TruPlasma Bias 4036 Rev.3.1.1.1.P.09.F
TruPlasma Bias 4036 Rev.3.1.1.1.P.09.F
DC Generator
USER MANUAL
Notice!
This operating manual is required for the safe operation
of the TruPlasma Bias 4036 Generators. Therefore, you should
keep the operating manual close to the unit.
TruPlasma Bias 4000 Family
Operating instructions
for TruPlasma Bias 4036
Generator
HUETTINGER Electronic
Sp. z o.o.
Marecka 47
PL - 05-220 Zielonka
tel: +48 22 761 38 00
fax: +48 22 761 38 01
[email protected]
www.huettinger.com
Headquarters
All rights reserved. This manual is purposed to enable the reader to install and
operate safely the equipment described below. Making copies of any part of this manual
for any purpose other than these is a violation of Poland copyright law.
Table of contents
page
5. INSTALLATION .....................................................................................................15
5.1. Installation site .................................................................................................................................. 15
5.2. Fusing ................................................................................................................................................... 15
10. INTERFACES......................................................................................................34
10.1. RS232 communication protocol for TruPlasma Bias 4036 units ............................................. 34
10.2. Profibus communication protocol ................................................................................................. 41
The TruPlasma Bias 4036 Power Supply is designed to power industrial vacuum
process chambers operating in PVD surface treatment technologies. Any other use, or any
use beyond the foregoing, is deemed to be improper. The HUETTINGER Electronic
company shall not be liable for any loss and damages resulting from such usage.
1.2. Personnel
Only qualified personnel may work with the TRUPLASMA BIAS 4036. "Qualified"
means that the staff will be familiar with safe installation, maintenance and operation.
All of the personnel working with this equipment must take precautions to protect
themselves against possible electrical shocks or other fatal injuries. They must be
acquainted with the entire TruPlasma Bias 4036 operating instruction manual and
understand all of its contents.
The TruPlasma Bias 4036 Power Supply was designed and constructed in
compliance with requirements included in the following standards and EC
directives:
Transportation
Storage
Storage environments should be dry, free of aggressive vapors and not exposed to
temperatures from beyond the 3k3 class range – EN 50178 (i.e.: -25, +55ºC). See table
‘Environment’.
A multi-control system gives the user a possibility of selecting from four optional
control sources:
• Local: DISPLAY console located on the front panel of the TRUPLASMA BIAS
4036.
• Remote RS232 / RS485 link for the PC computer.
• Remote Profibus
• Remote: ANALOG - potentiometers, switches, LEDs and gauges connected to
the analog control connectors (*optional).
The power supply section is equipped with appropriate voltage, current and power
regulators, and dual (HV and LV) mode circuits. It delivers the sufficient voltage to the
pulse-unit section which is responsible for detecting and quenching arc occurrences, and
also pulsing the output.
A block diagram of the TruPlasma Bias 4036 is shown below. TruPlasma Bias 4036
block diagram consists of the following functional blocks:
• input EMI filter to reduce the EMI interferences delivered to the mains.
• power relays providing a soft switch-on
• three-phase rectifier and filter
• high frequency switched-mode DC/AC power converter
• 4 high frequency pulse transformers and high frequency rectifiers
• 4 pulse units
• solid state switch coupled with arc switch-off circuitry
• HV / LV range selection circuitry
• control electronics and LCD display panel
Overall
Mains voltage V 3 x 400 ±10%
Mains frequency Hz 50 – 60Hz
Maximum mains input current A 3 x 64A
Recommended fusing A 3 x 80A, C class
Output
Operation modes - HV (High Voltage) DC
- LV (Low Voltage) DC
- HV (High Voltage) Pulsed
- LV (Low Voltage) Pulsed
Arc Management
Arc detection criteria: Imax
UxI
dU
Imax an arc is detected when the adj. Imax threshold 10 … 100% In
output current exceeds the Im separately in HV and LV modes
value
U x I (cross detection) adj. Ux threshold 0 … 200V,
an arc is detected when output adj. Ix threshold 10 … 100% In
current exceeds the Ix threshold Both values adjustable separately in
value while the output voltage
drops below the Ux value
HV and LV modes
dU (dynamic voltage change)
a spark is detected (in case
spark detection mode is preset ∆U = 75% Uact
selected) when the output
voltage drops rapidly by 75% of
its value
Arc detection time µs <1
Spark quenching time µs <0,5
Arc quenching delay µs User setting: 2 … 10
Maximum arcing frequency Arc/s 50 Arcs/s
Maximum allowable peak output V 1500V in HV mode
voltage 400V in LV mode
Pulse frequency kHz 2 – 100kHz
Pause duration s 1 – 10µs set with 1µs resolution
Reverse voltage % 15 % of output voltage
Mechanical specification
Size (W x H x D) mm (19”) 482 x 410 x 743
Weight kg 86
Environmental specification
Ambient operating temperature °C 0 … +40
°F +32…+104
Storage temperature °C -25 … +55
°F -13…+131
Relative humidity % 5...85 (Non-condensing)
g/m3 1…25
Air pressure kPa 80-106
mbar 800-1060 (approximately 2000
above sea level)
Pollution degree <2 (see chapter 5.1 – installation site
– contamination)
U[V]
1200
HV mode
300
LV or HV LV mode
0
30 120 I [A]
U [V]
Urev
t
t [µs]
Aux Time
Uset
Upeak
Pause Time (PT) - the pulse unit’s pause duration. This value can be set in the range of
1÷10µs with 1µs resolution and with respect to some limits due to the frequency setting
and hardware properties. The pause time limit can be described by an equation:
Urev – the value of the output voltage during the pause time. Urev is equal to 15% of
the value of the output voltage just before the pause time.
Upeak and Aux Time – The hardware circuit generates an additional voltage peak at the
beginning of each succeeding pulse for a time, which is equal to the pause time. The peak
voltage value at this time is:
Uset - The required output voltage value which is set by the user. In DC mode the output
voltage is equal to this value. In pulsed mode the voltage which appears after the Aux
time is equal to the Uset.
Unpacking
Inspect the devices packaging for damage and compare its contents with delivery
documents. Use crane and lifting bracket to lift and position the module.
Enclosure
The TruPlasma Bias 4036 power supply is built into a standard 19” casing and is
designed to fit into a standard 19”, 800mm deep rack cabinet. The weight of this device
is ca. 86kg. The mechanical construction of the cabinet should be strong enough to hold
it. Forced ventilation inside the cabinet is recommended. Inlet air temperature must not
exceed +35°C.
Contamination
Cooling air should be free from corrosive vapors and particles that are conductive
or could become conductive after exposure of moisture. A proper environment conditions
ensure long lasting reliable performance- significantly increasing the MTBF.
5.2. Fusing
External fusing is recommended. A set of 80A, C class external fuses will provide
the necessary circuit protection.
Profibus PE terminal
(under the front plate) at least 16mm2 cable
3x at least
OUTPUT terminals Analog control terminals RS232 control 16mm2
2x at least 35mm2 (DC and pulse mode) cable for
twisted or shielded MAINS
HV cable for output
Synchro connector
(or dummy)
power terminals
at least 8cm
for air flow
protection plate
slide rails
22 HV on Digital output Voltage from pin 20 is coupled to this pin to show, that the
indication. (isolated) power supply is running in HV mode. Maximum voltage at
this pin is 30V. Maximum current is 10mA
23 LV on Digital output Voltage from pin 20 is coupled to this pin to show, that the
indication. (isolated) power supply is running in LV mode. Maximum voltage at
this pin is 30V. Maximum current is 10mA
21 Arc occurs Digital output Voltage from pin 20 is coupled to this pin for ca 20ms to
indication (isolated) show, that an arc has occurred. These signals are not
synchronized with the actual arc occurrence (50 ... 500ms
time shift). The number of “blinks” shows the number of
arcs.
20 Common Digital output All optocoupler collectors are connected to this common pin.
collectors (isolated) Max. voltage between this pin and pins 21 and 22 may not
exceed 30V. Max. current drawn from pins 21 and 22 may
not exceed 10mA each
13, 25 Alarm Digital output Potential – free contacts open when alarm state occurs or no
mains present at mains terminals. Maximum load is 30V,
0,5A. This signal can also be used as READY indication.
COM
RS 232 standard cable X232
PC 1 1 1 1
TRUPL
MP-5
6 6 6 6 ASMA
2 2 2 2
TxD 7 7 7 7 TxD
3 3 3 3
RxD 8 8 8 8 RxD
4 4 4 4
9 9 9 9
5 5 5 5
GND GND
Shield
male female female male
PMP3
+5V
PROFIBUS
1 1
6 6
2 2
7 7
3 3 RxD/TxD-P
8 8
4 4 RxD/TxD-N
9 9
5 5
X
Synchronized operation requires, that the cooperating units are connected with a
synchronization cable. The length and the amount of terminals on this cable depends on
the way the units are installed inside the cabinet. This cable can be made by the user, or
ordered at AC as an accessory. The layout of the cable is shown in the drawing below. It
is recommended to use a shielded cable with 3 twisted pairs of wires. A standard shielded
Ethernet cable (4 twisted pairs) can be used as well, with one of the pairs unused. As
much care as possible must be taken to ensure proper connections of the wires and
shielding.
DUMMY PLUG
1
9
2
10
3
In case the synchronization feature is not used, a properly 11
4
cabled dummy plug must be placed into the SYNCHRO 12
5
connector. The connection layout for this plug is presented 13
6
here. 14
7
15
8
The TruPlasma Bias 4036 power supply is equipped with a SYNCHRO connector,
which enables synchronized operation of several pulsed power supplies – in pulsed mode
as well as in DC-spark detection mode. In order to configure the power supplies to run in
synchronized mode a special SYNCHRO cable must be used to connect all cooperating
pulsed power supplies. The layout of this cable is presented above.
LCD Display
LED lines;
Voltage and
current indication
Menu/Cancel Key
LED indicators
Enter/Accept Key
Cursor Keys
The most important states are displayed on LED indicators for quick identification.
These are:
Name Color Meaning
Standby green The power supply is powered, but not switched-on yet.
Analog, Shows the actual control mode. Both LEDs dark when controlled by the display
RS232 green console. RS232 LED blinks to show proper RS transmission during PC monitoring.
Alarm red Blinks when critical conditions occur. Also an audible signal is sounded then.
Arc occ. yellow Blinks each time an arc is detected. Sparks are not indicated.
Reg U green
Reg I green Indicate which parameter is actually considered by the regulators
Reg P green
* This LED blinks in standby mode when parameters are being changed (display panel in Modify Mode) to
indicate the mode that the parameters refer to.
Init On/Off
The ACCESS CODE feature keeps critical data from being accidentally changed. It
also provides access to additional item lists, which are used during testing and service
operations.
The initial access level is STANDARD (STRD). This allows the user to change the
voltage, current and power settings for the power supply’s regulators, reset the arc
counters, switch the power supply on and off, change the operating modes and – of
course – change the access level by entering the appropriate ACCESS CODE.
Selecting SETUP (SETP) access level will reveal a two additional item lists and allow
the user to change the rest of the settings. The access code for this level is initially 1. This
code can be changed from a PC.
There is one more level. It is the SERVICE (SERV) access level. It enables
modification of input and output calibration values, voltage thresholds etc. Since
improper modification of any of these settings which may cause a malfunction of the
device, the access code to this level is known by the service staff only.
>Iout= 10.0/ 3.5 A< Yes Current regulator setting (first number) and actual
power supply’s output current readout(second
number).
>Pout= 5.0 / 2.4kW< Yes Power regulator setting (first number) and actual
power supply’s output power readout (second
number).
ALARM: NONE No When the ALARM LED blinks, this cyclically displays
the states which caused the alarm.
>ACCESS CODE STRD< Yes Entering the appropriate access code gives access
to the USER SETUP MENU list and SERVICE SETUP
list.
>PULSE MODE: PULSED< Yes, but Displays the current pulse unit mode.
only if If the control mode is set to DISPLAY-panel,
DISPLAY the pulse unit can be switched to ARCDET,
mode SPRKDET PULSED or SLAVE mode can be
selected selected
PULSE FREQ= 30kHz The actual pulse unit’s frequency setting with
reference to the control source (DISPLAY,
ANALOG or RS232).
PULSE TIME= 5us The actual pulse unit’s pause duration setting
with reference to the control source (DISPLAY,
ANALOG or RS232)
A spark is detected when the output voltage is rapidly decreased by 75% of its
value. The Imax and UxI threshold settings can be separately adjusted in each mode. In
order to change these settings from the display panel you must switch to SETUP ACCESS
(enter code “1”) and select the USER SETUP MENU screen.
The parameters, which influence the response to arcs are listed below
Parameter Description Notes
>ArcDet ImHV= 30A< Current threshold for the Imax detection criteria in HV
mode
>ArcDet IxHV= 5A< Current threshold for the UxI detection criteria in HV 1
mode.
>ArcDet UxHV=100V< Voltage threshold for the UxI detection criteria in HV
mode
>ArcDet ImLV= 60A< Current threshold for the Imax detection criteria in LV
mode
>ArcDet IxLV= 15A< Current threshold for the UxI detection criteria in LV 1
mode
>ArcDet UxLV= 80V< Voltage threshold for the UxI detection criteria in LV
mode
>BreakTime = 20ms < The output power is inhibited for this time. 10 … 100ms
>RampRate = 100V/ms< The voltage come-back ramp. 20 … 200V/ms
Notes:
1. This setting should always be LOWER then the set-point for the output current regulator, otherwise the
output current will not be able to trip the arc detection level.
The basic principal of the arc detectors operation is shown on the graph below.
The dU (dynamic voltage change) detector is the fastest possible way of detecting an arc.
This is because the output of the power supply is inductive, and an arc makes the voltage
drop much faster then the current can rise. However the dU detector can fail in case the
succeeding arcs occur before the voltage reaches a certain value from which a voltage
drop will be recognized. This value is ca. 150V.
The UxI detector is static and will detect an arc as well as a long-term short circuit at the
output of the power supply protecting the treated surface from being burnt by arcs. The
reaction time in this case is 10…100 times longer then the response of the dU detection.
The Imax detector will switch off the power if the output current exceeds the Imax level
regardless the reason (arc or overload).
Ix
Voltage
U1
Current Arc energy
I1
150V
U2
25% U1
Ux
Uarc
0 AB C D E F G H J K L Time
[see description below]
This figure shows the response of the dU, UxI and Imax detector. The events are as
follows:
The Bias acts as a slave device in the communication process. It never initiates a
transmission. The master computer (PC) sends a command which is executed by the Bias
and a reply is generated (with respect to note 1). The recognized commands are
presented below. Additional commands can be implemented if necessary.
The baud rate can be set from 2400 to 38400 from the Bias front panel console to
correspond to the rate set at the PC.
PC to Bias
0 1 2 3 4 5 6 7 8 9 10 11
$16 $E9 $89 $13 Adr Uset0 Uset1 Uset2 Uset3 Iset0 Iset1 Iset2
12 13 14 15 16 17 18 19 20 21 22 23
Iset3 Pset0 Pset1 Pset2 Pset3 Freq PDT Bits SH SL
Where:
Adr RS485 address 0..255
Uset (float) Voltage setpoint [V] 0..300V (LV), 0..1200V (HV)
Iset (float) Current setpoint [A] 0... 120A (LV), 0..30A (HV)
Pset (float) Power setpoint [kW] 0...36kW
Freq (byte) Pulse frequency [kHz] 2...100
PDT (byte) Pause Time [us] 1...10
Control Bits:
0: Take over control (1); Do not take over control (0)
1: PlasmaBit ON (1); OFF (0)
2: Mains relays ON (1), Relays OFF (0)
3: Power ON (1), Power OFF (0)
4: Mode: HV (1), LV (0)
5: Arc counter reset(1 – for 1 transmission)
6: Pulsed mode ON (1); OFF (0)
7: Spark Detection (ON (1); OFF (0)
Bias to PC
0 1 2 3 4 5 6 7 8 9 10 11
$16 $E9 $40 $00 Uact0 Uact1 Uact2 Uact3 Iact0 Iact1 Iact2 Iact3
12 13 14 15 16 17 18 19 20 21 22 23
Sprk0 Sprk1 Arc0 Arc1 Bits0 Bits1 Freq PDT SH SL
Where:
Uact (float) Output voltage [V] 0...1200V
Iact (float) Output current [A] 0... 120A
Sprk (integer) Spark counter 0...10000
Arc (integer) Arc counter 0...10000
Freq Actual pulsing frequency setting 2...100 kHz
PDT Actual pause time setting 1...10 us
Bits0: Acknowledge bits 1:
0: Digital control Ack (1); other (0)
1: Plasma ON Ack
2: Relays ON Ack
3: Power ON Ack
4: Mode Ack: 1: HV; 0: LV
5: Pulsed mode Ack
6: Spark Detection Ack
7: =1 for 1 transmission after reset
PC to Bias
0 1 2 3 4 5 6
$0B $F4 $51 $12 xx Adr $EA
7 8 9 10 11
$62 0 0 SH2) SL2)
Where:
Adr Address for RS485 0..255 1)
xx Ignored
PC to Bias
0 1 2 3 4 5 6
$0D $F2 $80 $03 Adr Chan1 Chan2
7 8 9 10 11 12
Val0 Val1 Val2 Val3 SH2) SL2)
Where:
Adr Address for RS485 0..255 1)
Chan (int) Channel number (see channel assignment tables)
Val (float) Value to be set
Bias reply
0 1 2 3 4 5
$06 $F9 AckH3) AckL3) SH2) SL2)
PC to Bias
0 1 2 3 4 5 6
$09 $F6 $80 $04 Adr Chan1 Chan2
7 8
SH2) SL2)
Where:
Adr Address for RS485 0..255 1)
Chan (int) Channel number (see channel assignment tables)
PC to Bias
0 1 2 3 4 5 6
$0A $F5 $80 $06 Adr Chan1 Chan2
7 8 9
Val SH2) SL2)
Where:
Adr Address for RS485 0..255 1)
Chan (int) Channel number (see channel assignment tables)
Val (byte) Value to be set
Bias reply
0 1 2 3 4 5
$06 $F9 AckH3) AckL3) SH2) SL2)
PC to Bias
0 1 2 3 4 5 6
$09 $F6 $80 $07 Adr Chan1 Chan2
7 8
SH2) SL2)
Where:
Adr Address for RS485 0..255 1)
Chan (int) Channel number (see channel assignment tables)
Where:
Val (byte) Asked byte value
PC to Bias
0 1 2 3 4 5 6
$09 $F6 $80 $09 Adr Chan1 Chan2
7 8
SH2) SL2)
Where:
Adr Address for RS485 0..255 1)
Chan (int) Channel number (see channel assignment tables)
Where:
Val (byte) Asked byte value
Special commands:
5105 Show Your RS485 Address
Do not use this command if more then 1 unit connected to the RS485 chain.
PC to Bias
0 1 2 3 4 5 6 7
$08 $F7 $51 $05 xx 255 SH2) SL2)
Where:
xx Ignored
Where:
Adr Actual address for RS485 0..255 1)
Float values:
Chan Parameter Description Range Modif.
0 ArcDet ImHV Current threshold for Imax arc 30 – 33 A Yes
detection in HV
1 ArcDet IxHV Current threshold for UxI arc detection 30 – 30 A Yes
in HV
2 ArcDet UxHV Voltage threshold for UxI arc detection 0 – 300V Yes
in HV
3 ArcDet ImLV Current threshold for Imax arc 12 – 132 A Yes
detection in LV
4 ArcDet IxLV Current threshold for UxI arc detection 12 – 120 A Yes
in LV
5 ArcDet UxLV Voltage threshold for UxI arc detection 0 – 300V Yes
in LV
6 T5: PULS1 Internal temperature at pulsator 0…100°C No
7 T6: PULS2 Internal temperature at pulsator 0…100°C No
8 T7: PULS3 Internal temperature at pulsator 0…100°C No
9 T8: PULS4 Internal temperature at pulsator 0…100°C No
10 U600 Rectified mains voltage 0…700V No
11 U24 Controller supply voltage 0...30V No
NOTES:
1) If Adr=255 the Bias will always react to the received command, regardless its own address, but
it will send a reply (confirmation) only if its own address matches the Adr.
2) SH, SL are the high and low bytes of the check-sum. The check-sum is an arithmetic sum of
bytes 2 … (n-2), where n is the number of the last byte of transmission.
3) AckH and AckL are acknowledge codes which are listed below.
4000 OK
Transmission OK. and command executed.
4001 Transmission length error
Byte1 is not a negation of byte0.
4002 Check sum error
The two byte checksum is not equal to the sum of bytes nr 2 … (n-2)
4003 Command not executable
Command is understood, but can not be executed due to technical conditions (for
instance channel don’t exist).
4004 Command not understood
Command is not implemented.
PROFIBUS is an interface that allows you communicate with the Bias 4036 from a
PROFIBUS master. Arc acts as a slave device in the communication process. It never
initiates a transmission. The PROFIBUS master sends a command coded in modules, which
is executed by Arc unit, and a reply is generated. The recognized modules are presented
below. Additional modules can be implemented if it is necessary.
Baud Rate for communication between PROFIBUS master and PROFIBUS slave
The PROFIBUS slave in Bias unit has the auto –baude feature, which allows to
adjust automatically to the rate of the PROFIBUS master system during start-up. Baud rate
are accessible in discrete steps from 9.6 kbits to 12 Mbits.
Settings of PROFIBUS ID
The ID number is setting by using the front panel console of Bias unit. The
software read the ID number from unit at the beginning the program. If the ID number
was changed, the unit must be restarted.
This module consists of two bytes, which represent voltage setpoint value in a 16-
bit integer format. The full voltage range of power supply:
0 … 1200 [V]
is represented by a
0 … 10000 integer value
This module consists of two bytes, which represent current setpoint value in a 16-
bit integer format. The full current range of power supply:
0 … 120 [A]
is represented by a
0 … 10000 integer value
This module consists of two bytes, which represent current threshold value for UxI
detection in a 16-bit integer format. The current sensitivity is stored in EPROM. The full
current range of power supply:
0 … 120 [A]
is represented by a
0 … 10000 integer value
This module consists one byte, which represent frequency setpoint in 8-bit byte
format. Scaling: 2..100 represents 2..100kHz
This module consists one byte, which represent pause duration time in 8-bit byte
format. Scaling: 1..10 represents 1..10 us
This module consists of two bytes and displays actual output current value in 16-bit
integer format. Full current range of power supply
0 … 120 [A]
is represented by a
0 … 10000 integer value
This module consists of two bytes which represent actual output voltage value in a
16-bit integer format. The full power range of power supply
0 … 1200 [V]
is represented by a
0 … 10000 integer value
This module consists of two bytes, which represent actual output power value in a
16-bit integer format. The full power range of power supply
0 … 36 [kW]
is represented by a
0 … 10000 integer value
This module consists of two bytes, which represent actual Arc counter value in a
16-bit integer format. The range of Arc counter is: 0 - 10000.
This module consists of 2 bytes which present basic binary status data. These bytes
are described below.
These three bytes enables to write new threshold values. The first byte represent
channel number, second and third bytes represent the new value in integer. The list of
available channels presented is on the next page.
Scaling is: 0..10000 represents 0..200 value.
These three byte enables to read threshold values or temperatures. The output
byte represent channel number of the value, which will be read. The read value is
represented by a 16 bit (two input bytes) integer number. The list of availability channel; is
presented on next page. Scaling is: 0..10000 represents 0..200 value. (with the exception
of channel no: 11)
For channel number 11 scaling is: 0..10000 represents 0..1000 value
These two bytes enables to write new byte values (new PI regulators settings, etc.).
The first byte represent the channel number and the second byte represent the new value
in byte. The list of available channels presented is on the next page.
These two byte enables to read byte value(new PI regulators settings, etc.) from
selected channel. The output byte represent channel number of the value, which will be
read.
The read value is represented by a one input byte. The list of availability channel; is
presented on next page.
The precision for integer value for all channel (in except channel no: 11) is:
for 0 - 200
0 - 10000
For channel number 11 (Rectified mains voltage) the precision is
for 0V - 1000V
0 - 10000
GSD files
GSD (Electronic data sheet of a device) files contain and describe the functions and
character of PROFIBUS device. Therefore, to use this unit in a PROFIBUS system, it needs
to have a specific GSD file that is compatible with the unit. Please, use only this GSD file,
which is delivered with DC unit.