www.gminternational.

com

Intrinsically Safe Isolators > Load Cell Input

D5263
I.S. SIL2 Load Cell/Strain Gauge Bridge Repeater
The Load Cell/Strain Gauge Bridge Repeater D5263 module is a unit TECHNICAL DATA
suitable for applications requiring SIL 2 level in safety related Supply
systems for high risk industries. The unit acts as a transparent 24 Vdc nom (18 to 30 Vdc), reverse polarity protected.
galvanic isolated interface installed between a weighing indicator in Current consumption: 75 mA @ 24 Vdc with four 350 Ω load cells
Safe Area and a load cell (or group of load cells) in Hazardous Area; connected, typical.
Power dissipation: 1.8 W @ 24 Vdc with four 350 Ω load cells connected,
it appears at the terminals of the indicator as a single load cell typical.
equivalent to the one in the field. It provides a fully floating power
supply voltage with remote sensing capability to load cell located in Input
Up to four 350 Ω load cells in parallel or up to five 450 Ω load cells in
Hazardous Area and repeats, while isolating, the mV signal output to parallel or up to ten 1000 Ω load cells in parallel.
drive a load in Safe Area depending on the host system reference Integration time: 12.5 ms.
voltage. Up to four 350 Ω load cells, or five 450 Ω load cells, or ten Bridge supply voltage: 4.0 Vdc nominal.
1000 Ω load cells can be connected in parallel. The Voltage Bridge output signal: 1 to 4 mV/V.
reference (Safe Area side) is set as an external supply. Output
Same as the input signal.
Output impedance: 500 Ω, typical.
FEATURES Excitation voltage: externally applied between 4 V and 15 V.
SIL 2 / SC 3 Transfer characteristic: linear.
Input from Zone 0 Response time: ≤ 20 ms (10 to 90 % step change).
Installation in Zone 2
Strain Gauge Bridge Transparent Repeater Performance
Up to four 350 Ω load cells in parallel Ref. Conditions: 24 V supply, 23 ± 1 °C ambient temperature.
High Accuracy Calibration accuracy: ≤ ± 0.003 % input FSR, after system calibration.
Three port isolation, Input/Output/Supply Linearity accuracy: ≤ ± 0.002 % input FSR.
Temp. influence: ≤ ± 0.002 % input FSR for a 1 °C change.
Isolation
ORDERING INFORMATION I.S. In/Out 2.5 kV; I.S. In/Supply 2.5 kV; Out/Supply 500 V.
Ordering codes
D5263S: 1 channel Environmental conditions
Operating temperature: temperature limits –40 to +70 °C.
Accessories Storage temperature: temperature limits –45 to +80 °C.
Bus Connector JDFT050, Bus Mounting Kit OPT5096.
Safety Description
Associated apparatus and non-sparking electrical equipment.
OVERALL DIMENSIONS Uo = 7.2 V, Io = 177 mA, Po = 471 mW at terminals 13-14-15-16-17-18.
Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70°C.
Mounting
DIN-Rail 35 mm, with or without Power Bus.
Weight: about 165 g.
Connection: by polarized plug-in disconnect screw terminal blocks to
accommodate terminations up to 2.5 mm² (13 AWG).
Dimensions: Width 22.5 mm, Depth 123 mm, Height 120 mm.

Functional Safety Management Certification:


GM International is certified to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3. In addition, GM International products have been granted I.S.
certificates from the most credited Notified Bodies in the world.
Data specified in this document are merely descriptive of the products and should be integrated with relevant technical specifications. Our products are in constant development and the information
presented herein refers to the time of document issue. No statements concerning a certain condition or suitability for a certain application can be derived from our information. The information given does not
release the user from the obligation of own judgment and verification. Terms & Conditions can be found at our website. For more information refer to istruction manual.
DTS0429-13 Page 1/2 © G.M. International s.r.l.
FUNCTION DIAGRAM
Additional installation diagrams may be found in Instruction Manual.

Hazardous Area Safe Area/Zone 2

Functional Safety Management Certification:


GM International is certified to conform to IEC61508:2010 part 1 clauses 5-6 for safety related systems up to and included SIL3. In addition, GM International products have been granted I.S.
certificates from the most credited Notified Bodies in the world.
Data specified in this document are merely descriptive of the products and should be integrated with relevant technical specifications. Our products are in constant development and the information
presented herein refers to the time of document issue. No statements concerning a certain condition or suitability for a certain application can be derived from our information. The information given does not
release the user from the obligation of own judgment and verification. Terms & Conditions can be found at our website. For more information refer to istruction manual.
DTS0429-13 Page 2/2 © G.M. International s.r.l.

You might also like