Earthing Calculation
Earthing Calculation
TOTAL
EARTHING
SNO. FROM TO LENGTH Ohm
SIZE
(METERS)
1 STRUCTURE DC EARTH PIT 1 25 X 3 0 0.00
2 STRUCTURE DC EARTH PIT 2 25 X 3 0 0.00
3 STRUCTURE DC EARTH PIT 3 25 X 3 0 0.00
4 STRUCTURE DC EARTH PIT 4 25 X 3 0 0.00
5 INVERTER & ACDB AC EARTH PIT 1 25 X 6 0 0.00
6 ISOLATOR & METERING AC EARTH PIT 2 50 X 6 0 0.00
7 INVERTER & ACDB AC EARTH PIT 1 50 X 6 0 0.00
8 ISOLATOR & METERING AC EARTH PIT 2 50 X 6 0 0.00
9 LIGHTING ARRESTOR LA EARTH PIT 1 50 X 6 0 0.00
10 LIGHTING ARRESTOR LA EARTH PIT 2 50 X 6 0 0.00
where,
rc = Resistivity of the infill material in ohm-m = 5.80 ohm-m [As per Indelec catalogue]
Bore dia-50mm- Rod dia
0.0328
D = Diameter of the infill material in m = m 17.2mm = 32.8mm
l = Length of the rod or pipe in m = 3 m
d= Diameter of the rod in m 0.0172 m [As per Indelec catalogue]
(As per Soil test report
r= Resistivity of the soil in ( ohm-m) =
100.00 ohm-m and for Average refer
Resistvity detail)
R= 29.8982 ohms
Total electrodes considered = 6 Nos.
288.59 A
Corrission Effect (1 % Every Year and calculate for 25 years)
Area of Cross Section (A) = Fault Current (If) X Fault Current Time √(t)/ Material Constant (K)
Effective
Rs2 = 2.10 ohms Resistance(Re) 1.48
LA EARTHING
Resistance of Earth strip as per IS: 3043
40 Meters length of earth strip of size 50 X 6 mm GI is burried in the plant at 100 mm depth.
Rs = 100 r loge 4Lohms
2p l w
where,
r= resistivity of the soil in ( ohm-m) = 100.00 ohm-m
l= length of the strip in cm = 4000 cm [As per Layout]
w= width of the strip in cm = 5 cm
Effective
Rs3 = 3.21 ohms Resistance(Re) 1.95
mtr long
ohms
NE DIAGRAM
DATASHEET
stant (K)
NE DIAGRAM
DATASHEET
TASHEET
l Constant (K)
s per Layout]
ohms
s per Layout]
ohms
s per Layout]
ohms