Structural Detail_waiting & Registration Office Building-model4

The document outlines construction specifications, including dimensions, materials, and reinforcement details for various structural components such as foundations, columns, beams, and slabs. It emphasizes adherence to specific standards and guidelines, including those for concrete mix and reinforcement placement. Additionally, it addresses masonry work requirements and the need for proper bonding between brick walls and RCC members.

Uploaded by

Amir Sohail
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
7 views

Structural Detail_waiting & Registration Office Building-model4

The document outlines construction specifications, including dimensions, materials, and reinforcement details for various structural components such as foundations, columns, beams, and slabs. It emphasizes adherence to specific standards and guidelines, including those for concrete mix and reinforcement placement. Additionally, it addresses masonry work requirements and the need for proper bonding between brick walls and RCC members.

Uploaded by

Amir Sohail
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

[GENERAL]

[1] ALL DIMENSIONS ARE IN INCHES. UNLESS OTHERWISE MENTIONED.


[2] ONLY FIGURED DIMENSIONS ARE TO BE FOLLOWED NEITHER THE BARS SHALL BE
COUNTED
NOR THE DIMENSIONS SCALED FROM THE DRG.
[3] ANY DISCREPANCY IN THE DRGS. SHALL BE BROUGHT TO THE NOTICE OF THE
ARCHITECT/
CONSULTANT AND CLARIFICATION OBTAINED IN WRITING PRIOR TO EXECUTION OF
WORK.
[4] HIGH YIELD STRENGTH DEFORMED BARS OF YIELD STRESS 500 N/MM2(Fe-500)
WHICH SHALL CONFORMTO 1786-1985 SHALL BE USED AS REINFORCEMENT
[5] CLEAR COVER OF OUTER LAYER REINF. SHALL BE AS FOLLOWS. (a)
FOUNDATION = 50 mm.
(b) COLUMN = 40 mm.(c) BEAM = 40mm. OR DIA OF BAR WHICHEVER IS MORE (d) SLAB =

1 2 3 4 5
15 mm.
c) WAIST SLAB = 25 mm.
[6] END/SIDE COVER OF ALL REINFORCEMENT IN BEAMS & SLAB = 25 mm. OR DIA OF BAR
WHICHEVER
IS MORE
[7] THE COVER BLOCK OF CEMENT MORTAR SHALL BE USED TO ENSURE THE
REQD.COVER OF REINF.

12390
[8] DEVELOPMENT LENGTH ( Ld ) FOR DIFFERENT DIA METER OF BARS FOR CONC.
MIX OF
GRADE M - 20 SHALL CONFORM TO 1786-1985 SHALL BE USED AS REINFORCEMENT BE
ASPER THE SCHEDULED GIVEN IN TABLE 1
(9) THE BUILDING HAS BEEN DESIGN FOR G

4115 1075 2970 4230


[10] CONC. MIX FOR R.C.C. WORK SHALL BE OF GRADE M - 25 CONFORMING
TO I.S. 456 - 2000.
[11] NECESSARY FIXTURE FOR ELECTRICAL, PLUMBING, ETC. SHALL BE
PROVIDED IN SLAB, BEAMS BEFORE EXECUTION AS PER RELEVANT DRGS.
[12] THE STRUCTURE HAS NOT BEEN DESIGNED FOR SEISMIC LOAD
[13] P.C.C.(1:4:8) SHALL BE PROVIDED. or as per speciticastion mentionel in
estimate(BOG)
[14] EXPANSION GAP SHALL BE PROVIDED ABOVE FOUNDATION RAFT LVL. TO
TERRACE LVL. AT LOCATION MARKED ON PLAN TERRACE LVL. AT LOCATION
MARKED ON PLAN
[15] ALL PLAIN CONCRETE & RCC SHALL BE STRICTLY IN ACCORDANCE WITH THE
B1(230X375) B1(230X375) B1(230X375) PROVISION OF IS - 456:2000 [15] CUTTING,BENDING,FIXING & PLACING OF BARS
SHALL BE IN ACCORDANCE WITH IS - 2502:1968, IS - 5525:1969 & IS - 456:2000
A

[COLUMNS]
[1] TIES IN PORTION OF COL. & BEAM JUNCTION SHALL BE SAME AS END ZONE.
[2] OVER LAPS ARE ALLOWED ONLY AT MIDDLE ZONE OF THE COLUMNS.
[3] NOT MORE THAN 50 % OF BARS SHALL BE LAPPED AT A SECTION AND LAPS
SHALL BE STAGGERED.
[4] TIES IN PORTION OF COL. BELOW PLINTH BEAM SHALL BE SAME AS END ZONE .
[5] VERTICAL BARS OF RCC COLUMN AT TOP SLAB SHALL BE EXTENDED UPTO TOP
OF BEAM & BENT INTO BEAM BY DEVELOPMENT LENGTH.

[BEAMS NOTES]
(I) ld= DEVELOPMENT LENGTH OF THE BARS SHALL BE AS PER TABLE.
(II) LENGTH ld SHALL BE TAKEN FOR THE BAR TO BE CURTAILED
(III)AT THE JUNCTION OF TWO NOS OF THE BEAM , COMMAN SUPPORT SHALL BE
CONSIDERED AS FIRST SUPPORT FOR THE HIGHER NO OF BEAM WHILE SECOND
L2 SUPPORT FOR THE LOWER NO OF BEAM.
(IV) AT THE LOCATION OF COMMAN SUPPORT HIGHER OF THE REINFORCEMENT
OF BOTH THE BEAMS SHALL BE ADOPTED.
(V) IF THE REINFORCEMENT PROVIDED AT THE SUPPORT AT BOTTOM FACE IS
MORE THAN THE REINFORCEMENT AT BOTTOM FACE AT MID SPAN ,SAME
1c CURTAILMENT RULE AS FOR TOP FACE REINFORCEMENT IS TO BE ADOPTED.
1c 1c (VI) IF REINFORCEMENT AT SUPPORT AT TOP FACE IS LESS THAN THE
REINFORCEMENT AT TOP FACE AT TOP FACE AT MID SPAN,SAME CURTAILMENT
RULE AS FOR BOTTOM FACE REINFORCEMENT IS TO BE ADOPTED.
(VII)LOCATION OF BEAMS IN PLAN WITH RESPECT TO THE COLUMNS SHALL BE
1b PROVIDED AS PER REQUIREMENT OF BRICK WALL ABOVE IT/AS PER
ARCHITECTURAL REQUIREMENT.
B3(230X375)

B4(230X375)

B3(230X375)

B3(230X375)
1b [SLABS]
4160

LI
[1] DOTTED LINES ARE SHOWN AS TOP FACE REINFORCEMENT AND FIRM LINES
AS BOTTOM FACE REINFORCEMENT.

P1 P1 P1 1a
[2] ALL TOP FACE REINF.AT C0NTINU0US EDGE OF SLAB SHALL BE CONTINUED
UP TO L/3 OF SPAN & AT DISCONTINUOUS EDGE SHALL BE PROVIDED UP TO
L/7 OF SPAN.
[3] THE CROSS REINF. / TEMP. REINF. BELOW TOP REINF OF SLAB .i.e. #8@200 c/c
IS TO BE PROVIDED JUST BELOW THE MAIN TOP STEEL WHICH HAS NOT BEEN
SHOWN IN THE DRG.
[4] THE FIRST MAIN BAR OF SLAB SHALL BE PLACED AT 80 mm. OR HALF THE
1c SPACING SPECIFIED WHICHEVER IS LESS FROM THE FACE OF SUPPORT

[MASONRY WORK]
[1] 115 TH.(1/2 BRICK) WALL -1:4 CEMENT: SAND MORTAR SHALL BE USED & #8,1
1a NOS. BARS AT EVERY 4th COURSE SHALL BE PROVIDED
[2] 250 TH.(1 BRICK) WALL - 1:6 CEMENT: SAND MORTAR SHALL BE USED.
[3] THE VERTICAL FACE OF CONCRETE AT JUNCTION OF WALL & RCC MEMBER
SHALL BE RAKED TO GIVE GIVE A ROUGH SURFACE & 1:4 CEMENT:SAND MORTAR
SHOULD BE APPLIED TO DEVELOPED BOND BETWEEN BRICK WALL & RCC
MEMBER.
[4] 125 TH. (1/2 BRICK) WALL EXCEEDING 3.0 M. IN LENGTH & 250 TH. BRICK WALL
EXCEEDING 4.5 M. IN LENGTH, VERTICAL STIFFENER HAS TO BE PROVIDE AS
SHOWN IN DETAILS OF STRENGTHENING MEASURES OF PANEL WALLS.
TYP. DETAILS OF PANEL
B

B2(230X375) B2(230X375) B2(230X375)

TERRACE BEAM -LAYOUT PLAN


d
L1 L2
Bar Cut OSF
0.3L1 0.3L1 0.3L2 Indication(typ.) 0.3L2
200
25 200 200
OVER
200
TYP. DET. SHOWING HOOKS SW W

NW
Ld+10xBARØ

S
LAP

N
FOR CLOSED STIRRUPS
d

SE
E NE

d₂ d₂
300
2d 2d MIN.2d 2d
STIRRUP SPACING STIRRUP SPACING
> d/2, (S2) > d/2, (S2)
STIRRUP SPACING STIRRUP SPACING
≤ d/4 AND 8d₂, (S1) ≤ d/4 AND 8d₂, (S1) OWNER'S
CONTINUOUS DISCONT.
TYPICAL ARRANGEMENT OF TRANSVERSE REINFORCEMENT IN BEAM SUPPORT
CONTINUOUS SUPPORT BIHAR URBAN INFRASTRUCTURE
SUPPORT
8# @ 150C/C(min) DEVELOPMENT
(WHEREVER NOT SHOWN, TO BE PROVIDE) 0.3 L1 0.3 L2 0.1 L2(500MIN) CORPORATION LIMITED. ( BUIDCO )
600 0.3L1
125

CONSTRUCTION OF CREMATORIUM
NAME OF (ELECTRIC – 1SET & O&M – 5 YEARS)
0.25L1 0.25L1 0.25 L2 0.15L2
r/f near span WORK UNDER NISCHAY – 2 IN HAJIPUR NAGAR

THICKNESS
alternate cut PRISHAD, BIHAR .
L1 (SPAN) L2(SPAN)
PANEL DETAILS AGENCY M/S ARVIND SINGH
TYPICAL LONG SECTION OF A SLAB
REINFORCEMENT DETAILS ALONG SHORTER DIRECTION REINFORCEMENT DETAILS ALONG LONGER DIRECTION PLINT BEAM LAYOUT AND REINF.
TITLE DETAILS
ALTHROUGH BOTTOM R/F EXTRA BOTTOM R/F ALONG TOP R/F ALONG SHORTER ALTHROUGH BOTTOM R/F EXTRA BOTTOM R/F ALONG TOP R/F ALONG LONGER
PANEL THICK.
ALONG SHORTER DIRECTION SHORTER DIRECTION DIRECTION ALONG LONGER DIRECTION LONGER DIRECTION DIRECTION
IN MM DRAWING No. AS/BUIDCO/HJ/STR/RO-WR/DWG/004
MARK DIA # SPACING C/C MARK DIA # SPACING C/C MARK DIA # SPACING C/C MARK DIA # SPACING C/C MARK DIA # SPACING C/C MARK DIA # SPACING C/C
SCALE SHEET SIZE REVISION
P1 125 1a 10 # 125MM C/C 1b 10 # 125MM C/C 1c 10 # 125MM C/C 2a 10# 125 MM C/C 2b 10 # 125MM C/C 1c 10 # 125MM C/C
NTS A2 R0