TWINVEY Electric Consultancy Danway LLC Saver Glass LLC

Dubai Dubai Ras Al Khaimah

Cable sizing calculation for LV Normal / Emergency Switchboard R960MS04022

A B C D E F G H I J K L M N O

Circuit description Cable Details Current Voltage drop calculation Breaker details
carrying
Total Derated
System Demand Load Current capacity of
From To Connected current
Voltage Diversity load Power Derating cable mV/A/m of Drop per Obtained Individual Overall
Sl.no Load Size in Length rating Total drop Rating Remarks
Factor Factor No of run Factor installed In cable run voltage Drop Drop
Feeder ID Model Type Tripunit
per phase air
Reference Level Reference Room loacation Function Instrument type Level
(kW) (kV) (kW) (A) mm2 Meters (A) (A) mV/A/m Volts Volts Volts (%) (%) (A)

1 R960-TR-01-012 Low voltage Normal / Emergency switchboard 10MQ01N 0.40 2815.20 - 1103.42 0.97 1641.95 1C x 630 4 61 0.68 1027 2787.69 0.170 16.89 4.22 395.78 1.055 1.055 2500 NW25H1 ACB Micrologic 6.0A
+ 2.9 A240
2 R960-TR-01-015 R960-MS-04-022 Low voltage Normal Dispatching Switchboard Switchboard cabinet + 8.4 10MQ04S 0.40 2815.20 - 1103.42 - 2500 NW25H1 ACB Micrologic 6.0A

Emergency supplied and production generators


3 R960-MS-04-025 + 8.4 A270 10MQS02E 0.40 1714.70 - 676.78 0.82 1191.31 4C x 400 3 61 0.62 728 1349.0568 0.165 11.89 3.96 396.04 0.991 0.991 2500 NW25H1 ACB Micrologic 6.0A
control systems

4 + 8.4 R960-TC-20-067 A240 Capacitor Bank Capacitor + 8.4 10Q05 0.40 200 kVar - - 1.00 288.68 4C x 240 2 22 0.68 546 741.03 0.210 1.33 0.67 399.33 0.167 1.222 400 NSX400 MCCB Micrologic 2.3

5 + 8.4 R960-CB-17-722 A108 Ventilation Transformer T01012 room Box Local distribution box + 2.9 25Q02 0.40 7.50 0.70 5.25 0.80 13.53 4C x 16 1 50 0.50 99 49.91 2.500 1.67 1.67 398.33 0.419 1.474 32 NSX100 MCCB TM32D

6 + 8.4 - - Spare - - 25Q03 0.40 22.00 -

Mold Cooling fan cabinet line 92 with VFD Panel


7 + 8.4 R492-VF-13-163 Variable frequency drive panel + 2.9 25Q05 0.40 355.00 0.72 256.49 0.98 522.87 4C x 300 3 149 0.50 628 949.72 0.185 14.36 4.79 395.21 1.197 2.253 800 NT08 H2 ACB Micrologic 6.0A
(Futur)
A116
Convoyer Cooling fan cabinet line 92 with VFD
8 + 8.4 R492-VF-13-164 Variable frequency drive panel + 2.9 25Q06 0.40 55.00 0.60 32.73 0.98 81.01 4C x 120 1 149 0.50 353 177.95 0.370 4.45 4.45 395.55 1.113 2.168 125 NSX160 MCCB TM125D
Panel (Futur)

9 + 8.4 - - Spare - - 25Q07 0.40 355.00 -


R960-MS-04-022
10 + 8.4 R390-AR-01-002 A220 Heavy fuel oil preheater cabinet - + 8.4 26Q03 0.40 240.00 0.60 142.80 0.80 433.03 4C x 240 3 66 0.50 546 825.72 0.21 6.00 2.00 398.00 0.500 1.556 800 NT08 H2 ACB Micrologic 6.0A

-
11 + 8.4 - - Spare - 26Q06 0.40 22.00 -

-
12 + 8.4 - - Spare - 26Q07 0.40 22.00 -

-
13 + 8.4 - - Spare - 26Q09 0.40 22.00 -

Batch Room Air conditionning Treatment Panel


14 + 8.4 R200-LP-10-901 Local control panel 20Q02 0.40 22.00 0.50 11.00 0.80 39.69 4C x 70 1 264 0.62 251 155.04 0.60 6.29 6.29 393.71 1.572 2.627 125 NSX160 MCCB TM125D
No.1 (Emergency Redundant)
D610 + 3.6
Batch Room and Batch Process Area lighting -
15 + 8.4 R200-CD-09-802 400 / 220 V Control Distribution Panel 20Q03 0.40 50.00 0.70 35.00 0.80 90.21 4C x 120 1 264 0.62 353 218.05 0.37 8.81 8.81 391.19 2.203 3.258 160 NSX160 MCCB TM160D
Socket Panel with transorfmer 400/220 V
Treatment Air for A220-A250-A270 of building in
16 R960-MS-04-022 + 8.4 R960-LP-10-910 A270 + 8.4 20Q05 0.40 61.00 0.70 42.70 0.80 110.06 4C x 120 1 88 0.50 353 177.95 0.37 3.58 3.58 396.42 0.896 1.951 160 NSX160 MCCB TM160D
level +8,40
Treatment Air Panel No.1 for A220 of building in
16.1 + 8.4 R960-LP-10-911 + 8.4 - 0.40 12.00 - - 0.80 21.65 4C x 16 1 27.5 0.50 99 49.91 2.50 1.49 1.49 398.51 0.372 2.323 - - - -
level +8,40
A220
Treatment Air Panel No.2 for A220 of building in
16.2 + 8.4 R960-LP-10-912 + 8.4 - 0.40 12.00 - - 0.80 21.65 4C x 16 1 27.5 0.50 99 49.91 2.50 1.49 1.49 398.51 0.372 2.696 - - - -
level +8,40
Treatment Air Panel No.1 for A250 of building in
16.3 + 8.4 R960-LP-10-913 Local control panel + 2.9 - 0.40 5.50 - - 0.80 9.92 4C x 16 1 72.6 0.50 99 49.91 2.50 1.80 1.80 398.20 0.450 3.146 - - - -
level +8,40
R960-LP-10-910 A250
Treatment Air Panel No.2 for A250 of building in
16.4 + 8.4 R960-LP-10-914 + 8.4 - 0.40 5.50 - - 0.80 9.92 4C x 16 1 72.6 0.50 99 49.91 2.50 1.80 1.80 398.20 0.450 3.596 - - - -
level +8,40
Treatment Air Panel No.1 for A270 of building in
16.5 + 8.4 R960-LP-10-915 + 8.4 - 0.40 5.50 - - 0.80 9.92 4C x 16 1 11 0.50 99 49.91 2.50 0.27 0.27 399.73 0.068 3.664 - - - -
level +8,40
A270
Treatment Air Panel No.2 for A270 of building in
16.6 + 8.4 R960-LP-10-916 + 8.4 - 0.40 5.50 - - 0.80 9.92 4C x 16 1 11 0.50 99 49.91 2.50 0.27 0.27 399.73 0.068 3.732 - - - -
level +8,40
Treatment Air No.1 Panel for A201 of building in
17 + 8.4 R960-LP-10-920 A201 Local Control Panel + 8.4 20Q06 0.40 5.00 0.5 2.50 0.80 9.02 4C x 16 1 99 0.50 99 49.91 2.50 2.23 2.23 397.77 0.558 1.614 16 NSX100 MCCB TM16D
level +8,40
Left Hot End Furnace and Underground lighting
18 + 8.4 R960-CD-09-034 A270 400 / 220 V Control Distribution Panel + 8.4 20Q07 0.40 75.00 0.60 44.63 0.80 135.32 4C x 120 1 11 0.50 353 177.95 0.37 0.55 0.55 399.45 0.138 1.193 160 NSX160 MCCB TM160D
with transformer 400/220V N°1 Panel

19 + 8.4 RP-960-UP-15-042 A230 DC UPS power system - + 8.4 20Q09 0.40 10.00 0.40 4.00 0.80 18.04 4C x 16 1 33 0.50 99 49.91 2.50 1.49 1.49 398.51 0.372 1.428 25 NSX100 MCCB TM25D
R960-MS-04-022
20 + 8.4 - - Spare - - 21Q02 0.40 60.00 -

Furnace Heating-Up No.1 & No.2 control Panel


21 + 8.4 R390-LP-10-100 A101 8.4 21Q03 0.40 22.00 0.01 0.22 0.80 39.69 4C x 25 1 28 0.50 131 66.04 1.65 1.80 1.80 398.20 0.450 1.506 50 NSX100 MCCB TM50D
(Stand-by for supply No.1)
Local control panel
22 + 8.4 R960-LP-10-940 A290 Emergency Chiller for Electrical Rooms Panel + 3.9 21Q05 0.40 80.00 0.26 20.40 0.80 144.34 4C x 150 1 63 0.50 406 204.66 0.30 2.72 2.72 397.28 0.679 1.734 200 NSX250 MCCB TM200D

Local load swith fuses box for Oil free screws 7


23 R960-MS-04-022 + 8.4 R960-CB-17-462 Local power box - 0.40 160.00 0.28 44.96 0.98 235.66 4C x 240 2 149 0.50 546 550.48 0.21 7.35 3.67 396.33 0.919 1.974 400 NSX400 MCCB Micrologic 2.3
bar air compressor No.2 Panel
A103 + 2.9
Oil free screws 7 bar air compressor No.22
23.1 R960-CB-17-462 + 2.9 R960-VF-13-122 Variable frequency drive panel 21Q06 0.40 160.00 0.28 44.96 0.98 235.66 -
(1110Nm3/h) with VFD Panel
Water Tower plant & LPG / Fuel Area lighting -
24 R960-MS-04-022 + 8.4 R120-CD-09-807 400 / 220 V Control Distribution Panel + 2.9 21Q07 0.40 50.00 0.70 35.00 0.80 90.21 4C x 120 1 105 0.62 353 218.05 0.370 3.49 3.49 396.51 0.872 1.927 125 NSX160 MCCB TM125D
Socket with transformer 400/220V Panel
F820
Air conditionning Traitement Panel
24.1 R120-CD-09-807 + 8.4 R120-CB-17-951 local distribution box + 3.6 - 0.40 1.50 - - 0.80 2.71 4C x 16 1 28 0.62 99 61.15 2.50 0.19 0.19 399.81 0.047 1.974 - - - -
( Reception office)
Recirculating cooling Water Furnace (900 Kwth)
25 + 8.4 R960-LP-10-481 F801 Local control panel + 2.9 21Q09 0.40 33.00 0.43 14.03 0.80 59.54 4C x 70 1 28 0.62 251 155.04 0.60 0.98 0.98 399.02 0.246 1.301 80 NSX100 MCCB TM80D
Tower N°1 Panel

26 + 8.4 - - Spare - - 22Q02 0.40 37.00 -

27 + 8.4 - - Spare - - 22Q03 0.40 11.00 -

28 R960-MS-04-022 + 8.4 - - Spare - - 22Q05 0.40 5.50 -

29 + 8.4 R960-LP-10-051 F860 Vapouriser LPG Pumps No.1 Panel Local control panel + 2.9 22Q06 0.40 45.00 0.43 19.13 0.80 81.19 4C x 150 1 347 0.62 406 250.79 0.30 8.44 8.44 391.56 2.110 3.165 100 NSX100 MCCB TM100D

30 + 8.4 - - Spare - - 22Q07 0.40 2.20 -

31 + 8.4 - - Spare - - 22Q09 0.40 30.00 -

32 R960-MS-04-022 + 8.4 R960-CS-07-007 A240 Change Switch Panel (LV) Switch control panel + 8.4 - 0.40 425.50 - - 0.80 767.72 4C x 300 3 28 0.50 628 949.72 0.19 3.91 1.30 398.70 0.325 1.381 1000 NT10 H2 ACB Micrologic 6.0A

Furnace Main Power Supply Cabinet: +P1


32.1 R960-CS-07-007 + 8.4 R390-AR-01-001 A220 Main distribution cabinet + 2.9 23Q02 0.40 425.50 0.43 180.84 0.80 767.72 4C x 300 3 94 0.50 628 949.72 0.19 13.28 4.43 395.57 1.107 2.162 -
(HORN)

33 R960-MS-04-022 + 8.4 R960-CS-07-008 A240 Change Switch Panel (LV) Switch control panel + 8.4 23Q03 0.40 125.00 - - 0.80 225.53 4C x 150 2 28 0.50 406 409.33 0.30 1.86 0.93 399.07 0.233 1.288 400 NSX400 MCCB Micrologic 2.3

Fire Water Pump (300m3/h) and Jockey Water


33.1 R960-CS-07-008 + 8.4 R960-PD-08-400 F820 Power distribution cabinet (400V) + 2.9 - 0.40 125.00 0.11 13.13 0.80 225.53 4C x 150 2 105 0.62 406 501.57 0.30 7.07 3.54 396.46 0.884 2.172 -
Pump (30m3/h) control Panel

34 R960-MS-04-022 + 8.4 R960-CS-07-009 A240 Change Switch Panel (LV) Switch control panel + 8.4 23Q05 0.40 55.00 - - 0.98 81.01 4C x 70 1 28 0.50 251 126.53 0.600 1.34 1.34 398.66 0.334 1.390 125 NSX160 MCCB TM125D

34.1 R960-CS-07-009 + 8.4 R960-CB-17-464 Local load switch fuse box Local power box + 2.9 - 0.40 55.00 - - 0.98 81.01 4C x 70 1 149 0.50 251 126.53 0.600 7.22 7.22 392.78 1.804 3.194 -
A103
Lubricated screws 7 bar air compressor N°4
34.2 R960-CB-17-464 + 2.9 R960-VF-14-124 Soft starter panel + 2.9 - 0.40 55.00 0.01 0.55 0.98 81.01 -
(500Nm3/h) Panel N° 1 with Soft Starter Panel

35 R960-MS-04-022 + 8.4 R960-CS-07-010 A240 Change Switch Panel (LV) Switch control panel + 8.4 23Q07 0.40 5.50 - - 0.80 9.92 4C x 16 1 28 0.50 99 49.91 2.50 0.68 0.68 399.32 0.171 1.226 16 NSX100 MCCB TM16D

Hot Cullet Return convoyers Control Cabinet


35.1 R960-CS-07-010 + 8.4 R960-MC-05-772 A116 Local control panel + 2.9 - 0.40 5.50 0.43 2.34 0.80 9.92 4C x 16 1 149 0.50 99 49.91 2.50 3.68 3.68 396.32 0.921 2.147 -
(Common for 91/92/93/94)

36 R960-MS-04-022 + 8.4 R960-CS-07-011 A240 Change Switch Panel (LV) Switch control panel + 8.4 23Q09 0.40 35.00 - - 0.80 63.15 4C x 70 1 28 0.50 251 126.53 0.60 1.04 1.04 398.96 0.260 1.316 80 NSX100 MCCB TM80D

Left Hot Cullet Return Scraper Control Lines


36.1 R960-CS-07-011 + 8.4 R960-MC-05-771 A102 Local control panel + 2.9 - 0.40 35.00 0.43 14.88 0.80 63.15 4C x 70 1 149 0.50 251 126.53 0.60 5.63 5.63 394.37 1.407 2.723 -
91/92 Cabinet

37 R960-MS-04-022 + 8.4 R960-CS-07-012 A240 Change Switch Panel (LV) Switch control panel + 8.4 24Q02 0.40 55.00 - - 0.80 99.23 4C x 120 1 28 0.50 353 177.95 0.370 1.01 1.01 398.99 0.252 1.308 125 NSX160 MCCB TM125D

Page 1 of 5
TEC293-DAN-SG-CSC-01 -REV 00
TWINVEY Electric Consultancy Danway LLC Saver Glass LLC
Dubai Dubai Ras Al Khaimah

Cable sizing calculation for LV Normal / Emergency Switchboard R960MS04022

A B C D E F G H I J K L M N O

Circuit description Cable Details Current Voltage drop calculation Breaker details
carrying
Total Derated
System Demand Load Current capacity of
From To Connected current
Voltage Diversity load Power Derating cable mV/A/m of Drop per Obtained Individual Overall
Sl.no Load Size in Length rating Total drop Rating Remarks
Factor Factor No of run Factor installed In cable run voltage Drop Drop
Feeder ID Model Type Tripunit
per phase air
Reference Level Reference Room loacation Function Instrument type Level
(kW) (kV) (kW) (A) mm2 Meters (A) (A) mV/A/m Volts Volts Volts (%) (%) (A)

Batch plant Emergency Convoyer Cabinet


37.1 R960-CS-07-012 + 8.4 R140-MC-05-xxxx D610 Main distribution cabinet + 3.6 - 0.40 55.00 0.80 44.00 0.80 99.23 4C x 120 1 264 0.62 353 218.05 0.370 9.69 9.69 390.31 2.423 3.731 -
(ZIPPE)

38 R960-MS-04-022 + 8.4 R960-CS-07-013 A240 Change Switch Panel (LV) Switch control panel + 8.4 24Q03 0.40 60.00 - - 0.80 108.26 4C x 120 1 28 0.50 353 177.95 0.370 1.10 1.10 398.90 0.275 1.331 160 NSX160 MCCB TM160D

38.1 R960-CS-07-013 + 8.4 R960-UP-15-043 A117 AC UPS for cold end process UPS included distribution board + 2.9 - 0.40 60.00 0.50 30.00 0.80 108.26 4C x 120 1 150 0.50 353 177.95 0.370 5.99 5.99 394.01 1.498 2.829 - - - -

39 R960-MS-04-022 + 8.4 R960-CS-07-014 A240 Change Switch Panel (LV) Switch control panel + 8.4 24Q05 0.40 60.00 - - 0.80 108.26 4C x 120 1 28 0.50 353 177.95 0.370 1.10 1.10 398.90 0.275 1.331 - - - -

AC- UPS (230VAC) Uninterruptible Power


39.1 R960-CS-07-014 + 8.4 R960-UP-15-041 A280 UPS included distribution board + 8.4 - 0.40 60.00 0.50 30.00 0.80 108.26 4C x 120 1 28 0.50 353 177.95 0.370 1.10 1.10 398.90 0.275 1.606 - - - -
Supply for Hot End Process

40 R960-MS-04-022 (MDB) + 8.4 R960-CS-07-015 A240 Change Switch Panel (LV) Switch control panel + 8.4 24Q07 0.40 35.00 - - 0.80 63.15 4C x 95 1 28 0.50 304 153.25 0.450 0.78 0.78 399.22 0.195 1.251 80 NSX100 MCCB TM100D

Cullet Silos Filling local Control Cabinet (To be


40.1 R960-CS-07-015 + 8.4 R150-MC-05-150 D610 Main Distribution MCC Cabinet + 3.6 - 0.40 35.00 0.80 28.00 0.80 63.15 4C x 95 1 264 0.62 304 187.78 0.450 7.50 7.50 392.50 1.876 3.126 -
confirmed by Elimko)

41 R960-MS-04-022 (MDB) + 8.4 R960-CS-07-016 A240 Change Switch Panel (LV) Switch control panel + 8.4 24Q09 0.40 100.00 - - 0.80 180.43 4C x 240 1 28 0.50 546 275.24 0.21 1.04 1.04 398.96 0.260 1.316 250 NSX250 MCCB TM250D

Water and Fuel Oil Pumps :Motor Control


41.1 R960-CS-07-016 + 8.4 R120-MC-05-775 F820 Local Motor Control centre (400 V) + 2.9 - 0.40 100.00 0.60 59.50 0.80 180.43 4C x 240 1 105 0.62 546 337.26 0.21 3.96 3.96 396.04 0.990 2.306 -
Center Cabinet

1.0. Cable calculation Note:


1.1. Derating factors 2.0. Standard of cable
Multicore cable Single core cable Cable 3.0 Maximum currents permitted of the cables according to the standard conditions : Refer COLUMN - K
Description Reference Description 4.0 Maximum currents permitted of the cables according to the site conditions : Refer COLUMN - L
Incomer from
Process area Other area Other area Feeders
transformer 5.0 Voltage drop calculation : Refer COLUMN-M.
o o o
Ambient Temperature 60 C 45 C 45 C Saverglass specification Conductor Copper
Correction factor 0.71 0.87 0.87 Insulation XLPE
No of Cables in tray 6 6 9 Voltage 0.6/1kV
IEC-60364-5-52
No of trays 3 2 3 Conductor type Stranded
Correction factor 0.71 0.71 0.78 Sheathing PVC + Flame retardant + Low smoke
No of Cores Single core Four core
Total derating factor 0.50 0.62 0.68 -
Armouring Aluminium wire * Steel wire **

1.2.Load current at the incomer is calculated based on the demand load.


1.3. Load current at the feeders is calculated based on the total connected load of respective feeder. * Armour shall be connected to earth at one end only.
1.4. Diversity factor (COLUMN-E) & Power factor (COLUMN-G) are referred from balance power (118163-47EG-7501-05 Rev.5) ** The Electricity wiring regulations 2007 clause (7.5.2)
1.5. Cable size for the incomer from the R960-MS-04-026 (Low voltage normal dispatching switchboard cabinet) to be finalised based on the load schedule. a . Cable maximum withstand conductor temperature in continous operation shall be 90 o C
1.6 Load details are referred from Electrical bill of material list (118163-47EL-7580-05). o
b. Cable temperature rise for limited period shall be 135 C
o
c. Cable final withstand temperature under fault shall be 250 C

Page 2 of 5
TEC293-DAN-SG-CSC-01 -REV 00
One-Line Diagram - R960-MS-04-022 (Load Flow Analysis)

U2
476.314 MVAsc
0 V
Bus1 2180 kW 1100
11 kV 1536 kvar
2180 kW
1536 kvar

Gen - MS04025
1.36 MW
R960TR01010
1.5 MVA
Bus2 6 V Bus85
0.4 kV 393. 0.4 kV
From Rescued transformer
2138 kW
Cable1 1283 kvar 0.4 kV
Cable71

Cable2
±
±
I>
I>

I>
Bus3 1468 kW Bus84 6 V
0.4 kV 980 kvar 0.4 kV 386.

7 kW 359 kW 56 kW 223 kW 20 kW 46 kW 57 kW 5 kW 70 kW 9 kW 21 kW 74 kW 161 kW 46 kW 31 kW 41 kW 392 kW 116 kW 56 kW 5 kW 32 kW 50 kW 55 kW 56 kW 32 kW 92 kW


6 V
5 kvar 75 kvar 11 kvar 167 kvar 386. 15 kvar 34 kvar 42 kvar 3 kvar 52 kvar 7 kvar 15 kvar 56 kvar 34 kvar 34 kvar 23 kvar 31 kvar 294 kvar 86 kvar 11 kvar 4 kvar 24 kvar 37 kvar 41 kvar 42 kvar 24 kvar 69 kvar

Cable38 Cable36 Cable43 Cable46 Cable48 Cable50


Cable5 Cable4 Cable9 Cable6 Cable7 Cable8 Cable14 Cable15 Cable16 Cable12 Cable13 Cable17 Cable54 Cable21 Cable22 Cable23 Cable55 Cable26 Cable59 Cable28 Cable29 Cable30 Cable31 Cable33 Cable52 Cable56 Cable61 Cable63 Cable67 Cable69
Cable24 Cable32

Bus48 3 V
Bus55 7 V Bus58 Bus61
6 V 385. 0.4 kV 385. 2 V V Bus65 V Bus68 V
386.
0.4 kV 0.4 kV 385. 0.4 kV 386 385.
7
385.
7 Bus71 6 V Bus74 6 V
Bus80 9 V Bus83 V
Bus36
0.4 kV 0.4 kV 0.4 kV 385. 0.4 kV 385. 0.4 kV 385. 0.4 kV 385.
6
Bus4 2 V Bus5 Bus6 2 V Bus7 1 V Bus8 Bus9 7 V Bus10 Bus14 Bus15 Bus37 8 V V Bus49 Bus20 Bus21 Bus23 Bus50 Bus27 385.7
V Bus30 390 kW 115 kW
0.4 kV 385. 382. 382. 0.4 kV 384. 378. Bus17
84.8 .1 V
3860.4
4 V
385. 0.4 kV 385.
1 V
384
V Bus25
82.9
V Bus28 Bus29 Bus31 7 V
Bus42 Bus39 56 kW 5 kW 32 kW 50 kW
0.4 kV 0.4 kV 0.4 kV 0.4 kV 0.4 kV 0.4 kV 0.4 kV 0.4 kV Bus13 V 0.4 kV 0.4 kV 3 0.4 kV kV 0.4 kV 0.4 kV 0.4 kV 3 0.4 kV 0.4 kV 0.4 kV 0.4 kV 378. 0.4 kV 293 kvar 86 kvar 11 kvar 4 kvar 55 kW 56 kW 32 kW 92 kW
0.4 kV 3 81.1 0.4 kV 0.4 kV 3 VBus54 7 V Bus57 24 kvar 37 kvar 41 kvar 42 kvar 24 kvar 69 kvar
Bus46 385. 385. 2 V V 7 V Bus67 7 V
7 kW 355 kW 55 kW 222 kW 45 kW 5 kW 70 kW 9 kW 20 kW 74 kW 160 kW 31 kW 0.4 kV 385. Bus60 386 Bus64 385. 385. 6 V Bus73 6 V Bus79 9 V Bus82 6 V
5 kvar 72 kvar 11 kvar 166 kvar 20 kW 34 kvar 3 kvar 52 kvar 7 kvar 15 kvar 55 kvar 32 kvar 23 kvar
40 kW 0.4 kV 0.4 kV 0.4 kV 0.4 kV 0.4 kV
Bus70 385. 385. 385. 385.
15 kvar 30 kvar 390 kW 115 kW 0.4 kV 0.4 kV 0.4 kV 0.4 kV
56 kW 5 kW 32 kW 50 kW
293 kvar 86 kvar 11 kvar 4 kvar 55 kW 56 kW 32 kW 92 kW
24 kvar 37 kvar 41 kvar 42 kvar 24 kvar 69 kvar
R960-TC-20-067 R960-CB-17-722 Spare R492-VF-13-163 R492-VF-13-164 Spare-7 F390-AR-01-002 Spare-1 Spare-6 Spare-8 R200-LP-10-901 R200-LP-10-902 R960-LP-10-920 R960-CD-09-034 R960-UP-15-042 Spare-9 R390-LP-10-100 R960-LP-10-940 R960-LP-10-481 Spare-10 Spare-11 Spare-4 R960-LP-10-051 Spare-12
200 kvar 9.4 kVA 27.5 kVA 55 kW 444 kVA 300 kVA 27.5 kVA 27.5 kVA 27.5 kVA 27.5 kVA 62.5 kVA 6.3 kVA 93.8 kVA 12.5 kVA 75 kVA 27.5 kVA 100 kVA R960-VF-13-122 Spare-13 Cable44
355 kW 160 kW 41.3 kVA 46.3 kVA 13.8 kVA 6.9 kVA 56.3 kVA 2.8 kVA 37.5 kVA Cable47 Cable45 Cable49 Cable51 Cable53 Cable60 Cable62 Cable66 Cable68

Bus47 Bus51
V 3 V Bus56
1 VBus59
0.4 kV 381. 0.4 kV 382. 377.
4
383
V Bus62 Bus66
7 V 1 V Bus69 Bus72 Bus78 Bus81
0.4 kV 0.4 kV 380. 377. 3 V 6 V 3 V 8 V
0.4 kV 0.4 kV 0.4 kV 380. 0.4 kV 384. 0.4 kV 379. 0.4 kV 381.
386 kW 114 kW 55 kW 5 kW
290 kvar 86 kvar 32 kW 49 kW 54 kW 55 kW 31 kW 91 kW
11 kvar 4 kvar 24 kvar 37 kvar
R390-AR-01-001 R960-PD-08-400 41 kvar 42 kvar 24 kvar 68 kvar
R960-VF-14-124 R960-MC-05-772 R960-MC-05-771 R140-MC-05-XXX
532 kVA 156 kVA 6.9 kVA R960-UP-15-043 R960-UP-15-041 R150-MC-05-150 R120-MC-05-775
55 kW 43.8 kVA 68.8 kVA 75 kVA 75 kVA 43.8 kVA 125 kVA

R960-LP-10-910 R120-CD-09-807
V 5 V
0.4 kV 383.
4 0.4 kV 383.

11 kW 11 kW 5 kW 5 kW 5 kW 5 kW 14 kW 1 kW 44 kW
8 kvar 8 kvar 4 kvar 4 kvar 4 kvar 4 kvar 10 kvar 1 kvar 33 kvar

Cable35 Cable34 Cable18 Cable20 Cable19 Cable25 Cable27 Cable58 Cable57

Bus38 Bus26 Bus16 Bus19 Bus18 Bus22 Bus24 7 V


Bus53 Bus52 7 V
V V kV V 0.4 kV 0.4
V kV 380. 0.4 kV 0.4 kV 381.
0.4 kV 2 0.4 kV 0.4
2 9 0.4 kV 0.4 kV
9 V 2 V 2 3 V
382. 382. 381. 381. 383. 383. 383.
11 kW 11 kW 5 kW 5 kW 5 kW 5 kW 14 kW 1 kW 44 kW
8 kvar 8 kvar 4 kvar 4 kvar 4 kvar 4 kvar 10 kvar 1 kvar 33 kvar
R960-LP-10-911 R960-LP-10-912 R960-LP-10-915 R960-LP-10-916 Other loads-2 R120-CB-17-951 Other Loads-3
R960-LP-10-913 R960-LP-10-914
15 kVA 15 kVA 6.9 kVA 6.9 kVA 6.9 kVA 6.9 kVA 18.8 kVA 1.9 kVA 60.6 kVA

Page 3 of 5
page 1 19:07:17 Jul 15, 2012 Project File: R960-MS-04-022
Project: Saver Glass
ETAP Page: 1
Location: RAS AL KHAIMAH 11.1.0C Date: 07-15-2012
Contract: TEC293 SN: PV1227TWIN
Engineer: PV/PK Revision: Base
Study Case: LF
Filename: R960-MS-04-022 Config.: Normal

Branch Losses Summary Report

Vd
CKT / Branch From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
% Drop
ID MW Mvar MW Mvar kW kvar From To in Vmag
R960TR01010 2.180 1.536 -2.138 -1.283 42.2 253.3 100.0 98.4 1.59
Cable1 2.138 1.283 -2.112 -1.239 25.6 44.1 98.4 96.7 1.76
Cable5 0.007 0.005 -0.007 -0.005 0.0 0.0 96.7 96.3 0.35
Cable6 0.056 0.011 -0.055 -0.011 0.6 0.2 96.7 95.5 1.13
Cable8 0.223 0.167 -0.222 -0.166 1.1 0.8 96.7 96.2 0.49
Cable9 0.359 0.075 -0.355 -0.072 3.6 3.2 96.7 95.6 1.10
Cable38 0.000 0.000 0.000 0.000 96.7 96.7 0.00
Cable12 -0.020 -0.015 0.020 0.015 0.4 0.1 95.3 96.7 1.38
Cable18 -0.005 -0.004 0.005 0.004 0.0 0.0 95.5 95.8 0.37
Cable17 -0.005 -0.003 0.005 0.003 0.0 0.0 96.2 96.7 0.46
Cable19 -0.005 -0.004 0.005 0.004 0.0 0.0 95.8 95.8 0.06
Cable20 -0.005 -0.004 0.005 0.004 0.0 0.0 95.5 95.8 0.37
Cable21 -0.009 -0.007 0.009 0.007 0.0 0.0 96.3 96.7 0.30
Cable25 -0.005 -0.004 0.005 0.004 0.0 0.0 95.8 95.8 0.06
Cable23 -0.020 -0.015 0.021 0.015 0.1 0.0 96.3 96.7 0.37
Cable27 -0.014 -0.010 0.014 0.010 0.1 0.0 95.2 95.8 0.68
Cable26 -0.160 -0.032 0.161 0.034 1.3 1.5 95.7 96.7 0.94
Cable34 -0.011 -0.008 0.011 0.008 0.1 0.0 95.5 95.8 0.30
Cable28 -0.031 -0.023 0.031 0.023 0.1 0.0 96.4 96.7 0.22
Cable32 -0.040 -0.030 0.041 0.031 1.0 0.4 94.7 96.7 1.99
Cable13 -0.045 -0.034 0.046 0.034 1.1 0.4 94.7 96.7 1.96
Cable35 -0.011 -0.008 0.011 0.008 0.1 0.0 95.5 95.8 0.30
Cable44 0.390 0.293 -0.386 -0.290 4.0 3.6 96.3 95.3 1.07
Cable43 -0.390 -0.293 0.392 0.294 1.2 1.1 96.3 96.7 0.32
Cable54 -0.070 -0.052 0.070 0.052 0.1 0.0 96.5 96.7 0.12
Cable55 -0.074 -0.055 0.074 0.056 0.6 0.3 96.0 96.7 0.65
Cable47 -0.114 -0.086 0.115 0.086 1.2 0.5 95.6 96.4 0.84
Cable57 -0.044 -0.033 0.044 0.033 0.3 0.1 95.4 95.9 0.44
Cable58 -0.001 -0.001 0.001 0.001 0.0 0.0 95.8 95.9 0.04
Cable46 -0.115 -0.086 0.116 0.086 0.3 0.1 96.4 96.7 0.22
Cable45 -0.055 -0.011 0.056 0.011 1.1 0.2 94.3 96.3 1.94
Cable48 -0.056 -0.011 0.056 0.011 0.2 0.0 96.3 96.7 0.36
Cable49 -0.005 -0.004 0.005 0.004 0.1 0.0 95.8 96.5 0.75
Cable50 -0.005 -0.004 0.005 0.004 0.0 0.0 96.5 96.7 0.14
Cable51 -0.032 -0.024 0.032 0.024 0.6 0.1 95.2 96.4 1.24

Page 4 of 5
Project: Saver Glass
ETAP Page: 2
Location: RAS AL KHAIMAH 11.1.0C Date: 07-15-2012
Contract: TEC293 SN: PV1227TWIN
Engineer: PV/PK Revision: Base
Study Case: LF
Filename: R960-MS-04-022 Config.: Normal

Vd
CKT / Branch From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
% Drop
ID MW Mvar MW Mvar kW kvar From To in Vmag

Cable52 -0.032 -0.024 0.032 0.024 0.1 0.0 96.4 96.7 0.23
Cable53 -0.049 -0.037 0.050 0.037 1.4 0.5 94.3 96.4 2.15
Cable56 -0.050 -0.037 0.050 0.037 0.1 0.1 96.4 96.7 0.23
Cable60 -0.054 -0.041 0.055 0.041 0.9 0.3 95.1 96.4 1.33
Cable61 -0.055 -0.041 0.055 0.041 0.2 0.1 96.4 96.7 0.25
Cable62 -0.055 -0.042 0.056 0.042 0.2 0.1 96.1 96.4 0.25
Cable63 -0.056 -0.042 0.056 0.042 0.2 0.1 96.4 96.7 0.25
Cable66 -0.031 -0.024 0.032 0.024 0.7 0.2 94.8 96.5 1.65
Cable67 -0.032 -0.024 0.032 0.024 0.1 0.0 96.5 96.7 0.18
Cable68 -0.091 -0.068 0.092 0.069 0.9 0.7 95.4 96.4 0.96
Cable69 -0.092 -0.069 0.092 0.069 0.2 0.2 96.4 96.7 0.26
Cable24 0.057 0.042 -0.056 -0.042 0.6 0.2 96.7 95.8 0.80
Cable59 0.046 0.034 -0.046 -0.034 0.5 0.2 96.7 95.9 0.79

93.3 312.9

Page 5 of 5