0% found this document useful (0 votes)
8 views10 pages

Schneider Electric - Modicon-TM3 - TM3TI8T

Uploaded by

stephen.s
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
8 views10 pages

Schneider Electric - Modicon-TM3 - TM3TI8T

Uploaded by

stephen.s
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

Product datasheet

Specifications

module TM3 - 8 inputs


temperature
TM3TI8T

Main
Range of product Modicon TM3

Product or component type Analog input module

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Range compatibility Modicon M221
Modicon M241
Modicon M251
Modicon M262

Analogue input number 8

Analogue input type thermocouple - 200...1000 °C with thermocouple J


thermocouple - 200...1300 °C with thermocouple K
thermocouple 0...1760 °C with thermocouple R
thermocouple 0...1760 °C with thermocouple S
thermocouple 0...1820 °C with thermocouple B
thermocouple - 200...400 °C with thermocouple T
thermocouple - 200...1300 °C with thermocouple N
thermocouple - 200...800 °C with thermocouple E
thermocouple 0...2315 °C with thermocouple C
NTC 10k thermistor -90...150 °C
PTC thermistor 100...10000 Ohm
thermocouple - 200...1000 °C

Complementary
Analogue input resolution 16 bits
15 bits + sign

Input impedance >= 1 MOhm thermocouple


>= 1 MOhm temperature probe
>= 1 MOhm thermistor

LSB value 0.1 °Cthermocouple


0.1 °C with NTC probe
1 Ohm with PTC/NTC probe

Conversion time 100 ms + 100 ms per channel + 1 controller cycle time

Sampling duration 100 ms

Absolute accuracy error +/- 0.2 % of full scale at 25 °C for thermocouple C 0...2315 °C
+/- 6 °C at 25 °C for thermocouple R, S 0...200 °C
+/- 0.2 % of full scale at 25 °C for thermocouple R, S 200...1760 °C
+/- 0.2 % of full scale at 25 °C for thermocouple B 300...1820 °C
+/- 0.4 % of full scale at 25 °C for thermocouple K - 200...0 °C
+/- 0.2 % of full scale at 25 °C for thermocouple K 0...1300 °C
+/- 0.4 % of full scale at 25 °C for thermocouple J - 200...0 °C
+/- 0.2 % of full scale at 25 °C for thermocouple J 0...1000 °C
+/- 0.4 % of full scale at 25 °C for thermocouple E - 200...0 °C
+/- 0.2 % of full scale at 25 °C for thermocouple E 0...800 °C
+/- 0.4 % of full scale at 25 °C for thermocouple T - 200...0 °C
+/- 0.2 % of full scale at 25 °C for thermocouple T 0...400 °C
+/- 0.4 % of full scale at 25 °C for thermocouple N - 200...0 °C
+/- 0.2 % of full scale at 25 °C for thermocouple N 0...1300 °C

Temperature drift +/- 0.01 %FS/°C

Repeat accuracy +/-0.5 %FS

23 Jul 2024 1
Non-linearity +/- 0.2 %FS

Cross talk <= 1 LSB

[Us] rated supply voltage 24 V DC

Supply voltage limits 20.4…28.8 V

Type of cable Twisted shielded pairs cable <30 m for input circuit

Current consumption 30 mA at 24 V DC via external supply


45 mA at 5 V DC via bus connector
40 mA at 5 V DC via bus connector

Local signalling 1 LED (green) for PWR

Electrical connection 10 x 1.5 mm² removable screw terminal block with pitch 3.81 mm adjustment for
inputs and supply
10 x 1.5 mm² removable screw terminal block with pitch 3.81 mm adjustment for
inputs

Insulation Between input and supply at 1500 V AC


Between input and internal logic at 500 V AC

Marking CE

Surge withstand 1 kV power supply common mode conforming to IEC 61000-4-5


0.5 kV power supply differential mode conforming to IEC 61000-4-5
1 kV input common mode conforming to IEC 61000-4-5

Mounting support Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
plate or panel with fixing kit

Height 90 mm

Depth 70 mm

Width 23.6 mm

Net weight 0.11 kg

Environment
Standards IEC 61131-2

Product certifications CE
UKCA
RCM
EAC
cULus
cULus HazLoc

Resistance to electrostatic 8 kV in air conforming to IEC 61000-4-2


discharge 4 kV on contact conforming to IEC 61000-4-2

Resistance to electromagnetic 10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3


fields 3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3
1 V/m 2 GHz...3 GHz conforming to IEC 61000-4-3

Resistance to magnetic fields 30 A/m conforming to IEC 61000-4-8

Resistance to fast transients 1 kV (I/O) conforming to IEC 61000-4-4

Resistance to conducted 10 V 0.15...80 MHz conforming to IEC 61000-4-6


disturbances 3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to
Marine specification (LR, ABS, DNV, GL)

Electromagnetic emission Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz
conforming to IEC 55011
Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz
conforming to IEC 55011

Immunity to microbreaks 10 ms

Ambient air temperature for -10…55 °C horizontal installation


operation -10…35 °C vertical installation

2 23 Jul 2024
ambient air temperature for -25…70 °C
storage
Relative humidity 10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)

IP degree of protection IP20

Pollution degree 2

Operating altitude 0...2000 m

Storage altitude 0…3000 m

Vibration resistance 3.5 mm at 5…8.4 Hz on DIN rail


3 gn at 8.4…150 Hz on DIN rail

Shock resistance 15 gn for 11 ms

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Height 7.516 cm

Package 1 Width 10.685 cm

Package 1 Length 12.739 cm

Package 1 Weight 210.0 g

Unit Type of Package 2 S02

Number of Units in Package 2 9

Package 2 Height 15 cm

Package 2 Width 30 cm

Package 2 Length 40 cm

Package 2 Weight 2.391 kg

Unit Type of Package 3 P06

Number of Units in Package 3 432

Package 3 Height 105 cm

Package 3 Width 120 cm

Package 3 Length 80 cm

Package 3 Weight 122 kg

23 Jul 2024 3
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right

Transparency RoHS/REACh

Well-being performance

 Toxic Heavy Metal Free

 Mercury Free

 Rohs Exemption Information Yes

 Pvc Free

Certifications & Standards


Reach Regulation REACh Declaration

Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)

EU RoHS Declaration

China Rohs Regulation China RoHS declaration

Environmental Disclosure Product Environmental Profile

Weee The product must be disposed on European Union markets following specific waste
collection and never end up in rubbish bins

Circularity Profile End of Life Information

4 23 Jul 2024
Product datasheet TM3TI8T

Dimensions Drawings

Dimensions

(*) 8.5 mm/0.33 in when the clamp is pulled out.

23 Jul 2024 5
Product datasheet TM3TI8T

Mounting and Clearance

Spacing Requirements

6 23 Jul 2024
Product datasheet TM3TI8T

Mounting on a Rail

Incorrect Mounting

23 Jul 2024 7
Product datasheet TM3TI8T

Mounting on a Panel Surface

(1) Install a mounting strip

Mounting Hole Layout

8 23 Jul 2024
Product datasheet TM3TI8T

Connections and Schema

Analogue Input Module

Wiring Diagram (Thermocouple Input Type)

(*) Type T fuse

(1) Thermocouple

Wiring Diagram (Temperature Probe Input Type)

23 Jul 2024 9
Product datasheet TM3TI8T

(*) Type T fuse

10 23 Jul 2024