RVAC
Ring Main Unit
Based on the design concept of full insulation and fully sealed, all
primary parts within RVAC RMU are fully sealed inside the
stainless-steel main enclosure, protect to against condensation and
external contaminated environment; the protection degree of the
main tank body is up to IP67, equipped with Cooper’s water-proof-
ing touchable cable bond, which can provide effective
protection against accidental flood in rainy climate.
2
RVAC Ring Main Unit Construction Feature
• Logical mechanical and electrical interlocks; • Flexible extension of unit modules on site, easy to build medium
voltage transformer substations according to different require-
• Complete enclosure earthing, to ensure zero potential for ments;
interface;
• Compartments protected against penetration of objects; • Two options are available for transformer and line protections:
load break switch-fuse combination units and circuit breakers
• Capacitive voltage detection system for verification of safe with relay protection.
isolation from supply;
• Feeder earthing by means of make-proof earthing switch.
All-weather and high adaptability to environment
Environmental-friendly concept • SF6 gas tank is made of stainless steel plates, with anti-rust
painting treatment on the surface, to protect against salt spray,
• Low power loss, low maintenance spending, ensuring more humidity, dirt and temperature, and to ensure durable nice
reasonable cost investment; appearance;
• Only reusable and/or recyclable materials can be used to do • COOPER pre-fabricated shielding touchable cable terminal is
the most compact design; supplied, suitable for long-term operation underwater or in other
• In normal working conditions, gas leakage rate of lower than severe conditions.
0.05% per year ensures more than 30 years life-cycle;
• Without gas work on site through installation, operation,
Operation
extension, and replacement of the product. • Complete design certified in accordance with GB / DL and IEC
standards;
• Arc fault tested according GB3906 / IEC 62271-200;
User friendly
• Quality assurance in accordance with ISO 9001;
• Cable connection and user interfaces for operation on the
same front side of the panel; • Touching safe and hermetically sealed primary enclosure;
• Ergonomic cable connection height; • Gas tank’s zero gauge voltage withstand (1min) can reach power
frequency withstand voltage.
• A customized low voltage compartment is optional;
• Clear and simple straightforward operation panels.
3
Main Construction
• All primary high-voltage components are completely enclosed in SF6 gas tank, free
from environment impact, thus ensuring fully insulation and maintenance-free;
• SF6 gas tank is made of high-quality stainless steel materials, free from
influence of salt spray, humidity, dirt and temperature, ensuring a durable nice
outlook;
• With IP67 protection degree, can reliably prevent from flood immersion in summer;
• Advance gas shielded welding as well as a sealing pressure system of less
than 0.05% leakage rate ensure a 30 year service cycle;
• Non-extensible is standard busbar extensible is optional.
• The load break switch applies metal deionizing arc suppress technology, ensuring
good interruption performance for the switch;
• The working speed of switch’s moving contact depends on its operation mecha
nism; and the open-close speed of the switch will not be influenced by operators;
• When moving from closing to opening, the load break switch depends on moving
contact speed and arc suppress devices simultaneously, to suppress arc and break
current;
• The spring operation mechanism with an operating handle to complete closing
and opening operations. Motorization module and opening coil can be added, to
achieve remote control.
4
Product Features
RVAC is developed to be an economical and ecological user-friendly power distribution device of compact size, reliable
performance and flexible configuration, with the application of advanced R&D technical resources.
Capacitive voltage detection Sealed enclosure design, to Anti-internal arcing concept Eaton supports the philosophy
system for verification of safe effectively protect against that it is best to avoid internal
Eaton has always been focusing
isolation from supply foreign objects arcs than to cure, in line with
on building consistently safe
the relevant standard GB 3906,
Each panel type within the In the design of RVAC, it is not switchgear devices for opera-
IEC 62271. Within the RVAC
RVAC family is equipped with a possible for external staff or tors. The biggest potential risk
design a double prevention
standard three phase Voltage tools to accidentally enter into for operators is internal arcing
philosophy is used. Firstly, the
Detection System for voltage the panel. within the switchgear device.
design is constructed in such a
testing. The VDS shows the
way that an internal arc is
operator if the panel is isolated Smooth contemporary design Therefore, design engineers
prevented. In the unlikely case
from supply or not. have taken all necessary
All compartments of the RVAC that an internal arc could occur,
meausres to prevent internal
panels are designed in such a the RVAC is equipped to
Logical mechanical and arcing during product design
way that the system is safe to provide maximum safety to the
electrical interlocks prevent process.
touch from the outside. By operator, and to control and
incorrect operation using a smooth and smart minimise damage to the rest of
Within the RVAC design design it is not possible for the the switchgear and room.
misoperation by an operator is operator to injure himself by
prevented by using different moving parts or by parts that
interlocks. The interlocks are stick out of the switchgear
mechanical and electrical. For when moving in front of the
example electrical and mechani- switchgear.
cal interlocks prevent operation
of the change-over switch when Routine tests
the circuit-breaker is switched Various prescribed routine tests
on. All mechanical interlocks are are carried out during the
constructed in such a way that production of the switchgear.
they directly block the mecha- To assure quality, all processes
nism. are in accordance with ISO
9001. This means that at every
Only when the cable stage of production the
compartment door is closed, components, circuit-breakers
the device can be operated to and current transformers are
power-on position inspected for correct functional-
Only when the switch is ity. When the entire installation
operated to Earthing position, has been assembled, a
the cable compartment door thorough visual inspection is
can be opened in a normal way. carried out, together with
Only when the cable compart- mechanical, functional and
ment door is closed completely, electrical checks.
a closing operation can be
conducted on the earthing
switch. After the earthing
switch is opened, the mains
switch can conduct closing
operation to complete power-on
process.
5
Sulfur Hexafluoride (SF6) Gas
6
Features and benefits
The benefit of a sealed for life tank Computer simulation design Smart grid readiness
A “sealed for life” steel enclosure contains 3D simulation design analysis softwares are Automation upgrading
all primary parts and driving mechanisms applied during R&D process to strengthen design • Remote close/open
• Maintenance free capacity, thus improving product reliability greatly.
• Auxiliary contacts for each
• Internal arc proof • Electric field analysis position local or remote
• Protection degree up to IP67 for prevention of • Magnetic field analysis indications
summer floods • Gas pressure and motion analysis • Measuring CT and current
• Mechanical strength analysis signal
The benefit of a compact design • Mechanical movement (speed and force) Option
analysis
• Trip indicator with auxiliary
• Minimal floor space • Finite element analysis contacts
• Low building costs
• Fault indicator
• Easy to install
• Current meter
Flexible solutions
• Reliable busbar extended design and interfaces reservered for future project expansion
on
• Complete types of functional units
Load break
Load break switch-fuse Circuit
switch panel combination panel breaker panel Rise panel
“K” “T” “V” & ”CB” “A” & ”B”
Metering Voltage
Busbar coupler Busbar coupler panel transformer panel
“L(k)” “L(v)” “M” “PT”
7
Configuration information
8
Load break switch-fuse combination panel (Function T)
Standard Options
630A load break switch Extension on both sides
Earth switch Lateral incoming and outgoing
Fuse tube Motorization mechanism
* SF6 pressure gauge Electric shunt release
Voltage presence indicator Bottom plate
Reliable interlock Cable inspection window
Operating handle Short circuit fault indicator
Cable clamp and bracket Fuse adapter *
LV compartment
* Adapter must be applied together with 12kV Fuse when the system rated
voltage is 12kV.
A 34 Fuse striker:
Medium type (according IEC 60282-1, DIN and GB 15166.2, alternating current switch-fuse
A+68 combinations).
9
Circuit breaker panel (Function V)
Standard Options
630A vacuum breaker Extension on both sides
3-position disconnector Lateral incoming and outgoing
SF6 pressure gauge Motorization mechanism
Voltage presence indicator LV compartment
Reliable interlock Cable inspection window
Operating handle Short circuit fault indicator
Cable clamp and bracket Protection relay
10
Voltage transformer panel (Function Bpt/Kpt)
Standard Options
SF6 pressure gauge LV compartment
Voltage presence indicator Voltage transformer and cable connection kits
Loadbreak switch (Kpt)
Function M
Rated voltage (kV) W (mm) D (mm) H (mm) Weight (kg)
24 800 1050 1500 260
12 750 830 1480 240
11
PBD protection relay
• 3-phase 3-step directional current protection (quick break, timed
quick break, over-current inverse time), with low voltage locking
function
• 3-phase 3-time reclosing (inspection for no voltage, inspection
for synchronization, no inspection), the number of reclosing
operations can be set, including the function of post-acceleration
• Zero sequence voltage locking direction zero sequence over
current protection (alarm, optional tripping operation)
• Low current grounding line selection function
• Low voltage protection
• Overload alarm
• External auxiliary power resource required(DC24/48/110, AC/DC
220)
• RS485 communication port
12
Main Components
Voltage indicator
Fault indicator
The indicator is used for detecting and indicating ground fault and
short-circuit fault in corresponding cable sections. The indicator Busbar Linker
light flashes with alarm when short-circuit fault or single-phase Connected existing module
ground fault occurs in the power distribution system. RVAC with another module
RVAC.
Insulation cap
When the cabinet is reserved busbar bushing for transformer on
the main busbar side, and the cable plug is not installed, you need
to use Insulation cap to protect the busbar bushing.
Fuse adapter
The adapter must be configured together with fuse when the
product is used in 12kV system.
13
RVAC Technical Data
14
RVAC Outlines and Dimensions
Type K panel dimension for 24kV Type T panel dimension for 24kV
K T
Type V panel dimension for 24kV Type M panel dimension for 24kV
2000
1500
800 1050
V M
15
RVAC Outlines and Dimensions
Type K panel dimension for 12kV Type T panel dimension for 12kV
K T
Type V panel dimension for 12kV Type M panel dimension for 12kV
V M
16
Basic Installation Diagram/Recommended Floor Plan
LV compartment
Mechanism compartment
Gas tank
Venting channel
Cable compartment
Earthing bar
723(For 8# U-steel)
Venting
Side View
Channel
(Landing Depth)
Optional for welding with base frame
M8X30
Cable Channel Cable Channel Cable Channel
Base frame
#8 U-steel
23.5
Drip Channel
I
Floor Plan
Type K T V
H 850 550 650
17
RVAC Series outdoor switching substation
• The cable inlets with sealed bottom plates are locked the
bottom of outdoor enclosure to prevent moisture from cable
channel into case body.
• The doors and lugs are sealed with sealing strips, the locks for
doors is rainproof. The limiting hook is installed on the door to
make door fix when the door is opened for maintenance.
18
Eaton is an intelligent power management company dedicated to
improving the quality of life and protecting the environment for people
everywhere. We are guided by our commitment to do business right,
to operate sustainably and to help our customers manage power
today and well into the future. By capitalizing on the global growth
trends of electrification and digitalization, we’re accelerating the
planet’s transition to renewable energy, helping to solve the world’s
most urgent power management challenges, and doing what’s best for
our stakeholders and all of society. Founded in 1911, Eaton has been
listed on the NYSE for nearly a century. We reported revenues of $19.6
billion in 2021 and serve customers in more than 170 countries.
Eaton entered the Chinese market in 1993, and has grown significantly
since then. In 2004, Eaton moved its Asia-Pacific headquarters from
Hong Kong to Shanghai. Today, Eaton has nearly 8,000 employees and
19 manufacturing facilities in China.
Eaton Corporation
No.3, Lane 280, Linhong Road,
Changning District,
Shanghai, China 200335