L N
S2 Voltage Current Power Overcurrent
Crkt. No. Description No. of Outlets Size of Wire Size of Conduit
(E) (Amps) (VA) Protection
2
2.0 mm2 stranded 12.7 mm. Ø PVC 60AT
1 1 8 230 1.11 255 15AT
32 VA CFL/LED Lamp THHN/THWN Cu. Tube 15AT
Wire
S2 20AT Circuit 1
3.5 mm2 stranded 12.7 mm. Ø PVC
2 32 VA CFL/LED Lamp 6 230 0.83 191 THHN/THWN Cu. 20AT
S2 Tube
Circuit 2
Wire 20AT
3.5 mm2 stranded 12.7 mm. Ø PVC
3 Special Purpose Outlet 2 230 3.91 899 THHN/THWN Cu. 20AT 20AT Circuit 3
Tube
Wire
Circuit 4 20AT
3.5 mm2 stranded 12.7 mm. Ø PVC
4 C.O./ Exhaust Outlet 7 230 8.77 2017 THHN/THWN Cu. Tube 20AT
Wire 20AT Circuit 5
2
3.5 mm stranded 12.7 mm. Ø PVC Circuit 6
S2 5 1 HP ACU 1 230 8.0 1840 THHN/THWN Cu. Tube 20AT
Wire
Main Conduit
LIGHTING LAYOUT
Incoming Single
Phase Supply LEGENDS & SYMBOLS
13.2kV Primary
Utility Line 32 VA LED Lamp 1 Circuit Homerun Electrical Supply Line (Lightings)
Voltage
Fuse Cut-out Convenience Outlet Electrical Supply Line (Power)
M Single Phase Kilowatt-Meter
3
Air Conditioning Unit Outlet
L Live Wire
Single Phase
4 M 60 Hertz
kWhr Meter NOTES AND SPECIFICATIONS
2 sets - 14mm2 THHN/THWN Cu. Wire 1. All electrical works and installation shall conform or comply with provision of the latest edition of the Philippine Electrical Code,
in 20mmØ PVC 40 Conduit local ordinances, rules and regulations of the local enforcing authority and the requirements of local electric company.
2. All electrical materials to be used shall be approved type and standard for the purpose and regulations. Unless otherwise
specified, the minimum size of wire to be used shall not be less than 2.0 mm2 (#14 AWG) THHN/THWN for lighting outlets and
5 not less than3.5 mm2 (#12 AWG) THN/THWN for power outlets. The main service entrance wire to be used is 14 mm2 (#6 AWG)
THNN/THWN Copper wire.
Pa
ne 3. The type of service entrance to be used shall be 230 volts, single-phase, 60 hertz.
lB
oa
rd 4. All electrical layout are diagrammatic only and can be altered during construction
5. All materials to be used shall be new and of approved type for both location and intended use.
POWER LAYOUT SINGLE LINE DIAGRAM
6. All electrical works shall be under supervision of a duly licensed Registered Electrical Engineer or Registered Master Electrician.
Address:__________________
PTR No.
PLACE
Date
Validity
Tin No.
SAMPLE RESIDENTIAL HOUSE
ELECTRICAL PLAN
JUAN F. DELA CRUZ JAYMARK ROSA
As Shown
E1