Availability Statement: Data are contained within the article.
Acknowledgments: The support of the Energy Conversion Technology Center of the University of
Talca, the Advanced Center for Electrical and Electronics Engineering AC3E (Conicyt/FB0008), and
the Chilean Solar Energy Research Center (Conicyt/FONDAP/15110019) is gratefully acknowledged.
Conflicts of Interest: The authors declare no conflicts of interest.
References
1. Fuchs, E.; Masoum, M. Power Quality in Power Systems and Electrical Machines; Academic Press: Cambridge, MA, USA, 2008.
[CrossRef]
2. Singh, B.; Chandra, A.; Al-Haddad, K. Power Quality Problems and Mitigation Techniques; John Wiley & Sons Ltd.: Hoboken, NJ,
USA, 2015; Volume 9781118922057, pp. 1–582. [CrossRef]
Mathematics 2024, 12, 774 17 of 18
3. Gönen, T. Electric Power Distribution Engineering; CRC Press: Boca Raton, FL, USA, 2014; p. 1049.
4. Divan, D.; Moghe, R.; Prasai, A. Power electronics at the grid edge: The key to unlocking value from the smart grid. IEEE Power
Electron. Mag. 2014, 1, 16–22. [CrossRef]
5. Kefalas, T.D.; Kladas, A.G. Harmonic impact on distribution transformer no-load loss. IEEE Trans. Ind. Electron. 2010, 57, 193–200.
[CrossRef]
6. Das, B.P.; Radakovic, Z. Is transformer kVA derating always required under harmonics? A manufacturer’s perspective. IEEE
Trans. Power Deliv. 2018, 33, 2693–2699. [CrossRef]
7. Divan, D.; Kandula, P. Distributed Power Electronics: An Enabler for the Future Grid. Cpss Trans. Power Electron. Appl. 2016,
1, 57–65. [CrossRef]
8. Liang, C.; Luo, L.; Li, Y.; Xu, J.; Qi, Q.; Chen, Y.; Zhou, G.; Deng, M. An Integrated Harmonic-Filtering Transformer for
Low-Voltage Distribution Systems. IEEE Trans. Magn. 2015, 51, 8402204. [CrossRef]
9. Liserre, M.; Buticchi, G.; Andresen, M.; De Carne, G.; Costa, L.F.; Zou, Z.X. The Smart Transformer: Impact on the Electric Grid
and Technology Challenges. IEEE Ind. Electron. Mag. 2016, 10, 46–58. [CrossRef]
10. Abu-Siada, A.; Budiri, J.; Abdou, A.F. Solid state transformers topologies, controllers, and applications: State-of-the-art literature
review. Electronics 2018, 7, 298. [CrossRef]
11. Huber J. E..; Kolar J. W. Applicability of Solid-State Transformers in Today’s and Future Distribution Grids. IEEE Trans. Smart
Grid 2019, 10, 317–326. [CrossRef]
12. Zheng, L.; Marellapudi, A.; Chowdhury, V.R.; Bilakanti, N.; Kandula, R.P.; Saeedifard, M.; Grijalva, S.; Divan, D. Solid-State
Transformer and Hybrid Transformer With Integrated Energy Storage in Active Distribution Grids: Technical and Economic
Comparison, Dispatch, and Control. IEEE J. Emerg. Sel. Top. Power Electron. 2022, 10, 3771–3787. [CrossRef]
13. Burkard, J.; Biela, J. Evaluation of topologies and optimal design of a hybrid distribution transformer. In Proceedings of the
2015 17th European Conference on Power Electronics and Applications, EPE-ECCE Europe 2015, Geneva, Switzerland, 8–10
September 2015. [CrossRef]
14. Carreno, A.; Perez, M.; Baier, C.; Huang, A.; Rajendran, S.; Malinowski, M. Configurations, power topologies and applications of
hybrid distribution transformers. Energies 2021, 14, 1215. [CrossRef]
15. Lee, H.J.; Yoon, S.W.; Yoon, Y.D. Hybrid Distribution Transformer Based on an Existing Distribution Transformer and a
Series-Connected Power Converter. IEEE Trans. Power Deliv. 2022, 37, 4202–4211. [CrossRef]
16. Yun, C.G.; Cho, Y. Active hybrid solid state transformer based on multi-level converter using SiC MOSFET. Energies 2019, 12, 66.
[CrossRef]
17. Costa, P.; Paraíso, G.; Pinto, S.F.; Silva, J.F. A four-leg matrix converter based hybrid distribution transformer for smart and
resilient grids. Electr. Power Syst. Res. 2022, 203, 107650. [CrossRef]
18. Zhang, L.; Liu, Y.; Wang, Y.; Liang, D.; Kong, Z.; Wen, Q.; Liu, H.; Gao, Y.; Wu, Z.; Wang, C.; et al. Multi-Layer Fault-Tolerant
Protection Strategies for Hybrid Distribution Transformers Integrated Photovoltaic Systems. IEEE Trans. Ind. Appl. 2023,
59, 3098–3109. [CrossRef]
19. Liu, Y.; Zhang, L.; Liang, D.; Jin, H.; Li, S.; Jia, S.; Li, J.; Liu, H.; Wang, Y.; Zhou, K.; et al. Quasi-Proportional-Resonant Control for
the Hybrid Distribution Transformer With LCL-Type Converters. IEEE Trans. Ind. Appl. 2022, 58, 6368–6385. [CrossRef]
20. Liu, Y.; Liang, D.; Kou, P.; Zhang, M.; Cai, S.; Zhou, K.; Liang, Y.; Chen, Q.; Yang, C. Compound Control System of Hybrid
Distribution Transformer. IEEE Trans. Ind. Appl. 2020, 56, 6360–6373. [CrossRef]
21. Carreno, A.; Malinowski, M.; Perez, M.A.; Baier, C.R. Circulating Active Power Flow Analysis in a Hybrid Transformer With the
Series Converter Connected to the Primary Side. IEEE Trans. Ind. Electron. 2024, 1–10. [CrossRef]
22. Malinowski, M.; Gopakumar, K.; Rodriguez, J.; Pérez, M.A. A Survey on Cascaded Multilevel Inverters. IEEE Trans. Ind. Electron.
2010, 57, 2197–2206. [CrossRef]
23. Kaniewski, J.; Fedyczak, Z.; Benysek, G. AC voltage sag/swell compensator based on three-phase hybrid transformer with
buck-boost matrix-reactance chopper. IEEE Trans. Ind. Electron. 2014, 61, 3835–3846. [CrossRef]
24. Radi, M.A.; Darwish, M. Var control considerations for the design of hybrid distribution transformers. IET Semin. Dig. 2015, 2015,
pp. 1–9. [CrossRef]
25. Zhang, L.; Liu, Y.; Liang, D.; Kou, P.; Wang, Y.; Gao, Y.; Li, D.; Liu, H. Local and Remote Cooperative Control of Hybrid
Distribution Transformers Integrating Photovoltaics in Active Distribution Networks. IEEE Trans. Sustain. Energy 2022,
13, 2012–2026. [CrossRef]
26. Carreno, A.; Perez, M.; Baier, C.; Espinoza, J. Modeling and Control of a Hybrid Transformer based on a Cascaded H-bridge
Multilevel Converter. In Proceedings of the IECON Proceedings (Industrial Electronics Conference), Singapore, 18–21 October
2020; pp. 1614–1619. [CrossRef]
27. Liu, Y.; Liang, D.; Wang, Y.; Kou, P.; Zhou, K.; Li, D.; Zhang, L.; Gao, Y.; Cai, S.; Wen, Q.; et al. Power Flow Analysis and DC-link
Voltage Control of Hybrid Distribution Transformer. IEEE Trans. Power Electron. 2021, 36, 12579–12595. [CrossRef]
28. Ferreira Costa, L.; De Carne, G.; Buticchi, G.; Liserre, M. The Smart Transformer: A solid-state transformer tailored to provide
ancillary services to the distribution grid. IEEE Power Electron. Mag. 2017, 4, 56–67. [CrossRef]
29. Liu, Y.; Peng, H.; Yang, Y. Reliability Modeling and Evaluation Method of CNC Grinding Machine Tool. Appl. Sci. 2019, 9, 14.
[CrossRef]
Mathematics 2024, 12, 774 18 of 18
30. Migisha, A.G.; Ntayi, J.M.; Buyinza, F.; Senyonga, L.; Abaliwano, J.; Adaramola, M.S. Review of Concepts and Determinants of
Grid Electricity Reliability. Energies 2023, 16, 7220. [CrossRef]
31. Vazquez, S.; Leon, J.I.; Franquelo, L.G.; Rodriguez, J.; Young, H.A.; Marquez, A.; Zanchetta, P. Model predictive control: A review
of its applications in power electronics. IEEE Ind. Electron. Mag. 2014, 8, 16–31. [CrossRef]
32. Rodríguez, J.; Pontt, J.; Silva, C.; Cortés, P.; Amman, U.; Rees, S. Predictive current control of a voltage source inverter. PESC
Record-IEEE Annu. Power Electron. Spec. Conf. 2004, 3, 2192–2196. [CrossRef]
33. Geyer, T.; Quevedo, D.E. Multistep finite control set model predictive control for power electronics. IEEE Trans. Power Electron.
2014, 29, 6836–6846. [CrossRef]
34. Khadkikar, V.; Chandra, A.; Singh, B.N. Generalised single-phase p-q theory for active power filtering: Simulation and DSP-based
experimental investigation. IET Power Electron. 2009, 2, 67–78. [CrossRef]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual
author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to
people or property resulting from any ideas, methods, instructions or products referred to in the content.